challenges of protection systems in distribution networks ... · source: ieee std. 3002.3-2018. 10...

53
Challenges of Protection Systems in Distribution Networks considering DER Juan Manuel Gers, PhD September 30 th 2020

Upload: others

Post on 25-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

  • Challenges of Protection Systemsin Distribution Networks

    considering DER

    Juan Manuel Gers, PhD

    September 30th 2020

  • Content

    • Introduction

    • High level comparison of US and Colombian systems

    • Protective relay in systems with DERs

    • Adaptive Protection during changing system conditions

    • Conclusions

  • Introduction

    Nonrenewable Energy

    Renewable Energy

    Nuclear Energy

    Coal Energy

    Oíl Energy

    Gas Energy

    Biomass Energy

    Solar Photovoltaic Energy

    Solar Thermal Energy

    Hidraulic Energy

    Ocean Thermal Energy

    Wind Energy

    Tidal Energy

    Sea Waves Energy

    Geothermal Energy

  • 5

    Photovoltaic systems are connected via DC/AC power electronics modules to the grid

    Technology

    Inversor

    National Grid

  • PV Generation

    Typical layout of a PV system

    PV Power Plant

    MPPT PWMReactive

    powercontroller

    AC FILTER

    =~

    Fire angle Amplitude

    𝑄𝑃𝑉𝑈𝐷𝐶𝐼𝐷𝐶

    𝑍𝑆 𝐸𝑆

    A photovoltaic system consists of anarrangement of several componentsto absorb and convert sunlight intoelectricity and a solar inverter tochange the electric current from DCto AC.

    It may also use a MPPT system toimprove the system's overallperformance.

    MPPT: Maximum Power Point TrackingPWM: Pulse Width Modulation

  • Wind Generation

    Circuit diagram of a Type 1 generatorFixed-speed WT

    Circuit diagram of a Type 3 generatorDoubly-fed induction generator WT

    Circuit diagram of a Type 2 generatorVariable-slip WT

    Circuit diagram of a Type 4 generatorFull-converter WT

  • 9

    Technology(DC synchronous generator behavior)

    Source: IEEE Std. 3002.3-2018

  • 10

    Technology(DC photovoltaic system behavior)

    Source: Fault current contribution from wind plants - IEEE PRSC

  • Considerations of Fault Current Contributions

    Considerations under fault conditions:

    • Inverters: 1.2 to 1.5 times the rated load current.

    • Synchronous generator: the fault contribution can reach more than six timesthe generator full-load current.

  • Content

    • Introduction

    • High level comparison of US and Colombian systems

    • Protective relay in systems with Renewables

    • Adaptive Protection during changing system conditions

    • Conclusions

  • High level comparison of US and Colombian systems

    Department of Energy

    Federal Energy Regulatory Comission

    Many Vertical Monopoloy Transmission OperatorsMany ISOs/RTOsThe ISO/RTO Council

    North American Electric Reliability Corporation

  • The US Regulatory & Market Scheme

    NERC■ ASCC Alaska Systems Coordinating Council

    ■ WECC Western Electricity Coordinating Council

    ■ MRO Midwest Reliability Organization■ SPP Soutwest Power Pool■ TRE Texas Reliability Entity■ NPCC Northeast Power Coordinating Council■ RFC Reliability First Corporation■ SERC SERC Reliability Corporation■ FRCC Florida Reliability Coordinating Council

  • The US Regulatory & Market SchemeVertical Monopoly Example

    Each Utility has:• Some generation units• Transmission• Distribution• Costumers• TSO rights

  • The US Regulatory & Market SchemeRegulatory responsibilities

  • High level comparison of US and Colombian systems

    Differences between* Highlights

    MinMinas DOE Both define responsibilities and policies for other organizations and entities.

