centennial towers elc – evstudio project # co11-003 ...evstudio.com/du2011files/addendum1.pdf ·...
TRANSCRIPT
1117 Cherokee St.1117 Cherokee St.1117 Cherokee St.1117 Cherokee St. 303.670.7242 ph303.670.7242 ph303.670.7242 ph303.670.7242 ph [email protected]@[email protected]@evstudio.com
Denver, CO 80204Denver, CO 80204Denver, CO 80204Denver, CO 80204 303.679.1862 fax303.679.1862 fax303.679.1862 fax303.679.1862 fax www.evstudio.comwww.evstudio.comwww.evstudio.comwww.evstudio.com
Date: May 17, 2011 6:00 PM Centennial Towers ELC – EVstudio project # CO11-003 Centennial Halls – EVstudio project # CO11-004 Addenda #1 REVISIONS TO CENTENNIALS HALLS DRAWINGS BY ARCHITECT: Sheet A2.0
1. Door, frame details and window hardware a. This has been updated to be “Door and Window Legend” b. Refer to attached AD1.5 for revised Door and Window Legend
2. Enlarged Reception Plan has been revised. Refer to AD1.3 attached. Sheet A2.1
1. Detail bubble labeled X/Ax at elevator lobbies and entrance to classroom/meeting should be labeled 15/A3.0. Refer to AD1.4 attached for a revised detail.
2. Note 75 should read: New gypsum board light cove. RE: 16/A3.0 3. Note 76 should read: 2’-0”X2’-0” ACT ceiling grid system. Hold as tight to ceiling
as possible while accommodating new lighting and existing sprinkler system. 4. Note 78 should read: 2’-0”x2’-0” act w/ compasso trim. Hold tight to underside of
fire sprinkler lines. 5. Note 80 should read: “New 3-1/8”X12” Douglas Fir 24F-V8 architectural grade
glulam beams at ceiling. RE: 7&8/A3.0 & 13/A3.1” Refer to AD1.1 attached for revised detail.
6. Note 87 should read: “New glass panel infill. RE: 12&14/A3.0”
Sheet A3.0 1. Elevation 1/A3.0 should show RB1 beneath the window, PT2 for the gypsum
board wall with the window and ACT for the ceiling tile in the adjoining space. 2. Elevation 3/A3.0 should show PBT1 in place of the CBT1 3. Elevation 8/A3.0 should show CWT1 at the face of the reception casework, ST1
at countertop and ACT at the ceiling 4. Elevation 6/A3.0 should show PBT1 in place of the CBT1. The tube steel should
be painted PT8E 5. Details 12 & 14/A3.0 should show 1x2 not 1x3 rift sawn red oak. 6. Detail 15/A3.0 has been revised. See AD1.4 attached.
Sheet A3.1
1. Detail 5/A3.1 should cut through the reception and transaction counter and not the accessible portion of the counter.
2. Detail 6/A3.1 CWT has been replaced with CWT1. The material finish note PT8E pointing to the underside of the counter has been replaced with PL2 and points to the top of the counter.
3. Detail 7/A3.1 The ST1 material finish note pointing to the face of the wall has been replaced with OVP
4. Elevation 3A/A3.1 the fireplace surround material finish callout has been relocated for better legibility. It should read CWT1. PT4 has been replaced with PT2
5. Elevation 4/A3.1 and screen D have been revised. See screen detail revised Sheet A3.2. 4/A3.1 sim.
6. Details 10 & 11/A3.1 have been revised to show a 2x2 rift sawn red oak edge piece and a 3” wide x 1.5” tall (actual size) piece in between. See AD1.0 and AD1.2 attached.
2222////7777
1117 Cherokee St.1117 Cherokee St.1117 Cherokee St.1117 Cherokee St. 303.670.7242 ph303.670.7242 ph303.670.7242 ph303.670.7242 ph [email protected]@[email protected]@evstudio.com
Denver, CO 80204Denver, CO 80204Denver, CO 80204Denver, CO 80204 303.679.1862 fax303.679.1862 fax303.679.1862 fax303.679.1862 fax www.evstudio.comwww.evstudio.comwww.evstudio.comwww.evstudio.com
Sheet A3.2
1. Screen walls A,B,C,D,E and F have been revised to only include one lit panel each. See revised sheet A3.2 attached
2. Screen wall D has been revised. See revised sheet A3.2 attached 3. The main floor finish schedule and finish legend have been revised. See revised
sheet A3.2 attached. 4. A lighting equipment schedule has been provided as an attachment.
Electrical
1. The contractor to provide (6) double head battery pack egress lights (DU standard) to be located as directed.
2. Sheet E2.1 Electrical outlet 3. Sheet E2.1 Switch for fireplace at reception
3333////7777
1117 Cherokee St.1117 Cherokee St.1117 Cherokee St.1117 Cherokee St. 303.670.7242 ph303.670.7242 ph303.670.7242 ph303.670.7242 ph [email protected]@[email protected]@evstudio.com
Denver, CO 80204Denver, CO 80204Denver, CO 80204Denver, CO 80204 303.679.1862 fax303.679.1862 fax303.679.1862 fax303.679.1862 fax www.evstudio.comwww.evstudio.comwww.evstudio.comwww.evstudio.com
RESPONSE TO QUESTIONS BY BIDDERS: Changes to Bid Timeline – 4:00 PM Tuesday May 24
th 2011
1. Add/Alternate: Provide 42 data ports total at Computer Lab, 21 of which are to be
installed above counter plus one outlet per chair. (Provide a plug mold strip just under and just above the countertop containing both power and data). Also provide dividers under the countertops separating each work station. Monitors to be installed on wall using arm wall mounts placed 14-18” above the finished countertop height. Provide 5” wood backing strips around countertop.
2. Add/Alternate: Provide two duplex outlets per wall in each classroom, instead of only one.
3. Clarification to Bid Form: (Chris Shelton) To any/all Mechanical contractors bidding this project: the Controls portion of your bid should be broken out as an Add/Alt.
4. Question 0.1 (Haselden Construction): Do you have an Asbestos Report on the ceilings
in the serving line and freezer areas that needs to be removed? Answer: Asbestos Report to be provided by University. Contact Chris Shelton.
5. Question 6.1 (Haselden Construction): Section 01 10 00.1.04.B says the University is supplying the shelving. There is no shelving shown on the drawings. Is there shelving with this project? Answer: There is no shelving included in the project.
6. Question 9.1 (Haselden Construction): Do you require the tile floor that is to remain to be floated level so the grout joints do not show through the carpet tiles? Answer: Yes, the remaining floor tile should be floated level.
7. Question 10.1 (Haselden Construction): Section 01 10 00.1.04.B say the University is to provide the Projectors. Are they also providing the mounting units for the projectors at the ceiling? Answer: (Chris Shelton) Yes, typically the only thing the contractor supplies is the roughed in utilities (this includes an empty j-box and conduit back to the professors station so that the AV contractor can pull his necessary wire, it also includes a data line and duplex outlet in the ceiling as well as at the professors station)
8. Question 15.1 (Western States Fire Protection): WSFP – See attached RFI from Western States Fire Protection? It was noted that the note #3 to demo the existing freezer units. Does this mean the entire room & ceiling in rooms #157, #160, #161 and #163? Also the rooms #148, 149 and 150 there is a low soffit & ceiling where the fire sprinkler lines are below the ceiling @ center line of 7’-4”, does this ceiling get demo’d? do I need to remove my pipe and raise it? On the RCP A2.0, rooms #157,161,162,164,165 and 166 call for an 8’-0” ceiling, is this going to stay at 8’-0”? Answer: All freezer units to be removed in all rooms, and ceiling to be removed and replaced throughout entire space. The pipe will need to be removed and raised to accommodate the 8’-0” ceiling height throughout. Yes, all rooms to be at an 8’-0” ceiling height.
