chapter 6 selection, installation and wiring of ex certified electrical equipments

Upload: jackckc866

Post on 06-Apr-2018

228 views

Category:

Documents


3 download

TRANSCRIPT

  • 8/3/2019 Chapter 6 Selection, Installation and Wiring of Ex Certified Electrical Equipments

    1/7

    33

    CHAPTER 6SELECTION, INSTALLATION AND

    WIRING OF Ex CERTIFIEDELECTRICAL EQUIPMENT

    Under the Division 1 classification, wire terminations

    are considered ignition sources.

    6.1 UNDERSTANDING THE DIFFERENCE INZONE VS DIVISION INSTALLATION METHODSTerminations are the key to understanding the differences in

    installation methods of Zone and Division rated equipment.

    Under the Zone system wire terminations rated as Ex-e,

    increased safety, are not considered sources of ignition.

    Terminations are tested to ensure that they do not heat up or

    vibrate loose and have sizable creepage and clearance

    distances to prevent arcing. Under the Division 1 classification,

    wire terminations are considered sources of ignition as it is

    assumed they could vibrate loose, short out and create an arc.

    This results in major differences in the way products are

    designed. To illustrate this refer to the push-button control

    stations shown below. Both stations contain an explosion-

    protected contact block. The one on the left is rated

    explosionproof for Division 1 and has an explosionproof metallic

    housing. The one on the right is rated flameproof and increased

    safety for Zone 1 and has a non-metallic housing. Each contact

    block prevents arcs from switch operations inside from igniting

    gases within the control station. Why then must the contact

    block located in a Division 1 area be housed in an

    explosionproof enclosure while the Zone 1 rated control

    stations is in a non metallic enclosure?

    The Division 1 control station has a metallic enclosure.

    The Zone 1 version has a non-metallic enclosure.

    Under the Division 1 system, wire terminations areconsidered ignition sources. If volatile gases and air accumulate

    inside an explosionproof enclosure and are ignited by the spark

    from a wiring fault on the terminals, the enclosure must contain

    the explosion. As the hot gases escape the enclosure by passing

    across a flat or threaded or serrated joint, they cool so they can

    no longer ignite gaseous mixtures in the hazardous area. In a

    Division 1 area, the contact block must be housed inside an

    explosionproof enclosure rated for the area.

    Explosionproof Contact Block in Division 1 Area

    Wire terminations are considered sources of ignition for Division 1 products.

    An explosionproof enclosure for the contact block is required.

    Under the Zone system, wire terminations are not considered

    an ignition source if they are rated as Ex-e or increased safety.

    If the contact block is rated flameproof with increased safety

    terminals, the switch can be housed in an increased safety

    housing, e.g. a non metallic enclosure that has a suitable

    construction and an IP rating to protect against moisture and

    dusts.

    Ex-de Contact Block with Increased Safety

    Terminals in Zone 1 Area

    Ex-e Wire terminations are not considered sources of ignition for Zone 1

    products, and Ex-de contacts can be housed in non metallic enclosures

    suitable for Zone 1.

    Determining which system is safer, less expensive or easier to

    install is very difficultsomewhat like comparing the metric and

    US systems of measurement. Each application has its own

    merits and depends on user preference, as well as how the

    areas are classified, and the wiring systems used in the facility.

    At the present time North American users have the advantage

    of being able to use either type of product in Division 2.

    Cooper Crouse-Hinds Ex DigestSelection, Installation and Wiring of Ex Certified Electrical Equipment

    Division 1 Vs. Zone 1

    Potential Ignition Source?

    Not a Source of Ignition

  • 8/3/2019 Chapter 6 Selection, Installation and Wiring of Ex Certified Electrical Equipments

    2/7

    Equipment listed and marked for use in Class I,Zone 0, 1, or 2 locations shall be permitted in Class I,

    Division 2 locations for the same gas and with asuitable temperature rating.

    6.2 STANDARDS AND INSTALLATIONPRACTICESEx Electrical equipment certified to U.S., Canadian, CENELEC,

    IEC or any other national standards must be installed and

    maintained correctly. To ensure that correct installation is

    achieved, every industrial country will use a recognized

    installation rules or a code of practice.

    In North America the installation requirements for Hazardous

    Locations is specified in Section 18 of the Canadian Electric

    Code and in Article 500 of the National Electric Code. Prior to

    1997 most Countries produced their own National Standards for

    installation in hazardous areas, which allows the use of Ex

    Electrical Equipment certified to CENELEC and other national

    standards. In 1997 the IEC Standard, IEC 60079-14 wasadopted as a European standard EN 60079-14. This was a

    large step forward toward on worldwide standard for the

    installation of electrical equipment in hazardous areas.

