chiller basics with phil rodin. things to check when chiller is not running or is in alarm

43
Chiller basics Chiller basics With Phil Rodin

Upload: damon-conley

Post on 12-Jan-2016

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Chiller basics

Chiller basics

With Phil Rodin

Page 2: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Things to check when chiller is not running or is in alarm

Page 3: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Alarm showing water flow, pumps both chilled and condenser water types of flow switches

Page 4: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Alarm showing water flow, pumps both chilled and condenser water types of flow switches

Page 5: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Alarm showing water flow, pumps both chilled and condenser water types of paddle switches

Page 6: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Alarm showing water flow, pumps both chilled and condenser water types of electronic flow switches

Electronic flow switches have probes

Page 7: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Alarm Conditions

High Pressure1. Low water flow2. Cooling tower3. Strainers (locations?)4. Valves (electric or manual types)5. The entering and leaving water temp.6. Approach temp

Page 8: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Alarm conditions

Page 9: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Sure flex #9

Page 10: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Alarm conditions

Page 11: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Alarm conditions

Page 12: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Alarm conditionsChilled water flow

1. Pumps2. Strainers3. Valves (manual and electric)4. Flow switches5. Water temp in and out6. Approach temp

Page 13: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Alarm conditionsChilled water flow (cont.)

PRV

Page 14: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

What is the oil temperature?

1. Feel the tank or read with inferred.2. Check control panel3. Check for power4. Think out of the box, How can we heat

this?

Page 15: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

What is the oil temperature?(cont.)

Page 16: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Tube sheets

Page 17: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Chiller barrel

Page 18: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Enhanced tubes

Page 19: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Inside and outside tubes

Page 20: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Vapor to liquid

Page 21: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Flooded Evaporator

Page 22: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

What is the oil temperature?(cont.)

Page 23: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Pressure & Temp. Gauges(electronic)

Page 24: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Pressure & Temp. Gauges(fluid type)

Page 25: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Chiller Surging

ASK YOURSELF?????1. Is it a high or low end surge?2. Are your amps going up or down?3. The sound? a. Is it an elephant b. Is it a grumble

Page 26: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Chiller Surging(High & Low Surging)

High Surge on Low Pressure Machines1. Water temp. in and out.2. Approach 3. Cooling Tower4. Purge5. Refrigerant levels

Page 27: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Chiller Surging(High & Low Surging)

Page 28: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Cooling Towers

Page 29: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Chiller Surging(High & Low Surging)

Page 30: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Chiller Surging(High & Low Surging)

Page 31: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Chiller Surging(High & Low Surging)

Page 32: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Chiller Surging(capacity control)

Page 33: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Chiller Capacity Control

Page 34: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Low End Surge

1. Water temp. In and out2. Approach Temp.3. Water pressure4. Refrigerant levels

Page 35: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Low End Surge

Page 36: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Low End Surge

Page 37: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Transducers & Sensors Types

Page 38: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Transducers & Sensors Types

Page 39: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Panel Codes

1. Carrier code 11112. York code 9675 aka YORK3. Trane code ++--++ (different

combinations)

Page 40: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

How’s the Chiller Running?

Is the chiller running in local?Is the chiller running in EMS?Are the pumps running?Are the valves open?Hand –off Auto (Think before going to hand)

Page 41: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Cavitation of Pumps

1. Strainers2. Water pressures3. Couplings4. Valves5. Primary or Secondary Loop

Page 42: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm

Questions(There is no such thing as a dumb question)

?

Page 43: Chiller basics With Phil Rodin. Things to check when chiller is not running or is in alarm