9. Question 15.1 (Western States Fire Protection): WSFP – On the plans note #16 stating about the asbestos abatement, is there going to be an abatement crew to cut and drill holes through the “hot tiles” and /or remove the asbestos? WSFP is NOT an abatement
4444////7777
1117 Cherokee St.1117 Cherokee St.1117 Cherokee St.1117 Cherokee St. 303.670.7242 ph303.670.7242 ph303.670.7242 ph303.670.7242 ph [email protected]@[email protected]@evstudio.com
Denver, CO 80204Denver, CO 80204Denver, CO 80204Denver, CO 80204 303.679.1862 fax303.679.1862 fax303.679.1862 fax303.679.1862 fax www.evstudio.comwww.evstudio.comwww.evstudio.comwww.evstudio.com
company and will not drill anchors for new pipe through the asbestos tiles without having them abated first. Who is doing the abatement? Answer: (Chris Shelton) Assuming this is pertinent only to Halls, there will be an asbestos company available if necessary but I’m not anticipating a major issue here since the tiles are not “hot” it is only the glue. If there is a big enough concern, we may have to have the contractor lay the walls out and snap lines on the ceiling, then the abatement company can come in and remove those tiles (and glue).
10. Question 15.2 (FPI): What is the University’s procedure for fire sprinkler system shut down and refill of the system? Answer: (Chris Shelton) I don’t think we have a “formal” procedure but they need to contact our Plumbing Shop (Don Auman @ 303-871-3219) at least 24 hours ahead of time so that Don can assist with drain down, a call also needs to be placed to our Campus Safety that the system will be offline for “x” many hours, their number is 303-871-2334.
11. Question 15.3 (FPI): The existing fire protection lines in the existing kitchen (Freezer areas) are at 7’-4” elevation AFF, and the new ceiling elevation is proposed at 8’-0”. Do you require the existing fire protection system be raised above the proposed ceiling elevation? Answer: Yes, the existing fire protection system will have to be raised to accommodate the proposed 8’-0” ceiling height.
12. Question 15.4 (M Tech): Do you have a preference for what brand of temperature controls you want included? Answer: The Specifications indicate to tie into existing.
13. Question 15.5 (M Tech): Are the temperature controls for the new work required to be tied into any existing campus BAS? Answer: Yes, the temperature controls are required to be tied into the existing campus BAS.
14. Question 15.6 (M Tech): Please identify where the new AHU is to be located. Answer: The new AHU is going to be in the same place as the existing unit in the Basement.
15. Question 15.7 (M Tech): Outside air is not shown. Please identify routing. Answer: Refer to sheet 3/M2.0, Mechanical AHU Layout Detail. The Outside Air routing is located at the back of the box. The Return Air comes through the top of the AHU.
16. Question 15.8 (M Tech): It appears the new walls go to the underside of the existing structure. Please identify air openings and return air paths to get back to the new AHU. Answer: The new walls do not go to the underside of existing structure.
17. Question 15.9 (M Tech): Are any fire / smoke dampers required? Answer: There are fire / smoke dampers required at the existing mechanical shaft on the East Wall. Also, 1-Hr fire stopping is required to be provided at the piping penetration.
18. Question (GH Phipps): Note 80/A2.1/Halls States Glue-Lam Ceiling Treatment, please clarify what this is. Answer: This note should read “GLULAM CEILING TREATMENT RE: 7 & 8/A3.0” Also the note “GLULAM BEAM. RE:9/A3.1” on 8/A3.0 should refer to 13/A3.1. Refer to AD1.1 attached for more information.
5555////7777
1117 Cherokee St.1117 Cherokee St.1117 Cherokee St.1117 Cherokee St. 303.670.7242 ph303.670.7242 ph303.670.7242 ph303.670.7242 ph [email protected]@[email protected]@evstudio.com
Denver, CO 80204Denver, CO 80204Denver, CO 80204Denver, CO 80204 303.679.1862 fax303.679.1862 fax303.679.1862 fax303.679.1862 fax www.evstudio.comwww.evstudio.comwww.evstudio.comwww.evstudio.com
19. Question (GH Phipps): Note 67/A2.0/Halls Alt#1. Should this be on the bid form?
Answer: See revised bid form attached.
20. Question (GH Phipps): Please confirm bid time is 4 p.m. 5/23 at 2240 East Wesley. Can be bids be emailed? Answer: Bid date has been revised to May 24
rd, 4:00 PM at the
campus architect’s office 2400 South Race Street. Only hard copies will be accepted.
21. Question (GH Phipps): Please confirm basketball court pricing is for budgeting only? Answer: Basketball court pricing is for school budgeting purposes and should be called out as such on the bid.
22. Question 0.1 (Haselden Construction): Please provide an asbestos report on all areas that require demolition or renovation? Answer: University to provide asbestos report when it becomes available.
23. Question 0.2 (Haselden Construction): The supports for the new ACT “Clouds” require anchoring to the structure above. Who is going to do the asbestos abatement to allow penetration to the existing glued on tile? Answer: (Chris Shelton) Assuming this is pertinent only to Halls, there will be an asbestos company available if necessary but I’m not anticipating a major issue here since the tiles are not “hot” it is only the glue. If there is a big enough concern, we may have to have the contractor lay the walls [,clouds and lights] out and snap lines on the ceiling, then the abatement company can come in and remove those tiles (and glue).
24. Question 0.3 (Haselden Construction): Removal of the recessed and semi-recessed lights will require an asbestos abatement contract. Who is scheduled to complete this portion of the work? Anser: Refer to answer given under answer 23.
25. Question 2.2 (Haselden Construction): Sport Court Alternate - The existing stairs to the courtyard that remain bear directly on the existing concrete slab. Do you want this portion of the slabs to remain? If no – What do you want to replace the bearing points? Answer: Maintain existing concrete slab underneath, to the sides, between stairs and to a point extending 3’-6” in the direction of travel from the stairs.
26. Question 10.1 (Haselden Construction): Toilet Partitions / Accessories – Plan calls for removal of all wall & floor tile in the men’s and women’s restrooms. This will require removal of the Toilet Partitions & Accessories. Sheet A2.0 indicates mounting heights for new Accessories. Do you require new Accessories & Partitions be installed in the remodeled restrooms? Answer: A new 18” grab bar mounted vertically per 3/A2.0 will be required. All remaining accessories, grab bars, fixtures and partitions are existing accessories and will be re-used. Mount the accessories as noted on 3/A2.0.
27. Question 15.1 (Haselden Construction). WSFP – See attached RFI’s Answer: Refer to answer given under answer 23.
28. Question 15.2 (Haselden Construction). FPI – Asbestos material at the ceiling is required to be abated. Please advise when this is to be accomplished. Answer: Refer to answer given under answer 23.
29. Question 1 (PCL Construction): The bid form doesn’t accommodate deductive alternates #1 and #2. Are we to include these? Answer: The bid form has been updated to include deductive alternates #1 and #2
6666////7777
1117 Cherokee St.1117 Cherokee St.1117 Cherokee St.1117 Cherokee St. 303.670.7242 ph303.670.7242 ph303.670.7242 ph303.670.7242 ph [email protected]@[email protected]@evstudio.com
Denver, CO 80204Denver, CO 80204Denver, CO 80204Denver, CO 80204 303.679.1862 fax303.679.1862 fax303.679.1862 fax303.679.1862 fax www.evstudio.comwww.evstudio.comwww.evstudio.comwww.evstudio.com
30. Question 2 (PCL Construction): It is understood that for doors labeled ‘1’ and ‘2’ will require new frames. The notes for doors labeled ‘A1’ to ‘A4’ also note in the details that they are also to have new frames to match DU standards as applicable. Please confirm that new frames for all doors are to be provided as opposed to new doors in existing frames. Answer: Doors 1 and 2 are new doors in new metal frames to the trash room #162 and Student Works Resource Center #114 as indicated on plan. Doors A1-A4 are part of a deduct alternate which calls for new doors in new metal frames to match University standard. Centennial Halls currently has a wide variety of door species and hardware types. The winning contractor is to coordinate with the University to update doors and frames to their standard. This contract will only include new doors, new frames, new strike plates and new hinges. This is deduct alternate 2. See AD1.5 attached.
31. Question 3 (PCL Construction): For door type 2: Assuming that this door (labeled ‘wood metal door’) is a metal door, please provide a specification for metal doors. Answer: It is a metal door. Please refer to the attached metal door specification.
