chapter 14: gas-vapor mixtures and...

37
Chapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint to accompany Thermodynamics: An Engineering Approach, 5th edition by Yunus A. Çengel and Michael A. Boles

Upload: dinhdiep

Post on 05-Jul-2018

238 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

Chapter 14

Gas-Vapor Mixtures and Air-Conditioning

Study Guide in PowerPoint

to accompany

Thermodynamics: An Engineering Approach, 5th edition

by Yunus A. Çengel and Michael A. Boles

Page 2: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

2

We will be concerned with the mixture of dry air and water vapor. This mixture is

often called atmospheric air.

The temperature of the atmospheric air in air-conditioning applications ranges from

about –10 to about 50oC. Under these conditions, we treat air as an ideal gas with

constant specific heats. Taking Cpa = 1.005 kJ/kgK, the enthalpy of the dry air is

given by (assuming the reference state to be 0oC where the reference enthalpy is

taken to be 0 kJ/kga)

The assumption that the water vapor is an ideal gas is valid when the mixture

temperature is below 50oC. This means that the saturation pressure of the water

vapor in the air-vapor mixture is below 12.3 kPa. For these conditions, the enthalpy

of the water vapor is approximated by hv(T) = hg at mixture temperature T. The

following T-s diagram for water illustrates the ideal-gas behavior at low vapor

pressures. See Figure A-9 for the actual T-s diagram.

Page 3: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

3

The saturated vapor value of the enthalpy is a function of temperature and can be

expressed as

Note: For the dry air-water vapor mixture, the partial pressure of the water vapor in

the mixture is less that its saturation pressure at the temperature.

P Pv sat Tmix @

Page 4: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

4

Consider increasing the total pressure of an air-water vapor mixture while the

temperature of the mixture is held constant. See if you can sketch the process on the

P-v diagram relative to the saturation lines for the water alone given below. Assume

that the water vapor is initially superheated.

P

v

When the mixture pressure is increased while keeping the mixture temperature

constant, the vapor partial pressure increases up to the vapor saturation pressure at

the mixture temperature and condensation begins. Therefore, the partial pressure of

the water vapor can never be greater than its saturation pressure corresponding to

the temperature of the mixture.

Page 5: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

5

Definitions

Dew Point, Tdp

The dew point is the temperature at which vapor condenses or solidifies when cooled

at constant pressure.

Consider cooling an air-water vapor mixture while the mixture total pressure is held

constant. When the mixture is cooled to a temperature equal to the saturation

temperature for the water-vapor partial pressure, condensation begins.

When an atmospheric air-vapor mixture is cooled at constant pressure such that the

partial pressure of the water vapor is 1.491 kPa, then the dew point temperature of

that mixture is 12.95oC.

0 2 4 6 8 10 1212

-25

25

75

125

175

225

275

325

375

s [kJ/kg-K]

T [

C]

1.491 kPa

Steam

TDP

Page 6: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

6

Relative Humidity, ϕ

Mass of vapor in air

Mass of in saturated air

m

m

P

P

v

g

v

g

Pv and Pg are shown on the following T-s diagram for the water-vapor alone.

0 2 4 6 8 10 1212

-25

25

75

125

s [kJ/kg-K]

T [

C]

Pv = 1.491 kPa

Pg = 3.169 kPa

Steam

o

Tdp

Tm Vapor State

Since P P orP

P

kPa

kPag v

v

g

,.

.. 1 100%,

1491

3169047

Page 7: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

7

Absolute humidity or specific humidity (sometimes called humidity ratio),

Mass of water vapor in air

Mass of dry air

m

m

PVM R T

PVM R T

P M

P M

P

P

P

P P

v

a

v v u

a a u

v v

a a

v

a

v

v

/ ( )

/ ( )

. .0 622 0 622

Using the definition of the specific humidity, the relative humidity may be expressed

as

P

Pand

P

P Pg

g

g( . )

.

