chilled water system presentation– chiller evaporator – longest circuit – coil – three way...
TRANSCRIPT
COMMERCIAL BUILDING SERVICES FLOW THINKING
Chilled Water System Presentation
COMMERCIAL BUILDING SERVICES FLOW THINKING
Constant Volume DistributionConstant Volume Distribution
COMMERCIAL BUILDING SERVICES FLOW THINKING
Air-conditioning System Components
COMMERCIAL BUILDING SERVICES FLOW THINKING
Constant Volume System Components
COMMERCIAL BUILDING SERVICES FLOW THINKING
Typical 3-way Valve Zone
COMMERCIAL BUILDING SERVICES FLOW THINKING
Full Load Condition
COMMERCIAL BUILDING SERVICES FLOW THINKING
Fully Loaded Coil
• Supply water temperature 45°F
• Design return water temp. 55°F
• Coil design flow 100 GPM
• Coil design pressure drop 20 FT
• Load (flow x 10°F∆ x 500) 500,000 Btuh
• Coil ∆P @ design flow 20 FT
• Bypass flow 0 GPM
• Bypass ∆P 3-way valve closed
• 3-way valve pressure drop 10 FT
• Pump flow and head 100 GPM @ 30 FT
• Actual return water temp 55 °F
COMMERCIAL BUILDING SERVICES FLOW THINKING
Unloaded Condition
COMMERCIAL BUILDING SERVICES FLOW THINKING
Unloaded Coil
• Supply water temperature 45°F
• Design return water temp. 55°F
• Coil design flow 0 GPM
• Coil design pressure drop 3-way valve closed
• Load (flow x 10°F∆ x 500) 0.0 Btuh
• Coil ∆P @ design flow 0 FT
• Bypass flow 100 GPM
• Bypass ∆P 20 FT
• 3-way valve pressure drop 10 FT
• Pump flow and head 100 GPM @ 30 FT
• Actual return water temp 45 °F
COMMERCIAL BUILDING SERVICES FLOW THINKING
So What?
• When the load on the coil is zero, the valve is returning “unused”chilled water at essentially supply temperature.
• Cold return water “unloads” the chillers, causing them to operate inefficiently.
COMMERCIAL BUILDING SERVICES FLOW THINKING
Part Load Condition
COMMERCIAL BUILDING SERVICES FLOW THINKING
Partially Loaded Coil
• Supply water temperature 45°F
• Design return water temp. 55°F
• Coil design flow 50 GPM
• Coil design pressure drop 20 FT
• Load (flow x 10°F∆ x 500) 250,000 Btuh
• Coil ∆P @ design flow 5 FT
• Bypass flow ??? GPM
• Bypass ∆P 3-way partially closed
• 3-way valve pressure drop 10 FT
• Pump flow and head ??? GPM @ 30 FT
• Actual return water temp ?? °F
COMMERCIAL BUILDING SERVICES FLOW THINKING
125
100
75
50
25
0
% Valve Stroke 25 50 75 100
% F
low
1/2 Through Coil1/2 Through Bypass
Fu
ll F
low
T
hro
ug
h C
oil
Fu
ll F
low
T
hro
ugh
Byp
ass
3-way Valve Characteristic
COMMERCIAL BUILDING SERVICES FLOW THINKING
What’s Really Happening?
COMMERCIAL BUILDING SERVICES FLOW THINKING
Coil with 3-way Valve at Mid-position
• Supply water temperature 45 °F
• Design return water temp. 55 °F
• Load (flow x 10°F∆ x 500) 250,000 Btuh
• Coil design pressure drop 20 FT
• Coil flow 62.5 GPM
• Coil ∆P @ 62.5% flow 7.8 FT
• Coil leaving water temp 53 °F
• Bypass flow 62.5 GPM
• Bypass ∆P 7.8 FT
• 3-way valve pressure drop 10 FT
• Pump flow and head 125 GPM @ 30 FT
• Actual return water temp 49 °F (62.5 GPM @ 53 °F+
62.5 GPM @ 45 °F)
COMMERCIAL BUILDING SERVICES FLOW THINKING
Head2 = Head1(Flow2/ Flow1)2
Head2 = 20(.625/1)2
Head2 = 20(.3906 )
Head2 = 7.8
COMMERCIAL BUILDING SERVICES FLOW THINKING
∆T = Load/ Flow X 500
∆T = 250,000/62.5 X 500
∆T = 8
Therefore, LWTcoil = 45 + 8 = 53
COMMERCIAL BUILDING SERVICES FLOW THINKING
RWT = (Flow1 X EWT + Flow2 X LWT)/ Flow1 + 2
RWT = (62.5 X 45 + 62.5 X 53)/125
RWT = 49
COMMERCIAL BUILDING SERVICES FLOW THINKING
3-way Valve in Mid Position
COMMERCIAL BUILDING SERVICES FLOW THINKING
1. Low return water temperatures.2. Robs chilled water from other coils at part
load conditions.3. Increases flow in primary piping.4. Adds additional chillers on line.5. Chiller performance is reduced.