    6.3 SELECTION OF EX PROTECTEDELECTRICAL EQUIPMENTThere are considerable international differences in the

    approach to hazardous area electrical installations. Therefore, it

    is important to clearly establish the documented safety rules

    that will be applicable to the installation before the selection

    process is undertaken. To illustrate this problem, hazardous

    area electrical equipment may be manufactured and certified to

    comply with the requirements of a Zone classification but may

    not be considered suitable for Division 1 Hazardous Locationclassified by the North American (USA and CANADA) Class

    and Division concept.

    This has become more relaxed with the addition of Article 501-

    1 in the NEC which states:

    Equipment listed and marked in accordance with Section 505-

    10 for use in Class I, Zone 0, 1, or 2 locations shall be permitted

    in Class I, Division 2 locations for the same gas and with a

    suitable temperature rating.

    This has given North American users a wider range of products

    to select from. Products which are rated for the IEC Zone

    classification system, and are adapted to North American wiringand installation practices can be installed in Division 2.

    Cooper Crouse-Hinds has received UL and cUL approvals on all explosion

    protected equipment manufactured by Cooper Crouse-Hinds CEAG in

    Europe. This product line, called SpecOne, is made out of either metal or

    plastic which will accommodate either cable or conduit installation methods.

    The SpecOne products include fluorescent lighting, control stations and

    panels, power distribution panels, terminal boxes, plugs and receptacles and

    disconnect switches.

    While there are still many differences between the standards

    and installation practices in North America and Europe, not to

    mention others in Latin America, Japan, Australia and South

    Africa, the gaps are narrowing. The main differences are:

    Local safety and fire codes for ordinary locations.

    No direct correlation between Class/Divisions and Zone

    classification.

    Different wiring methods for conduits and cables.

    Cable entry hole threads, NPT versus metric openings.

    Gas Groupings are different.

    Conductor cross sectional areas and current ratings.

    Nonacceptance of the Increased Safety concept in Class 1

    Division 1 Hazardous Locations. (Connections & terminations

    are still considered sources of ignition.)

    These differences define the way equipment is selected,

    installed and maintained and must be taken account of when

    projects are designed.

    6.4 BACKGROUND OF WIRINGIn the early 1900s when industry was converting from the use

    of natural gas to electrical wiring, it was natural for contractors

    to use the gas pipe as a raceway or conduit to run the electrical

    conductors. Although this sounded easy, a need developed to

    also have junction boxes and elbows to pull and terminate

    cables and fixture hangers to assemble the new light fixtures.

    Cooper Crouse-Hinds Ex DigestSelection, Installation and Wiring of Ex Certified Electrical Equipment

    34

    Two entrepreneurs

    from Syracuse, N.Y.,

    Jesse L. Hinds andHuntington B.

    Crouse, made outlet

    boxes for the new

    conduit wiring

    systems. They coined

    the term condulet,

    which was a

    combination of

    conduit and outlet box

    as seen in an early

    advertisement.

  • 8/3/2019 Chapter 6 Selection, Installation and Wiring of Ex Certified Electrical Equipments

    3/7

    35

    In the 1920s when oil refineries were being constructed, there

    was a new need for outlet boxes, fittings and fixtures which

    would prevent electrical sparks and heat generating products

    from causing explosions. The industry came up with the

    concept of Division 1 to define these locations where volatile

    gases would be present.

    Mr. Crouse and Mr. Hinds engineered and manufactured explosionproofproducts for the oil and gas industry.

    In the 1980s Canadian industry readily adopted the use of

    TECK cable which is similar to metal clad cable except with an

    extra PVC jacket. Now the industries with Hazardous Locations

    use a variety of wiring methods ranging from rigid conduit to

    various types of cable.

    6.5 TYPICAL INSTALLATION CONDUITVS. CABLEThere are primarily 3 different types of wiring systems used:

    rigid metal conduits, armored cables, and non-armored cables.

    The use of each method is embedded in the electrical

    installation culture of the area.

    6.5.1 RIGID CONDUITThis system is widely used by specifiers and installers in the

    USA and parts of Canada as well as parts of South America,

    Middle East and Asia where the NEC is used. This method

    ensures the maximum protection of conductors against

    mechanical and chemical attack.