0 622

0 622

Volume of mixture per mass of dry air, v

vV

m

m R T P

ma

m m m m

a

/

After several steps, we can show (you should try this)

vV

mv

R T

Pa

aa m

a

Page 8: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

8

So the volume of the mixture per unit mass of dry air is the specific volume of the dry

air calculated at the mixture temperature and the partial pressure of the dry air.

Mass of mixture

m m m mm

mma v a

v

a

a ( ) ( )1 1

Mass flow rate of dry air, ma

Based on the volume flow rate of mixture at a given state, the mass flow rate of dry

air is

/

/m

V

v

m s

m kg

kg

sa

a

a 3

3

Enthalpy of mixture per mass dry air, h

hH

m

H H

m

m h m h

m

h h

m

a

a v

a

a a v v

a

a v

Page 9: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

9

Example 14-1

Atmospheric air at 30oC, 100 kPa, has a dew point of 21.3oC. Find the relative

humidity, humidity ratio, and h of the mixture per mass of dry air.

2.5480.6 60%

4.247

v

g

P kPaor

P kPa

0 6222 548

100 2 548001626.

.

( . ).

kPa

kPa

kg

kg

v

a

h h h

C T T

kJ

kg CC

kg

kgC

kJ

kg

kJ

kg

a v

p a

a

o

o v

a

o

v

a

, ( . . )

. ( ) . ( . . ( ))

.

25013 182

1005 30 0 01626 25013 182 30

7171

Page 10: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

10

Example 14-2

If the atmospheric air in the last example is conditioned to 20oC, 40 percent relative

humidity, what mass of water is added or removed per unit mass of dry air?

At 20oC, Pg = 2.339 kPa.

P P kPa kPa

wP

P P

kPa

kPa

kg

kg

v g

v

v

v

a

0 4 2 339 0 936

0 622 0 6220 936

100 0 936

0 00588

. ( . ) .

. ..

( . )

.

The change in mass of water per mass of dry air is

m m

m

v v

a

, ,2 1

2 1

m m

m

kg

kg

kg

kg

v v

a

v

a

v

a

, ,( . . )

.

2 10 00588 0 01626

0 01038

Page 11: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

11

Or, as the mixture changes from state 1 to state 2, 0.01038 kg of water vapor is

condensed for each kg of dry air.

Example 14-3

Atmospheric air is at 25oC, 0.1 MPa, 50 percent relative humidity. If the mixture is

cooled at constant pressure to 10oC, find the amount of water removed per mass of

dry air.

Sketch the water-vapor states relative to the saturation lines on the following T-s

diagram. T

s

At 25oC, Psat = 3.170 kPa, and with = 50% 1

,1 1 ,1

,1 @

0.5(3.170 ) 1.585

13.8v

v g

o

dp sat P

P P kPa kPa

T T C

Page 12: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

12

wP

P P

kPa

kPa

kg

kg

v

v

v

a

1

1

1

0 622 0 62215845

100 15845

0 01001

. ..

( . )

.

,

,

Therefore, when the mixture gets cooled to T2 = 10oC < Tdp,1, the mixture is saturated,

and = 100%. Then Pv,2 = Pg,2 = 1.228 kPa. 2

,2

2

,2

1.2280.622 0.622

(100 1.228)

0.00773

v

v

v

a

P kPaw

P P kPa

kg

kg

The change in mass of water per mass of dry air is

m m

m

kg

kg

kg

kg

v v

a

v

a

v

a

, ,

( . . )

.

2 1

2 1

0 00773 0 01001

0 00228

Page 13: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

13

Or as the mixture changes from state 1 to state 2, 0.00228 kg of water vapor is

condensed for each kg of dry air.

Steady-Flow Analysis Applied to Gas-Vapor Mixtures

We will review the conservation of mass and conservation of energy principles as

they apply to gas-vapor mixtures in the following example.

Example 14-3

Given the inlet and exit conditions to an air conditioner shown below. What is the

heat transfer to be removed per kg dry air flowing through the device? If the volume

flow rate of the inlet atmospheric air is 200 m3/min, determine the required rate of

heat transfer.