3-way Valve System Deficiencies
COMMERCIAL BUILDING SERVICES FLOW THINKING
1.1
20 30 40 50 60 70 80 90 10010
1.0
0.9
0.8
0.7
0.6
0.5
KW
per T
on
Percent Load
Chiller Performance Curve
COMMERCIAL BUILDING SERVICES FLOW THINKING
Pump Sizing
• Select for full chiller flow
• Head must be adequate for:
– Chiller evaporator
– Longest circuit
– Coil
– Three way valve
– Air separator
COMMERCIAL BUILDING SERVICES FLOW THINKING
System Configuration
Constant Volume
Any Questions?
Variable Volume Constant Speed
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary – Secondary System
Primary – Includes Chillers & Primary Pump. Circuit Constant water flow through the chiller
is maintained and chilled water isproduced
Secondary – Chilled water is circulated to the Circuit demand area (load) by using
Secondary pumps.
Variable Volume Constant Speed
COMMERCIAL BUILDING SERVICES FLOW THINKING
PRIMARY - SECONDARY
COMMERCIAL BUILDING SERVICES FLOW THINKING
Other Famous Names of Primary-Secondary
Primary – Production Loop
Secondary – Distribution Loop
COMMERCIAL BUILDING SERVICES FLOW THINKING
Fundamental Idea
COMMERCIAL BUILDING SERVICES FLOW THINKING
No Secondary Flow
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary = Secondary
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary > Secondary
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary < Secondary
COMMERCIAL BUILDING SERVICES FLOW THINKING
Control Valve in Secondary
COMMERCIAL BUILDING SERVICES FLOW THINKING
• Use the flow of the largest chiller
– Chiller staging at half of this flow is common
• Head loss in common <1 1/2 ft
– Distribution pipe size is often used where reductions would be inconvenient
• Three pipe diameters between tees
– Excessive length increases total head loss
• Low velocities in system piping
Common Pipe Design Criteria
COMMERCIAL BUILDING SERVICES FLOW THINKING
Variable flow through coil Constant flow through system
Three Way Valve
Variable flow through coil Variable flow through system
Two Way Valve
Control Valve in Secondary
COMMERCIAL BUILDING SERVICES FLOW THINKING
PRIMARY – SECONDARY CIRCUIT
Variable Volume Constant Speed
COMMERCIAL BUILDING SERVICES FLOW THINKING
Head
F1 F2 F3
H1
H2
H3
Flow
Control Valves Change the Secondary System Curve
COMMERCIAL BUILDING SERVICES FLOW THINKING
% Flow
125
100
75
50
25
150
25 50 75 100
HDVarying differential pressure absorbed by control valve
System resistance
TDH of pump
Pump curve
Head Absorbed by 2-way Valves
COMMERCIAL BUILDING SERVICES FLOW THINKING
HP
125
100
75
50
25
150
25 50 75 100
% Design Flow
Primary Pumps = V/V
Secondary Pumps +
Constant Flow Primary Pumps, only
Pump Horsepower Comparison
COMMERCIAL BUILDING SERVICES FLOW THINKING
% Flow
90
80
70
60
50
40
30
20
10
0 10 1009080706050403020
100
110
120
130
140
150
BaseDesignHP %
% Full Load(Design) HP
Pump Over-haded by 150%Constant Flow, C/S Pump
(3 Way Valve)
Constant Flow, C/S Pump
(3 Way Valve)
C/S Pump(2 Way Valve)
Pump HD Matchedto System @Design Flow
C/S P
ump (2 W
ay Valve)
Constant vs Variable Volume
Any Questions?