    There are an equal number of proponents as there are

    opponents to the use of rigid conduit. While some maintain that

    conduit leads to higher installation costs, others argue the

    merits of greater mechanical protection. A recent survey

    showed that Canadian users favor TECK cable over rigidconduit. The USA industry is equally divided between favoring

    cable over conduit. For example, offshore installations favor

    cable over conduit, which is more susceptible to corrosion.

    Conduit systemsprovide

    mechanical

    protection of

    wires and

    conductors.

    6.5.2 TECK CABLEInstead of conduit, cable systems are used more often under

    the Zone concept. There are 5 types: TECK, steel wire

    armored, steel wire braided, lead sheathed and unarmored.

    TECK cable is a variation of the armored cable which is used

    primarily in Canada. The TECK cable is a metal clad (mc) cablewith an extra PVC sheath for additional insulation. Special

    TECK connectors are used to secure and terminate the cable

    into enclosures.

    Teck cable has an extra PVC sheath for additional insulation.

    6.5.3 ARMORED CABLESArmored cables are widely used in the United Kingdom and

    former commonwealth countries and ensures the mechanical

    protection and earth continuity. Special cable glands must be

    used to guarantee the earth continuity (ground).

    6.5.3.1 STEEL WIRE ARMORED (SWA)SWAcable consists of individual PVC-coated conductors within

    an aluminum screen surrounded by a PVC coating, then by a

    series of steel wires within an exterior PVC coating. The steel

    wires are conical in shape and protect the conductors in the

    same way as metal-clad cable. SWA is a very high-strength,

    durable cable and used in many power applications.

    Cooper Crouse-Hinds Ex DigestSelection, Installation and Wiring of Ex Certified Electrical Equipment

  • 8/3/2019 Chapter 6 Selection, Installation and Wiring of Ex Certified Electrical Equipments

    4/7

    36

    6.5.3.2 STEEL WIRE BRAIDED (GSWB)GSWB cable consists of individual conductors within an

    aluminum screen surrounded by an inner sheath, then by a

    steel braid, similar to a basket weave, underneath an outer

    sheath. The braid makes this cable more flexible than SWA.

    This durable cable is used in many instrumentation applications

    or where shielding is required for signal applications.

    6.5.3.3 LEAD SHEATH (LWA)

    LWA cable consists of individual conductors surrounded by alead sheath for protection from hydrocarbons. A PVC coating

    then surrounds the exterior. This cable is popular in the oil

    industry and is usually buried in the ground. The lead sheath

    protects the conductors from ground spills of oil byproducts.

    Crouse-Hinds offers brass,

    stainless steel, steel and and non-

    metallic cable glands for

    any type of cable or thread.

    6.5.3.4 NON-ARMORED CABLEThis cable is similar to tray or SO-type cable and normally

    contains a ground conductor or earth core. Since the cable is

    not considered a source of ignition, under the Zone concept the

    cable does not require its own mechanical protection. The

    protection is usually provided by open conduit or other cable-

    tray type protection called a cage or mounting grid. This

    method, which is used in France, Germany, Italy and parts ofAfrica and Asia, can be very flexible, fast and economical. If the

    installation is subject to mechanical risks, it is advisable to use

    armored cable or an open conduit system. Most exposed

    vertical cables are housed in open conduits or pipes to avoid

    mechanical abuse.

    Cooper Crouse-Hinds non-metallic mounting plate on mounting grid offers a

    quick installation method of control stations and switches.

    Table 6.1

    Typical Cable Systems by World RegionAREA CABLE TYPE THREAD

    TYPE

    Canada TECK NPT

    North America Metal Clad Aluminum NPT

    Central Europe Unarmored Cable Metric*Germany

    Europe offshore Steel Wire Braid Metric

    Ireland, Norway, Steel Wire Armor MetricHolland, Belgium, Unarmored CableSpain

    Italy, Belgium Steel Wire Armor Metric

    Unarmored Cable & NPT

    Middle East Steel Wire Armor MetricUnarmored Cable NPT

    Far East Steel Wire Armor MetricUnarmored Cable & NPT

    CIS States Steel Wire Armor Metric(Azerbaijan, Unarmored CableKazakhstan)

    * Metric threads have replaced Panzer gage (PG) threads

    Cooper Crouse-Hinds Ex DigestSelection, Installation and Wiring of Ex Certified Electrical Equipment

    (Saudi Arabia & Kuwait)

    Steel wire

    braided cable

    is more flexible

    than SWA

    Crouse-Hinds NCG non metallic cable glands are offered with

    NPT or metric males threads for tray and other flexible cables.

