chapter ii 2

26
Part C: Suppression oJ fire Regulation 10 .1 a grease trap readily removable for cleaning; .2 a fire damper located in the lower end of the duct; .3 arrangements, operable from within the galley,for shutting off the exhaustfans;and .4 fixed means for extinguishing a fire within the duct. Regulation 1,0 Fire fighting 1 Purpose The purpose of this regulation is to suppress and swiftly extinguish a fire in the space of origin. For this pulpose, the following functional requirementsshall be met: .1 fixed fire-extinguishing systems shall be installed, having due regard to the fire growth potential ofthe protected spaces; and .2 fire-extinguishing appliancesshall be readily available. 2 'W-ater supply systems Ships shall be provided with fire pumps, fi.re mains, hydrants and hoses complying with the applicable requirements of this regulation. 2.1 Fire mains and hydrants 2.1.1 Ceneral Materials readily rendered ineffective by heat shall not be used for fire mains and hydrants unlessadequately protected. The pipesand hydrantsshalibe so placedthat the fire hoses m?y be easily coupled to them The "rr".rg.-.nt of pipes and hydrants shall be such as to avoid the possibility of fr,eezing. Suitable drainage pro'oiiion, shail te provided for fire main piping. Isolation valves shall be installed for all open deck fire main branch., .rr.d for purposes other than-fire fighting. In shipswhere deck cargo may b9 carried, the positions of the hydrants shall be such that they are alwaysreadily accessible and the pipes shall be arranged as far as practicable to avoid risk of damage by such cargo. L1.2 Ready auailability of water supply The arrangements for the ready availabiliry of water supply shall be: .1 in passenger ships: .1.1 of 1,000 gross tonnageand upwards such that at leastone effective jet ofwater is immediately available Fro- "ny hldrant in an interior location and so as to ensurethe continuation of the output of water by the automatic startingof one required fire pump; .1.2 of less than 1,000 gross tonnage by automatic start of at least one fire pump or by.remote starting from the naiigation bnJge of at least one fire pump. lf the pump starts automatically or if the bottom valve .it trot be opened from where the pump is remotely started, the bottom valve shall always be kePt oPen; and .1.3 if fitted with periodicallyunattendedmachinery spaces in accordancc with regulation Il-1'154' the Administiation shall determine provisions for fixed water fire-extinguishing arrangements for such spaces equivalentto those required for normally attendedmachinery spaces; .2 in cargo ships: .2.1 to the satisfaction of the Admrnistration; and .2.2 with a periodicallyunattended machinery space orwhen only one personis required on watch, there shallbe immediate water delivcry from the fire main system at a suitable pressure, either by remote starting of one of the main fire pumps with remote starting from the navigation bndge and fire co-ntrol station, if any, or permanent pressurizationof.the fire main systemby on.*of the main fire pumps, excepf that the Administration may waive this requirement for cargo ships of less than i,600 gtos totr.r"ge if the fire pump starting arrangement in the machinery space is in an easily accessible position- 153

Upload: raj-graffiti

Post on 16-Dec-2015

12 views

Category:

Documents


2 download

DESCRIPTION

Chapter II 2

TRANSCRIPT

  • Part C: Suppression oJ fireRegulation 10

    .1 a grease trap readily removable for cleaning;

    .2 a fire damper located in the lower end of the duct;

    .3 arrangements, operable from within the galley, for shutting off the exhaust fans; and

    .4 fixed means for extinguishing a fire within the duct.

    Regulation 1,0Fire fighting1 PurposeThe purpose of this regulation is to suppress and swiftly extinguish a fire in the space of origin. For thispulpose, the following functional requirements shall be met:

    .1 fixed fire-extinguishing systems shall be installed, having due regard to the fire growth potentialofthe protected spaces; and

    .2 fire-extinguishing appliances shall be readily available.

    2 'W-ater supply systemsShips shall be provided with fire pumps, fi.re mains, hydrants and hoses complying with the applicablerequirements of this regulation.

    2.1 Fire mains and hydrants2.1.1 CeneralMaterials readily rendered ineffective by heat shall not be used for fire mains and hydrants unless adequatelyprotected. The pipes and hydrants shali be so placed that the fire hoses m?y be easily coupled to them The"rr".rg.-.nt of pipes and hydrants shall be such as to avoid the possibility of fr,eezing. Suitable drainagepro'oiiion, shail te provided for fire main piping. Isolation valves shall be installed for all open deck firemain branch., .rr.d for purposes other than-fire fighting. In ships where deck cargo may b9 carried, thepositions of the hydrants shall be such that they are always readily accessible and the pipes shall be arrangedas far as practicable to avoid risk of damage by such cargo.

    L1.2 Ready auailability of water supply

    The arrangements for the ready availabiliry of water supply shall be:.1 in passenger ships:.1.1 of 1,000 gross tonnage and upwards such that at least one effective jet ofwater is immediately

    available Fro- "ny hldrant in an interior location and so as to ensure the continuation of theoutput of water by the automatic starting of one required fire pump;

    .1.2 of less than 1,000 gross tonnage by automatic start of at least one fire pump or by.remotestarting from the naiigation bnJge of at least one fire pump. lf the pump starts automatically orif the bottom valve .it trot be opened from where the pump is remotely started, the bottomvalve shall always be kePt oPen; and

    .1.3 if fitted with periodically unattended machinery spaces in accordancc with regulation Il-1'154'the Administiation shall determine provisions for fixed water fire-extinguishing arrangementsfor such spaces equivalent to those required for normally attended machinery spaces;

    .2 in cargo ships:

    .2.1 to the satisfaction of the Admrnistration; and

    .2.2 with a periodically unattended machinery space orwhen only one person is required on watch,there shall be immediate water delivcry from the fire main system at a suitable pressure, eitherby remote starting of one of the main fire pumps with remote starting from the navigationbndge and fire co-ntrol station, if any, or permanent pressurization of.the fire main system byon.*of the main fire pumps, excepf that the Administration may waive this requirement forcargo ships of less than i,600 gtos totr.r"ge if the fire pump starting arrangement in themachinery space is in an easily accessible position-

    153

  • Chapter II-2Regulation

    ' Construction - t'ire protectiln, detection, extinctiln1 0

    2.1.3 Diameter of fre mams

    The diameter of the fi,re main and water service pipes shall be suflicient for the effective distribution of the

    maximum required discharge from tr,vo tir. p.t-p, operating simuftlllout;l ttttp' that in the case oi

    .rrgo rfripr the diametcr r-r.!d only be sufficient for the discharge of 140 m-'/h'

    2.1.4 Isolating ualues and relief ualues

    2.1.4.1 Isolating valves ro separate the section of the fire main within the machinery space.containing the

    main fire pump or pumps from the ..* -oi rh. fire main sliall be fitted

    in an easily accessible and tenablc

    position outside trr. -".'fr".ry ,p"..r. The fire main shall be so arranged that when the isolating valves are

    shut all the hydrants on the ship, except those in the machinery space rJferred to above, can be supplied with

    warer by another fire pump or an emerg.;;t.fit; pyTP. The emergency fire .Pt-p, its seawater inlet' and

    suction and delivery'pry.', and isoladlng ./rLrr"r'shali bc.located outiide thc machinery- space' If this

    arrangement cannor'bJ ir"d., the sea-ch-est may be fitted in the machinery space if the valve is remotelr'

    controlled from a position in the ,"-. .o-p"rtme1t.as.the emergency fire pump and the suction pipe is as

    ,t-,or, ", practicabie. "-Sh;;t

    lengths of s.tction or discharge piping may pcnetrate the machinery spacc'

    provided they are enclosed in aiubstantial steel casing o, # itrr"trt".a t""'A-00" class standards' The pipes

    shall have substantial wall thickness, but in no case jes' than 11 mm' and shall be welded except for the

    flanged connection to the sea inlet valve'

    2.1.4.2 A valve shall be fitted to serve each fire hydrant so that any fire hose may be removed while the fire

    pumps arc in oPeration.

    2.1.4.g Relief valves shall be provided in conjunction with fire pumps if the.pumps are capable ofdeveloping " p..rrrr. ."l..ai"g the design pr.rJ.rr" of the water seryict piptt' hydrants and

    hoses' These

    valves shall be so placed and adjusted as to prevent excessivc pressurc in any part of the fire main system'

    2.1.4.4 In tankers, isolarion valves shall be fitted in the fire main at the poop front in a protected position

    and on the tank deck at intervals of not more than 40 m to preserve the integrity of the fire main system in

    case of fire or exPloston.

    2.1.5 Nunbcr and posit ion of hydranrs

    2.1.5.1 The number and position of hydrants shall be such that at least two jcts of water not emanatinqfrom the same hydrant, one of which rfrrff fr. from a single length of hose, miy reach any part

    of the ship

    normally accessible to the passengers or crew while the -"ship is=being navigated and any part of any cargo

    space when empty, any ro-ro sp1ce. or ally vehicle-space, in which l"tttr tast the nvo iets shall reach anv

    part of the space, .J'ir;; " riJJ"l."gih of hose. Fr]rthermor., ,rr.h hydrants shall be positioned near theaccesses to the Protected sPaces.

    2.1.5.2 In addition to the requirements in paragraph 2'1'5'1' passenger ships shall comply with the

    followinq:

    in the accommodation, service and machinery spaces' the.numbcr and position of hydrants shall

    be such that the ,.q#.-.ni, of p"rrgn ph 2.1'.5.1' may !e co.mplied with when all watertight

    doors and all doors ln main vertical 2"". bulkheads are closed; and

    where access is provided to a machinery space of category A at a low level from an adjacent shahtunnel, two hydranrr th"ll L" p.""id.d e"ternal to,lri near the entrance to, that machinen

    space. 'Where

    such "...r, i, p-iid.a f.o- oth.. spaces, in one of those spaces wvo hydran$ shellbe provided near the "nirrni. to the machinc*p"." of ."tegory A. Such provision need not

    be

    -"d. *h.re the tunnel or adjacent spaces are not part of the escape route.