Step Function of Chillers
COMMERCIAL BUILDING SERVICES FLOW THINKING
Production = Distribution
COMMERCIAL BUILDING SERVICES FLOW THINKING
Distribution > Production
COMMERCIAL BUILDING SERVICES FLOW THINKING
Production > Distribution
COMMERCIAL BUILDING SERVICES FLOW THINKING
“Loading” a Chiller
• A chiller is a heat transfer device. Like most equipment, it ismost efficient at full load.
• To “load” a chiller means:
– Supply it with its rated flow of water
– Insure that water is warm enough to permit removal of rated Btu without freezing the water
COMMERCIAL BUILDING SERVICES FLOW THINKING
Chiller Performance Curve
1.1
20 30 40 50 60 70 80 90 10010
1.0
0.9
0.8
0.7
0.6
0.5
KW
per T
on
Percent Load
COMMERCIAL BUILDING SERVICES FLOW THINKING
Check Valve in Common?
COMMERCIAL BUILDING SERVICES FLOW THINKING
What can we do?
COMMERCIAL BUILDING SERVICES FLOW THINKING
What else can we do?Reset Supply Temperature
• Lower chiller set point when mixing occurs to maintain a constant temperature to the system.
• Expect increases in cost of chiller operation at lower set point: 1-3% per degree of reset.
• Delays start of the next chiller.
COMMERCIAL BUILDING SERVICES FLOW THINKING
What else can we do?
• Coils that are selected at higher supply temperatures will not be impaired by small changes.
• Loads that require fixed temperatures may use a small chiller toreverse the effects of mixing.
COMMERCIAL BUILDING SERVICES FLOW THINKING
Multiple Chillers
COMMERCIAL BUILDING SERVICES FLOW THINKING
60/40 Chiller Split to Help Minimize Low Part Load Operation
COMMERCIAL BUILDING SERVICES FLOW THINKING
0-10 30-40 60-70 90-1000
5
10
15
20
25
30
0-10 30-40 60-70 90-100
% T
ime
% Load
Typical Load Profile
COMMERCIAL BUILDING SERVICES FLOW THINKING
Three Unequally Sized Chillers
COMMERCIAL BUILDING SERVICES FLOW THINKING
% Load
Time
Approaching Flow = Load
Any Questions?Alternate
Pumping MethodsComparison
COMMERCIAL BUILDING SERVICES FLOW THINKING
Two Pipe Direct Return
COMMERCIAL BUILDING SERVICES FLOW THINKING
Two Pipe Reverse Return
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary-Secondary Pumping.
• Simplest to install.
• Simplest to operate.
• Flexible in design for present and future.
• Efficient to operate.
• May over-pressurize near zones.
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary-Secondary-Tertiary
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary-Secondary-Tertiary Pumping.
• Best piping flexibility.
• Best expansion flexibility.
• Provides hydraulic decoupling.
• Efficient to operate.
• May require added horsepower.
• Requires additional pumps and piping.
• Increased controls complexity.
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary-Secondary-Tertiary Hybrid
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary-Secondary-Tertiary Hybrid Pumping.
• Low present horsepower.
• Low future horsepower.
• Good piping flexibility.
• Good expansion flexibility.
• Provides hydraulic decoupling.
• May require added horsepower
• Requires additional pumps and piping.
• Increased controls complexity.
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary-Secondary Zone Pumping
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary-Secondary Zone Pumping.
• Low ‘built out’ horsepower.
• Low system head.
• Increased control complexity.
• Present horsepower total higher due to future needs.
• Present pumps sized for future requirements.
• Difficult to apply in retrofits projects.
Any Questions?
Variable Volume Variable Speed
COMMERCIAL BUILDING SERVICES FLOW THINKING
Why Do We Need Variable Speed Secondary Pumps ???
•For Energy Saving….
•For better & optimise operation….
COMMERCIAL BUILDING SERVICES FLOW THINKING
How Do We Achieve This Reduction In Power Consumption ??
By Using Variable Frequency Drive and Logic controller with the Secondary Pumps….
COMMERCIAL BUILDING SERVICES FLOW THINKING
Power Comparison at Reduced Speed
COMMERCIAL BUILDING SERVICES FLOW THINKING
Basic Law which helps in achieving this – Affinity law
1. Flow2 = Flow1(Speed2/ Speed1)
2. Head2 = Head1(Speed2/ Speed1)2
3. BKW2 = BKW1(Speed2/ Speed1)3
If Diameter of Impeller is to be trimmed then instead of speed the same can be used in above formulas.