  • 8/3/2019 Chapter 6 Selection, Installation and Wiring of Ex Certified Electrical Equipments

    5/7

    37

    The use of twist-on connectors, known as wire nuts

    or marets, is not allowed in Europe as increased

    safety terminals.

    The Ex-e push in connectors are a major advantage

    for OEMs, and for installation of lighting circuits.

    6.6 TERMINATION METHODSTraditionally Ex-e connections are made at increased safety

    terminal blocks mounted inside of metal or non-metallic, Ex-e

    enclosures. The terminals are rated for creepage and clearance

    distances.

    6.6.1 TWIST ON CONNECTORSThe most popular method of termination in North America is

    with the use of twist-on connectors, also known as wire nuts or

    marets. For products approved for use in Europe, twist-on

    connectors or wire nuts are not allowed. Some form of terminal

    blocks or screw terminals must be used. Twist-on connectors

    versus terminal blocks are the main differences between theNorth America and European wiring methods. North American

    wiring methods will not be quick to abandon using twist-on

    connectors in favor of terminal blocks for branch circuits

    especially when both systems are safe when they are installed

    properly. Until recently, twist-on type connectors were not rated

    as increased safety.

    Cooper Crouse-Hinds pioneered the first

    Ex-e wire nuts which offer major

    advantage for OEMs, and for

    installation of lighting circuits.

    6.6.2 TERMINAL BOXESThe specifications for terminals according to IEC and

    CENELEC standards are very stringent. Certified electrical

    terminals for connecting wires in hazardous areas will be tested

    with the following requirements:

    Insulation resistance to tracking (CTI)

    Temperature limitation (thermal stability) Measured Creepage &b clearance distances

    Voltage and current ratings

    Wire pull out test

    Antivibration locking

    Thermal end to end resistance

    Conductor clamping method (pinch screws are

    not permitted)

    The connection of wires to terminals is most commonly made

    via DIN rail mounted terminals. The underlying design principle

    for terminals is a pressure plate contact with the conductor and

    an antivibration locking feature to prevent self loosening for the

    connected conductors. Other types of reliable certified terminals

    include saddle clamps, slotted type clamps (often used for

    lighting circuit terminations) and screwless cage clamp

    terminals.

    6.7 TERMINATING ARMORED CABLE ANDCONDUIT IN NON-METALLIC ENCLOSURESThe armor of steel wire or braided cables must be effectively

    connected to the earth/ground system. If a phase to armor

    circuit fault occurs there can be thousands of amps flowing.

    Therefore the armor must have a low impedance to

    earth/ground via the cable gland. The enclosure to which the

    armored gland is connected may not be tested to carry fault

    currents so internal and or external connections are required.

    The biggest dilemma of mixing zone and division installation

    methods is the practice of using terminating conduits or

    armored cable into non-metallic enclosures. The majorconsiderations are: pull out strength of the conduit from the

    enclosure and ensuring a continuous and secure path to

    ground. There are 2 different methods commonly used, the

    zone rated hub or the integral grounding plate.

    Cooper Crouse-Hinds Ex DigestSelection, Installation and Wiring of Ex Certified Electrical Equipment

    Under IEC installation

    methods it is permitted to

    combine two or more

    wires in a compression-

    type terminal provided

    that the terminal is

    designed for that purpose,

    such as the Cooper

    Crouse-Hinds eAZK

    enclosures with Ex-e

    U-slot terminals.

    Ex-e U-Slot terminals,

    which accommodate

    different sized wires,

    are found in Ex-e

    terminal boxes (eAZK)

    and in some Ex-d light

    fixtures

  • 8/3/2019 Chapter 6 Selection, Installation and Wiring of Ex Certified Electrical Equipments

    6/7

    38

    6.7.1 ZONE RATED HUBSThis hub is specifically designed for Zone applications to be

    non-loosening and to have the required IP rating. For through

    holes the male threads must have a locking ring which has an

    increased safety grounding point and an extra security screw to

    ensure against loosening of the locking ring. Either the hub or

    the locking ring will have serrated teeth for extra clamping

    protection into the non-metallic enclosure. Both of thesefeatures protect the connection from loosening against vibration

    and long term use. The hub has an integral silicone rubber o-

    ring or gasket to guarantee the require IP rating of the

    enclosure. The hubs are machined to accept either NPT or

    metric thread form.

    The SpecOne Myers

    hubs

    are rated for

    Zone 1 usage.

