SC B5: PS1, Q7 Transformer Inrush Currents
EFFECT OF TRANSFORMER INRUSH CURRENTS ON PROTECTION FUNCTIONS
Where to Look,
Security,
Dependability
© A
BB
- 3
Transformer Inrush Currents – Where to look?
Measured in Phase Currents or in Differential Currents? 2nd harmonic
4th harmonic
5th harmonic
DC offset
Wave shape recognition
etc.
Set block level depends on position where measurement is taken
© A
BB
- 4
Transformer Inrush Currents – Security?
Security? Block for all inrush cases
Not good practice to put burden on the end user to completely set this logic
15% or 7%?
Adaptive 2nd harmonic + WaveBlock good results
Correct and easy to use design is manufacturer responsibility
© A
BB
- 5
Transformer Inrush Currents – Dependability?
Dependability? Trip for all internal faults
Insure that restraint level will trip in spite of CT saturation
Use of adaptive second harmonic blocking insures that
Paper in IEE DPSP 2001