cil procedure · web view2017. 8. 29. · cairn india limited procedure. standard maintenance...
TRANSCRIPT
CIL Procedure
CAIRN INDIA LIMITED PROCEDURE
Standard Maintenance Procedure - Instrumentation : 8 channel Digital Temp Scanner.
Revision Number
0
Date of Issue
17.12.2009
Next Review
16.12.2010
Owner
Instrument Dept.
Application
Instrument Maintenance : MANGALA PROCESSING TERMINAL, RAJASTHAN OPEARATION
Classification
Internal
8CAIRN INDIA PROCESS
Standard Maintenance Procedure - Instrumentation: 8 Channel Digital Temp Scanner
Document Control No. MANGALA TRAIN-PRO-SMP-INST-042
SMP for 8-Channel Digital Temperature Scanner
Document Change History
Rev
Date
Section
Nature of Change
0
17.12.2009
Entire Document
For Approval
Distribution List
Copy Identification
Recipient
Issue Date
Master Copy
Information Management – RJON
Hard copy
Instrument Supdt. - RJON
Soft copy
Information Management - Gurgaon
Soft copy
Installation Manager - RJON
Soft copy
Field Maintenance Manager - RJON
Soft copy
Maintenance Manager - RJON
Table of Contents
Sr. No.
Description
Page No.
1
Purpose
5
2
Scope
5
3
HSE Requirement
5
3.1
Safety Aspects
5
3.2
Environmental Aspects
6
4
Task /Activity
7
5
Acceptance Criteria
8
6
Records
8
7
Replacement
8
8
References
8
9
Annexure-1
9
1. Purpose
The purpose of this Standard Maintenance Procedure is to define safe and best Calibration/ Maintenance procedure for digital temperature scanner.
2. Scope This procedure is applicable to all the digital temperature scanner installed at Mangala Processing Terminal Operation Facility for Preventive/Corrective Maintenance.
The Planned Maintenance Routines and their Frequencies as indicated in the
Cairn’s Generic Maintenance Strategy is as follows:
PMR Number
PMR Description
Frequency
NA
Digital temperature Scanner (8 channel) – Function Test & Calibration Checks
1 Year
3. HSE Requirement3.1 Safety Aspects
1. Obtain a work permit prior to commencing work.
2. Use appropriate hand tools
3. Use appropriate personal protective equipment while performing the work
4. Ensure that the particular Instrument is isolated properly and completely depressurised before starting the job.
.
3.2 Environmental Aspects
1. Store any faulty electronic card in designated place for final disposal as per waste management plan.
2. Dispose empty aerosol cans as per the waste management plan.
3. Collect any spillage / leakage of condensate during draining / depressurisation in containers for final disposal as per waste management plan.
4. Carry out thorough check of hand pumps / calibrators before calibration. Collect any hydraulic oil spills with containment tray for final disposal as per waste management plan.
5. Wipe oil spills with cotton waste. Store used / oil soaked cotton waste in designated bins for further disposal as per waste management plan.
6. Collect and store non functional spares and used consumables such as tubing, faulty transmitters, junction boxes, regulators, scrapped cable, wires, PVC material, etc in designated place for disposal as per Waste Management Plan.
7. Store waste paper, cardboards and packing materials generated in the nearby dust bins and send for incineration.
4. TASK / ACTIVITY:
TOOLS: IS Multimeter, Multi function calibrator & Hand tools.
4.1Procedure for 8 channel digital temperature scanner
1. Obtain Work Permit from Production Department. Override the trip if it is connected to any trip system.
2. Connect 230 V Ac 50 Hz power supply to Temperature scanner.
3. Keep calibrated channel in manual by Auto/Man switch.
4. Apply Resistance if RTD input or apply milivolts if Thermocouple input corresponding to lower range value and check indication.
5. If it is not matched then change scanner mode from run to program mode and calibrate channel by front panel key.
6. Apply Resistance if RTD input or apply milivolts if Thermocouple input corresponding to upper range value and check indication.
7. If it is not matched then change scanner mode from run to program mode and calibrate channel by front panel key.
8. Check low and high alarm set value by applying input to the scanner.
9. Two discrete LEDs are provided per channel for visual annunciation.
10. LED blinks on scanner for each channel for low or high value of temperature.
11. Low and high set alarm value, zero and span value, input type, is configurable for each channel Program mode is used to display/ change alarm limits,scan time and skip status of channels.
12. Configuration mode is used to change basic configuration of unit like scanner type, input type, set-point type, abnormal status, relay status, alarm latching, open sensor, hysteresis, zero and span value, decimal point position, password, serial number, serial output type, baud rate and open collector type.
13. Same way check and calibrate other channels.
14. Restored termination of scanner and put it in Auto mode
15. Check reading of all channels on scanner.
16. Check alarm LED’s of all channels on scanner, it should be normal.
17. Inform Production Department & Normalize the override if applicable.
Close the Work Permit.
5.ACCEPTANCE CRITERIA:
1. No leakage from the system. Normalise the trip override if applicable.
2. Digital temperature scanner should be accepted only if their accuracy & performance are meeting the requirement as per specified design data sheets given by OEM
6.RECORDS:
1. Maintenance activities shall be entered into Maintenance management system as applicable.
2. The Inspection details and the measured values shall be recorded in the approved Checklist for all the digital temperature scanner which are calibrated/ Checked. The report shall provide details of valid Certificates of standard calibrators.
Refer Annexure-1 for the Checklist.
7.REPLACEMENT:
Any replacement parts must be from Original Equipment Manufacturer (OEM) only.
8.REFERENCES:
1. Vendor Manual. – Digital temperature scanner, Make: Masibus, Model 85XX
9.Annexure:1
Digital temperature scanner Check list
1. Tag No: _______________________ 2. Service: ___________________________
3. Model No.:_____________________ 4. Serial No.__________________________
1. Range: ________________________
7. General cleanness: Yes: _____ No: _____
8. Rain/Sun protection in place: Yes: _____ No: _____
9. Connection tightness: Yes: _____ No: _____
10. Display check : Yes: _____ No: _____
Input
Temperature Indication (As observed)
Temperature Indication (As Left)
Deg C
Ch.1
Ch.2
Ch.3
Ch.4
Ch.5
Ch.6
Ch.7
Ch.8
Ch.1
Ch.2
Ch.3
Ch.4
Ch.5
Ch.6
Ch.7
Ch.8
Input
Current output (As observed)
Current output (As Left)
Deg C
Ch.1
Ch.2
Ch.3
Ch.4
Ch.5
Ch.6
Ch.7
Ch.8
Ch.1
Ch.2
Ch.3
Ch.4
Ch.5
Ch.6
Ch.7
Ch.8
12. Calibration check :
Checked By _______________________Verified By __________________
Date _____________________________ Date _______________________
Prepared by
Instrument Supdt.
Reviewed by
Manager Maintenance
Field Manager Maintenance
Approved by
Installation Manager
Designation
Date
Document Number
MANGALA TRAIN-PRO-SMP-INST-042
Page 1 of 1
Page 9 of 9