    . 1

    t54

  • Part C: Suppression of JireRegulation 10

    llI /)rc-t-rrrre at hydrants13, :::r :hc rwo pumps simultaneously delivering water through the nozzles specified. in paragraph 2.3.-3, withfrrr .:'.r.rrrtify of #rr.t as specified in

    -paragaph- 2.1.3, through any adjacent hydrants, the followingr-:-,:::lLlnr pressures shall be maintained at all hydrants:

    0.40 N/mm20.30 N/mm'

    0.27 N/mm20.25 N/mm-

    .l for passenger shiPs:4,000 gross tonnage and uPwardsless than 4,000 gross tonnage

    2 for cargo ships:6,000 gross tonnage and uPwardsless than 6,000 gross tonnageand

    .3 the maximum pressure at any hydrant shall not exceed that at which the eflective control of a firehose can be demonstrated.

    ll.l I,rternational shore connection

    ll 7 | Ships of 500 gross tonnage and upwards shall be provided with at least one international shore- :r--::.:.tiorrcomplying with the Fire Safery Systems Code.

    1,lt2 Facilities shall be available enabling such a connection to be used on either side of the ship'

    U Fire pumps

    221 l)unrps accepted as fire PumPs\:--::.rn'. bal1ast, bilge or general service pumps may-be accepted as fire pumps' provided that they are not=,-.-,.,i1.. ,r.d io, pi*pitig oil and that iithey a,:e subject to^occasional duty for the transfer or pumping of,* :'.:cl. suitable change-over an:angements are tltted.

    ?-22 \'unfter of fire Pumqsr:-::. shall be provided with independently driven fire pumps as follows:

    .l in passenger shiPs of;4,000 gross tonnage and uPwardsless than 4,000 gross tonnage

    .2 in cargo ships of:1,000 gross tonnage and uPwardsless than 1,000 gross tonnage

    223 .lrrangement of fre pumps and fre mains

    I ? 3.1 Fire pumpsl::c.rrrangement of sea connections, fire pumps and their sources of power shall be as to ensure that:

    .l in passenger ships of 1,000 gross tonnage and upwards, in the event of a fire in any onecomparrment, ali the fire p,t-pr will not be put out of action; and

    .2 in passenger ships of less than 1,000 gross tonnage and in cargo llipt, if a fire in any onecomparrment could put all the pumps out of action, there shall be an alternative meansconsisting of ,n .-..gency fire pump complying with the provisions of the Fire Safery SystemsCode with its source 6f po*., -a r." cotrtrectiJtt located outside the space where the main firepumps or their sources of power are located'

    22.3.2 Requirements for the space containing the emergency fire pump

    22.3.2.1Location of the sPace

    .1c space containing the fire pump shall not be contiguoT_to'the boundaries of machincry spaces of....go'ry A or those"spaces .otrt"ltritrg main fire pumpt. Where this is not practicable' the common

    at least threeat least fi,vo

    at least Nvoat least tlvo power-driven pumps' onc ofwhich shall be independently driven

    155

  • Chapter II-2: Construction - Jire protection, detection, extinctionRegulation 10

    bulkhead between the two space s shall bc insulatcd to a standard of structural fire protection equivalent tothat requirecl for a control station.2.2.3.2.2Access to the emergency fire pumpNo direct access shall be perrnitted between the rnachinery space and the space containing the emergency firepump and its source of power. When this is impracticable, the Administration may accept an arrangementwhere the access is by means of an airlock with the door of the machinery space being of "4-60" class standardand the othcr door being at least steel, both reasonably gastight, self-closing and without any hold-backarrangements. Alternatively, the access may be through a watertight door capable of being operated from aspace remote from the rnachinery space and the space containing the emergency fire pump and unlikely to becut offin thc cvcnt of firc in those spaccs. In such cases, a second means of access to the space containing theemergency fire pump and its source of power shall be provided.2.2.3.2.3 Ventilation of thc emergency fire pump spaceVentilation affangements to the spacc containing thc independent source of power for the emergency fircp.u'rr'):\N\t:rrfn a:\s pret\rr\e, a:\ar as pracircbo\e, tne posi\o\rg o\ srr-ro\e\rorn a mac\rnery spacehrcentering or being drawn into that space.2.2.3.3 Additional pumps for cargo shipsIn addition, in cargo ships where otherpurnps, such as general service, biige and ballast, etc., are fitted in rmachinery spacc, arrangemcnts shall be made to ensurc that at least onc of these pumps, having the capacrnand pressure required by paragraphs 2.1 .6.2 and2.2.1.2, is capable of providing water to the fire main.2.2.4 Capacity of

    .fire pumps2.2.4.1 Total capaciry of required fire pumpsThc required firc pumps shall be capable of dclivering for firc-fighting purposes a quantity of watcr, at the'pressure specified in paragraph 2.1..6, as follows:

    .l pumps in passenger ships: the quantity of water is not less than two thirds of the quandnrequired to be dealt with by the bilgc pumps whcn cmployed for bilge pumping; and

    .2 punlps in cargo ships, other than any emergency punlp: the quantiry ofwater is not less than fourthirds of the quantity required under regulation II-1/35-1 to be dealt with by each of thtindependcnt bilge purnps in a passcngc'r ship of thc same dimension when employed in bilgcpun1pu1g, provided that in no cargo ship need the total required capaciry of the fire pumpscxceed 180 ni-'/h.

    2.2.4.2 Capaciry o{ 'erch f i rc punrpEach of the rcquired fire pumps (other than any emergency pump required in paragraph 2.2.3.1.2 for cargoships) shall have a capacity not less than B0%r of the total required capacity divided by the minimunrnumber of rcquired fire pumps, but in any case not lcss than25 mt/h, and each such pump shall in anvevent be capable of delivering at least the two required jets of water. These fire pumps shall be capable ofsupplying the fire nlain system under the required conditions. Where more punps than the minimum ofrequired pumps are installed, such additional pumps shall have a capaciry ofat lc'ast 25 nr3/h and shall bccapable of dclivering at least the two jets of water requircd in paragraph 2.1.5.1.2.3 Fire hoses and nozzles

    2.3.1 Cencral spcci,fications2.3.1.1 Fire hoses shall be of non-perishable naterial approved by the Administration and shall be suflicientin length to project a jet of water to any of the spaces in which they may be required to be used. Each hoseshall be provided with a nozzle and thc necessary couplings. Hoses specified in this chapter as "fire hoses"shall, together with any nccessary fittings and tools, be kcpt ready for usc in conspicuous positions near thewater service hydrants or connections. Additionally, in interior locations in passenger ships carrying morethan 36 passenllers, fire hoses shall be connected to the hydrants at all times. Fire hoses shall have a length ofat least 10 m, but r-tot morc than:

    .l 15 rn in machinery spaces;

    1 5 6

  • Part C: Suppression oJ ltreRegulation 10

    20 nr in othcr spaces and open decks; and25 nr for open decks on ships with a maximum breadth in excess of 30 nr.

    in the ship, there shall bc conplcte23.1.2 Unlcss one hose and nozzle is providcd for each hydrant:.'rchangeabiliry of hose couplings and nozzles.

    23.2 \nmber dnd diameter of lire hoses

    ?3.2.1 Ships shall be provided with fire hoses, the number and diameter of which shall be to the:. t ict ion of thc At l t t r in istrat ion-

    23.2.2 I' passengcr ships, there shall be at least one fLre hose for each of the hydrants recluircdby paragraph.5 ancl these hoses'shall be used only for the purposes of extitrguishing fires or testing the fire-

    :rnqr.tishing apparatus at fire drills and surveys'

    23.2.3 ln cargo shiPs:

    .2

    .3

    . 1 of 1,0(X) gloss tonnage and upwards, the number of fire hoses to b-e provided.shall bc onc for"".1r :O nilength of ih. ship and olre spare, but in no case less than five in all. This nun-rber doesnot include ",-t:y hos., required in any engine-room or boiler room' The Administration mayincrease the number of hoies required so as"to ensure that hoses in suflicient number are availableand accessible at all timcs, having regard to the type of ship and the natlrre of trade in which the,6rp i, enployed. Ships carryitfi dittg"tous goods in aciordance with regulation 19 shall be

    f.J"id.d *irh,hr.. hoses and Jozzlei in addition to those required above; and

    of less than 1,000 gross tonnage, thc number of firc hoses to be provided shall .bc calculatcd in"f.o.d"n.. -lth the provisionJof paragraph 2.3.2.3.1. However, the number of hoses shall in nocase be less than three.

    2 3.3 S'i":e and typts oJ nozzles

    23.3.1 For the purposes of this chaptcr, standard ttozzle sizes shall bc 12 mn-r, 16 mnr and 19lrrn or as. ,r rSereto ", porribl.. Larger diameter nozzles may be permitted at the discretion of the Adrninistration'

    Z3.l.Z For acconrnrodation and service spaces, anozzle size greater than 12 mm nccd not bc uscd'

    2 3.3.3 For rnachinery spaces and exterior locations, thc nozzle size shall be such as to obtaitr the maximum..11l..g. possible fro-'r*o jets at the pressure mentioned in paragraph 2.L.6 fron the smallest pLlmp',,i.lcld that a 'ozzle size gieatcr than 19 mm need not be used.

    2 3.3.4 Nozzles shall be of an approvcd dual-purpose fype (i'e. spray/jet type) incorporating a shr'rtofl'

    3 Portable fire extinguishers*3 1 Type and design

    ,rr:rblc fire cxtinguishers shall conrply with the rcquirements of the Firc Safcry systcms code '

    3.2 Awangement of fire extinguishers

    3.2.1 AcconrmocJation sp:rccs, scrvice spaces and control stations shall be provided with portable-.firc..ti'suishers of rpprop.'i"te rypes and jn',sutlicient number to the satisfaction of thc Admrnistratiore' Ships' f ,tXtO gro*, tor't,-t"g. altd upwards shall carry at lcast five portablc firc extinguishers'

    3.2.2 One of the portable fire ertinguishers intended for use in any space shall be stowed near the cntrance, that space.

    3 2.3 Clarbon dioxicle fire extinguishers shall not be placed in accommodation spaccs. In control statiollsr.l other spaces cont;ing eleitrical or electronic equiprlent or appliances necessary for the safety of the

    ia..ti.r," ,h.. hrprovcd (luiclclines for nrarinc portablc fire cxtinguishers adopted by-the Orgaruzation by resolution A 951(23).r U'ilicd i'terprctatron of SC)LAS chapter II-2 on the rrurnbeiand arrangement of portable {ire extinguis}rcrs on board ships

    ' . 1 \ ( 1 . 1 / C i r c . 1 2 7 5 ) .

    157

  • Chapter II-2Regulation

    Construction - t' ire protection, detection, extinctiln1 i )

    sl-rip, fire ertinguishers shall bc providcd whosc extingurshing media are neither electricaily conductive norharmful to the equipment and appliances.

