chapter 3 the air distribution system
TRANSCRIPT
-
8/12/2019 Chapter 3 the Air Distribution System
1/40
The Air Distribution System
MEC 351
DR HAMID YUSOFF
-
8/12/2019 Chapter 3 the Air Distribution System
2/40
AHU
-
8/12/2019 Chapter 3 the Air Distribution System
3/40
The purpose of air distribution system
is to create the proper combination oftemperature, humidity and air velocity
in the occupied zone of the
conditioned room. If not properly designed, the air
distribution system has the potential to
compromise the comfort conditions it
was designed to maintain.
-
8/12/2019 Chapter 3 the Air Distribution System
4/40
Terminology
Diffusiontemperature
Supply air to space airtemperature difference is
termed diffusiontemperature. In theexample, the room designtemperature, Tr is 25 deg C.and the supply temperatureTla, is 13 deg.C, hence thediffusion temperature is (2513) = 12 deg C.
-
8/12/2019 Chapter 3 the Air Distribution System
5/40
Terminology
Induction,entrainment, oraspiration
Involve mixing of roomair with the supply air
outside the occupiedzone. Entrainment isdefined as themovement of room airinto the jet caused bythe air stream
discharged from theoutlet (secondary airmotion).
aspiration
-
8/12/2019 Chapter 3 the Air Distribution System
6/40
Terminology
Throw (blow) andradius of diffusion
The throw or blow andthe radius of diffusionrefer to the horizontaldistance that the supply
air travels before reachinga specified low velocityknown as the terminalvelocity. Generally, throwor blow refers to dischargefrom the sidewall outlet,and the radius of diffusionrelates to the ceilingoutlets.
-
8/12/2019 Chapter 3 the Air Distribution System
7/40
TERMINOLOGY
AHU
An air handler, or air handling unit (often abbreviatedto AHU), is a device used to condition and circulate airas part of a heating, ventilating, and air-conditioning(HVAC) system. Usually, an air handler is a large metal
box containing a blower, heating and/or coolingelements, filter racks or chambers, sound attenuators,and dampers. Air handlers usually connect to ductworkthat distributes the conditioned air through the
building, and returns it to the AHU. Sometimes AHUsdischarge (supply) and admit (return) air directly to andfrom the space served, without ductwork.
-
8/12/2019 Chapter 3 the Air Distribution System
8/40
Terminology
Occupied Zone 3 inches to 72 inches above the floor level.
Two feet in from the walls
-
8/12/2019 Chapter 3 the Air Distribution System
9/40
Evaluating Comfort
Comfort criteriaGood room air distribution requires the following characteristics forcomfort:Comfort is maintained through the change in seasons when thefollowing conditions are maintained in the space occupied zone.
Air temp maintained between 73-77F
RH maintained between 25-60%
Maximum air motion in the occupied zone1. Air velocities throughout the occupied zone (called residual
velocities ) between 2535 FPM for applications where peopleare seated. (FPM feet perminute)
2. Moving peopleare higher air velocities are acceptable ( 50 -70FPM)
Maximum temperature gradient (temperature fluctuation)1-2 cooling
4 heating
Note: Occupied zone of most spaces is considered to be from the floor to an
elevation of 6 ft. Above this height, greater temperature fluctuations are
permissible
-
8/12/2019 Chapter 3 the Air Distribution System
10/40
effective draft temperature - Kelvin
As mentioned previously, certain parameters can be controlled to ensure a
relatively comfortable environment. The question is how does one
evaluate the system to make sure that the actual parameters are within
the allowable range? Standard methods exist to evaluate these
parameters in real or simulated spaces to determine if the conditions are
being met. The first evaluation concept is called the effective draft
temperature - Kelvin , which uses the local air temperature and velocity in
a single equation to determine a relative feeling of coolness. The equation
is:
The effective draft temperature is evaluated at many locations throughout
the space and comfort studies have shown that the effects of temperature
and velocity on comfort will be acceptable if is kept between -3 and +2F
-
8/12/2019 Chapter 3 the Air Distribution System
11/40
TheAir Diffusion Performance Index
(ADPI)
The percentage of locations in a space in whichthe limits of the effective draft temperature aremet. In other words, an ADPI of 80 means that80%; of the locations in the space have an
effective draft temperature of -3 to +2 F.Obviously, an ADPI of 100%; would be theultimate condition, but the efforts required toachieve this condition would often cost much
more than the added benefit. Studies haveshown that an ADPI of 80%; or more results insatisfactory comfort.