COMMERCIAL BUILDING SERVICES FLOW THINKING
0
50
100
150
200
250
300
350
400
450
50 100 150 200 250 300 350 400 450 500
Motor Horsepower
An
nu
al O
pe
rati
ng
Co
st
$1
00
0
$0.10/kWh
Operating Cost
COMMERCIAL BUILDING SERVICES FLOW THINKING
Head
Flow
Pump Curve
System
Curve
System Curveas two wayvalves close
Variable flow system
COMMERCIAL BUILDING SERVICES FLOW THINKING
Q
H
Pump Curve
System Curveat design flow
System Curveat part load
Increased head loss
Energy savings offset
COMMERCIAL BUILDING SERVICES FLOW THINKING
Head
Flow
SinglePump
Pumps inParallel
SystemCurve
Pumps in parallel
COMMERCIAL BUILDING SERVICES FLOW THINKING
Horsepower%
100
90
80
70
60
50
40
30
20
10
00 10 20 30 40 50 60 70 80 90 100
Flow%
Single Large Pump
Two ParallelPumps
Single ParallelPump
Parallel pumping power savings
COMMERCIAL BUILDING SERVICES FLOW THINKING
Theoretical Savings
COMMERCIAL BUILDING SERVICES FLOW THINKING
���
���
���
��
��
��
��
��
��
��
�
�
�
��� ��� ��� ��� ��� �� �� ��� ��� �����
100 %
90 %
80 %
70 %
60 %
50%
40 %
30 %
80 %
85 %80 %70 %60 %50 %
85 %
% Speed Curves
Constant Efficiency Curve
% EfficiencyH
ead,
Fe
et
GPM
Establishing Efficiency Curves
COMMERCIAL BUILDING SERVICES FLOW THINKING
750
900 1150 1450 1770600
900
1150
1450
1770
600
A
B
C
D
E
4500 gpm @ 100 FT, 85.9 %
Variable Speed Efficiencies
COMMERCIAL BUILDING SERVICES FLOW THINKING
“No Valve” System Curve
Flow
piping headloss curve
Distribution
Pum
p T
DH
Overall system curve
Head 80
60
40
20
110
0200 400 600 800 1000 1200 1400 16000
100
Set Point
25 FT Differential Head Maintained Across Load
(Set Point)
COMMERCIAL BUILDING SERVICES FLOW THINKING
Effect of Constant Set Point
piping headloss curve
Distribution
Pum
p T
DH
Overall system curve
Head
80
60
40
20
110
0200 400 600 800 1000 1200 1400 16000
Flow
100
Control curveSet point,
25 FT
COMMERCIAL BUILDING SERVICES FLOW THINKING
100%
75%
50%
Flow
Head
Control Curve
Variable Head Loss∆P
P1 P2
Control curve
COMMERCIAL BUILDING SERVICES FLOW THINKING
Annual
Operating
Cost
($1000/year
@
$0.10/kwh)
50
45
40
35
30
25
20
15
10
05
00
1000 2000 3000 4000 5000
Total Equivalent Pipe Length (feet)
Single C/S Pump, N
o Overheading
Singl
e C/S
Pum
p, 2
00%
Ove
rhea
ded
Variable Speed Pump
Large systems, long pipe runs
COMMERCIAL BUILDING SERVICES FLOW THINKING
Variable Head Loss Ratio
Perc
ent D
esig
n B
HP
% Flow
90
80
70
60
50
40
30
20
10
0 10 1009080706050403020
100C/S, Constant Flow System Pump Head Matched to
System at Design Flow
C/S, Variable Flow
V/S, 0% Variable Hd Loss, 100% Constant ∆ Hd
V/S, 25% Variable Hd Loss, 75% Constant ∆ Hd
V/S, 50% Variable Hd Loss, 50% Constant ∆ Hd
V/S, 75% Variable Hd Loss, 25% Constant ∆ Hd
V/S, 100% Variable Hd Loss, 0% Constant ∆ Hd
Base
COMMERCIAL BUILDING SERVICES FLOW THINKING
Variable Head Ratio w/ Overheading
90
80
70
60
50
40
30
20
10
0 10 1009080706050403020
100
110
120
130
140
150
BaseDesignHP %
% Full Load(Design) HP
Pump O’Headed by 150%Constant Flow, C/S Pump
(3 Way Valve)
Constant Flow, C/S Pump
(3 Way Valve)
C/S Pump(2 Way Valve)
Pump HD Matchedto System @Design Flow
* 25/75 Means:25 % Variable HD Loss75 % Constant HD Loss
C/S Pump (2 W
ay Valve)
V/S, 1
00% Constant H
D
V/S, 25/75*
V/S, 50/50
V/S, 75/25
V/S, 1
00% V
ariable H
D
COMMERCIAL BUILDING SERVICES FLOW THINKING
Locations of Sensor
Where to install the Sensor?