    3.2.4 Fire extinguishers shall be situated ready for use at easily visible places, whigh can be reached quicklvand casily "t "n! time in drc cvent of a fire, and in such a way that their serwiceability is not impaircd by therveathcr, vibraiion or other external factors. Portable fire extinguishers shall be provided with deviceswhich indicate whether they have been used.

    3.3 Spare charges3.3.1 Spare charges shall be provided for I00%t of the first ten extinguishcrs and 50(/o of the remaining fireexting;ishers cJpable of being recharged on board. Not more than sixty total spare charges are required.Instructions for recharging shall be carried on board.

    3.3.2 For fire ertingpishers which cannot be recharged on board, additional portable firc extinguishers.of thesame quanrlry, rype, capacity and number as determined in paragraph 3.3.1 above shall be provided in lieu ofsparc cnargcs.

    4 Fixed fire-extinguishing systems

    4.1 Types of fixed fire-extinguishing systems

    4.1.1 A fixed firc-extinguishing system rcquired by paragraph 5 below may bc any of the followrng systems:.t a fixed gas fire-extinguishing system complyingwith the provisions of the Fire SaGry Systems

    Code ;a fixed high-expansion foam fire-extinguishing systenr complying with the provisions of the FircSaGry Systems Code; anda fixed pressure water-spraying fire-extinguishing system complying with the provisions of theFire SaGry Systems Code.

    4.1.2 Where a fixed fire-extinguishing system not required by this chapter is installed, itrequirements of the reievant regulations of this chapter and the Fire SaGty Systems Code.

    4.1.3 Fire-extinguishing systems using Halon 1211, 1301., and 2402 and per{luorocarbons shall beprohibited.4.1,4 In general, the Administration shall not permit the use of steam as a fire-cxtinguishingrnedium infixed firelextinguishing sysrems. Where the use of steanl is permitted by the Adnin'stration, it shail be usedo1ly in restrictJd ,r."r-", an addition to the required fire-extingr-rishing systen and shall comply with therequirements of the Fire Safety System Code.

    4.2 Closing appliances for fixed gas fire-extinguishing systems

    Where a fixed gas fire-extinguishing system is used, openings which may admit air to_, or allow gas to escapefrom, a protecied space shall be capable of being closed from outside the protected space.

    4.3 Storage rooms oJfre-extinguishing medium

    When the fire-extinguishing medium is stored outside a protected space, it shall be stored in a room whichis located behind thJforward collision bulkhead, and is uscd for no other purposes. Any entrance to such astorage room shall preferably be from thc open deck and shall be indcpendent ofthc protected spacc..If the,to."!. space is located below deck, it shall be located no more than one deck below the open deck

    -andshall ie directly accessible by a stairway or ladder from the open deck. Spaces which are located below deckor spaccs whcie acccss from the open dcck is not provided shall bc fitted with a nrechanical ventilationsystem designed to take exhaust air from the bottom of the space and shall be sized to provide at least 6-air.h"ng., p"i'ho.rr. Access doors shall open ouf\,vards, and bulkheads and decks, including doors and.other-."trr of closing any opening therein, which form the boundaries between such rooms and adjacentenclosed spaces shall be gastight. For thc purpose of thc application of tables 9.1 to 9.8, such storage roomsshall be treated as fire control stations.

    meet the

    1 5 8

  • Part C'. Suppression oJ JireRegulation 10

    4.4 Water pumps for other fire-extinguishing systemsl)umps, other than those serving the fire main, required for the provision of water for fire-extinguishing\\'stems required by this chapter, their sources of power and their controls shall be installed outside the\pace or spaces protected by such systems and shall be so arranged that a fire in the space or spaces protectedu'ill not put any such system out of action.

    5 Fire-extinguishing arrangements in machinery spaces

    5.1 Machinery spaces containing oil-fired boilers or oilfuel wnits

    5.1.1 F ixed fire-extinguishing sy stems\lachinery spaces of category A containing oil-fired boilers or oil fuel units shall be provided with any one,f rhe fixed fire-extinguishing systems in paragraph 4.1.In each case, if the engine-room and boiler room,rc not cntirely separate, or if fuel oil can drain from the boiler room into the engine-room, the combined- nqine and boiler rootrls shall be considered as one compartment.

    5.1 .2 A ddi t io n dl f re - e x t ingu i sh i ng arra ngeme n t s*5.1.2.1 There shall be in each boiler room or at an entrance outside of the boiler room at least one portable' ',uri applicator unit complyingwith the provisions of the Fire Safety Systems Code.

    5.12.2 Thete sha\\ be at \east t\rvo po$ab\e foam extinguishets or equi\alert in each {rtrng space in eachIroiler room and in each soace in which a oart of the oil fuel installation is situated. There shall be not lessrhan one approved foanr-rype extinguisher of at least 135 /capacity or cquivalent in cach boilcr room.These extinguishers shall be provided with hoses on reels suitable for reaching any part of the boiler room.hr the case of domestic boilers of less than 175 kW an approved foam-type extinguisher of at least 135 /capacity is not required.5.1.2.3 In each firing space there shall be a receptacle containing at least 0.1 m-3 sand, sawdust impregnatedri'ith soda, or other approved dry material, along with a suitable shovel for spreading the material. An-rpproved portable extinguishcr may be substituted as an alternative.

    5.2 Machinery spaces containing internal combustion machinery

    5.2.1 F ixed fre-extinguishing sy stems\{achinery spaces of category A containing internal combustion machinery shall be provided with one of:hc fixcd fire-cxtinguishing systems in paragraph 4.1.

    5.2.2 A d d i ti o nal fi re - e x t ingu i sh i ng a rra nge m e nt s*5.2.2.1 There shal1 be at least one portable foam applicator unit complying with the provisions of the Fire:,rfcry Systems Code.5.2.2.2 There shall be in each such space approved foam-rype fire extinguishers, each of at least 45 I capaciqr,,r' equivalent, sufficient in number to enable foam or its equivalent to be directed onto any part of the fuel andLrbricating oil pressure systems. gearing and other fire hazards. In addition, there shall be provided a sufficient:rumber of portable foam extinguishers or equivalent which shall be so located that no point in the spacc is:rrore than 10 m walking distance from an extinguisher and that there are at least two such extinguishers in,'rch such space. For smaller spaces of cargo ships the Administration may consider relaxing this requirement.

    5.3 Machinery spaces containing steam turbines or enclosed steam engines

    5.3.1 F ixed -fire-ex tinguishing sy stems

    In spaces containing steam turbines or enclosed steam engines used for main propulsion or other purposes:rlving in the aggregate a total output of not less than 375 kW, one of the fire-extinguishing systems specified:n paragraph 4.1 shall be provided if such spaces are periodically unattended.

    I\efer to Unified interpretation of SOLAS chapter II-2 on the number and arrangement of portable fire extinguishers on boardrrps (MSC. 1/Cuc.1.27 5).

    1 5 9

  • Chapter II-2:Regulation

    Construction - fire protection, detection, extinction10

    5.3.2 A ddit i o n al fi re - e x tingu i sh i ng a rr a nge m e n t s

    5.3.2.1 There shall be approved foam fire extinguishers, each of at least 451 capaciq' or.equivalent,sufficient in number to enable foam or its equiialent to be directed on to any-p_art of the pressure

    lubrication system, on to any part of the casingsinclosing pressure-lubricatcd-parts of the turbincs, engines

    or associared gearing, ;"J ;;y other fire haz"ards. Howiver, such extingufu!.Tt. shall not be required if

    prorection, at least equivalent to that required by this subparagraph, is provided in such spaces by a fixedh..-.*tirrg.rishing ,yri.- fitted in compliance with paragraph 4'1'

    5.3.2.2 There shall be a suficient number of portable foam extinguishers* or equivalent which shall be so

    located thar no point in the space is more than 1o m walking- distince from an extinguishct- 11jl1:ltTare at least rwo su.h extinguishers in each such space, eT.gp! that such extinguishers shall not be requlred ln

    addition to any providedln compliance with paragraph 5'1'2'2'

    5.4 Other machinetY sqaces'w'here, in the opinion of the Administration, a fsre hazard exists in any machinery space-for which, no

    #;;tfi; p.o.ririo,is for firc-extinguishing appliances are.prescribed in paragraq\s 5,1, 5'2 and 5'3' there shall

    be provided in, or adjacent to, that space's'u.h " number of approved portibl. fire extinguishers or other-."r* of fire extinction as the Administration may deem sufficient.

    5.5 Additional requirements Jor passenger ships

    In passenger ships carrying more- than36 passengers' each machinery space of category A shall be provided*ith at lelst two suitable water fog applicators'f

    5.6 Fixed local application fire-extinguishing systems

    5.6.1 Paragraph 5.6 shall apply to passenger ships of 500 gross2,000 gross tonnage and above.

    tonnage and above and cargo ships of

    b.6.2 Machinery spaces of category A above 500 m3 in volume shall, in addition_-to *:,it9"_1t::s . u , & r v r @ v t u r r v r / v r eextinguishing ryrr"- i.q;;;;;"rlgraph 5..1.1, be protected by an approved,Yq:-:ffi1:.1^f::o*:*:A;i;?ffiiili;;ii."";; n;5:i;",1"'ryishing 'v*"i', ui'gi "i-:l: *f9'*':.,*::1*9-Y",:*L U U r V q r l r r ( r v r s r q H td.e"i"",i"n.1 In ;[.-.; of periodicillv ""it'"{9{ rycninery spac.es] :-l: T;:Yfl'^*':qJ,'j::Jn"?i'rr"".'u.rrr r"r.*#;"d;;;;;l;;#ase capabilities. In the case^of continuously-manned machinery,pr..r, the fire-extinguishing system is only required-to have a manual release capability'

    b.6.3 Fixed local application fire-extinguishing systems are to protect areas such as the following without

    th. r-r...rriry of etrgitt. shutdown, perionnel bvacuation, or sealing of the spaces:

    .l the fire hazardportions of internal combustion machinery used for the ship's main propulsionand power generation;boiler fronts;the fire hazard portions of incinerators; andourifiers for heated fuel oil.

    5.6.4 Activation of any local application system shall give a yilya.l and distinct audible d":--tl:|1t:t"S:l;;';;;;;;;ilil;""'""J ;;;;;- in. ,1",- shatl indicat:-,:l_..1p..11.-y.':":"1:,,:::*,Tl:,il;#;;;;;;;;;; a"'.'iu"a wllh1n this paragraqh a1e in addition to, and not a substitutc for, thei.t".ti." and fiie alarm system required elsewhere in this chapter.