32. Questions 4 (PCL Construction): Specifications 08 12 13, 08 14 16, and 08 71 00 all note at 3.05 of each respective specification section that a schedule is shown on the drawings. No schedule is shown on the drawings. Please provide a door schedule. Answer: These should reference the Doors & Windows Legend on sheet A2.0. See attached AD1.5 for revision.
33. Question 5 (PCL Construction): The drawings detail the connection of the sawn red oak to the tube steel as being a ‘1/2 x 2 ½ bolt with washer 12” o.c. each side and painted PT8E’. Please clarify: The effect desired is a bolt head at either side – is the expectation to tap the steel column in lieu of a nut connection? Answer: Please refer to sheet AD1.0 attached.
34. Question 6 (PCL Construction): Where the red oak sandwiches red oak at the glazing and we are place the bolts 12” o.c., how are we thread these? Answer: Refer to detail sheet AD1.0 attached.
35. Question 7 (PCL Construction): Please define how the floor and wall connectors detailed by detail 9 of A3.1 attach to the steel / glu-lam members being supported. Answer: Refer to detail sheet AD1.1 attached.
36. Question 8 (PCL Construction): The glazing at the screen walls is to be held in place by ½” x ½” metal angle to be painted PT8E. How is this angle attached to the structure? Answer: Refer to sheet AD1.2 attached.
37. Question 9 (PCL Construction): With regard to the LED strips that’s to be placed above the frosted glass panels at the screen walls, would it be acceptable to consider the structure as acceptable conduit for the power leads? A: It is expected that the power supplies and/or drivers will be located in or near the abandoned back-lit glass cavity. The leader cables can be run through the tube steel without conduit. Openings as needed for power runs shall be indicated on the shop drawings and ultimately concealed as part of final construction.
38. Question 10 (PCL Construction): Please define the size, species, and grade of the glu-lam beams Answer: New 3-1/8”X12” Douglas Fir 24F-V8 architectural grade glulam beams
7777////7777
1117 Cherokee St.1117 Cherokee St.1117 Cherokee St.1117 Cherokee St. 303.670.7242 ph303.670.7242 ph303.670.7242 ph303.670.7242 ph [email protected]@[email protected]@evstudio.com
Denver, CO 80204Denver, CO 80204Denver, CO 80204Denver, CO 80204 303.679.1862 fax303.679.1862 fax303.679.1862 fax303.679.1862 fax www.evstudio.comwww.evstudio.comwww.evstudio.comwww.evstudio.com
39. Question 11 (PCL Construction): Please define how the west end of the glu-lam beams are secured to the structure Answer: Refer to detail sheet AD1.1 attached.
40. Question 12 (PCL Construction): The drawings show a direct vent gas fireplace that is vented through the roof. Please define: The fireplace finishes, The roof modifications to support, The vent, Mechanical modifications, Flu design, Gas design, Controls for fireplace, Electrical modifications, Switching Answer: Contractor to bid logs, pebbles. Submit samples of full color range available during submittal process. Roof modifications, flue design, gas design and controls are design build and per fireplace manufacturer’s requirements. Also see work not 70 on sheet A2.0. The fireplace will be switched at the reception counter. Refer to attached product cut sheet and electrical drawing detail.
41. Question 17 (PCL Construction): The screen wall details on page A3.2 have an abbreviation ‘BL’ at several openings. Please define ‘BL’. Answer: Luminaire BL is the LED tape. See attached lighting equipment schedule.
42. Question 18 (PCL Construction): The drawings state that the contractor is to move the ATM and Vending Machines. Please confirm that this is acceptable with ATM and Vending Machine owners. Answer: The University’s vendors will relocate the ATM and vending machines.
43. Question 19 (PCL Construction): Please provide a section cut of the wall mounted leaflet display shown on A2.0 Answer: Leaflet display is part of furniture package, NIC.
44. Question 20 (PCL Construction): Page A2.0 plan note 55 is shown in rooms 145, 102, and 114 where there is no ‘new screen’. Please clarify. Answer: Plan note 55 has been revised to read “Paint and repair existing radiator shroud.”
Attachments: AD1.0 AD1.2 AD1.3 AD1.4 AD1.5 A3.2 Electrical Computer Room Revision Electrical EM LTG Revision Electrical Fire Place Switch Revision Electrical Outlet Revision Fireplace Specification Metal Door Specification Lighting Equipment Schedule
2'-5
1
2
"2'-6
1
2
"
8"
3"
6"x6" TUBE STEEL
3"x6" TUBE STEEL
FROSTED GLASS PANEL.
RE: 10/11/A3.1
COLUMN SADDLE. RE:9/A3.1
BOTTOM OF
SPRINKLER LINE. V.I.F.
4"
EXISTING COLUMN WITH
NEW TILE
10"
2'-3"
1'-8"
1'-0"
1'-0"
GP4 GP3
6'-0"2'-5"
2'-4"
6"
1'-10"
1'-0"
3'-3"
1'-6"
3"x6" TUBE STEEL
FROSTED GLASS PANEL
COLUMN SADDLE TOP AND
BOTTOM. RE: 9/A3.1
BOTTOM OF SPRINKLER
LINE. V.I.F.
2'-5"
EXISTING COLUMN
3'-1"
17'-0"
3'-1"
2'-9"
1'-6"
1'-0"
6"
DROP CEILING PER A2.1
DIRECT-VENT FIREPLACE
READING
NOOK
READING
NOOK
GP3
GP2
GP3
GP4
BL
2'-5"2'-5"
6'-0
1
2
"
1'-0"
8"
1'-2"
2'-2"
2'-7"
6"x6" TUBE STEEL
3"x6" TUBE STEEL
GLASS PANEL.
RE:10/11/A3.1
LUMINAIRE RE:A2.1
COLUMN SADDLE. RE: 9/A3.1
OUTLET PER ELECTRICAL
8'-4" +
/-
BOTTOM OF SPRINKLER
LINE. V.I.F.
2'-5"
EXISTING COLUMN
2X6 WOOD MEMBER
GP4
GP4 GP2
OPPOSITE
SIDE
GP5
OPPOSITE
SIDE
GP2
OPPOSITE
SIDE
GP3
BL AT GP2
BL AT GP5
GP2
2'-6
1
2
"
BL AT GP2
BL AT GP5
4'-10"
4
1
2
"
2'-6"
7
1 2
"
8"
7"
1'-6"
6"
8"
4'-5" +
/-
6"x6" TUBE STEEL
3"x6" TUBE STEEL
FROSTED GLASS PANEL WITH
TOP AND BOTTOM EDGE
LIGHTING. RE:
FROSTED GLASS PANEL. RE: 10/11/A3.1
LUMINAIRE RE:A2.1
COLUMN SADDLE. RE:9/A3.1
DUPLEX OUTLET.
8'-4" +
/-
BOTTOM OF SPRINKLER LINE.
V.I.F.
2'-6
1
2
"
9
1 2
"
2X6 WOOD MEMBER
GP2
GP5
BL
BL
2'-5" 2'-5"
4
1
2
"
5'-8"
2'-4"
8"
3"
1'-0"
2'-1"
2'-6"
1'-0"
6"x6" TUBE STEEL
3"x6" TUBE STEEL
FROSTED GLASS PANEL
WITH TOP AND BOTTOM
EDGE LIGHTING. RE:
10/11/A3.1
LUMINAIRE RE:A2.1
COLUMN SADDLE. RE: 9/A3.1
DUPLEX OUTLET.
7'-6"
8'-4" +
/-
BOTTOM OF SPRINKLER
LINE. V.I.F.
2'-6
1
2
"
2X6 WOOD MEMBER
GP3
GP4 GP3
BL
BL
4'-11
1
2
"
2'-5"
4
1
2
"
2'-6"
1'-3"
1'-0"
3'-3"
8"
1'-7"
1'-0"
9"
2'-6"
1'-6"
6"x6" TUBE STEEL
3"x6" TUBE STEEL
FROSTED GLASS PANEL. RE:
FROSTED GLASS PANEL
WITH TOP AND BOTTOM
EDGE LIGHTING. RE:
10/11/A3.1
LUMINAIRE RE:A2.1
COLUMN SADDLE. RE:9/A3.1
OUTLET PER ELECTRICAL
8'-0"
8'-4" +
/-
BOTTOM OF SPRINKLER
LINE. V.I.F.