    CREG FERC/NERC

    • CREG has a smaller market, regulates nation-wide• FERC regulates only interstate markets• NERC regulates technical aspects for planning and operation• USA has 50 different markets• Each state has its own regulations (e.g. FL’s Public Service Commision)• Each state can change FERC regulations to a certain degree

    UPME NERC

    • NERC is made up from nine big reliability entities.• NERC is a non-government organization, but it is an international regulatory authority• UPME makes proposals for CREG regulatory updates, NERC develops and enforces reliability

    standards• Term planning

    • UPME to mid and long term• NERC to short and long terms

    XM IRC• XM is the sole ISO for Colombia• IRC integrates every USA’s ISO into a single voice for desition-making and participation

    * Same row entities are not purely equivalent, as shown

  • Content

    • Introduction

    • High level comparison of US and Colombian systems

    • Protective relay in systems with Renewables

    • Adaptive Protection during changing system conditions

    • Conclusions

  • System Protection with DER’s

    Protectionsystem

    Reliability

    Response speed

    Selectivity

    Flexibility

  • Impacts of DERs on Protection

    • A traditional distribution system is a radial one-end-source system,• The present DGs also contribute to the fault current• Changes on the short-circuit level• Type, location and capacity of the DG affects the operation of the relay

    in the distribution network.

    Source: Fusheng, L Microgrid Technology and Engineering Application. 2016

  • Challenges of DERs in Protection Systems

    • Blindness of Protection• Unsynchronized Reclosing • Miscoordination• False Tripping

    Main impacts

    Source: L. Che. Et al. 2014A. Hooshyar. 2017

  • Synchronization Parameter Limits

    Source: IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric PowerSystems Interfaces," in IEEE Std 1547-2018 (Revision of IEEE Std 1547-2003) , vol., no., pp.1-138, 6 April 2018, doi:10.1109/IEEESTD.2018.8332112.

  • DER Response to Abnormal Frequencies

    Source: IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric PowerSystems Interfaces," in IEEE Std 1547-2018 (Revision of IEEE Std 1547-2003) , vol., no., pp.1-138, 6 April 2018, doi:10.1109/IEEESTD.2018.8332112.

  • Frequency Ride-through Requirements for DERs

    Source: IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric PowerSystems Interfaces," in IEEE Std 1547-2018 (Revision of IEEE Std 1547-2003) , vol., no., pp.1-138, 6 April 2018, doi:10.1109/IEEESTD.2018.8332112.

  • Source: IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric PowerSystems Interfaces," in IEEE Std 1547-2018 (Revision of IEEE Std 1547-2003) , vol., no., pp.1-138, 6 April 2018, doi:10.1109/IEEESTD.2018.8332112.

    Frequency Ride-through Requirements for DERs

  • System Protective Responses- OOS

    • PRC-024-2 Voltage and Frequency• OOS Based on the responses of multiple

    elements along the power system

    PSB of distance and underimpedanceprotection

    PSP of synchronous generators

    OST in transmission lines

    -0.60

    -0.10

    0.40

    0.90

    -0.40 0.10 0.60 1.10 1.60

    Rea

    ctan

    ce (p

    .u.)

    Resistance (p.u.)

    Path of Z in the plane R-X

    Contingency_1Contingency_2

    Power System Studies

    PRC-024-2Protective Set-Up

  • Protective relay in systems with Renewables

    Solar Panels are normally arranged in Strings. These can be connected inparallel to form a set of strings.

    Arrays are either strings connected in parallel either individually or in blocks ofstrings

    - + - + - +

    - + - + - +

    String 1

    String 2

    Array

    -+

    Combiner box

  • Protective relay in systems with Renewables

    +

    -

    Solar modules String combiner

    DC Connection +

    -

    Sub-array combiner

    Array fuse links

  • Protective relay in systems with Renewables

    Each individual string has to have fuses at both the positive and negativeends. Likewise, each array has to have fuses at both the positive andnegative terminals.

    The criteria to select fuse links for string protection when number of strings inparallel is higher than 3 according to the IEC 60269-6 are:

    • Voltage rating: ≥ 120% the open circuit voltage times the number ofmodules in series per string.

    • Current rating: ≥ 156% the short circuit current, but no more than thePV module maximum overcurrent protection rating specified by IEC61730-2.

  • Case Example of a 20 MVA Solar Farm

    One PV array consists of 504 PVPanels organized in 24 strings of21 modules.

    Five PV arrays are connected tothe DC input of the correspondinginverter.

    Two inverters are connected toeach power transformer. Thereare 10 power transformers perloop.

    The plant has two MV Loops.