What type of Sensor?
COMMERCIAL BUILDING SERVICES FLOW THINKING
Chillers
Primary Pumps
Secondary Pumps
Load
Balancing Valve 2 – Way Valve
Panel with PLC & VFD`s
Air -Separator
Co
mm
on
Single Point Pressure Sensing
Single Point Pressure Sensor
COMMERCIAL BUILDING SERVICES FLOW THINKING
Single Point Pressure Sensor
Is Single Point Pressure Sensor Correct?
Wrong !!
Why?
-Pump is a differential pressure device.
-A single point is only influence by pressure. This is good for booster only.
-In a closed loop system, system pressure rises due to thermal expansion,
pumps will slow down.
-When static pressure decrease, pumps will speed up.
-This is self-defeating since now the pump speed is not influence by the
system load changes, but rather by system water pressure.
-Therefore, single pressure sensor are a misapplication in a closed loop
HVAC system.
COMMERCIAL BUILDING SERVICES FLOW THINKING
Chillers
Primary Pumps
Secondary Pumps
Load
Balancing Valve 2 – Way Valve
Panel with PLC & VFD`s
Air -Separator
Co
mm
on
Primary - Secondary Circuit With Variable Speed Secondary Pumps
DPT
Single Point Differential Pressure Sensor
COMMERCIAL BUILDING SERVICES FLOW THINKING
Opening/Closing of 2- Way Valve-Signal from the sensor, installed at load
regulates the valve opening & closing.
-This way differential across 2-way valve also
changes & accordingly output signal is given to
PLC.
```
Temperature Sensor
Load
Output to PFU from DPT
2 Way Valve Control
Question:
Can we put the DPT across coil alone?
Question:
Across the pumps?
COMMERCIAL BUILDING SERVICES FLOW THINKING
Primary - Secondary Circuit With Variable Speed Secondary Pumps
Single Point Differential Pressure Sensor
To Maximize energy system, we must maximize the
variable head loss in the system. This is done by locating
the sensor at the most remote zone ( hydraulically) in the
system.
COMMERCIAL BUILDING SERVICES FLOW THINKING
piping head loss curve
Distribution
Pu
mp
TD
H
Overall system curve
Ft H
d
80
60
40
20
110
0
200 400 600 800 1000 1200 1400 16000
Flow, gpm
100
Control curve
Set point, 25 FT
System Control Curve
COMMERCIAL BUILDING SERVICES FLOW THINKING
Variable vs Constant Head Loss
COMMERCIAL BUILDING SERVICES FLOW THINKING
The “Active Zone”
• Zone set points do not have to be the same.
• Pump controller scans all zones often, comparing process variable to set point in each case.
• Pumps are controlled to satisfy the worst case.
• What happens to the rest of the zones?
COMMERCIAL BUILDING SERVICES FLOW THINKING
PFU
PMU
4 – 20 mA
Set Value
From Field Sensor (DPT)
PFU – Pump Functional Unit
PMU – Pump Management Unit
Basic Concept
Output
To
VFD/Pump
COMMERCIAL BUILDING SERVICES FLOW THINKING
ChillersSecondary
Pumps
Balancing Valve
DPTDPT
Co
mm
on
Panel with PLC & VFD`s
Load
Different Sensor Signal To Common PFU Panel
Multi Point Differential Pressure Sensor
COMMERCIAL BUILDING SERVICES FLOW THINKING
PFU
PMU
Set Value
Multiple Process Signals From Field Sensors
POSSIBILITY OF MULTIPLE PROCESS SIGNALS FROM DIFFERENT ZONES
All zones can have different set values
Module
VFD
VFD
Multi Point Differential Pressure Sensor
COMMERCIAL BUILDING SERVICES FLOW THINKING
PFU
PMU
Set ValueMultiple Process Signals From Field Sensors
POSSIBILITY OF MULTIPLE PROCESS SIGNALS FROM DIFFERENT ZONES
All zones can have different set values
Signal
Comparator
VFD
VFD
Multi Point Differential Pressure Sensor
Signal
Comparator
4 – 20 mA Sig
COMMERCIAL BUILDING SERVICES FLOW THINKING
HVAC Control System
DPT Signal Comparator
COMMERCIAL BUILDING SERVICES FLOW THINKING
HVAC Control System
DPT Signal Comparator
- High and Low Signal Selections
- Signal Averaging
- High/Low Limit Control
The module has the addition following features :
1) LED status indications
2) Accepts voltage or milliamp input signal
3) DIP switch-selectable operating modes
4) Accepts 24 VAC/DC power
COMMERCIAL BUILDING SERVICES FLOW THINKING
HVAC Control System
DPT Signal Comparator
Benefits
1) We are able to supply VFD systems with multiple inputs signals ranges to compete
with our competitors.