GP3
GP2
GP4
BL
BL
2'-6
1
2
"
8"
3"
7"
10"
2'-2"
2'-8"
1'-0"
1'-2"
6"x6" TUBE STEEL
3"x6" TUBE STEEL
COLUMN SADDLE. RE:9/A3.1
BOTTOM OF
SPRINKLER LINE. V.I.F.
EXISTING COLUMN WITH
NEW TILE
NOTE: ALL WIRING FOR
OUTLETS AND LIGHTING TO BE
RUN INSIDE OF TUBE STEEL
FRAME.
ENTIRE
SHEET
REVISED
WARNING: If the information in these instructions are not followed exactly, a fi re or explosion may result causing property damage, personal injury or loss of life.
FOR YOUR SAFETYDo not store or use gasoline or other fl ammable vapors and liquids in the vicinity of this or any other appliance.
Installation and service must be performed by a qualifi ed installer, service agency or the gas supplier.
FOR YOUR SAFETYWhat to do if you smell gas:Do not try to light any applianceDo not touch any electrical switch:
do not use any phone in your building.
Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fi re department.
FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4918-883a
Regency Horizon™ HZ54EGas Fireplace
04/26/10
Owners & Installation Manual
www.regency-fi re.com
Tested by:Installer: Please complete the details on the back cover
and leave this manual with the homeowner.Homeowner: Please keep these instructions for future reference.
MODELS: HZ54E-NG Natural Gas HZ54E-LP Propane
2Regency Horizon HZ54E Gas Fireplace
This appliance can only be used with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
This appliance may be installed as an OEM installation in a manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer's instruction and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the Untied States, or the Standard for Installation in Mobile Homes, CAN/CSA Z240 MH, in Canada.
MANUFACTURED MOBILE HOME REQUIREMENTSINFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE
This Regency® product has been tested and listed by Warnock Hersey/Intertek as a Direct Vent Wall Furnace to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88-2009 / CSA 2.33-2009 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN / CGA 2.17-M91.
This appliance may only be installed in an aftermarket permanently located, manufactured (U.S.A only) or mobile home, where not prohibited by local codes.
This Direct Vent System Appliance must be installed in accordance with the manufacturer's installation instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or the current Standard of Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240-MH Mobile Home Standard in Canada.
This appliance installation must comply with the manufacturer's installation instructions and local codes, if any. In the absence of local codes follow the current National Fuel Gas Code, ANSI Z223.1 and the current National Electrical Code ANSI/NFPA 70 in the U.S.A., and the current CAN/CGA B149 Gas Installation Code and the current Canadian Electrical Code CSA C22.1 in Canada.
This appliance comes equipped with a dedicated #8 Ground Lug for attachment of the ground wire to the steel chassis as applicable to local codes.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
Ensure that structural members are not cut or weakened during installation.
Regency Horizon HZ54E Gas Fireplace3
To the New Owner:
Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The HZ54E has been designed to provide you with all the warmth and charm of a wood fi replace at the fl ick of a switch. The model HZ54E has been approved by Warnock Hersey/Intertek for both safety and effi ciency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency® Fireplace.
4Regency Horizon HZ54E Gas Fireplace
TABLE OF CONTENTSSAFETY LABEL
Copy of Safety Decal .....................................................5
REQUIREMENTS
MA Code - CO Detector.................................................6
DIMENSIONS
Unit Dimensions ............................................................7Faceplate & Door frame overlay Dimensions ................7
INSTALLATION
Important Message ......................................................8Before You Start ............................................................8General Safety Information............................................8Installation Checklist ......................................................9Locating Your Gas Fireplace .........................................9Heatwave kit ..................................................................9Heatrelease kit...............................................................9Clearances ..................................................................10Non-Combustible Requirements .................................10Top non-combustible facing board............................... 11Mantel Clearances.......................................................12Mantel Leg Clearances................................................12Framing & Finishing.....................................................13Unit Assembly Prior To Installation ..............................15
Standoff Assembly ...............................................15Nailing Strips ........................................................15
Venting Introduction .....................................................15Vent Restrictor Position ...............................................16Exterior Vent Termination Requirements .....................17Venting Arrangements ................................................18
Horizontal Termination (Flex) ...............................18Rigid Pipe Venting Systems ........................................19
Basic Horizontal & Vertical Terminations .............195” x 8” Rigid Pipe Cross Reference Chart ...................20Venting Arrangements ................................................22
Allowable Horizontal Terminations for HZ54E-ng 22Venting Arrangements ................................................22
Allowable Horizontal Terminations for HZ54E-lp .22Venting Arrangements ................................................25
Allowable Vertical Terminations for HZ54E-ng .....25Venting Arrangements ................................................26
Allowable Vertical Terminations for HZ54E-lp ......26Unit Installation with Horizontal Termination ................27Unit Installation with Vertical Termination ....................28Unit Installation ............................................................29
Horizontal Termination .........................................29with Flex Vent System .........................................29
High Elevation .............................................................30Gas Line Installation ....................................................30
Pilot Adjustment ...........................................................30Gas Pipe Pressure Testing ..........................................30886 S.I.T. Valve ...........................................................30Valve cover removal ....................................................31Aeration Adjustment ....................................................32Wiring Diagram ............................................................32Profl ame system GTMF with optional fan....................33Optional fan Wiring Diagram ......................................34Optional Wall Thermostat ...........................................35Optional Remote Control .............................................35Wall Switch ..................................................................35Battery & on | off switch installation ............................37GT remote installation .................................................38GTM remote installation ..............................................39GTMF remote installation ............................................41Optional Refl ective Panel Installation ..........................43Glass Crystals or optional ceramic stones ..................44Installation On Burner ..................................................44Glass Crystals or optional pebbles ..............................45Installation On fi rebox base .........................................45Optional Log set Installation ........................................46Faceplate & Door frame overlay Installation................49Optional fan installation ...............................................51
OPERATING INSTRUCTIONS
Operating Instructions .................................................54First Fire ......................................................................54Lighting Procedure ......................................................54Shutdown Procedure ...................................................54Normal Operating Sounds of Gas Appliances .............54Copy of Lighting Plate Instructions ..............................55
MAINTENANCE
Maintenance Instructions.............................................56General Vent Maintenance ..........................................56Glass Gasket ...............................................................56Glass Door...................................................................56
Glass Replacement .............................................56Glass Door Removal ...................................................57Valve Tray Replacement ..............................................58HZ54E-NG unit ............................................................59HZ54E-LP unit .............................................................60
PARTS LIST
Main Assembly ............................................................61Accessories .................................................................62
WARRANTY
The Warranty: Limited Lifetime ...................................63
Regency Horizon HZ54E Gas Fireplace5
SAFETY LABELThis is a copy of the label that accompanies each HZ54E-NG and HZ54E-LP Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review.
NOTE: Regency® units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
CO
PY O
F SA
FETY
DEC
AL
For the State of Massachusetts, installation and repair must be done by a plumber or gasfi tter licensed in the Commonwealth of Massachusetts.
For the State of Massachusetts, fl exible con-nectors shall not exceed 36 inches in length.
For the State of Massachusetts, the appli-ances individual manual shut-off must be a t-handle type valve.
The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.
DO
NO
TR
EM
OV
ET
HIS
LA
BE
L/N
EP
AS
EN
LE
VE
RC
ET
TE
ÉT
IQU
ET
TE
363
DO
OR
SE
AL
:P
lea
se
ch
ec
kth
at
the
do
or
isp
rop
erl
ys
ea
led
FP
IFir
epla
ceP
rod
uct
sIn
tern
atio
nal
Ltd
.Del
ta,B
C,C
anad
a
Min
imu
mC
lear
ance
sto
Co
mb
ust
ible
s/
Deg
agem
ent
Min
imu
mD
eM
ater
iau
xC
om
bu
stib
les
Se
ria
lNo
./N
od
ese
rie 9
18-8
85
MA
YB
EIN
STA
LL
ED
INM
AN
UFA
CT
UR
ED
(MO
BIL
E)
HO
ME
SA
FT
ER
FIR
ST
SA
LE
.