    . R.{L,r- r" Ur"fied interpretation of SOLAS chapter II-2 0n the number and arrangement of portable fire extinguishcrs on boardships (MSC.1/Circ.127 5).r A warer fog applicator might consist of a me-tal L-shaped pipe, the long linrb being about 2 m in length, capable

    of being fitted to a

    fire hose, and the short limb being about 250 mm t;i.;gl,li, fiti"d *iih a fixed uiater fognozzre oi capable of being fitted with a

    water spray nozzle.I Refer to the Guidelines for the approval of fixed water-based local application fire-fightin^g systems

    for use in category A

    machinery spaces (MSC/Circ.g13), Utiinggl11*nrerations of the Guidelittir fo. the "ppto,ril of fixed water-based local applicationfire-fighting sysrcms (MSC/Circ.913) (MSC/Circ.tOAz; atra Unified interpretationstf Soras chapter II-2 (MSC'1/Circ'1'276)'

    .2

    .3

    .4

    160

  • Part C: Suppression oJ t'ireRegulation 10

    6 Fire-extinguishing arrangernents in control stations, accommodation and service spaces

    6.1 Sprinkler and water-spraying systems in passenger ships

    6.1.1 Passenger ships carrying more than 36 passengers shall be equipped with an automatic-sprinkler, fire.lctection "id fi.. "1"r- iyrt"- of an approved rype complying with the requirements of the Fire Safety\\-stems Code in all control stations, accommodation and service spaces, including corridors and stairways.\lternatively, control stations, where water may cause damage to essential equipment,,may be fitted with an,;.,proved fixed firc-extinguishing system of another rype. Spaces having_littlc or no fire risk such as voids,,.,rbli. toilets, carbon dioxide roo-r and similar spaces need not be fitted with an automatic sprinkler.\'stem.

    6.1.2 In passenger ships carrying not more than 36 passengers, when a fixcd smoke detection and fire alarm.\'srem i"mplyr"g with the piovisions of the Fire Safery Systems Code is provided ""ly 11 corridors,.rrirways ,trd .r.ip. routes within accommodation spaces, an automatic sprinkler system shall be installed::r rrccordance with regulation 7.5.3.2.6.1 .3 A fixed pressure water-sprayrng fire-extinguishing system complying with_ the provisions of the

    .Fire',.rfc'ty Systemi Code shall be rnstalled on cabin balconies of ships to which regulation 5.3.4 applies,yhg.:, , ; . , . r r i iu reandfurn ish ingsonsuchba lcon iesarenotasdef ined in regu la t ions3.40 .1 ,3 .40 .2 ,3 .40 .3 ,3 .40 .6,nc' l 3.40.7.

    6.2 Sprinkler systems for cargo ships.:r c:rrgo ships in which method IIC specified in regulation 9.2.3.L1.2 is adopted, an automatic sprinkler,::rc cle-Icction and fire alarm system shall be fitted in accordance with the requirements in regulationT.5-5.2.

    6.3 Spaces containingflammable liquid

    5.3.1 Paint lockers shall be protected by:.l a carbon dioxide system, designed to give a minimum volume of free gas equal to 40o/o of the

    gross volume of the protected space;.2 a dry powder system, designed for at least 0.5 kg powder/m3;.3 a water spraying or sprinkler system, designed for 5 lfm2 min. Water spraying systems may be

    connected to the fire main of the ship; or.4 a system providing equivalent protection, as determined by the Administration.

    .:r :rll cases, the system shall be operable from outside thc protected space.

    6.3.2 Flarnmable liquid lockers shall be protccted by an appropriate fire-extinguishing arrangementi'Proved by the Administration.

    6.3.3 For lockers of a deck area of less than 4 m2, which do not give access to accommodation spaces, a:.,.,rtable carbon dioxide fire extingursher sized to provide a minimum volume of frce gas eqrlaf to 40(% of::rc gross volume of the tp".. -ry be accepted in lieu of a fixed system. A discharge port shall be arranged;1 tf,e locker to allow the discharge of the extinguisherwithout having to enter into the protected space.f6e required portable fire extinguisher shall be itowed adjacent to the port. Alternatively, a port or hose.rnnection may be provided to facilitate the use of fire main water.

    6.4 Deep-fat cooking equltment. )cep-fat cooking equipment shall be fitted with the following:

    .l an automatic or manual fire-extinguishing system tested to an international standard acceptableto the Organization;*

    .2 a primary and baikup thermostat with an alarm to alert the operator in the cvent of failure ofcither thermostat;

    I\efcr ro the recornmendations by rhe International Organization for Standardization, in particular publication ISO 15371:2009,':ttps and marine terhnology - Fire-extinguishing systems for protection of galley cooking equipment.

    t61

  • Chapter II-2: Construction - Jire protection, detection, extinctionRegulation 10

    arrangements for automatically shutting off the electrical power upon activation of the fire-extinguishing system;

    .4 an alarm for indicating operation of the fire-cxtinguishing system in the gallcy wherc theequipment is installed; and

    .5 controls for manual operation of the fire-extinguishing systern which are clearly labelled forready use by the crew.

    7 Fire-extinguishing arrangements in cargo spaces7.1 Fixed gas fire-extinguishing systems for general cargo

    7.1.1 Except as provided for in paragraph 7.2,the cargo spaces ofpassenger ships of 1,0()0 gross tonnage ancupwards shal b! protected by i fixed iarbon dioxide or inert gas fire-extinguishing system complying withthe provisions ofihe Fire Safety Systems Code or by a fixed high-expansion foam fire-extinguishing systemwhich grves cquivalent protection.7.1.2 Where it is shown to the satisfaction of the Administration that a passenger ship is engaged on voyagesof such short duration that it would be unreasonable to apply the requirements of paragraphT.l.l and alsoin ships ofless than 1,000 gross tonnage, the arrangements in cargo spaces shall-bc to the satisfaction of theAdministration. provided ihat the ship is fitted with steel hatch covers and effective means of closing allventilators and othe. opcnings leading ro the cargo spaces.

    7.1.3 Except for ro-ro and vehicle spaces, cargo spaces on cargo ships of 2,000 gross tonnagc' and upwards shallbe protected by a fixed carbon dioxide or ineit gis fire-extinguishing system complying with the provisions ofthe Fire SaGry Systems Code, or by a fire-extinguishing system which gives equivalent protection.

    7.1.4 The Admrnistration may exempt from the requirements of paragraphs 7.1.3 and7.2 cargo spaces of an1'cargo ship if constructed, and solely intended, for the carriage of ore, coal, grain, unseasoned timber, non-.oirburtitle cargoes or cargoes which, in the opinion of the Administratiou, constitute a low fire risk.. Suchexemptions *ry t . g."ut.d only if the ship is fitted with steei hatch covcrs and cffectivc means of closingallventilators and' other openings leading io the cargo spaces. When such exemptions are granted, theAdnrinistration shall issue an Exemption Certificate, irrespective of the date of construction of the shipconcerned, in accordance with regulation l/12(a)(vi), and shall ensurc that the list of cargoes the ship ispermitted to carry is attached to the Exemption Certificatc.

    7.2 Fixed gas fire-extinguishing systems for dangerous goods

    A ship engaged in the carriagc of dangerous goods in any cargo spaccs shall bc providcd with a fixed carbondioxiie oi inert gas fire-extinguishing system complying with the provisions of the Fire SaGry SystemsCode or with a dre-extinguishing syJt.m which, in the opinion of the Administration, gives equivalentprotection for the cargocs carried.

    I Cargo tank protection8.1 Fixed deck foam fire-extinguishing systems8.t.1 For tankers of 20,000 tonnes deadweight and upwards, a fixed deck foam fire-extinguishing systenlshall be provided complying with the provisions of the Fire Safety Systems Code, except that, in lieu of theabove, tire Adminirttrliotl, ift.r having given consideration to the ship's arrangement and equipment, mavaccept other fixed installations if they- afford protection equivalent to the abovc, in accordance withreguiation I/5. The requirements for alternative fixed installations shall cornply witli the requirements inparagraph 8.1.2.8.1.2 In accordance with paragraph 8.1.1, whcre the Administration accepts an equivalent fixed installationin lieu of the fixed deck foam fire-extinguishing system, the installation shall:

    .t be capable of extinguishing spill fires and also preclude ignition of spilled oil not yet ignited; and

    .2 be capable of combating fires in ruptured tanks.

    . I\cfer to the Code of Safe Practice for Solid Buik Cargocs, enlergcncy schcdule B1,1, entry for coal, and to thc Lists of solid bulkcarlloes for which a fixed gas fire-extinguishing system is ineffective (MSC.1/Circ.1146).

    .3

    162

  • Part C; suppression of lrreRegulation 10

    8.1.3 Tankers of less than 20,000 tonnes deadweight shall be provided with a deck foam fire-extinguishing.'.\reln complying with the requirements of the Fire Safery Systems Code.

    9 Protection of cargo pump-rooms in tankers

    9.1 Fixed fire-extinguishing systems: rch cargo pulnp-rooln shall be provided with otre of the following fixed fire-extinguishing systL'lns..ratcdhom a riadily accessible pbsition outside thc pump-room. Cargo pump-rooms shall be provided,.:th a system suitable for machinery spaces of category A.

    9. 1 .l A carbon dioxide fire-extinguishing system complying with the provisions of the Fire Safery Systenrs, '.1c and with thc following:

    .1 the alarms giving audible warning of the release offire-extinguishing rnedium shall be safe for uscin a flamrnable cargo vapour/air nixture; and

    .2 a noticc shall bc cxhibited at the controls stating that, due to the electrostatic ignition hazard, thcsystem is to bc used only for fire cxtinguishing and not for inerting purposes.

    Ll.2 A high-expansion foan fire-extinguishing systcnr complyingwith the provisions of the Fire Safcty\..:rcmS Cod., providcd that thc foam loncentrate supply is suitable for cxtinguishing fircs invoiving tirc

    ,rgocs carrlecl.9.1.3 A fixed pressurc water-spraying fire-extinguishing system complying with the provisions of the Firc. , t i rv Systenrs Code.