Page 14: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

14

Before we apply the steady-flow conservation of mass and energy, we need to decide

if any water is condensed in the process. Is the mixture cooled below the dew point

for state 1?

,1 1 ,1

,1 @

0.8(4.247 ) 3.398

26.01v

v g

o

dp sat P

P P kPa kPa

T T C

So for T2 = 20oC < Tdp, 1, some water-vapor will condense. Let's assume that the

condensed water leaves the air conditioner at 20oC. Some say the water leaves at

the average of 26 and 20oC; however, 20oC is adequate for our use here.

Apply the conservation of energy to the steady-flow control volume

( ) ( )Q m hV

gz W m hV

gznet i

inlets

i net e

exits

e

2 2

2 2

Neglecting the kinetic and potential energies and noting that the work is zero, we get

Q m h m h m h m h m hnet a a v v a a v v l l 1 1 1 1 2 2 2 2 2 2

Conservation of mass for the steady-flow control volume is

m mi

inlets

e

exits

Page 15: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

15

For the dry air:

m m ma a a1 2

For the water vapor:

m m mv v l1 2 2

The mass of water that is condensed and leaves the control volume is

( )

m m m

m

l v v

a

2 1 2

1 2

Divide the conservation of energy equation by , then ma

( )

( )

Q

mh h h h h

Q

mh h h h h

net

a

a v a v l

net

a

a a v v l

1 1 1 2 2 2 1 2 2

2 1 2 2 1 1 1 2 2

( ) ( )

Q

mC T T h h hnet

a

pa v v l 2 1 2 2 1 1 1 2 2

Page 16: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

16

Now to find the 's and h's.

11

1 1

0.622 0.622(3.398)

100 3.398

0.02188

v

v

v

a

P

P P

kg

kg

P P

kPa kPa

P

P P

kg

kg

v g

v

v

v

a

2 2 2

22

2 2

0 95 2 339 2 222

0 622 0 622 2 222

98 2 222

0 01443

( . )( . ) .

. . ( . )

.

.

Page 17: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

17

Using the steam tables, the h's for the water are

1

2

2

2555.6

2537.4

83.91

v

v

v

v

l

v

kJh

kg

kJh

kg

kJh

kg

The required heat transfer per unit mass of dry air becomes

2 1 2 2 1 1 1 2 2( ) ( )

1.005 (20 30) 0.01443 (2537.4 )

0.02188 (2555.6 ) (0.02188 0.01443) (83.91 )

8.627

netpa v v l

a

o v

o

a a v

v v

a v a v

a

QC T T h h h

m

kgkJ kJC

kg C kg kg

kg kgkJ kJ

kg kg kg kg

kJ

kg

Page 18: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

18

The heat transfer from the atmospheric air is

8.627netout

a a

Q kJq

m kg

The mass flow rate of dry air is given by

mV

va

1

1

3

11

1

3

0.287 (30 273)

(100 3.398)

0.90

a a

a

a

kJK

R T kg K m kPav

P kPa kJ

m

kg

3

3

200min 222.2

min0.90

aa

a

mkg

mm

kg

Page 19: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

19

1min 1222.2 (8.627 )

min 60

31.95 9.08

aout a out

a

kg kJ kWsQ m q

kg s kJ

kW Tons

The Adiabatic Saturation Process

Air having a relative humidity less than 100 percent flows over water contained in a

well-insulated duct. Since the air has < 100 percent, some of the water will

evaporate and the temperature of the air-vapor mixture will decrease.

Page 20: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

20

If the mixture leaving the duct is saturated and if the process is adiabatic, the

temperature of the mixture on leaving the device is known as the adiabatic

saturation temperature.

For this to be a steady-flow process, makeup water at the adiabatic saturation

temperature is added at the same rate at which water is evaporated.

We assume that the total pressure is constant during the process.

