![Page 1: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/1.jpg)
Chilled Beam and
Radiant Cooling Basics
Salt Lake City, UT ASHRAE Chapter
December 2013Nick Searle
![Page 2: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/2.jpg)
Contents
• Radiant Ceilings & Chilled Beam Basics
• Energy & Space Savings
• First and Lifecycle Costs
• Maintenance
• Application Suitability
• Design Considerations
• Application Example # Laboratories
• Case Study – 250 S. Wacker, Chicago
![Page 3: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/3.jpg)
Fan Energy Use in Buildings
“Energy Consumption Characteristics of Commercial Building HVAC
Systems” � publication prepared for U.S. Department of Energy
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
Central VAV Central CAV Packaged CAV
Desig
n L
oad
KW
/SF
Chiller/Compressor
Supply & Return Fans
Chilled Water Pump
Condenser Water Pump
Cooling Tower Fan
Condenser Fan
0
1
2
3
4
5
6
7
Central VAV Central CAV Packaged CAV
En
erg
y U
se K
Wh
/SF
![Page 4: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/4.jpg)
Water = Efficient Transport
¾” diameterwater pipe
10”
1 Ton of Cooling
requires 550 CFM of air
or
4 GPM of water
![Page 5: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/5.jpg)
Chilled Ceilings
Many buildings heated only
PC’s appearing on desks
Restricted ceiling cavity
1980 1990 2000 2010
Chilled Ceilings
![Page 6: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/6.jpg)
Chilled Ceilings Radiant Effect
45%Radiant
55%Convective
CW Supply59�62°F
CW Return62�66°F
76°F Dry Bulb
74°F radiant
temperature
(black bulb)
![Page 7: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/7.jpg)
Chilled CeilingsAdvantages Design Issues
• Low cooling output‒ 20 to 25 BTUH/ft2 100%
coverage‒ 14 to 18 BTUH/ft2 70% coverage
• High cost
• Separate air system required
• Excellent thermal comfort
• Reduced space requirements‒ Will fit into 6#8” cavity
• Self regulating‒ Simple controls
• Low noise
• Low maintenance
![Page 8: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/8.jpg)
Chilled Sails
![Page 9: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/9.jpg)
Chilled Sails
![Page 10: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/10.jpg)
Advantages Design Issues
• Cooling output‒ 40 to 50 BTUH/ft2
• Separate air system required
• High cost
• Cannot heat
• Need good acoustic treatment to avoid hard spaces
• Many connections
• Aesthetics ?
• Good thermal comfort
• Reduced space requirements
• Freely suspended
• Self regulating
• Simple controls
• Low noise
• Low maintenance
Chilled Sails
![Page 11: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/11.jpg)
Passive Chilled Beams
• Increased cooling loads‒ Equipment‒ Occupancy‒ Day#lighting
• Inadequate perimeter cooling
1980 1990 2000 2010
Chilled Ceilings
Passive Chilled Beams
![Page 12: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/12.jpg)
Passive Chilled Beams 1 Operation Principle
Perforated tile
Water coil
Suspension rod
Soffit
Fabric skirt
![Page 13: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/13.jpg)
Passive Chilled Beams 1 System Highlights
• Good thermal comfort
• Cooling capacity up to 40 BTUH/FT2 floor space‒ Up to 500 BTUH per LF of beam
• Reduced ductwork, riser and plant sizes‒ Water transports most of sensible cooling
• Self regulating‒ simple two position controls
• Low noise
• Low maintenance
![Page 14: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/14.jpg)
Design Considerations
• Sensible cooling only‒ Latent gains must be controlled by air system
• High free area perforated metal ceiling required‒ 28% free area minimum‒ Exposed beams (no ceiling) are an option
• Beams cannot be installed tight against slab‒ Typically 40% of beam width required above beam
• Separate heating system must be installed
• Separate air system must be installed
![Page 15: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/15.jpg)
Passive Chilled Beams 1 Airflow Pattern
![Page 16: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/16.jpg)
Passive Chilled Beams 1 Recessed Type
![Page 17: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/17.jpg)
Passive Chilled Beams 1 Exposed Type
![Page 18: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/18.jpg)
Active Chilled Beams1980 1990 2000 2010
Chilled Ceilings
Passive Chilled Beams
Active Chilled Beams
• Higher space loads
• Higher occupant densities
• Combined ventilation/cooling preferred
• Integration into fiber tile ceilings required
![Page 19: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/19.jpg)
Active Chilled Beam 1 Operation Principle
Suspended ceiling
Primary air plenum
Primary air nozzles
Heat exchanger
1 Part Primary Air
4 Parts Room Air