    1 PV Panel = 235 W

    21 panels / string x 235 W = 4,935 W / string

    24 strings / array x 4935 W / string = 118,440 W / array

    5 array / inverter x 118440 W / array = 592,200 W / inverter

    2 inverter / transformer x 592200 W / inverter = 1,184,400W per transformer.

    10 power transformers x 1,184,400 W / transformer= 11,844,000 W per loop.

    2 loops x 11,844,000 W / loop = 23,688.000 W @ plant

    Plant Power = 23.69 MW

  • Case Example of a 20 MVA Solar Farm

    24 String Connections PV Panels connected in series

  • General Single Line Drawing for one 20 MVA Solar PV Plant

    Case Example of a Solar Farm

  • Single Line Drawing showing AC-DC connection

    Case Example of a Solar Farm

  • • MV Switchgear

    • Three winding Transformer: 1 MVA, 13.2 kV / 2 x 200 V

    • Inverters, 1000 V, 600 kVA each.

    • DC Fuses, 350 A, 1000 V.

    • 5 arrays connected to each inverter.

    • 1 array is composed 24 strings connected in parallel.

    • 1 string is composed of 21 PV solar panels connected in series. There are 504 PV modules per array.

    Case Example of a Solar Farm

  • Protective relay in systems with Renewables

    Large Machine Protection IEEE C37.102-2006

  • Protective relay in systems with Renewables

    Recommended protective scheme for wind farmsFunctional Block Diagram

    52

    27X 59X 59N 60V 59 27

    87

    50P 51V 46 50BF 67P

    50G 51G 67G

    32 32R 32L

    50N 51N 67N

    81U 81O VTFF

  • Protective relay in systems with Renewables

    SECTION DESCRIPTIONZone-1 = smaller of the two following criteria:1. 120% of unit transformer2. 80% of Zone 1 reach setting of the line relay on the shortest line (neglecting in-feed); time = 0.5 sZone-2 = the smaller of the three following criteria:A. 120% of longest line (with in-feed). If the unit is connected to a breaker and ahalf bus, thiswould be the length of the adjacent line.B. 50% to 66.7% of load impedance (150% to 200% of the generator capabilitycurve) at the RPFAC. 80% to 90% of load impedance (111% to 125% of the generator capabilitycurve) at themaximum torque angle; time > 60 cycles

    Note: Maximum load impedance at rated power factor does not encroach intothe reach. A value of 150% to 200% is recommended to avoid tripping duringnormal load. Zone2

  • Protective relay in systems with Renewables

    Table 1 - Recommended Settings

    IEEE No. FUNCTION Per IEEE C37.102 SECTION DESCRIPTION

    32 Reverse Power 4.5.5.3 & A.2.9

    Pickup setting should be below the following motoring limits: Gas : 50% rated power; time < 60 s Diesel : 25% rated power; time < 60 s Hydro turbines : 0.2% - 2% rated power; time < 60 s Steam turbines : 0.5% - 3% rated power; time < 30 s

    40

    Loss-of-field Approach # 1

    4.5.1.3 & A.2.1

    UNIT 1 Offset: X'd/2; Diameter: 1.0 pu; time: 0.1 s UNIT 2 Offset: X'd/2; Diameter: Xd; time: 0.5 to 0.6 s

    Loss-of-field Approach # 2

    UNIT 1 Offset: X'd/2; Diameter: 1.1 Xd - X'd /2 or 1.25Xd - X'd /2 ; Time: 0.25 s

    UNIT 2 Offset: XTG + X min SG1; Diameter: 1.1 Xd + XTG + Xmin SG1 or 1.25 Xd + XTG + Xmin SG1 Time: 1.0 s < t < 60 s.

    Angle of directional element = -13o

  • Protective relay in systems with Renewables

    SECTION DESCRIPTION

    46 Negative Sequence Overcurrent4.5.2 & A.2.8

    Pickup setting should be below the permissible I2 percent expressed in percent of rated current, which are indicated below:Salient pole: 10% With connected amortisseur windings : 10% With non-connected amortisseur windings : 5% Cilindrical rotor Indirectly cooled : 10%Directly cooled - Up to 350 : 8% - 351 MVA TO 1250 MVA : 8% (MVA-350)/300 - 1251MVA TO 1600 MVA : 5%Permissible K (I22 t)Salient pole generator : 40Synchronous condenser : 30Cylindrical rotor indirectly cooled : 30Cylindrical rotor directly cooled (0 MVA to 800 MVA) : 10 Directly cooled (801 MVA -1600 MVA) : See Figure 4-39

    50/87Differential via flux

    summation CTs or split-phase protection

    4.3.2.5.1The pickup of the instantaneous unit should be set above the CT error currentsthat may occur during external faults. The resulting settings offers little turn faultprotection.