    9.2 Quantity oJfire-extinguishing mediumI'here the fire-extinguishing medium used in thc cargo pump-room systen is also used in systems serving:hcr spaccs, the quantiry oimedium providcd or its delivery rate nccd not be morc than the maximum,.prired for the largest compartment.

    l0 Fire-fighter'soutfits

    10.1 Types of fire-fighter's owtfits, ::'c-fishter's outfits shall cornply with the Fire Safery Systems Code.

    10.2 Number of fire-fi.ghter's outfits10.2.1 Ships shall carry at least two fire-fighter's outfits.

    10.2.2 In addition, in passenger ships there shall be provided:.1 for every B0 m, or part thereof, of the aggregate of the lengths of all passenger spaces and. serwice

    spaces on the deck which carrics such spaces or, if therc is morc than one such deck, on the dcckwhich has the largest aggregate of such lengths, two fire-fighter's outfits and, in addition, rwosers of personal equiprnent, each sct comprising the items stipulated in the Fire Safery SystcmsCode. it-r p"s"ng.. thipr carrying more than 36 passengers, Nvo additional fire-fighter's outfitsshall be provided for .".h main vertical zonc. However, for stair:way enclosures which constitutcindividull main vertical zones and for the main vertical zones in the fore or aft end of a shipwhich do not contain spaces of categories (6), (7), (8) or (12) defined in regulation9.2.2.3,noadditional fire-fightcr's outfits are rcquired; and

    .2 on ships carrying more than 36 passengers, for each pair of breathing apparatus, one water fogapplicator which shall be stored adjacent to such apparatus.

    10.2.3 In addition, in tankers, two firc-fighter's outfits shall be provided.

    10.2.4 The Administration rnay require additioreal sets of personal equipment and breathing apparatus,n-ing due regard to the size and fype of the ship.

    10.2.5 Two spare charges shall be provided for each required breathing apparatus. Passenger ships carrying\)r more than 36 prir.ng"rt ,trd .rrgo ships that are equipped with suitably located means for fully

    t63

  • Chapter II-2: Construction - t'ire protection, detection, extinctionRcsulation 11

    recharging the air cylinders free from contamination need carry only one spare charge for cach requiredapparatus. In passenger ships carrying nlore than 36 passengers, at least two spare charges for each breathingapparatus shall bc provided.

    10.3 Storage of fire-fighter's outfits10.3.1 The fire-fighter's outfits or sets of personal equipment shall bc kept ready for use in an easilr'acccssible location that is pcrmanently and clcarly marked and, where morc than or-rc firc-fiehter's outfit ormore than one set of personal equipment is carried, they shall be stored in widely separated positions.

    10.3.2 In passcltger ships, at least fwo fire-fighter's outfits and, in addition, one set ofpersonal equiprnent shallbe availablc at any onc position. At lcast two fire-fightcr's outfits shall be storcd in each nrain vertical zone.

    Regulation 11Structttral inteqrity1 PurposeThe purpose of this regulation is to maintain structural integrity of the ship, preventing partial or wholccollapse of th. ship structures due to strength deterioration by heat. For this purposc, uraterials uscd in thcships' strrrcture shall ensltrc that the structural integrity is not dcgraded duc to fire.

    2 Material of hull, superstructures, structural bulkheads, decks and deckhousesThc hull, supcrstrllctures, structural bulkheads, decks and deckhouscs shall be constructed of steel or othcrequivalent miterial. For the purpose of applying the definition of steel or other equivalent tnaterial as given irrregulation 3.43, the "applicable fire exposure" shall be according to the integrity and insulation standardsgiven in tables 9.1 to9.4. For example, where divisions such as dccks or sides and ends of deckhouses arcpermittcd to have "B-0" fire intcgriry, the "applicable firc cxposure" shall be half an l-rour.

    Structure of aluminium alloylJnless othcrwise spccified in paragraph 2, in cascs where any part of thc structure is of alutniniurn al1oy, tl-rcfollorving shall apply:

    .1 thc insulation of aluminium alloy conlponents of "A" or "B" class divisions, except structllrcwhich, in the opinion of the Administration, is non-load-bearing, shall be such that thcrenrperarure of the structural core does not rise more than 200'C above the ambient temperaturcat any time during the applicable fire exposure to the standard firc test; andspccial attention shall be givcn to the insulation of aluminium alloy componernts of columns.stanchions and other structural members required to support lifeboat and lifcraft stowage.launching and embarkation areas, and "A" and "B" class divisions to ensure:

    that for such n-rcmbers supporting lifcboat and lifcraft arcas and "A" class divisions, thctemperature rise limitation specified in paragraph 3.1 shall apply at the end of one hour; andthat for such nrembers required to support "8" class divisions, the tempcrature rise limitationspccified in paragraph 3.'l shall apply at the cnd of half an hour.

    Machinery spaces of category A

    Crowns and casingsCrowns and casings of nrachinery spaces of category A shall bc of steel construction and shall bc insulated asrequired by tables 9.5 and 9.7, as appropriate.

    4.2 Floor platingThe floor plating of nonnal passageways in machinery spaces of category A shall be rnade of steel.

    .2 .1

    4.1

    r64

  • Part C: Suppression of t'ireRegulation 11

    5 Materials of overboard fittingsMaterials readily rendered ineflective by heat shall not be used for overboard scuppers, sanitary discharges,.rnd other outlets which are close to thc waterlinc and wherc the failurc of the matcrial in the event ofh..rvould give rise to danger of flooding.

    6 Protection of cargo tank structure against pressure or vacuum in tankers6.1 CeneralThe venting arrangemcnts shall be so designed and opcrated as to cnsure that neitl-rer prcssure nor vacuumrn cargo tanks shall exceed design parametcrs and be such as to provide for:

    .1 the flow of the small volumes ofvapour, air or inert gas mixtures caused by thermal variations ina cargo tank in all cases through pressure/vacuurn valvcs; and

    .2 the passage of large volurnes of vapour, air or inert gas mixtures during cargo loading andballasting, or during discharging.

    6.2 Openings for small Jlow by thermal uariationst)penings for pressure release required by paragraph 6.1.1 shall:

    .1 have as great a hcight as is practicablc above thc cargo tank deck to obtain maximunr dispersal offlantmable vapours, but in no case less than 2 m above the cargo tank deck; and

    .2 be arranged at the furthest distance practicable, but not lcss than 5 rn, from the nearest air intakcsand.openings-to-cnclosed spaces containing r sourcc of ignition and fi-orn dcck machincry andequipment which may constitute an ignition hazard. Anchor windlass and chain locker openingsconstitute an ignition hazard.

    6.3 Sofety measures in cargo tanks

    6.3.1 Preuentiue measures against liquid rising in the uenting systemI)rovisions shall be made to guard against liquid rising in the venting sysrcnl to r height which would:sceed the design head of cargo tanks. This shall be accomplished by high-level alarms or overflow control.\'stems or other equivalent means, together with independent gauging devices and cargo tank filling:.rocedures. For the purposes of this regulation, spill valves are not considered equivalent to an ovcrflow. \-5tem.

    6.3.2 Secondary means for pressuref uacuum relie;f\ secondary mcans of allowing full flow relief of vapour, air or inert gas rnixtures shall bc provided toprcvent over-prcssure or under-pressure in the event of failure of the arrangements in paragraph 6.1 .2.\lternatively, pressure sensors may be fitted in each tank protected by the arrangenlent required inr:rragraph 6.1 .2,with a monitoring system in the ship's cargo control room or the position fronr which..rrgo operations are normally carried out. Such monitoring equipment shall also provide an alann facility''rhich is activated by detection of over-pressurc or under-pressure conditions within a tank.

    6.3.3 Bypasses in uent mainsI're ssure/vacuutn valves required by paragraph 6.1.1 may be provided with a bypass arrangernent when they.rre located in a vent main or masthcad riser. 'Where such an arrangenrent is provided therc shall be suitablerndicators to show whether thc bypass is open or closcd.

    6.3.4 Pre s suref uacuum - breaking deuic e s()ne or morc pressure/vacuum-brcaking devices shall bc provided to prevent thc cargo tanks from being.trbject to:

    . 1

    .2

    a positive pressure, in excess of the test pressure of the carlo tank, if the cargo were to be loadedat the maximum rated capaciry and all othcr outlets are left shut; anda negative pressure in excess of 700 mm water gauge if the cargo were to be discharged at themaximum rated capacity of the cargo pumps and the inert gas blowers were to fail.

    1 6 5

  • Chapter II-2: Construction - Jire protection, detection, extinctionRegulation 11

    Such devices shall be installed on the inert gas main unless they are installed in the venting system requiredby regulation 4.5.3.I or on individual cargo tanks. The location and design of the devices shailbe inaccordance with regulation 4.5.3 and paragraph 6.

    6.4 Size of uent outletsVcn_t outlets_for cargo loading, discharging and ballasting required by paragraph 6.1.2 shall be designed onthe basis of the maximum designed loading rate multiplied by a factor ofat leist 1.25 to take account ofgasevolution, in order to prevent the pressure in any cargo tank from exceeding the design pressure. Thelnaster shall be provided with information regarding the maximum permissible loading rate for each cargotank and, in the case of combined venting systems, for each group of cargo tanks. n

    .\

    tT*

    tAf 4

    t{

    R,.rII

    2z l

    22

    t1 r

    r66

  • Part D: EscapeRegulation 13

    Part DEscape

    Regulation 12\-otification of crew and passengers

    I PurposeI-hc purpose of this regulation is to notifii crcw and passcngers of a firc for safe evacuation. For this purpose,, qeneral emergency alarm system and a public address systen shall be provided.

    2 General emergency alarrr system\ qeneral emergency alarm system required by regulation 11116.4.2 shall be used for notifying crew and:r.lssengers of a fire.

    3 Public address systems in passenger ships\ public address system or other effective means of comrnunication complyng with the requirements of:'.'qulation IIV6.5 shall bc available throughout the accommodation and service spaces and control stations,nd open decks.

    Regulation 13\[t'ans of escapeI Purposef he purpose of this regulation is to provide means of escape so that persons on board can safely and swiftly- \cf,pe to the lifeboat and liferaft embarkation deck. For this purpose, the following functional requirements.ir.r1l bc rnet:

    .1 safe escape routes shall be provided;

    .2 escape routes shall be maintained in a safe condition, clear of obstacles; and

    .3 additional aids for escapc shall be provided as nccessary to ensure accessibiliry, clcar marking, andadequate design for emergency situations.

    2 General requirements2.1 lJnless expressly provided otherwise in this regulation, at least rwo widely separated and ready means't cscape shall be provided from all spaces or groups of spaces.

    2.2 Lifts shall not be considered as forming one of the means of escape as required by this regulation.

    3 Means of escape from control stations, accommodation spaces and service spaces

    3.1 General requirements3.1.1 Stair-ways and laddcrs shall be so arranged as to provide ready means of escape to the liGboat andrtbraft embarkation deck from passenger.and crew accommodation spaces and from spaces in which the- rcw is normally employed, other than machinery spaces.