Lis
ted
:C
ert
ifie
dfo
r/C
ert
ifi
ep
ou
r:Teste
dto
:W
N#
16577
VE
NT
ED
GA
SF
IRE
PLA
CE
HE
AT
ER
/C
AN
AD
Aand
U.S
.A.
FO
YE
RA
UG
AZ
ÀÉ
VA
CU
AT
ION
éC
AN
/CG
A-2
.17-M
91,A
NS
IZ
21.8
8a-2
007/C
SA
2.3
3a-2
007
. NO
TF
OR
US
EW
ITH
SO
LID
FU
EL
./N
EP
AS
UT
ILIS
ER
AV
EC
DU
CO
MB
US
TIB
LE
SO
LID
E.
Made
inC
anada/F
abrique
au
Canada
(See
Inst
ruct
ion
Man
ual
for
det
aile
din
stru
ctio
ns)
ÉÉ
éQ
UIP
AL
'US
INE
PO
UR
GA
ZP
RO
PA
NE
CO
NC
UP
OU
RC
ET
PO
EL
E:
Mo
dle
HZ
54E
-LP
PR
OP
AN
EG
AS
:M
od
elH
Z54
E-L
P
AP
PAR
EIL
FO
NC
TIO
NN
AN
TA
UN
AT
UR
AL
GA
SC
ON
CU
PO
UR
CE
TP
OE
LE
:M
od
le
Pre
ssio
nd'
allim
enta
tion
min
imum
Pre
ssio
nà
latu
bulu
red'
chap
pem
ent
lev
eP
ress
ion
àla
tubu
lure
d'ch
appe
men
tbas
seG
rand
eur
del'i
njec
teur
Dbi
tm
inim
umse
lon
Dbi
tm
axim
umse
lon
l'alti
tudeC
alor
ifiqu
eC
alor
ifiqu
e
é
éé
éé
é é
HZ
54E
-NG
Pre
ssio
nd'
allim
enta
tion
min
imum
Pre
ssio
nà
latu
bulu
red'
chap
pem
ent
lev
eP
ress
ion
àla
tubu
lure
d'ch
appe
men
tbas
seG
rand
eur
del'i
njec
teur
Dbi
tm
inim
umse
lon
Dbi
tm
axim
umse
lon
l'alti
tudeC
alor
ifiqu
eC
alor
ifiqu
e
éé
éé
é é
D
E
F
AB
C
Sid
eW
alls
A4
”(1
02
mm
)
B40-7
/8”
(1038m
m)
C2
0"
(50
8m
m)
D1
3”
(33
0m
m)
E8
3"
(21
08
mm
)
F3
6"
(91
4m
m)
Cei
ling
Min
.Man
telH
eig
ht
Max
.Man
telD
epth
Alc
ove
Wid
th
Alc
ove
Dep
th
This
applia
nce
must
be
inst
alle
din
acc
ord
ance
with
loca
lcodes,
ifany;
ifnone,fo
llow
the
Natio
nalF
uelG
as
Code,A
NS
IZ
223.1
,or
Natu
ralG
as
and
Pro
pane
Inst
alla
tion
Code,C
SA
B149.1
.T
his
applia
nce
must
be
inst
alle
din
acc
ord
ance
with
the
Sta
ndard
CA
N/C
SA
Z240
MH
,Mobile
Housi
ng,i
nC
anada,o
rwith
the
Manufa
cture
dH
om
eC
onst
ruct
ion
and
Safe
tyS
tandard
,Titl
e24
CF
R,P
art
3280,i
nth
eU
nite
dS
tate
s,orw
hen
such
ast
andard
isnota
pplic
able
,AN
SI/N
CS
BC
SA
225.1
/NF
PA
501A
,Manufa
cture
dH
om
eIn
stalla
tions
Sta
ndard
orA
NS
IA11
9.2
ou
NF
PA
501C
Sta
ndard
forR
ecr
eatio
nalV
ehic
les
This
applia
nce
isonly
foru
sew
ithth
ety
pe
ofg
as
indic
ate
don
the
ratin
gpla
teand
may
be
inst
alle
din
an
afterm
ark
et,
perm
anently
loca
ted,m
anufa
cture
d(m
obile
)hom
ew
here
notp
rohib
ited
by
loca
lcodes.
See
ow
ner's
manualf
ord
eta
ils.
Inst
alle
rl'a
ppare
ilse
lon
les
codes
ou
règle
ments
loca
ux,
ou,e
nl'a
bse
nce
de
tels
règle
ments
,selo
nle
sco
des
d'in
stalla
tion
AN
SIZ
223.1
,Natio
nalF
uelG
as
Code
ou
CS
A-B
149.1
en
vigueur.
Inst
alle
rl'a
ppare
ilse
lon
lanorm
eC
AN
/CS
A-Z
240,S
érie
MM
,Mais
on
mobile
sou
CA
N/C
SA
-Z240
VC
,Véhic
ule
sde
cam
pin
g,o
ula
norm
e24
CF
RP
art
3280,M
anufa
cture
dH
om
eC
onst
ruct
ion
and
Safe
tyS
tandard
.Sic
es
norm
es
ne
sontp
as
pert
inente
s,util
isez
lanorm
eA
NS
I/N
CS
BC
SA
225.1
/NF
PA
501A
,Manufa
cture
dH
om
eIn
stalla
tions
Sta
ndard
,ou
AN
SIA
119.2
ou
NF
PA
501C
Sta
ndard
for
Recr
eatio
nal
Vehic
les.
Th
isve
nte
dg
asfi
rep
lace
hea
teri
sn
otf
oru
sew
ith
airf
ilter
s.N
ep
asu
tilis
erd
efi
ltre
àai
rave
cce
foye
rau
gaz
àév
acu
atio
n.
FO
RU
SE
WIT
HG
LA
SS
DO
OR
SC
ER
TIF
IED
WIT
HT
HE
AP
PL
IAN
CE
ON
LY
Ceta
ppare
ildoit
êtr
eutil
ize
uniq
uem
enta
vec
lety
pe
de
gaz
indiq
ué
surl
apla
que
signalé
tique.C
eta
ppare
ilpeutê
tre
inst
allé
dans
une
mais
on
pré
fabriquée
ou
mobile
(É.-
U.s
eule
ment)
inst
allé
eà
dem
eure
sile
srè
gle
ments
loca
ux
leperm
ettent.
Voir
lanotic
ede
l'util
isate
urp
ourp
lus
de
rense
ignem
ents
.
PO
UR
UT
ILIS
AT
ION
UN
IQU
EM
EN
TA
VE
CL
ES
PO
RT
ES
EN
VE
RR
EC
ER
TIF
IÉE
SA
VE
CL
'AP
PA
RE
IL
Min
.S
up
ply
Pre
ssu
re1
2“W
C(2
.98
kpa
)L
ow
Se
ttin
gM
an
.P
ress
ure
6.4
"WC
(1.5
9kp
a)
Ma
x.M
an
ifold
Pre
ssu
re1
0"W
C(2
.49
kpa
)O
rific
eS
ize
#4
9D
MS
Min
imu
mIn
pu
t3
0,0
00
Btu
/M
axi
mu
mIn
pu
t3
7,0
00
Btu
/h(1
0.8
4kW
)(8
.79
kW)
0-4
50
0ft
/pi
(0-1
37
2m
)A
ltitu
de
Min
.S
up
ply
Pre
ssu
re5
“W
C(1
.25
kpa
)L
ow
Se
ttin
gM
an
.P
ress
ure
1.6
"WC
(0.4
0kp
a)
Ma
x.M
an
ifold
Pre
ssu
re3
.5"W
C(0
.87
kpa
)O
rific
eS
ize
#3
0D
MS
Min
imu
mIn
pu
t2
9,0
00
Btu
/hM
axi
mu
mIn
pu
t4
1,5
00
Btu
/h(1
2.1
6kW
)(8
.50
kW)
0-4
50
0ft
/pi
(0-1
37
2m
)A
ltitu
deNA
TU
RA
LG
AS
:M
od
elH
Z54
E-N
G
6Regency Horizon HZ54E Gas Fireplace
REQUIREMENTS
5.08: Modifications to NFPA-54, Chapter 10
(2) Revise 10.8.3 by adding the following additional requirements:
(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for
residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than
seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall
be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery
operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon
monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of
thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon
monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions
shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL
OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a)1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the
instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a
Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies
"special venting systems", the following requirements shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and
detailed installation instructions.