![Page 20: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/20.jpg)
Heat Removal Ratio
70% of sensible heat removed by chilled beam
water coil
Airflow requirement
reduced by 70%
![Page 21: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/21.jpg)
Active Chilled Beam 1 Airflow Pattern
![Page 22: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/22.jpg)
Active Chilled Beams 1 System Highlights
• Very high cooling capacity‒ Up to 100 BTUH/FT2 floor space‒ Up to 1500 BTUH per LF
• Integrated cooling, ventilation and heating‒ All services in the ceiling cavity
• Suitable for integration into all ceiling types‒ Reduces ceiling costs compared to Passive Beams
![Page 23: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/23.jpg)
Active Chilled Beams 1 System Highlights
• Significant space savings‒ Smaller ductwork saves space in shafts, plant rooms and ceiling
• Can be installed tight up against the slab‒ Reduced floor to floor heights‒ Reduced construction costs on new buildings
• Low noise levels
• Low maintenance‒ No moving or consumable parts
![Page 24: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/24.jpg)
Energy Savings 1 Compared to VAV
Source Technology Application % Saving*
US Dept. of Energy Report (4/2001) Beams/Radiant Ceilings General 25#30
ASHRAE 2010 Technology Awards Passive Chilled Beams Call Center 41
ACEE Emerging Technologies Report (2009) Active Chilled Beams General 20
ASHRAE Journal 2007 Active Chilled Beams Laboratory 57
SmithGroup Active Chilled Beams Offices 24
*Compared to VAV
“Energy Consumption Characteristics of Commercial Building HVAC
Systems” � publication prepared for U.S. Department of Energy
![Page 25: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/25.jpg)
Active Chilled Beams 1 First Costs
• Office Building, Palo Alto, CA
• 80,000 ft2
• Thermostat in each office for beam design
*HPAC Engineering Article “European Technology Taking Hold in the U.S.: Chilled
Beams, Peter Rumsey, PE, CEM, FASHRAE, FRMI
“costs were in line with VAV”*
![Page 26: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/26.jpg)
Active Chilled Beams 1 First Costs
• Office Building, Denver, CO
• 600,000 ft2 design/build renovation
• Elimination of two air handlers per floor due to beams
*HPAC Engineering Article “European Technology Taking Hold in the U.S.: Chilled
Beams, Peter Rumsey, PE, CEM, FASHRAE, FRMI, January 1st 2010
“the chilled�beam system was equal
to the VAV system”*
![Page 27: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/27.jpg)
Active Chilled Beams 1 Lifecycle Costs
• 100,000 ft2 Office Building, Cincinnati, OH
• 15 year lifecycle study
• 15% Energy Savings Compared to VAV‒ $0.79 versus $0.93 ft2
• 22% reduction in mechanical installation costs‒ $19.50 versus $25.00 per ft2
• Lifecycle costs analysis over 15 years‒ Favored chilled beam system by 20%‒ $32 ft2 versus $40 ft2
HIXSON ARCHITECTURAL INTERIORS � Spring 2009
![Page 28: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/28.jpg)
LEED Certification 1 LEED NC V3.0
• Optimize Energy Performance# up to 48% (new) or 44% (existing)
more efficient than ASHRAE 90.1(EA Credit 1) # up to 19 points
• Increased Ventilation# 30% more outdoor air than
ASHRAE 62(IEQ Credit 2) # 1 point
• Controllability of Systems# individual temperature control(IEQ Credit 6.2) # 1 point
• Thermal Comfort# meet ASHRAE 55(IEQ Credit 7.1) # 1 point
(Minimum 40 points needed for certification
out of 100 maximum)
![Page 29: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/29.jpg)
Maintenance
• No moving parts
• No filter
• No condensate pumps
• No consumable parts
• Up to 4 year inspection & clean
• Easy maintenance access
![Page 30: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/30.jpg)
Cleaning Access
![Page 31: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/31.jpg)
Active Chilled Beams 1 Typical Installation
![Page 32: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/32.jpg)
Active Chilled Beams 1 Typical Installation
![Page 33: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/33.jpg)
Active Chilled Beams 1 Typical Installation
![Page 34: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/34.jpg)
Concealed Active Beams
![Page 35: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/35.jpg)
Bulkhead Active Chilled Beams
![Page 36: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/36.jpg)
ACTIVE CHILLED BEAM DESIGN
CONSIDERATIONS
![Page 37: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/37.jpg)
Building Suitability
Building Characteristics that favor Active Chilled Beams
• Zones with moderate#high sensible load densities‒ Where primary airflows would be significantly higher than needed for