    3.1.2 Unless cxpressly provided othcrwise in this regulation, a corridor, lobby, or part of a corridor from.i hich there is only one route of escape shall be prohibited. Dead-end corridors used in setwice areas which,re necessary for the practical utilify of the ship, such as fuel oil stations and athwartship supply corridors,

    1 6 7

  • Chapter II-2: Construction - Jire protection, detection, extinctionRegulation 13

    shall be permitted, provided such dead-end corridors are separated from crew accommodation areas and areirra.cerribl. from passenger accommodation areas. Also, a part of a corridor that has a depth not exceedingits width is considered J recess or local extension and is permitted.

    3.1.3 All stairways in accommodation and service spaces and control stations shall be of steel frameconstruction except where the Administration sanctions the use of other equivalent material'

    3.t.4 If a radiotelcgraph station has no direct access to the open deck, Nvo means of es,c-ape from, or accessio, the sration ,6"1t 6. provided, one of which may be a porthole or window of sufficient size or othernleans to the satisfaction of the Administration.

    3.1.5 Doors in escape routes shall, in general, opcn in way of the direction of escape, except that:

    .l individual cabin doors may open into the cabins in order to avoid injury to persons thecorridor when the door is opened; and

    .2 doors in vertical emergency escape runks may open out of the trunk in order to permit thetrunk to be used both for escape and for access'

    3.2 Means of escape in passenger ships-

    3.2.1 Escape from spaces below the bulkhead deck

    1.2.1.1 Below the bulkhead deck, two means of escape, at least one of which shall be independent ofwatertight doors, shall be provided from each watertighi compartment or similarly restricted -space or groupof ,p"cJr. Exceptionally, th. Admini-stration maydispense wilh one of the neans of escape-for-crew spacesthat^are .r-rt.r"d only occasionally, if the required "t."p. route is independent of watertight doors'

    3.2.1.2 Where the Administration has granted dispensation under the provisions of paragraph 3.2'1'1, thissole means of .r."p. ,h"f pro"id. ,"f.".r."p.. However, stairways shall not be less than 800 mm in clearwidth with handrails on both sidcs.

    3.2.2 Escape from spaces aboue the bulkhead deck

    Above the bulkhead deck there shall be at least Nvo means of escape from each main vertical zone orsimilarly restricted space or group of spaces, at least one ofwhich shall give access to a stairway forming avertical escape.

    3.2.3 Direct a(rcss to stairway cnclosuresStairway enclosures in accommodation and service spaces shall have direct access from the corridors and beof a su{ficient area to prevent congestion, having in view the number of persons likely to use them in an.-.rg.rr.y. Within t'fr. p..i-"tJr of-such stiirway enclosures, only public toilets, lockers of non-combustible material pro.ridir.g storage for non-haz"rdont safery equipme-nt and open information counters,r. p.r-itted. Only public ,p"...r, Jorridors, lifts, public toilets, special category spaces and open ro-ro,p".i., to which "ny pirr.nge rs carried_ can have "...rr, other escape itairways required by paragraph 3 '2 '4 '1and external areas "'i. p.r"*i,red to have direct acccss to these stairway.enclosures. Small corridors or,,lobbies" used to ,"p"."t. an enclosed stairway from-galleys,or main laundries may have direct access to the,;;;y provided they have a minimum deck area of-4.5 m2, a width of no less than 900 mm and contain afire hose station.

    3.2.4 Detaik o-f means oJ escaPe

    1.2.4.1 At least one of the means of escape required by paragraphs 3.2.1.1 and 3.2.2 shall consist of a readilyaccessible enclosed ri"i.*"y, which shali provid".otriitrrois ire shclter from the level of its originto the"ppropri"t" lifeboat and lifeiaft embarkation decks, or to the uppermost weather deck if the embarkationdeck does not extend to the main vertical zone being consid.ied. In the latter case, direct access to theembarkarion deck bf -"y' of external cipen stairways* and passlggwals shall be provided and shall haveemergency lighting in ,..o.d"nce with iegulation itrytt.S^anaihp-fte. sufaces underfoot. Boundariesfacin!' ."tlrnil opJn stairways and p"rr"g.#"y, forming part of att es."p. route and boundaries in such a

    Rcfer to the Guidelines for evacuarion anaiysis for new and existing passenger ships (MSC.1/Circ.1238)'

    168

  • Part D: EscapeRegulation 13

    position that their failure during a fire would impede escape to the embarkation deck shall have fireintegriry, including insulation values, in accordance with tables 9.1 to 9.4, as appropriate.

    3.2.4.2 Protection of access from the stairway enclosures to the lifeboat and liferaft embarkation areas shallbe provided either directly or through protected internal routes which have fire integrity and insulationvalues for stairway enclosures as determined by tables 9.1 to 9.4, as appropriate.

    3.2.4.3 Stairways serving only a space and a balcony in that space shall not be considered as forming one ofthe required means of escape.3.2.4.4 Each level within an atrium shall have f\,vo means of escape, one ofwhich shall give direct access toan enclosed vertical means of escape meeting the requirements of paragraph 3.2.4.1.

    3.2.4.5 The widths, number and continuity of escapes shall be in accordance with the requirements in theFire Safety Systems Code.

    3.2.5 Marking of escape routes3.2.5.1 In addition to the emergency lighting required by regulationsll-1,142 and III/11.5, the means ofe-scape, including stairways and exits, shall be marked by lighting or photoluminescent strip indicatorsplaced not more than 300 mm above the deck at all points of the escaPe route, including angles andintersections. The marking must enable passengers to identiSr the routes of escape and readily identify theescape exits. If electric illumination is used, it shall be supplied by the emergency source_ of power and rt.hali be so arranged that the failure of any single light or cut in a lighting strip will not result in the markingbeing ineflectiv;. Additionally, escape route signs and fire equipment location markings_ shall be ofphotoluminescent material or marked by lighting. The Administration shall ensure that such lighting orphotoluminescent equipment has been evaluated, tested and applied in accordance with the Fire SaGrySystems Code.3.2.5.2 In passenger ships carrying more than36 passengers, the requirements of the paragraph 3.2.5.1 shall.rlso apply to the crew accommodation areas.

    3.2.6 Normally locked doors that form part of an esrupe route

    3.2.6.1 Cabin and stateroom doors shall not require keys to unlock them from inside the room. Neithershall there be any doors along any designated escape route which require keys to unlock them whenrnoving in the direction of escape.

    3.2.6.2 Escape doors from public spaces that are normally latched shall be fitted with a means of qrrickrelease. Such means shall consist of Jdoor-latching mcchanism incorporating a device that releases the latchupon the application of a force in the direction of escape flow. Quick release mechanisms shall be designec.rnd installed to the satisfaction of the Administration and, in particular:

    .l consist of bars or panels, the actuating portion of which extends across at least one half of thewidth of the doofleaf, at least 760 mm and not more than 1.,1.20 mm above the deck;

    .2 cause the latch to release when a force not exceeding 67 N is applied; and

    .3 not be equipped with any locking device, set screw or other arrangement that prevents therelease of the latch when pressure is applied to the releasing device.

    3.3 Means of escape in cargo ships

    3.3.1 GeneralAt all levels of accommodation there shall be provided at least two widely separated means of escape fromcach restricted space or group of spaces.

    .

    3.3.2 Escape from spaces below the lowest open deck

    Below the lowest open deck the main means of escape shall be a stairway and the second escape may be arrunk or a stairway.

    r69

  • Chapter II-2: Construction - t'ire protection, detection, extinctionRegulation 13

    3.3.3 Escape Jrom spaces aboue the lowest open deck

    Above the lowest open deck the means of escape shall be stairways or doors to an open deck or acombination thereof.

    3.3.4 Dead-end corridors

    No dead-end corridors having a length of more than 7 m shali be acceptcd.

    3.3.5 Width and cttntinuity of escape routesThe width, number and continuiry of escape routes shall be in accordance with the requirements in theFire Safery Systems Code.3.3.6 Dispensation from two means of escape

    Exceptionally, the Administration may dispense with one of the ncans of escape,_for crcw spaces that are.nt.rid only occasionally, if the required escape route is independent of watertight doors.

    3.4 Emergency escape breathing devices3.4.1 Emergency escape breathing devices shall comply with the Fire Safery Systems Code. Spareemergency escape breathing devices shall be kept on board.

    3.4.2 All ships shall c^rry at least rwo cmergency cscape breathing devices within accotnmodation spaces.

    3.4.3 In all passenger ships, at least f\,vo emergency escape breathing devices shall be carried in each mainvertical zone.

    3.4.4 In all passenger ships carrying rnore than 36 passengers, t\tvo emergency escape breathing devices, inaddition to those lequired in paragraph 3.4.3 above, shall be carried in each main vertical zone.

    3.4.5 However, paragraphs 3.4.3 and 3.4.4 do not apply to staitway enclosures which constitute individualmain vertical zones itrd to the main vertical zones in the fore or aft end of a ship which do not containspaces of categories (6), (7), (B) or (12) as defined in regulation 9.2.2.3.

    4 Means of escape from machinery spaces

    4.1 Means of escape on passenger shipsMcans of escape from cach machinery space in passenger ships shall comply with thc following provisions-

    4.1.1 Escape Jrom spaces below the bulkhead deckWhere the space is bclow the bulkhead deck, the two mcans of escape shall consist of either:

    .1 Nvo sers of steel ladders, as widely separated as possible, leading to doors in the upper part of thespace, similarly separated and from which access is provided to the appropriate lifeboat andliferaft embarkation decks. One of these ladders shall be locatcd within a protected enclosure thatsarisfies regulation 9.2.2.3, category (2), or regulation 9.2.2.4, category (4), as appropriate, fromthe lower part of the space it serves to a safe position outside the space. Seltclosing fire doors ofthe same fire integrity .standards shall be fitted in the enclosure. The ladder shall be fixed in sucha way that heat is not transGrred into the cnclosure through non-insulated fixing points. Theprotected enclosure shall have minimum intcrnal dimensions of at least fl00 mm x 800 mm,and shall have emergency lighting provisions; or

    .2 one sreel ladder leading to a door in the upper part of thc space from which access is providcd to theembarkation deck and additionally, in the lower part of the space and in a position well separatedfrom the ladder referred to, a steel door capable of being operated from each side and whichprovides access to a safe escape route from the lower part of the space to the embarkation deck.