Apply the conservation of energy to the steady-flow control volume

( ) ( )Q m hV

gz W m hV

gznet i

inlets

i net e

exits

e

2 2

2 2

Neglecting the kinetic and potential energies and noting that the heat transfer and

work are zero, we get

m h m h m h m h m ha a v v l l a a v v1 1 1 1 2 2 2 2 2 2

Conservation of mass for the steady-flow control volume is

m mi

inlets

e

exits

Page 21: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

21

For the dry air:

m m ma a a1 2

For the water vapor:

m m mv l v1 2 2

The mass flow rate water that must be supplied to maintain steady-flow is,

( )

m m m

m

l v v

a

2 2 1

2 1

Divide the conservation of energy equation by , then ma

h h h h ha v l a v1 1 1 2 1 2 2 2 2 ( )

What are the knowns and unknowns in this equation?

Solving for 1

12 1 2 2 2

1 2

2 1 2 2

1 2

h h h h

h h

C T T h

h h

a a v l

v l

pa fg

g f

( )

( )

( )

( )

Page 22: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

22

Since 1 is also defined by

11

1 1

0 622

.P

P P

v

v

We can solve for Pv1.

PP

v11 1

10 622

.

Then the relative humidity at state 1 is

11

1

P

P

v

g

Page 23: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

23

Example 14-4

For the adiabatic saturation process shown below, determine the relative humidity,

humidity ratio (specific humidity), and enthalpy of the atmospheric air per mass of dry

air at state 1.

Page 24: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

24

Using the steam tables:

2

1

2

67.2

2544.7

2463.0

f

v

v

v

fg

v

kJh

kg

kJh

kg

kJh

kg

From the above analysis

2 1 2 2

1

1 2

( )

( )

1.005 16 24 0.0115 (2463.0 )

(2544.7 67.2)

0.00822

pa fg

g f

o v

o

a va

v

v

a

C T T h

h h

kgkJ kJC

kg kgkg C

kJ

kg

kg

kg

Page 25: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

25

We can solve for Pv1.

1 11

10.622

0.00822(100 )

0.622 0.00822

1.3

v

PP

kPa

kPa

Then the relative humidity at state 1 is

1 11

1 @24

1.30.433 43.3%

3.004

o

v v

g sat C

P P

P P

kPaor

kPa

The enthalpy of the mixture at state 1 is

1 1 1 1

1 1 1

1.005 (24 ) 0.00822 2544.7

45.04

a v

pa v

o v

o

a a v

a

h h h

C T h

kgkJ kJC

kg C kg kg

kJ

kg

Page 26: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

26

Wet-Bulb and Dry-Bulb Temperatures

In normal practice, the state of atmospheric air is specified by determining the wet-

bulb and dry-bulb temperatures. These temperatures are measured by using a device

called a psychrometer. The psychrometer is composed of two thermometers

mounted on a sling. One thermometer is fitted with a wet gauze and reads the wet-

bulb temperature. The other thermometer reads the dry-bulb, or ordinary,

temperature. As the psychrometer is slung through the air, water vaporizes from the

wet gauze, resulting in a lower temperature to be registered by the thermometer. The

dryer the atmospheric air, the lower the wet-bulb temperature will be. When the

relative humidity of the air is near 100 percent, there will be little difference between

the wet-bulb and dry-bulb temperatures. The wet-bulb temperature is approximately

equal to the adiabatic saturation temperature. The wet-bulb and dry-bulb

temperatures and the atmospheric pressure uniquely determine the state of the

atmospheric air.

Page 27: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

27

The Psychrometric Chart

For a given, fixed, total air-vapor pressure, the properties of the mixture are given in

graphical form on a psychrometric chart.

The air-conditioning processes:

Page 28: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

28

Page 29: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

29

Example 14-5

Determine the relative humidity, humidity ratio (specific humidity), enthalpy of the

atmospheric air per mass of dry air, and the specific volume of the mixture per mass

of dry air at a state where the dry-bulb temperature is 24oC, the wet-bulb temperature

is 16oC, and atmospheric pressure is 100 kPa.