2) We are able to use Grundfos PFU 2000 as the main processor to control the full system
operations.
3) We will be minimising outsourcing or external controller in order to serve the HVAC
market.
4) The MM allows us to integrate into the system multiple sensor control at a more cost
effective price.
COMMERCIAL BUILDING SERVICES FLOW THINKING
Other Types of Systems
HVAC System
COMMERCIAL BUILDING SERVICES FLOW THINKING
Chillers
Primary Pumps
Balancing Valve
Secondary Pumps
Air -Separator
Expansion Tank
Load
Panel with PLC & VFD`s
Co
mm
on
DPT
2 – Way Valve
DPT
Separate System for Each Zone
COMMERCIAL BUILDING SERVICES FLOW THINKING
Systems In Multi - Zones
Two options:
1. Separate Systems can be used for different zones. So each zone will have its own sensor.
2. Signal from different zone sensors is given to the common PFU and most deviated signal, from the set point, is given as output.
Separate System for Each Zone
COMMERCIAL BUILDING SERVICES FLOW THINKING
Chillers
Primary Pumps
Balancing Valve
Air -Separator
Expansion Tank
Load
Co
mm
on
DPT
2 – Way Valve
DPTVFD pumps For Each Zone
E-pumpsE-pumps
Tertiary Pumping System
Secondary Pump
COMMERCIAL BUILDING SERVICES FLOW THINKING
Reverse Return Pumping
Load
Air -Separator
Chillers
Primary Pumps
Secondary Pumps
Balancing Valve
Panel with PLC & VFD`s
Co
mm
on
DPT
COMMERCIAL BUILDING SERVICES FLOW THINKING
Reverse Return Pumping
Benefits :
1) Equalize the pressure drops of each zone.
2) Selections of the sensor becomes easier.
3) If load are similar or symmetrical, 1 centrally located sensor
is adequate.
4) As in direct return system, multiple sensor can still provide a
benefit to the end user.
COMMERCIAL BUILDING SERVICES FLOW THINKING
Type of VFD Systems
COMMERCIAL BUILDING SERVICES FLOW THINKING
Possible Options of Variable Speed panels
Type ME - Multiple Pumps & Multiple VFDs.
Type MF - Common VFD for Multiple Pumps.
COMMERCIAL BUILDING SERVICES FLOW THINKING
Signal from Field Sensor(s) (DPT)
Panel with
PFU & PMU
VFD - 1 VFD - 2
Secondary Pumps
System with Multi Pumps & Multi VFDs
COMMERCIAL BUILDING SERVICES FLOW THINKING
Signal from Field Sensor(s) (DPT)
VFD
Panel with
PFU & PMU
Secondary Pumps
System with Common VFD for All Pumps
COMMERCIAL BUILDING SERVICES FLOW THINKING
APPROVAL FROM INTERNATIONAL AGENCIES
Approval from – CE, U/L Conforms to - Electromagnetic compatibility (89/336/EEC) to standard EN 50 081 – 1 and EN 50 082 – 2 and Electrical equipment design 73/23/EEC standard to EN 60 204-1.
COMMERCIAL BUILDING SERVICES FLOW THINKING
PFU
PMU
Single PMU For Control of 8 Zones/Pumps
PFU
COMMERCIAL BUILDING SERVICES FLOW THINKING
PFU
PMU
Single PMU For Control of 8 Zones/Pumps
PFUPFU PFU
The End