    4.1.2 Escape from spaces aboue the bulkhead'deckWhere the space is above the bulkhead deck, the two means of escape shall be as widely separated aspossible and the doors leading from such means of escape shall be in a position from which access isprovided to the appropriate lifbboat and liferaft embarkation decks.

    'Where such means of escape require the

    use of ladders, these shall be of steel.

    t70

  • | 1.3 Dispensation from two means of escape.r ship of less than 1,000 gross tonnage, the Administration may dispense with. one of the means of

    .,.,;.,., hr. regard being paii to rhc wiJth and disposition of the upper part of the spacc- ln a ship ofl( ) gross tonnage and"a6orre, the Administration may dispense with one means of escape from any such

    ,- ,;c. including a-nor-ally unattended auxiliary machineryspace, so long as either a door or a steel ladder, ,r,iclcs a ,"fe".r.ap. r.o.ri. to the embarkation deck, duc regard being paid to the nature and location of

    .

    - \pacc and whether persons are nonnally employcd in that space. In thc stecring_gcar space,a scc.ond-.,16 of .r."pe shall be provided when the emergency steering position is located in that space unless there-irrect access to the oPen deck.

    11.4 Escapefrom machinery control rooms

    . ... tr 'reans of escape shall be provided from a machinery control room located within a machinery space,.

    .elsr one of whiih will provide continuous fi.re shelter to a saG position outside the machinery space.

    | 2 Means of escape on cargo shiPs,.,.,..rr.rs of escape from each machinery space in cargo ships shall comply with the following provisions.

    12.1 Escapefrom machinery spdces o;f category A

    i ..;cpr as provided in paragraph 4.2.2, nvo mcans of escape shall_be provided from each machinery spacc o1:.Sory A. Ir. parti.nir., or. of the following provisions shall be complied with:

    .l rwo sets of sreel ladders, as widely separated as possible, leading to doors in the 9pp:t part^of thcspace, similar\ separated and from which "c..tt is provided to the open dcck. One of thcseladders shall be located within a protected enclosure that satisfies regulation 9.2'3.3, category (4),from the lower part of the spac-e it serves to a safe position outside the space- Self-closing firedoors of the ,r-. fir. integriry standards shall be fined in the enclosure. The ladder shall be fixedin such a way rhat heat is iot transferrcd into thc enclosurc through non-insulatcd fixing pgiltl:The enclosuie shall have minimum internal dimensions ofat least 800 mm x 800 mm, and shal-have emergency lighting provisions; or

    .2 one steel laddcr leading to a door in the upper part of thc spacc fromwhich access is provided torhe open deck and, ad?itionally, in the lower part of the Jpace and.in a position well separatedfrom the ladder referred to, a steel door capaLle of being operated from each side and whichprovides access to a saG escape route from the lower part of the spacc to thc open deck.

    1.2.2 Dispensation from two means of escape

    .r ship of le ss than 1,000 gross tonnage, the Administration may dispens. _*-t.th one. of the means of escape

    -

    - .1,,ire'd under paragraph 4"2.1., dur' r."gard being paid to the dimension and disposition of the upper part.of. r.: ,p.... tn adiitioin, ih. -"rn, of erJape from machinery_spaces of category A need not comply with the--.1,,i 'rement for an enclosed fire sheltei listed in paragraph-4.2.1 .1'.In the steering gear space, a sec-ond, .1.,.,, of .r.ape shall be provided when the .-.tg*.yite.ritrg position is located in that space unless there. Jircct access to thc oPcn deck.

    1.2.3 Escape;from machinery spdces other than those of category A

    i :,rn machinery spaces other than those of category A, tr;vo escape routes shall be provided except that a.::rgle escape route may be accepted for spaces tliat are entered only occasionally and for spaces where thc:r.r-ximum-travel distance to the door is 5 m or less.

    4.3 Emergency escape breathing deuices

    4.3.1 On all ships, within the machinery spaces, emgrgengy escape b.reathing devices shall be situated ready. )r use at casily visible places, which ."n b. rcachcd q"l.t iy and casily at,anl time ir-r the cvent of firc. The,eation of emergency'escape breathing devices shalftake into account the layout of thc machinery space

    .:rcl the number of p.rronJtto.ttrally working in the spaces'*

    Part D: EscapeRegulation 13

    l{efer to thc Guidelines for the performance, location, use and care of emergency escape brcathing devices (MSC/Circ'849)'

    . J

    171

  • Chapter II-2: ConstructionRegulation 13

    - Jire protection, detection, extinction

    4.3.2 The number and location of these devices shall be indicated in the fire control plan requiredregulation 15.2.4.4.3.3 Emergcncy escape breathing devices shall comply with the Fire Safety Systems Code.

    Means of escape on passenger ships from special category and open ro-ro spacesto which any passengers carried can have access

    5.1 In special category and open ro-ro spaces to which any passengers carried can have access, the numberand locations of the means of escape both below and above the bulkhead deck shall be to the satisfaction of thcAdministration and, in gencral, the saGry of access to the embarkation deck shall bc at least equivalent to thatprovided for under paragraphs 3.2.1,. I ,3.2.2,3.2.4.1 and 3.2.1.2. Such spaces shal l be provided srrhdesignated walkways to the means of escape with a breadth of at least 600 mm. The parking arrangemenrs tb,rthe vehicles shall maintain the walkways clcar at all timcs.5.2 One of the escape routes from the machinery spaces where the crew is normally employed shall avoiddirect access to any special category space.

    Means of escape from ro-ro spacesAt least f\,vo means of escape shall be provided in ro-ro spaces whcrc the crew are normally employcd. Theescape routes shall provide a safe escapc to the lifeboat and liGraft embarkation decks and shall be located atthe fore and aft ends of the space.

    7 Additional requirements for ro-ro passenger ships7.1 General7.1.1 Escape routes shall be provided from every normally occupicd space on the ship to an assemblsstation. These escape routes shall be arranged so as to provide the most direct route possible to the assemblvstation,* and shall be marked with symbols based on the guidelines developed by the Organization.t7.1.2 The escape routc from cabins to stairway enclosures shall be as dircct as possiblc, with a minimunrnumber of changes in direction. It shall not be necessary to cross from one side of the ship to the other toreach an escape route. It shall not be necessary to climb more than rwo decks up or down in order to reachan assembly station or open deck from any passcnger space.7.1.3 External routes shall be provided from open decks, as referred to in paragraph7.l.2, to the survivalcraft embarkation stations.7.1.4 Where enclosed spaccs adjoin an open dcck, openings from the enclosed spacc to the open dcck shall.where practicable, be capable of being used as an emergency exit.7.1.5 Escape routes shall not be obstructed by furniturc and other obstructions. 'With the exccption of tablcsand chairs which may be cleared to provide open space, cabinets and other hearl' furnishings in publicspaces and along escape routes shall be secured in place to prevent shifting if the ship rolls or lists. Floorcoverings shall also be secured in place. When the ship is under way, escape routes shall be kept clear ofobstructions such as cleaning carts, bedding, luggage and boxes of goods.

    7.2 Instruction for safe escape7.2.1 Decks shall be sequentially numbcred, starting with "1" at the tank top or lowest deck. Thc numbersshall be prominently displayed at stair landings and lift lobbies. Decks may also be named, but the decknumber shall always be displayed with the name.7.2.2 Simple "mimic" plans showing the "you are here" position and escape routes marked by arrows shallbe prominently displayed on the inside of each cabin door and in public spaces. The plan shall show thedirections of escape and shall be properly oriented in relation to its position on the ship.

    - Refer to Indication of the assembly stations in passcngcr ships (MSC/Circ.777).r Refer to Symbols related to life-saving appliances and arrangernents adopted by thc Organization by resolurion A.760(18), asamended by resolution MSC.82(70).

    t 72

  • Part D: EscapeRegulation 13

    7 3 Strength of handrails and corridors7 3.1 Handrails or other handholds shall be provided in corridors along the entire escape route so that a firm

    :r,-'lhold is availablc at evcry step of the way, where possiblc, to thc assembly stations and embarkation-

    ,iieps. Such handrails shall be piovided on both sides of longitudinal corridors more than 1.8 m in width::l rransverse corridors more thin 1 m in width. Particular attention shall be paid to the need to be able to- ,.s lobbics, atriums and other large open spaces along escape routes. Handrails and othcr handholds shall. ,rf such srrength as to withstand a diitribulcd horizontal load of 750 N/m applied_in the direction of the.:rrre of the clrridor or space, and a distributed vertical load of 750 N/m applied in the downward

    '::rction. The two loads need not be applied simultaneously.

    7 3.2 The lowesr 0.5 m ofbulkheads and other partitions forming vertical divisions along escape routes shall- .rble to sustain a load of750 N/m to allow them to be used as walking sufaces from the side ofthe escape

    - :rtc with the ship at large angles of heel.

    t 4 Euacuation analysis*: .i.rpe routes shall be evaluated by an evacuation analysis early in the design proce-ss. The analysis shall be

    .-'.1 ro identifir and eliminatc, as far as practicable , congcstion which may develop during an abandonment,:.:. ro norm"i-orr"-.nt of passengeis and crew along escape routes, includingthe possibiliry that crew,.1. leed to move along these rout; in a direction opposite to the movement of passengers. In addition,

    .

    .. llalysis shall be.rr"Jto dcmonstrate that escape arrangements are sufficiently flexiblc to provide for the:- ,.sibiliry that certain escape roures, assembly stitions, embarkation stations or survival craft may not be

    rilable as a result of a casualry.

    Refer to thc Guidelines for evacuation analysis for new and existing passcnger ships (MSC.1/Circ.1238).

    173

  • Chapter II-2: Construction - Jire protection, detection, extinctionRcgulation 14

    Part EOperational requirements

    Regulation 14Operational readiness and mdintenance

    1 PurposeThe purpose of this regulation is to maintain and monitor the eflectiveness of tl-re fire safery measurcs theship is provided with. For this purposc, thc following functiorral requirements shall be met:

    .1 fire- protection systems and fire-fightins systens and appiiances shall be maintained ready for use;ancl

    .2 fire protection systerns and fire-fighting systcrxs and appliances shaii be properly tested andlnspectccl.

    2 General requirementsAt all times while the ship is in service, the requirements of paragraph 1 .1 shall be cornplied with. A ship isnot in service when:

    .1 it is in for rcpairs or lay-up (either at anchor or in port) or in dry-dock;

    .2 it is dcclared not in service by the owlrer or the owner's representative; and

    .3 in the case of passengcr ships, thcrc arc no passcnllcrs on board.