(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions,
all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of
the installation.
MA Code - CO Detector(for the State of Massachusetts only)
Regency Horizon HZ54E Gas Fireplace7
DIMENSIONS
59” (1499mm)
52-5/8” (1337mm)
48-1/2” (1232mm) 20-1/2” (521mm)
19-3/4” (502mm)
10-5/8”(270mm)
1-1/2”(38mm)
31
-5/8
”(8
03
mm
)
46
-3/8
”(1
17
8m
m)
35
-1/4
”(8
95
mm
)
22
-3/8
”(5
68
mm
)
17
-1/8
”(4
35
mm
)
5-1
1/1
6”
(144m
m)
8”(203mm)Outer Dia.
5” (127mm)Inner Dia.
FACEPLATE & DOOR FRAME OVERLAY DIMENSIONS
UNIT DIMENSIONS
8Regency Horizon HZ54E Gas Fireplace
INSTALLATION
10) Be aware of electrical wiring locations in walls and ceilings when cutting holes for termination.
11) Under no circumstances should this appliance be modifi ed. Parts that have to be removed for servicing should be replaced prior to operating this appliance.
12) Installation and any repairs to this appliance should be done by an authorized service per-son. A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.
13) Do not slam shut or strike the glass door.
14) Under no circumstances should any solid fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.
15) The appliance area must be kept clear and free of combustible materials, (gases and other fl ammable vapours and liquids).
Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.
IMPORTANT MESSAGE SAVE THESE
INSTRUCTIONSThe HZ54E Direct Vent Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual fi rst. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fi replace is installed in compliance with manufacturers instructions and all applicable codes.
BEFORE YOU STARTSafe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI Standards to make you aware of the following:
GENERAL SAFETY INFORMATION
1) The appliance installation must conform with lo-cal codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CAN1-B149 or ANSI Z223.1 Installation Codes.
2) The appliance when installed, must be electri-cally grounded in accordance with local codes, or in the absence of local codes with the current National Electrical Code, ANSI/NFPA 70 or CSA C22.1 Canadian Electrical Code.
3) See general construction and assembly in-structions. The appliance and vent should be enclosed.
4) This appliance must be connected to the speci-fi ed vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is fi tted as per Venting instructions.
5) Inspect the venting system annually for blockage and any signs of deterioration.
6) Venting terminals shall not be recessed into a wall or siding.
7) Any safety glass removed for servicing must be replaced prior to operating the appliance.
8) To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fi replace.
9) Wear gloves and safety glasses for protection while doing required maintenance.
CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPE-CIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAY TO AVOID BURNS OR CLOTHING IGNITION.
INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL, ETC. IT IS IMPERATIVE THAT CONTROL COMPARTMENTS, BURNERS AND CIRCULATING AIR PASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.
DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.
WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.
CLOTHING OR OTHER FLAMMABLE MATERIAL SHOULD NOT BE PLACED ON OR NEAR THE APPLIANCE.
YOUNG CHILDREN SHOULD BE CARE-FULLY SUPERVISED WHEN THEY ARE IN THE SAME ROOM AS THE APPLI-ANCE.
Regency Horizon HZ54E Gas Fireplace9
INSTALLATIONThis includes:
1) Clocking the appliance to ensure the correct fi ring rate (rate noted on label 41,500 Btu/h (NG), after burning appliance for 15 minutes.
2) If required, adjusting the primary air to ensure that the fl ame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that causes sooting or carboning that results in dam-age is not the responsibility of the manufacturer.
LOCATING YOUR GAS FIREPLACE
A) Flat on WallB) Flat on Wall CornerC) Recessed into Wall/AlcoveD) Corner
Diagram 1
1) When selecting a location for your fi replace, ensure that the clearances are met.
2) The appliance must be installed on a fl at, solid, continuous surface For example a wood, metal or concrete fl oor or in a raised (on the wall) ap-plication. The appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
3) The HZ54E Direct Vent Gas Fireplace can be installed in a recessed position or framed out into the room as in A, B, C and D. See Diagram 1.
INSTALLATION CHECKLIST
1) Locate appliance a) Room location (Refer to "Locating Your Gas
fi replace" section) b) Clearances to Combustibles (Refer to
"Clearances" section) c) Mantle Clearances (Refer to "Mantel
Clearances" section) d) Framing & Finishing Requirements (Refer
to "Framing & Finishing" section) e) Venting Requirements (Refer to "Venting"
section)
2) Assemble Top and Side Standoffs (Refer to "Unit Assembly Prior to Installation).
3) Slide unit into place.
4) Install vent (Refer to "Venting Arrangement" sections).
5) Make gas connections (Refer to "Gas Line Installation section).
6) Install 4 AA batteries into battery pack.
7) Test the pilot (Refer to "Pilot Adjustment" section).
8) Test Gas Pressure (Refer to "Gas Pipe Pressure Testing" section).
9) Install standard and optional features. Refer to the following sections:
a) Optional Log Set Installation b) Glass Crystals/ Optional Ceramic Stones c) Optional Firebox Base Pebbles d) Optional Refl ective Panels e) Faceplate / Door Frame Overlay f) Remote Control g) Wall Thermostat h) Wall Switch
10) Final check.
Before leaving this unit with the customer, the installer must ensure that the appliance is fi ring correctly and operation fully explained to customer.
4) This appliance is Listed for bedroom installations using the standard Remote (millivolt thermostat system). Some areas may have further requirements, check local codes before installation.
5) The HZ54E Direct Vent Gas Fireplace is approved for alcove installations, see "Clearances" section for details.
6) We recommend that you plan your installation on paper using exact measurements for clearances and fl oor protection before actually installing this appliance. Have an authorized inspector, dealer, or installer review your plans before installation.
Note: For vent terminations refer to "Exterior Vent Termination Locations" section.
HEATWAVE DUCT SYSTEM
OPTIONAL KIT #946-556The HeatWave Air Duct Kit increases the effectiveness of your fi replace by dispersing warm air from the fi replace to remote locations in the same room or other rooms in your home.
Up to two kits may be installed on the fi replace.
Please Note: Only 1 HeatWave kit may be operated at one time. This includes the internal blower option as well.
OPTIONAL HEAT RELEASE KIT
#946-570The Heat Release Kit expels warm air from the fi replace to the outside of the building, allowing the fi replace to be operated with less heat entering the room. The kit may be used on either the left or right side.
The HeatWave Duct Kit has different clearance and framing requirements, check the HeatWave manual for details.
10Regency Horizon HZ54E Gas Fireplace
INSTALLATION
Caution RequirementsThe top, back and sides of the fi replace are defi ned by
standoffs. The metal ends of the standoff may NOT be recessed into combustible construction.
WARNINGFire hazard is an extreme risk if these clearances (air space) to combustible materials are not adhered to. It is of greatest importance that this fi replace and vent system be
installed only in accordance with these instructions.
CLEARANCESThe clearances listed below are Minimum distances unless otherwise stated:
A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fi replace and vent system be installed only in accordance with these instructions.
F
B
E
D
A
Installed Close
to Floor
G
Clearance: Dimension Measured From:A: Mantel Height (min.) 20" (508mm) Top of Fireplace Opening
B: Sidewall (on one side) 4" (102mm) Side of Fireplace Opening
C: Ceiling (room and/or alcove) 40-7/8" (1038mm) Top of Fireplace Opening
D: Mantel Depth (max.) 13" (330mm) 30" Above Fireplace Opening
E: Alcove Width 83" (2108mm) Sidewall to Sidewall (Minimum)
F: Alcove Depth 36" (914mm) Front to Back Wall (Maximum)G: To Floor 28 - 7/8" (733mm) Top of Fireplace OpeningNote 0" No hearth required
F
B
C
Installed Closeto Ceiling
Flue Clearances to CombustiblesHorizontal - Top 3"Horiztonal - Side 2"Horiztonal - Bottom 2"Vertical 2"
Passing through wall/f loor/cei l ing - when fi restop is used.