    50/27Inadvertent Energization Overcurrent with 27, 81

    Supervision

    5.4.2.4 & A.2.4

    50: pickup ≤ 50% of the worst-case current value and should be > 125% generator rated current.27: 50% Vn, time: 1.5 s

    Table 1 - Recommended Settings

    IEEE No. FUNCTION Per IEEE C37.102

  • Protective relay in systems with Renewables

    SECTION DESCRIPTION

    50 BF Generator Breaker Failure Protection4.7 & A.2.11

    Current detector: picku should be more sensitive than the lowest current present during fault involving currents.Timer > Generator breaker interrupt time + Curr det. dropout time + safety margin

    51N Stator Ground Over-current (Low,Med Z Gnd,Phase CT Residual)

    4.3.3.2The grounding resistor is selected to limit the generator's contribution to a single phase-to-ground fault at its terminals to a range of current between 200 A and150% rated full load current

    50/51NStator Ground Over-current(Low, Med Z Gnd, Neutral CT or Flux

    Summation CT)

    51GN, 51N Stator Ground Over-current(High Z Gnd)

    4.3.3.1.1

    Typically, the overvoltage relay has minimum pickup setting of approximately 5

    V. With this setting and with typical distribution transformar ratios, this scheme

    is capable of detecting faults to within 2% to 5% of the stator neutral.

    50/51 Time overcurrent protection(against overloads)

    4.1.1.2

    51 pickup: 75-100% FLC, time: 7 s at 218% FLC. FLC means full load current.

    50 pickup: 115% FLC, time: instantaneous unit is set to pick up at 115% of full-

    load current and is used to torque control the time-overcurrent unit. The

    instantaneous unit dropout should be 95% of higher of pickup setting.

    Table 1 - Recommended Settings

    IEEE No. FUNCTION Per IEEE C37.102

  • Protective relay in systems with Renewables

    SECTION DESCRIPTION

    51VC Voltage Controlled Overcurrent4.6.1.2 &

    A.2.6

    Overcurrent pickup: 50% FLCControl voltage: 75%Vn.Inverse time curve and dial settings should be set to coordinate with system line relays for close-in faults on the transmission lines at the plant.

    51VR Voltage Restrained Overcurrent4.6.1.2 &

    A.2.6

    Overcurrent pickup: 150% FLC at rated voltageInverse time curve and dial settings should be set to coordinate with system line relays for close-in faults on the transmission lines at the plant.

    59 Overvoltage 4.5.6. & A.2.12

    Relays with inverse time charac and instantaneousPickup: 110%Vn; t= 2.5 s at 140% of pickup settingInst : 130 - 150% VnRelays with definite time charac and 2 stagesAlarm pickup : 110%Vn; 10< t < 15 sTrip pickup : 150% Vn; time: 2 cycles

  • Protective relay in systems with Renewables

    Table 1 - Recommended Settings

    IEEE No. FUNCTION Per IEEE C37.102 SECTION DESCRIPTION

    67IE Directional O/C for Inadvertent Energization

    78 Out of Step 4.5.3 & A.2.2

    Mho Diameter : 2X'd + 1.5 XTG Blinder distance (d) = ((X'd + XTG + XmaxSG1)/2) x tan (90-(d/2)); d: angular separation between generator and the system which the relay determines instability. If there is not stability study available d = 120º t = as per transient stability study Typically 40 < t < 100 ms

    81 Over/under frequency (60 Hz systems) 4.5.8 & A.2.14

    Typical Setting 81U ALARM: 59.5 Hz Time: 10 s. The underfrequency load shedding setting in the systems is given as 59.3 Hz with a delay of 14 cycles. 81U TRIP: The generator 81U relay should be set below the pick-up of underfrequency load shedding relay set-point and above the off frequency operating limits of steam turbine.