    2.1 Operationalreadiness2.1.1 Thc following firc protcction systenrs shal1 be kept in good order so as to cnsurc thcir rcquiredperformance if a fire occurs:

    ,t structural fire protection, including fi.re-resisting divisions, and protection of openings andpcr.rctrations in thcsc divisions,

    .2 fire dctcction and fire alarm systens; rnd

    .3 means of cscapc systerns and appliances.2.1.2 Firc-fighting systcms and applianccs shall bc kcpt in good working order and readily available forimnrediate use. Portablc extinguishers which have been discharged shall be imrnediately recharged orrcplaced with an equivalent unit.2.2 Maintenance, testing and inspections2.2.1 Maintenance, testing and inspections shall be carried out based on the guidelines developcd by theC)rganization* and in a nranner having duc regard to cnsuring the reliabiliry of fire-fighting systerls andapprlances.2.2.2 Thc maintcnance plan shall bc kcpt on board the ship and shall be available {br inspection wheneverrequired by the Administret iorr .2.2.3 The maintenance plan shall include at least the following fire protection systems and fire-fightingsysterns and applianccs, whcrc installcd:

    .1 fire mains, fire purnps and hydrants, including hoses, nozzlcs and intcrnational shoreconnections;

    .2 fixed fire detection and fire alarm svstems;

    l\cti'r to thc Guidclines on tnaintcnancc and inspcction of firc protcction systenrs and applianccs (MSC/Circ.850).

    174

  • Part E: Operational requirementsRegulation 15

    .3 fixed fire-extinguishing systems and other fire-extinguishing appliances;

    .4 automatic sprinkler, {ire detection and fire alarm systems;

    .5 vcntilation systems, including fire and smoke darnpers, fans and their controls;

    .6 emergency shutdown of fuel supply;

    .7 fire doors, including their controls;

    .8 gencral emergency alarm systems;

    .g emergency escape breathing devices;

    .10 portable fi.re extinguishers, including sparc chargcs; and

    .t 1 fire-fighter's outfits.

    2.2.4 The maintenance programme may be computer-based.

    3 Additional requirements for passenger ships

    In addition to the firc protecion systcms and appliances listcd in-16 passengers shall develop a maintenance plan for low-location

    4 Additional requirements for tankers

    In addition to the firc protection systems and appliances listedl)laintenancc plan ltor:

    .1 inert gas systems;

    .2 deck foam systems;

    .3 fire safery arrangements in cargo pump-rooms: and

    .4 flammable gas detectors.

    paragraph 2.2.3, ships carrying more thanlighting and public address systems.

    in paragraph 2.2.3, tankers shall havc a

    Regulation 15lnstructions, on-board training and drills

    1 PurposeThe purpose of this regulation is to mitigate thc consequences,of firc by mcans of proper instructions forraining ind drills ofpeisons on board in correct procedures under emergency conditions. For this purpose,rhe crei.v shall have the necessary knowledge and skills to handle fire emergency cases, including passengercare.

    2 General requirements

    2.1 Instructions, duties and organization

    2.1.1 Crew members shall receive instruction on firc safery on board thc ship.

    2.1.2 Crew members shall receive instructions on their assigned duties.

    2.1.3 partics responsiblc for firc exringuishing shall bc organized. These parties shall have the capabiliry tocomplete their duties at all times while the ship is in service.

    2.2 On-board training and dills

    2.2.1 Crew members shall be trained to be familiar with the arrangements of the ship as well as the locationand operation of any fire-fighting systems and appliar-rces that they may be called upon to use.

    Z.Z.Z Training in the use of the emergency escape breathing devices shall be considered as part of on-boardtraining.

    175

  • Chapter II-2: Construction - t'ire protection, detectiln, extinctionRegulation 15

    2.2.3 Performance of crew members assigned fire-fighting duties shall be periodically evaluated bycond^ucting on-board training and drills to identify areas in need of improvement, to ensure competcncy infire-fighting skills is maintained, and to ensure the operational readiness of the fire-fighting organization.2'2'4 On-board training in the use of the ship's fire-extinguishing systems and appliances shall be plannedand conducted in accordance with the provisions of regulationlIIl19.4.1.2'2.5 Ffte drills shall be conducted and recorded in accordance with the provisions of regulations III/19.3and I I I /19.5.

    2.3 Training manuals2'1'1 A training manual shall bc provided in each crcw mess room and recreation room or in each creucaDln.

    2.3.2 The training manual shall be writrcn in the working language of the ship.2'3'3 The training manual, which may comprise several volumes, shall contain the instructions andinformation rcquired in paragraph 2.3.4 in easily understood terms and illustrated wherever possible . Anr.part of such information rnay be provided in the form of audio-visual aids in lieu of the manual.2.3.4 The training manual shall cxplain the following in detail:

    .1 general fire saGty practice and precautions related to the dangers of smoking, electrical hazards.flarnmable liquids and similar cornmon shipboard hazards;

    .2 general instructions on fire-fighting activities and fire-fighting procedurcs, including procedurcsfor notification of a fire and use of manuallv operated call ooints:

    .3 meanings of the ship's alarrns;

    .4 operation and use of fire-fighting systems and appliances;

    .5 operation and use of fire doors;

    .6 operation and use of fire and smoke dampers; and

    .7 escape systems and appliances.

    2.4 Fire control plans*2,4.1 General arrangement plans shall be perrnanently exhibited for the guidance of the ship's oftrcers.showing clearly for each deck the control stations, the various fire sections enclosed by "A" class divisions.the sections enclosed by "8" class divisions together with particulars of the firc detection and fire alanlsystems, the sprinkler installation, the fire-extinguishing appliances, means of access to differenrc.ompartments, decks, etc., and the ventilating system, including particulars of the fan control positions.the position of dampers and identification numbers of the ventilating fans serving each section.Alternatively, at the discretion of the Administration, the aforementioned details may be set out in abooklet, a copy of which shall be supplied to each ofTicer, and one copy shall at all times be available onboard in an accessible position. Plans and booklets shall be kept up to date ; any alterations rhereto shall bcrecorded as soon as.practicable. Descnption in such plans and booklets shall be in the languagc or languagcsrequired by the Administration. If the language is neither English nor French, a translation into one-ofthose languages shall be included.

    2.4.2 A duplicate set of fire control plans or a bookiet containing such pians shall be perrnanently srored in apromrnently marked weathertight enclosure outside the deckhouse for the assistance of shore-side fire-fightinsoersonnel. t

    - Rcfcr to Clraphical symbols for shipboard fire control plans, adopted by the Or:ganization by resolution A.952(23).l Re{br to the Guidancc concerning the location of fire control plans for assistance of shoresidc fire-fighting personnel (MSCCi rc . '151) .

    176

  • Part E: Operational requirementsRegulation 16

    3 Additional requirements for passenger ships

    3.1 Fire drillsln addition to the requirement of paragraph2.2.3, fire drills shall be conducted in accordance witlr thcprovisions of regulation IIV30, having due iegard to notification of passengers and movement of passengersto assembly stations and embarkation decks.

    3.2 Fire control plansIn ships carrying more than 36 passengers, plans and booklets required by- this regulation shall provrdeinformation i.g;rai"g fire proteciion, fire deiection and fire extinction based on the guidelines developedby the Organization."

    Regulation 16Operations1 PurposeThe purpose of this regulation is to provide information and instructio-ns for proper ship and cargo.handling,rp.."tio6 in relation to fire safety. For this purpose, the following functional requiretnents shall be nret

    .1 fire safery operational booklets shall be provided on board; and

    .2 flammable vapour releases from cargo tank venting shall bc controllccl.

    2 Fire safety operational booklets

    2.1 The required fire safety operational booklet shall contain the necessary information and instructionstor the saG oiperation of the'ship and cargo handling operations in relation to fire safety. The booklet shallrpclude infonlation concerning the criv's ..rpo^ibilities for the general fire saGty of the_ship whileloading and discharging cargo ".rd *hil. under way. Necessary fire safety plgcagtions for handling general."rgo.i shall be e*pi"iried. For ships carrying dangerous goods and flammable bulk cargoes, the fire saferyopJrational booklei shall also provide referen-ce to th. pertinent-fire-fighting and emergency cargo handlingrristructions contained in the Code of Safe Practici for Solid Bulk Cargoes, the International BulkChemical Code, the International Gas Carrier Code and the International Maritime Dangerous GoodsCode. as appropriate.2.2 The fire saGty operational booklet shall be provided in each crew mess room and recreation room orin each crew cabin.

    Z.l The fire safery operational booklet shall be written in the working language of the ship.

    The fire safety operational booklet may be combined with the training manuals required in regula-15.2.3.

    Additional requirements for tankers

    Generalfhe fire safery operational booklet referred to in paragraph 2 shall include provisions for preveuting fire.pread to the'."[o area due to ignition of flammible vapours and include procedures of cargo tank gas-;'urging and/or gis-freeing, taking into account the provisions in patagtaph 3.2.

    3.2 Procedures for cargo tank purging andf or gas-freeing

    3.2.1 When the ship is prbvided with air inert gas system, the cargo_tanks shall first be purged_in accordanceri.ith the provisioni ofiegulation4.5.6 until the concentration of hydrocarbon vapours in the cargo tanks

    ' l{eGr to the Guidelines on rhe information to be provided with fire control plans and bookiets required by SOLAS regulationsll-2120 and 41-2, adopted by the Organization by resoiution A.756(18)'

    2.4rion

    33 .1

    177

  • Chapter II-2: Construction - Jire protection, detection, extinctionResulation 16

    has bce n reduced to less than 2o/o by volume. Thereafter, gas-free ing may take place at the cargo tank deck1evel.

    3.2.2 When the ship is not provided with an inert gas system, the operation shall be such that the flammablevapour is dischargcd initially through:

    .l the vent outlets as specified in regulation 4.5.3.4;

    .2 oudets at least 2 m above the cargo tank deck levcl with a vertical efflux velocity of at least 30 m/smaintained during the gas-freeing operation; oroutlets at least 2 m above the cargo tank deck level wrth a vertical efilux velociry of at least 20 m/sand which are protected by suitable devices to prevent the passage of flame.

    3.2.3 The above outlets shall be located not less than 10 m, measured horizontally, from the nearest airintakes and openings to enclosed spaces containing a source of ignition and from deck machinery, whichmay include anchor windlass and chain locker openings, and equipment which may constitute an ignitionhazard.

    3.2.4 When the flammable vapour concentration at the outlet has been reduced to 30o/o of the lowerflammable limit, gas-freeing may be continued at cargo tank deck level.

    178