ventilation‒ Sensible Heat Ratio’s (SHR) of 0.8 and above
• Buildings most affected by space constraints‒ Hi – rises, existing buildings with induction systems
• Zones where the acoustical environment is a key design criterion
• Laboratories where sensible loads are driving airflows as opposed to air change rates
• Buildings seeking LEED or Green Globes certification
![Page 38: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/38.jpg)
Building Suitability
Characteristics that less favor Active Chilled Beams
• Buildings with operable windows or “leaky” construction
‒ Beams with drain pans could be considered‒ Building pressurization control should be used
• Zones with relatively low sensible load densities
• Zones with relatively low sensible heat ratios and low ventilation air requirements
• Zones with high filtration requirements for the re#circulated room air
• Zone with high latent loads
![Page 39: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/39.jpg)
APPLICATION EXAMPLE:
LABORATORIES
![Page 40: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/40.jpg)
Laboratory Design Issues
• Sensible heat gains of up to 70 BTUH/ft2
• Space ventilation requirements of 6 to 8 ACH
• Laboratories where chemicals and gases are present require 100% outdoor air
• Air systems require 15 to 20 ACH of outside air to
satisfy sensible load
![Page 41: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/41.jpg)
Cooling Load and ACH
![Page 42: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/42.jpg)
Benefits of Active Beams in Labs
• Eliminated or reduced reheat‒ Reheat can account for 20% or more HVAC energy costs
• Water more efficient transport medium‒ Reduces fan energy costs
• Smaller space requirements‒ System sized for 6 ACH instead of 15 ACH
![Page 43: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/43.jpg)
Active Chilled Beam DesignCooling Load = 65 BTU/H ft2
Ventilation Rate = 6 Air Changes
VAV Solution = 15 Air Changes
Chilled Beam Solution = 6 Air Changes
Active Chilled Beam Solution = 6 x 6’ Long, 130 CFM each
![Page 44: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/44.jpg)
Reheat ReductionVAV System ACB System
• Minimum Airflow‒ 6 ACH = 760 CFM
• Cooling Load‒ 65 BTU/H ft2
‒ 41,000 BTU/H Peak
• Maximum Airflow‒ 760 CFM
• Minimum Cooling without reheat‒ 6 ACH @ 65°F
‒ 8,300 BTU/H
• Turndown without reheat‒ 8,300/41,000‒ 80%
• Minimum Airflow‒ 6 ACH = 760 CFM
• Cooling Load‒ 65 BTU/H ft2
‒ 41,000 BTU/H Peak
• Maximum Airflow‒ 1,860 CFM (15 ACH)
• Minimum Cooling without reheat‒ 6 ACH @ 55°F‒ 16,600 BTU/H
• Turndown without reheat‒ 16,600/41,000‒ 59%
![Page 45: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/45.jpg)
CASE STUDIES
![Page 46: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/46.jpg)
250 South Wacker
Chicago, IL
![Page 47: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/47.jpg)
250 S. Wacker, Chicago 1 Case Study
• 16#story tower –215,000 sq. ft. 1st floor retail2 – 16th floor offices
• Separate HVAC systemsfor 1st and 16th floors
• Perimeter induction systemwith floor#mounted unitsserving 2 # 15th floors
• Interior constant volume/variable temperaturesystem serving 2 – 15th floors
![Page 48: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/48.jpg)
250 S. Wacker, Chicago – Case Study
Building Renovated with 1
• 100% glazing with E#glass (190 Btuh/Ln.ft. heat loss)
• Single duct cooling only VAV interior system
• Evaluated fan#powered VAV oractive chilled beamperimeter system
• Seeking LEEDcertification
![Page 49: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/49.jpg)
250 S. Wacker, Chicago – Case StudyPerimeter SystemType
Existing
Induction System
Proposed
Fan#powered
VAV System **
Proposed
Active Chilled Beam System **
Design Cooling Load
262 tons(382 sq.ft./ton)
156 tons(641 sq.ft./ton)
156 tons(641 sq.ft./ton)
Primary Airflow 25,600 cfm(0.5 cfm/sq.ft.)
86,270 cfm
(1.7 cfm/sq.ft.)
15,880 cfm(0.3 cfm/sq.ft.)
Fan Energy at Design
64 kW 182 kW 22 kW
Fan Energy at 70% of Design
64 kW 116 kW 22 kW
Pump Energy 28 kW 8 kW 12 kW
Combined Fan & Pump Energy
92 kW 190 kW @ Design
124 kW @ 70%
34 kW
** Required larger ductwork/risers ** Used existing ductwork/risers
![Page 50: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/50.jpg)
250 S. Wacker, Chicago – Case Study
![Page 51: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/51.jpg)
25 250 S. Wacker, Chicago – Case Study
![Page 52: Chilled Beam and Radiant Cooling Basics - Utah ASHRAEutahashrae.org/wp-content/uploads/2013/12/Chilled Beam Basics.pdf · Chilled Beam and Radiant Cooling Basics ... ASHRAE 2010 Technology](https://reader034.vdocuments.us/reader034/viewer/2022051009/5a78c7137f8b9a83238c4b39/html5/thumbnails/52.jpg)
QUESTIONS?