    They are also

    available as

    metric adapters for

    entering

    metric threaded

    female hubs or

    plates.

    6.7.2 BRASS BONDING PLATESMany non-metallic enclosures also have integral brass bonding

    plates. Because of their nominal thickness these normally have

    metric or parallel threaded openings. Each plate must have an

    internal and/or external ground point. These plates can be field

    drilled or drilled at the factory. If the holes are not used they

    must be plugged with a blanking plug certified to Ex-e standards

    for the required IP protection.

    Ex-e blanking plugs are required to fill in threaded openings for IP

    protection as seen on the Cooper Crouse-Hinds GHG 74 Series Ex-e

    Enclosures.

    For ease of wiring the SpecOne control stations, D2Z distribution panels,

    Safety Switches, interlocked 309 receptacles and terminal boxes all have an

    brass grounding plates. These have metric female threads for European

    armored cable glands. For NPT entries use the Zone 1 Myers metric

    adapters which are available in zinc or stainless steel.

    6.8 CABLE SEALS

    Cable glands have multiple options for material types for Ex-dand Ex-e types of protection. Ex-d cable glands have a brass,

    aluminum, steel or stainless steel construction with at least two

    seal systems to ensure the flameproof properties and ingress

    protection. Ex-e cable glands normally have only one sealing

    system for ingress protection and are available in a plastic

    construction in addition to brass or stainless steel.

    Three types of seal materials are most generally used in cable

    glands.

    Neoprene, a durable oil-resistant rubber compound with good

    weather and ozone resistance. To meet the strict deluge test

    requirements of the offshore oil industry, glands employ up to

    three neoprene seals. These are used on offshore oilplatforms where they may be submerged for long durations.

    Conductive, a neoprene seal with iron filings used to seal lead

    sheathed cable.

    Silicone, a compound with high fire resistance which holds its

    properties well in temperature extremes. This seal may be

    used in temperatures as low as -60C to as high as +180 C.

    It also does not give off smoke when burning (zero halogen

    applications) and is used in tunnels or other similar

    applications.

    Typical Seals and Application Temperatures

    Seal Type Temperature Range

    Neoprene (deluge tested) -20 to + 80CConductive -20 to + 80C

    Silicone -60 to + 180C

    Cooper Crouse-Hinds Ex DigestSelection, Installation and Wiring of Ex Certified Electrical Equipment

  • 8/3/2019 Chapter 6 Selection, Installation and Wiring of Ex Certified Electrical Equipments

    7/7

    39

    Typical installation of Zone 1 Myers hubs glands into a Cooper

    Crouse-Hinds Ex-e stainless steel enclosure.

    6.9 WHEN IS NICKEL PLATING REQUIRED?The inherent corrosion-resistance nature of brass eliminates

    the need for plating in most cases. However, brass and

    aluminum create a natural galvanic reaction, so nickel plate or

    other finishes are required where the brass gland is used with

    aluminum enclosures or aluminum cable.

    Do not use brass

    glands in aluminum

    housings, which will

    result in corrosion.

    Use nickel plated

    glands.

    6.10 TERMINATING NON-METALLIC EX-eGLANDSIncreased safety non-metallic glands must be certified for

    ingress protection, impact resistance and aging resistance.

    There are 2 versions, which depend on the use of the glands.

    For installations where the cables are secured, the glands have

    lower requirements for strain relief. If the cables are not secured

    trumpet glands are used. Their main purpose is to provide strain

    relief where bending, twisting or pulling is common.

    Trumpet glands (on handset)

    are used on portable

    equipment when support for

    the cable is not practical or if

    there are extensive tensile or

    torsional forces.

    Cables should be secured close

    to the apparatus.

    6.10.1 SELECTION OF NON-METALLICGLANDSCable glands are sold either as separate items mounted on the

    apparatus or packaged with the cable. Selecting the proper

    gland depends on the following criteria:

    Cable type

    Hazardous area rating

    Seal type

    Entry thread

    Finish

    Cable diameter

    Material

    Use

    The one variable, which usually creates havoc for end users, is

    holding the tolerance on the cable diameter especially ifflameproof cable glands are used. If the diameters exceed the

    tolerances of the glands, they may not fit or seal properly which

    could affect the flameproof integrity of the glands.

    Cut-away of trumpet gland

    For questions or comments, please contact the author at

    [email protected]

    Cooper Crouse-Hinds Ex DigestSelection, Installation and Wiring of Ex Certified Electrical Equipment

    Lever prevents pull-out or

    torsional twisting.

    Seal for IP

    Protection