-
8/12/2019 Chapter 3 the Air Distribution System
12/40
Successful Design Achieves
Good ventilation effectiveness
Avoids dumping (lambakan)
Avoids draft
-
8/12/2019 Chapter 3 the Air Distribution System
13/40
Description of terms used in air distribution
Throw (T)- The maximum horizontal distance from the center of the air
outlet to a point in the airstream where the air velocity has decayed
(menyusut) to some arbitrary terminal velocity(typically 150, 100, and
50 fpm). The common unit of measure is feet (ft)
Drop (D)- The vertical distance from an air outlet to the lower edge of
a horizontally projected airstream envelope. The common unit of
measure is feet (ft).
-
8/12/2019 Chapter 3 the Air Distribution System
14/40
Air patterns
The are a few facts about how facts about how an air supply to aroom will behave which are important to understand in order toselect and locate air supply devices properly and to balance andadjust the devices.
1. When air lower temperature than room air is supplied (as in
summer), it will drop.2. When air higher in temperature than room air is supplied (as in
winter), it will rise.
3. When air is supplied parallel to and near a ceiling, it will tend tohug the ceiling for some distance. This is called the ceiling orsurface effect.
4. The supply air to the room ( called the primary air) whendistributed from air supply device, will induce room air (calledsecondary air) into air stream, thus rapidly mixing the supply airand the room air.
-
8/12/2019 Chapter 3 the Air Distribution System
15/40
Outlet location
High wall. This is a good location for coolingbecause the cold air will drop naturally andadequate air circulation throughout the occupiedzone will occur.
Ceiling. This is excellent location for coolingbecause the cold air will drop naturally.
Low wall. This is a good location for heatingbecause the warm air will rise naturally.
Floor or sill. This is an excellent location forheating if located under windows, because itcounteracts the cold air downdraft.
-
8/12/2019 Chapter 3 the Air Distribution System
16/40
location
Coolinggood air distribution
Floor or sill location under window forheating provides good air distribution
Heatingpoor air distribution
Ceiling outlet location for cooling providesgood distribution
-
8/12/2019 Chapter 3 the Air Distribution System
17/40
Supply air outlets and air distribution
patterns
Grilles and registers These consist of a frame and
fixed or adjustable parallel bars.
Ceiling diffusers These consists of a series of
separated concentric rings or louvres with a collar or
neck to connect to the duct.
Slot diffusers A slot diffuser is a long strip-shaped
outlet with one or more narrow openings.
Plenum ceiling panels The confined space above
the ceiling is used as a large plenum from which the
supply air is delivered through slots or holes,
particularly to large zones of uniform temperature.
-
8/12/2019 Chapter 3 the Air Distribution System
18/40
-
8/12/2019 Chapter 3 the Air Distribution System
19/40
Outlet Classification
Types of air supply devices
Group A. Outlets mounted in or near the ceiling that discharge air
horizontally.
Group B. Outlets mounted in or near the floor that discharge air
vertically in a non-spreading jet.
Group C. Outlets mounted in or near the floor that discharge air
vertically in a spreading jet.
Group D. Outlets mounted in or near the floor that discharge airhorizontally.
Group E. Outlets mounted in or near the ceiling that project
primary air vertically.
-
8/12/2019 Chapter 3 the Air Distribution System
20/40
Group A
High Sidewall Grilles
-
8/12/2019 Chapter 3 the Air Distribution System
21/40
Group A Ceiling Diffusers
-
8/12/2019 Chapter 3 the Air Distribution System
22/40
Neck, face, core & free area
-
8/12/2019 Chapter 3 the Air Distribution System
23/40
Neck Area & Neck Velocity
-
8/12/2019 Chapter 3 the Air Distribution System
24/40
Outlet Discharge Patterns
-
8/12/2019 Chapter 3 the Air Distribution System
25/40
Circular
Diffuser
The downward-jet
pattern may be of
benefit when the
outlet is installed in a
tall space and HVAC
(heating, ventilation air
conditioning) is in
heating Mode Thevisualization
Shows consequences for
cooling mode
-
8/12/2019 Chapter 3 the Air Distribution System
26/40
Square/Rectangular Diffusers
-
8/12/2019 Chapter 3 the Air Distribution System
27/40
Square
Diffuserprovides flexibility
for distributing air
in a variety of
patterns
-
8/12/2019 Chapter 3 the Air Distribution System
28/40
Slot Diffuser
-
8/12/2019 Chapter 3 the Air Distribution System
29/40
Slot Diffuser
allows directingthe air downward
-
8/12/2019 Chapter 3 the Air Distribution System
30/40
Air distribution system design
Room air distribution
Outlet selection and location procedure
Return air system
-
8/12/2019 Chapter 3 the Air Distribution System
31/40
Room air distribution
Conditioned air should be supplied so that natural convection,radiation and conduction effects are counteracted.