    81O ALARM:Pick-up: 60.6 Hz, Time Delay 5 sec.

  • Protective relay in systems with Renewables

    SECTION DESCRIPTION

    87G Generator Phase Differential 4.3.3.2 & A.2.5Pickup : 0.3 ASlope : 10%time: instantaneous

    87GN Generator Ground Differential4.3.2

    87UD Unit Differential 4.3.2.6

    Table 1 - Recommended Settings

    IEEE No. FUNCTION Per IEEE C37.102

  • 61

    Application Example

  • 62

    Application Example

  • 63

    Application Example – Internal Fault

  • 65

    Application Example

  • 66

    Ejemplo de aplicación51V Falla Externa

  • 67

    Ejemplo de aplicación51V Falla Externa

  • Content

    • Introduction

    • High level comparison of US and Colombian systems

    • Protective relay in systems with Renewables

    • Adaptive Protection during changing system conditions

    • Conclusions

  • Outage of G2 I’r1 =It1+It2 Ir2 =It1

    T1 T2

    1

    2

    3

    4

    Grid

    G1

    G2

    Loss of a DG Source

    t2

    Ir2

    t’2aR1

    Ir1

    t1

    I’r1

    t’1

    R2

    Normal Condition Ir1 =It1+It2+Ig2 Ir2 =It1

    R2a

    Coordination is lost in the yellow area unless a setting group change is enabled

    Adaptive Protection during changing system conditions

  • System Protection with DER’s

    R-1 R-2

    R-DG

    RTU

    1 2

    1 21 2

    L-1 L-2

    Grid DG

    S. Group

    S. Group

    S. Group

    Example of adaptive protection setting with a RTU device

  • Content

    • Introduction

    • High level comparison of US and Colombian systems

    • Protective relay in systems with Renewables

    • Adaptive Protection during changing system conditions

    • Conclusions

  • Conclusions

    • Protection schemes of photovoltaic units are based mostly on fuses for both,string and array type modules. Setting procedure is simple to implement andnormally the short circuit level on the busbar is not incremented significantlywhen they are connected.

    • Wind generation units are more complex to coordinate than solar units for theprotection coordination.

    • The protection scheme of wind generators is similar to those used inconventional generators, which are more elaborate due to the dynamicbehavior of the generators and the complexity of the control systems.

    • Consideration of multiple scenarios and topologies must be done to guaranteealways proper protection and selectivity

    • Use of multiple setting protection groups is suggested whenever differentscenarios is an option. This requires the application of numerical-type ofrelays.

  • [email protected]

    Challenges of Protection Systems in Distribution Networks �considering DER ContentIntroductionTechnologyPV GenerationWind GenerationTechnology(DC synchronous generator behavior)Technology(DC photovoltaic system behavior)Considerations of Fault Current ContributionsContentHigh level comparison of US and Colombian systems�The US Regulatory & Market Scheme�The US Regulatory & Market Scheme�Vertical Monopoly ExampleThe US Regulatory & Market Scheme�Regulatory responsibilitiesHigh level comparison of US and Colombian systemsContentSystem Protection with DER’sImpacts of DERs on ProtectionChallenges of DERs in Protection SystemsSynchronization Parameter LimitsDER Response to Abnormal FrequenciesFrequency Ride-through Requirements for DERsFrequency Ride-through Requirements for DERsSystem Protective Responses- OOSProtective relay in systems with RenewablesProtective relay in systems with RenewablesProtective relay in systems with RenewablesCase Example of a 20 MVA Solar FarmCase Example of a 20 MVA Solar FarmCase Example of a Solar FarmCase Example of a Solar FarmCase Example of a Solar FarmProtective relay in systems with RenewablesProtective relay in systems with RenewablesProtective relay in systems with RenewablesProtective relay in systems with RenewablesProtective relay in systems with RenewablesProtective relay in systems with RenewablesProtective relay in systems with RenewablesProtective relay in systems with RenewablesProtective relay in systems with RenewablesApplication ExampleApplication ExampleApplication Example – Internal FaultApplication ExampleEjemplo de aplicación�51V Falla ExternaEjemplo de aplicación�51V Falla ExternaContentSlide Number 74System Protection with DER’sContentSlide Number 77Slide Number 78