1-1/2"
48"
(121
9mm
)
4"(102mm)
5-5/8”(143mm)
28
”(7
11m
m)
20
"(5
08
mm
)
22
-3/8
”
52-5/8”
60-1/2" (1537mm)
Non-combustibleMaterial
Non-combustible Material
No
n-c
om
bu
stib
leM
ater
ial
No
n-c
om
bu
stib
leM
ater
ial
Metal Stud (header)
Wood StudWood Stud
NON-COMBUSTIBLE REQUIREMENTS
The HeatWave Duct Kit and the Heat Release Kit have different clearance and framing requirements, check the HeatWave and Heat Release manual for details.Heat Release Kit
Regency Horizon HZ54E Gas Fireplace11
INSTALLATION
48"
(121
9mm
)
4"(102mm)
6-1/2”(165mm)
28
”(7
11m
m)
20"
(508m
m)
21
-3/4
”
52-5/8”
61-1/2" (1537mm)
Non-combustibleFacing Board
Non-combustible Material
No
n-c
om
bu
stib
leM
ater
ial
No
n-c
om
bu
stib
leM
ater
ial
Metal Stud (header)
Wood StudWood Stud
INSTALLATION OF TOP FACING
Non- combustible board(calcium silicate)
Non-combustible boardMUST BE PRIMED.
Non-combustible board(from building supply store)
61-1/2”
½”
20”
Caution: This non-combustible board can be damaged if dropped or struck. Handle with care.
1) Using drywall screws - secure non combustible material around unit, framing and top nailing strip every 6 inches.
Important Note: To avoid cracking the board - pre-drill holes prior to securing to unit/ framing.
2) Wipe any debris/dust from the non combustible material and drywall.
3) Prior to taping and mudding it is highly recommended to prime the facing using a quality primer. This will ensure proper adhesion of both the tape and mud. The optional board is very porous.
4) Tape the seams using a mesh type tape.
5) Mud seams as normal. We recommend using a product called Durabond high strength compound - for the fi rst coat This product can be found at any hardware store. Mud must be cured as per manufacturer’s recommendations.
6) Prime wall for a second time for proper adhesion of paint
7) Paint walls using a high quality paint which will withstand the high temperatures being emitted from this appliance.
Note: Due to the high temperatures being emitted from this appliance, mudded joints may crack.
Note: In addition to the top piece of non-combustible board - other non-combustible boards will be required to complete this installation. These materials can be found at most building supply stores.
If fi nishing the wall above the unit with paint - the top non-combustible board (Part # 476-936 - shipped separately from the unit) should be installed.
Calcium silicate board is a high - grade material with cement, quartz, natural and selected minerals as the main raw materials. It is widely used for partitions and ceilings in buildings. It is fi re proof and earthquake proof.
If fi nishing the wall above the unit with materials such as tile, brick, marble, etc. non-combustible board available from the building supply store can be used.
TOP NON-COMBUSTIBLE FACING BOARD(PART # 476-936)
22-3
/8"
5-5/8"(123mm)
12Regency Horizon HZ54E Gas Fireplace
INSTALLATIONMANTEL CLEARANCES
Due to the extreme heat this fi replace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in
Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.
MANTEL LEG CLEARANCESCombustible mantel leg clearances as per diagram:
4"
Allowable mantelleg projection
5-1/2” (140mm)
8” (203mm)
11” (279mm)
1.5" (38mm)
MANTEL LEG 4”(102mm)Non-Combustible
7”
Drywall
2
0
12 6 4810
Top ofFireplaceOpening
13" (330mm)
3 ½" (89mm)
Standoff
Metal Stud(On Edge)
0
14
Non-combustibleFacing
To UnitBase Legs
1" (25mm)30”
20”
21”
28-1/8”
Combustible Material
the diagram on the right.
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board.
Regency Horizon HZ54E Gas Fireplace13
INSTALLATION
N6) Determine the total thickness of facing material (eg. hardiboard + ceramic tile) to ensure the fi nished surface is fl ush with the front edge of the unit (see diagram below). If necessary, side and top nailing strips are adjustable, loosen the 1/4" screws and adjust.
Total non-combustible facing allowable: Min. = 1/2" Max. = 1- 1/2" See diagram below.
FRAMING & FINISHING1) Frame in the enclosure for the unit with framing material.
IMPORTANT: Header must be metal stud. All other framing may be of combustible type such as 2x4 / 2x6 framing materials.
ote: When constructing the framed opening, please ensure there is ac-cess to install the gas lines when the unit is installed.
2) For exterior walls, insulate the enclosure to the same degree as the rest of the house, apply vapour barrier and drywall, as per local installation codes. (Do not insulate the fi replace itself.)
WARNING: Failure to insulate and add vapor barriers to the inside of the exterior wall will result in operational and performance problems including, but not limited to: excessive condensation on glass doors, poor fl ame package, carbon, blue fl ames etc. These are not product related issues.
3) The unit does not have to be completely enclosed in a chase. You must maintain clearances from the vent to combustible materials: See "Clear-ances" section. Combustible materials can be laid against the side and back standoffs and the stove base.
4) The combined total of non-combustible facing materials (ie. hardiboard + tile, slate, etc) may be brought up to and overlap the face of the unit (top and bottom). The minimum thickness = 1/2"
to a maximum thickness = 1-1/2", as shown in the diagram below. If material is thicker than 1-1/2" - it will not be possible to mount
the faceplace.
5) When fi nishing around the faceplate, if material such as brick, stone, etc. extend past the faceplate depth - the minimum opening
dimensions noted below must be adhered to, this is to assure removal of the faceplate.
1-1/2”(38mm)
Max
½”(13mm)
Min
Important:Finishedfacingmaterial tobe flush withedge of unit.
FinishedMaterial
Nailing StripPosition
1/2" 1"
1" 1/2"
1-1/2" 0" (fl ush)
Unit
Nailing Strip1” Forward
Unit
Nailing Strip½” Forward
Unit
Nailing StripFlush w/unitFactory Set
Nailing Strips
14Regency Horizon HZ54E Gas Fireplace
INSTALLATION
A
B
C
D
E
F
G
H
I
J
K L
Non-CombustibleFacing
Metal Stud (Header)on edge
Metal Stud(Header)on edge
(Located on the right side of the fireplace)
Framing Dimensions Description HZ54E
A Framing Height 46-5/8” (1184mm)B Framing Width 60” (1524mm)
C* Framing Depth* 22” (559mm)D Minimum Height to Combustibles 51” (1295mm)E Corner Wall Depth 72" (1829mm)F Corner Facing Wall Width 101-7/8 (2586mm)G Vent Centerline Height 44” (1118mm)H Non-combustible facing height 20” (508mm)I Gas Connection Opening Height 1-1/2” (38mm)J Gas Connection Height 4” (102mm)K Gas Connection Inset 7-1/4” (184mm)L Gas Connection Opening Width 3-1/4” (83mm)
* Framing depth measurement is noted with the side nailing strips set as far forward on the fi rebox as possible. The side nailing strips can be adjusted back up to 1” to allow for varying thicknesses in non-combustible mate-rial & wall fi nishes.Important: The minimum framing dimensions given for height, width and depth must be maintained even if using non combustible materials. Dangerous operating conditions will occur if minimum framing dimensions are not adhered to.
Regency Horizon HZ54E Gas Fireplace15
INSTALLATIONNAILING STRIPS
The nailing strips come attached to the unit. There is 1 plate on each side,1 on the top, and one on the bottom that can be folded out as required. The top and side nailing strips are secured to the framing. The bottom nailing strip is secured to the unfi nished fl oor - if installing the unit directly on the fl oor.
Note: The bottom nailing strip will need to be bent on site and adjusted to accommodate the thickness of the facing material.
The top stand off / nailing strip is shipped attached to the back of the unit as shown below.
1) Remove one screw in location shown below. Replace the screw on the back the unit after removing the standoff / nailing strip.
2) Bend the 3 tabs at the bottom of the stand off / nailing strip to 90°, bend in the same direction as the top tabs.
3) Install on the top front of the unit as shown in diagram 3. Do not fully tighten the screws when installing - until the facing thickness has been determined.