Return grilles should be so located that direct by passing of air fromthe supply outlet to the return grill will not occur.
Adequate return grilles should be provided and the same should be
sized for low friction loss. Supply outlets should be so selected that their throw puts the
conditioned air where it is needed, but excessive throw should notbe allowed in which case the air would bounce off the walls andcreate draft. The desirable length of throw is up to three fourth ofthe distance to the opposite side of the wall.
Noise level of supply outlets must kept low.
Supply outlets should have adjusting features so that good room airdistribution can be obtained.
-
8/12/2019 Chapter 3 the Air Distribution System
32/40
Outlet Selection and location
procedure1.Determine Air Volume Requirements & Room Size. In case more than one air outletis used, the total air flow rate needs to be divided by the number of outlets. =
1.2
= (3 /)
= (
)
= ()
2.Select diffuser type and location within room. Considering factors as air quantity, distanceavailable for throw, structural characteristics and architectural constraints. For example, if circularceiling diffusers are to be used, each would be centred in a ceiling area that is roughly square inshape as the air is supplied in all directions from the diffuser.
3.Determine room characteristic length from table, L
-
8/12/2019 Chapter 3 the Air Distribution System
33/40
ASHRAE Outlet Selection Steps
4.Select recommended throw to length ratio from the ADPI selection guide
-
8/12/2019 Chapter 3 the Air Distribution System
34/40
ASHRAE
Outlet Selection Steps
5.Calculate throw .
-
8/12/2019 Chapter 3 the Air Distribution System
35/40
-
8/12/2019 Chapter 3 the Air Distribution System
36/40
-
8/12/2019 Chapter 3 the Air Distribution System
37/40
Return air system
Several factors should be considered in locating return airgrilles
Location of grilles should avoid causing drafts in theoccupied zone.
The return air duct system should be sized for low pressuredrop to reduce noise generation.
It is not required to locate a return air grille in each space.Excessive air collected at a single return should be avoided,because of the possibility of creating drafts or noise.
Return air grilles should be so located that short circuiting isavoided prior to complete mixing and heat exchange ofsupply air.
-
8/12/2019 Chapter 3 the Air Distribution System
38/40
Recommended Sound Reduction
Methods
The following steps can be taken to reduce the sound generation of air outlets and airinlets:
Reduce the airflow delivered to each device by utilizing a greater number of devicesfor the same total airflow to or from the space. However, the size of the devices mayneed to be reduced to maintain the proper room air motion.
Increase the size of the air outlet or air inlet, which decreases the face velocity and
pressure loss.However, increasing the size of an air outlet without increasing theairflow will result in shorter throws and may cause conditioned air to drop into theoccupied zone.
Balancing dampers should not be used in the neck of the air outlet. This can addanywhere from 5 to 16 NC to the sound rating, depending on the amount of damperclosure. Balancing dampers should be located as far upstream from the air outlet aspossible.
The approaching ductwork to the air outlet should be kept as straight as possible. Anyoffset or abrupt bend will add up to 15 NC to the sound rating. If flexible duct is used,sharp bends should be prevented at the neck of the air outlet.
As a general rule of thumb, the face velocity of an air outlet should not exceed 800fpm and the face velocity of an air inlet should not exceed 400 fpm.
-
8/12/2019 Chapter 3 the Air Distribution System
39/40
Example 1
Select a round ceiling diffuser for a room in an office building, as shown in below.
The room, 4.2 m wide by 4.8 m long and with ceiling 2.4 m above the floor, is to be
supplied with 120 litres/s of conditioned air. The room load was estimated to be
125 W/m2. A noise criteria (NC) of 20 -35 would be acceptable.
4.2 m
4.8 m
diffuser
-
8/12/2019 Chapter 3 the Air Distribution System
40/40
Example 2
Specify circular ceiling diffusers for cooling a school room to
be maintained at 25 deg. C. The cooling load for the room is
13.2 kW and the supply air temperature is 13 deg.C.
10 m
12 m