From the psychrometric chart read

44%

8 0 0 008

46

08533

. .

.

g

kg

kg

kg

hkJ

kg

vm

kg

v

a

v

a

a

a

Page 30: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

30

Example 14-6

For the air-conditioning system shown below in which atmospheric air is first heated

and then humidified with a steam spray, determine the required heat transfer rate in

the heating section and the required steam temperature in the humidification section

when the steam pressure is 1 MPa.

Page 31: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

31

The psychrometric diagram is

-10 -5 0 5 10 15 20 25 30 35 40

0.000

0.005

0.010

0.015

0.020

0.025

0.030

0.035

0.040

0.045

0.050

T [C]

Hu

mid

ity R

ati

oPressure = 101.3 [kPa]

0.2

0.4

0.6

0.8

0 C

10 C

20 C

30 C

Psychrometric Diagram

1

2

3

1= 2=0.0049 kgv/kga

3=0.0091kgv/kga

h2=37 kJ/kga

h1=17 kJ/kga

h3=48 kJ/kga

v1=0.793 m^3/kga

Apply conservation of mass and conservation of energy for steady-flow to process

1-2.

Conservation of mass for the steady-flow control volume is

m mi

inlets

e

exits

Page 32: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

32

For the dry air

m m ma a a1 2

For the water vapor (note: no water is added or condensed during simple heating)

m mv v1 2

Thus,

2 1

Neglecting the kinetic and potential energies and noting that the work is zero, and

letting the enthalpy of the mixture per unit mass of air h be defined as

h h ha v

we obtain

( )

E E

Q m h m h

Q m h h

in out

in a a

in a

1 2

2 1

Page 33: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

33

Now to find the and h's using the psychrometric chart. ma

At T1 = 5oC, 1 = 90%, and T2 = 24oC:

The mass flow rate of dry air is given by

mV

va

1

1

Page 34: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

34

min

.

.min

min.m

m

m

kg

kg

s

kg

sa

a

a a

60

0 793

75661

601261

3

3

The required heat transfer rate for the heating section is

. ( )

.

Qkg

s

kJ

kg

kWs

kJ

kW

ina

a

1261 37 171

2522

This is the required heat transfer to the atmospheric air. List some ways in which this

amount of heat can be supplied.

At the exit, state 3, T3 = 25oC and 3 = 45%. The psychrometric chart gives

Page 35: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

35

Apply conservation of mass and conservation of energy to process 2-3.

Conservation of mass for the steady-flow control volume is

m mi

inlets

e

exits

For the dry air

m m ma a a2 3

For the water vapor (note: water is added during the humidification process)

( )

. ( . . )

.

m m m

m m m

m m

kg

s

kg

kg

kg

s

v s v

s v v

s a

a v

a

v

2 3

3 2

3 2

1261 0 0089 0 0049

0 00504

Page 36: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

36

Neglecting the kinetic and potential energies and noting that the heat transfer and

work are zero, the conservation of energy yields

( )

E E

m h m h m h

m h m h h

in out

a s s a

s s a

2 3

3 2

Solving for the enthalpy of the steam,

( ) ( )m h m h h

hh h

a s a

s

3 2 3 2

3 2

3 2

(48 37)

(0.0089 0.0049)

2750

as

v

a

v

kJ

kgh

kg

kg

kJ

kg

Page 37: Chapter 14: Gas-Vapor Mixtures and Air-Conditioningmechfamilyhu.net/download/uploads/mech1434187184323.pdfChapter 14 Gas-Vapor Mixtures and Air-Conditioning Study Guide in PowerPoint

37

At Ps = 1 MPa and hs = 2750 kJ/kgv, Ts = 179.88oC and the quality xs = 0.985.

See the text for applications involving cooling with dehumidification, evaporative

cooling, adiabatic mixing of airstreams, and wet cooling towers.