Chiller selection Software Version 4.41 (8-DEC-2007) - Copyright © 2000-2007, Carrier Corp. * Project Date 8/10/2008 2:22:16 PM Location Company name Contact name CARRIER reference Rajesh Malik CMS Sales Dubai * Product 30RA100-opt16-B Range 30RA 100-140 Opt16 High Ambience * List of the options selected : Hydronic Module Gross capacity 93 kW Unit absorbed power 42.4 kW Compres. Input power 37.2 kW C.O.P. 2.2 No of capacity steps 4 Minimum step 25 % Refrigerant R22 Expansion valve TXV * Evaporator Fluid Water Leaving T. 7.2 °C Delta T. 5.5 K Entering T. 12.7 °C Flow rate 4.04 L/s Evaporator pressure drop 26 kPa Available Pressure 142 kPa Fouling factor 0.04403 m²-K/kW Water connection size 2" Victaulic Max operating pressure 300 kPa * Condenser Air 46.1 °C Altitude 0 m T.H.R. 128 kW * No of compressors 3 Compressor type hermetic scroll Compressor motor speed 48.3 r/s Starter type Direct * Volts/Phases/Hertz 400-3-50 Power Factor (at max power) 0.82 Maximum current drawn 73.8 A (U nom.)

Upload: ajay-bhatt

Post on 03-Jan-2016

17 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Chiller Selection Software-30RA100 With Hydronic Module Single Pump

Chiller selection SoftwareVersion 4.41 (8-DEC-2007) - Copyright © 2000-2007, Carrier Corp.

* Project Date 8/10/2008 2:22:16 PM Location Company name Contact name CARRIER reference Rajesh Malik CMS Sales Dubai

* Product 30RA100-opt16-B Range 30RA 100-140 Opt16 High Ambience

* List of the options selected : Hydronic Module

Gross capacity 93 kW Unit absorbed power 42.4 kW Compres. Input power 37.2 kW C.O.P. 2.2 No of capacity steps 4 Minimum step 25 % Refrigerant R22 Expansion valve TXV

* Evaporator Fluid Water Leaving T. 7.2 °C Delta T. 5.5 K Entering T. 12.7 °C Flow rate 4.04 L/s Evaporator pressure drop 26 kPa Available Pressure 142 kPa Fouling factor 0.04403 m²-K/kW Water connection size 2" Victaulic Max operating pressure 300 kPa

* Condenser Air 46.1 °C Altitude 0 m T.H.R. 128 kW

* No of compressors 3 Compressor type hermetic scroll Compressor motor speed 48.3 r/s Starter type Direct

* Volts/Phases/Hertz 400-3-50 Power Factor (at max power) 0.82 Maximum current drawn 73.8 A (U nom.) Maximum starting current 199.7 A Voltage limits 360/440 V

* Operating weight 1106 kg Refrigerant charge 29 kg Length/Width/Height 2071 mm 2278 mm 1329 mm

The Input Power and Cooling Capacity are supplied excluding pump

Page 2: Chiller Selection Software-30RA100 With Hydronic Module Single Pump

* Acoustic power (dB ref. 1e-12 W) (Full load) Octave band (Hz) 125 250 500 1K 2K 4K 8K Global Lw 92 85 85 83 78 70 67 94 Lw(A) 76 77 82 83 79 71 66 87 Global Acoustic power dB(A), according to EUROVENT standard = 87

Average acoustic pressure (dB ref. 2e-5 Pa). Distance 5 m Octave band (Hz) 125 250 500 1K 2K 4K 8K Global Lp 66 59 58 57 52 43.8 40.4 68 Lp(A) 49.5 50 55 57 53 44.8 39.3 61 Global pressure level in dB(A) = 61

* Full-load and Part-load calculation

1 The Unit capacity is the Gross Unit capacity. 2 The Unit kW input includes Compressor and Fan (when Fan). 3 The Unit C.O.P. is the Unit capacity divided by the Unit kW input.

Please note that for units with Hydronic module the values are supplied excluding pump.