UNIT ASSEMBLY PRIOR TO
INSTALLATIONThe Top Standoff/ Nailing Strip, side nailing strips and standoffs must be correctly positioned and attached to the unit before sliding the unit into position.
STANDOFF ASSEMBLY
The top, side, rear and bottom standoffs are shipped in a fl at position and must be folded into shape and attached - see diagram 1.
1) Remove the standoffs from the unit.
2) Take each standoff and bend into the correct shape. Bend up at the bend lines until the screw holes in the standoff and the pre-punched screw holes on the unit line up.
VENTING INTRODUCTIONThe HZ54E uses the "balanced fl ue" technology Co Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These fl ue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.
IMPORTANT NOTEFraming depth measurement is noted with the side nailing strips set as far forward on the fi rebox as possible. The nailing strips can be adjusted back up to 1” to allow for varying thicknesses in non-combustible material & wall fi nishes.
Remove this screw to release top standoff / nailing strip
Standoff
Nailing Strips
Standoff
Diagram 1
Diagram 2
Diagram 3
Standoff
Standoff
16Regency Horizon HZ54E Gas Fireplace
INSTALLATION
Vent restriction is required for certain venting installations, see the diagrams in the "VentingArrangements" section to determine if they are required for your installation.
The Vent Restrictor plate is located on the inside top of the fi rebox.
To set the vent restriction as indicated in the venting arrangements diagrams, refer to the following instructions;
1) Remove the glass door.
2) Remove the screws that hold the vent restrictor plate in place.
3) Adjust the vent restrictor plate to the required vent restrictor position as per the diagrams shown.
4) Once the vent restrictor plate is in the required position, secure with screws.
VENT RESTRICTOR POSITION
Vent Restrictor Settings for HZ54E-NG
Vent Restrictor Settings for HZ54E-LP
4.25”
3”
2”
Vent Restrictor Set 1Factory Set Vent Restrictor(No adjustment required)
Vent Restrictor Set 2
Vent Restrictor Set 3
SET 2THIS HOLE SETS THEVENT RESTRICTOR
AT 3”
SET 1THIS HOLE SETS THEVENT RESTRICTOR
(factory setting)AT 4.25”
SET 3THIS HOLE SETS THEVENT RESTRICTOR
AT 2”
4.25”
2”
1”
Vent Restrictor Set 1Factory Set Vent Restrictor(No adjustment required)
Vent Restrictor Set 3
Vent Restrictor Set 4
SET 1THIS HOLE SETS THEVENT RESTRICTOR
(factory setting)AT 4.25”
SET 3THIS HOLE SETS THEVENT RESTRICTOR
AT 2”
SET 4THIS HOLE SETS THEVENT RESTRICTOR
AT 1”
Regency Horizon HZ54E Gas Fireplace17
INSTALLATION
EXTERIOR VENT TERMINATION REQUIREMENTS
Minimum Clearance Requirements Canada1 USA2
A Clearance above grade, veranda, porch, deck, or balcony 12"(30cm) 12"(30cm)
B Clearance to window or door that may be opened 12"(30cm) 9" (23cm)
C Clearance to permanently closed window * *
D Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm) from the center line of the terminal (check with the local code)
24"(60cm) 24"(60cm)
E Clearance to unventilated soffi t 24"(60cm) 24"(60cm)
F Clearance to outside corner: with AstroCap Termination Cap. 13"(33cm) 13"(33cm)
Clearance to outside corner: with all other approved Termination Caps. 13"(33cm) 13"(33cm)
G Clearance to inside corner: with AstroCap Termination Cap 13"(33cm) 13"(33cm)
Clearance to inside corner: with all other approved Termination Caps. 13"(33cm) 13"(33cm)
H Clearance to each side of center line extended above meter/regulator assembly 36"(90cm)a *
J Clearance to service regulator vent outlet 36"(90cm) *
K Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance 12"(30cm) 9" (23cm)
L Clearance to a mechanical air supply inlet 72"(1.8m) 36"(90cm)b
M Clearance above paved sidewalk or a paved driveway located on public property 84"(2.1m)┼ *
N Clearance under veranda, porch, deck, or balcony 12"(30cm)‡ *
1 In accordance with current CSA B149.1, Natural Gas and Propane Installation Code2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code┼ A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor
* Clearance in accordance with local installation codes and the requirements of the gas suppliera 3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assemblyb 3 feet (91cm) above - if within 10 feet (3m) horizontally
18Regency Horizon HZ54E Gas Fireplace
INSTALLATION
8” dia.Flue pipe
5” dia. flue pipe
spring spacer
Termination CapAstroCap XL
TM
(Part #946-623/P)
Vent Guard - if required*(Part #946-506/P)Wall Thimble
(Mandatory in allHorizontal Terminations)
Vinyl SidingStandoff
VENTING ARRANGEMENTS HORIZONTAL TERMINATION (FLEX)
Regency® Direct Vent System
These venting systems, in combination with the HZ54E, have been tested and listed as a direct vent system by Warnock Hersey/Intertek. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram from the "Exterior Vent Termination Locations" section.FPI Direct Vent (Flex) System Termination Kits include all the parts needed to install the HZ54E using a fl exible vent.Notes: 1) Liner sections should be continuous without any joints or
seams.
2) Only Flex pipe purchased from FPI may be used for Flex installations.
3) Horizontal vent must be supported every 3 feet.
4) A wall thimble is mandatory for all horizontal terminations due to high temperatures.
FPI Kit # Length Contains:#946-615 4 Feet 1) 8” fl exible liner (Kit length)
2) 5” fl exible liner (Kit length)3) spring spacers4) thimble5) AstroCap termination cap6) screws7) tube of Mill Pac8) plated screws9) S.S. screws #8 x 1-1/2” drill point10) vinyl siding standoff
#946-618 6 Feet
#946-616 10 Feet
Regency Horizon HZ54E Gas Fireplace19
INSTALLATION
RIGID PIPE VENTING SYSTEMS
BASIC HORIZONTAL & VERTICAL TERMINATIONS
Rigid Pipe Vent Systems offer a complete line of component parts for installation of both horizontal and vertical installations. Many items are offered in decorative black, as well as galvanized fi nish.
The minimum components required for a basic Horizontal Termination are:
1 AstroCap XL Termination Cap 1 90o Elbow 1 Rigid Pipe Adaptor 1 Wall Thimble 1 Length of rigid pipe to suit wall thickness
The minimum components required for a basic Vertical Termination are:
1 Vertical Termination Cap 1 Rigid Pipe Adaptor 1 Lengths of pipe to adequately penetrate roof 1 Ceiling Firestop 1 Flashing 1 Storm Collar
Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl, furring strips may be used, instead of a vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal must not be recessed into siding. Measure the wall thickness including furring strips.
If a Vinyl Siding Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add 2 inches.
When using Rigid Vent other thanSimpson Dura-Vent, 3 screws must be used to secure rigid pipe to adaptor.
The FPI AstroCap XLTM is certifi ed for installations using FPI venting systems as well as Simpson Dura-Vent® Direct Vent Pro, ICC Excel and Selkirk Direct-Temp. AstroCap XLTM is a proprietary trademark of FPI Fireplace Products International Ltd. Dura-Vent® and Direct Vent are registered and/or proprietary trademarks of Simpson Dura-Vent Co. Inc.
This product has been evaluated by Intertek for using a Rigid Pipe Adaptor in conjunction with Simpson DV Pro, Metal-Fab Sure-Seal, ICC Excel and Selkirk Direct-Temp systems. Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Warnock Hersey/Intertek listing of components.
WARNING:
Do not combine venting components from different venting systems.
Exception: However, use of the the AstroCap XLTM is acceptable with all systems.
Alternate SnorkelTermination Cap
HOT
Alternate Horizontal Termination
Caps
Rigid PipeAdaptor (770-994)
Pipe Length
Vertical Terminal
Storm Collar
Flashing
Ceiling Firestop
PipeLength
Pipe Length
90 Elbowo
AstroCap XLTermination Cap
(Part #946-623/P)
Wall Thimble(Mandatory in all
Horizontal Terminations)
Vinyl SidingStandoff (Optional)
Vent Guard - if required*(Part #946-506/P)
20Regency Horizon HZ54E Gas Fireplace
INSTALLATION
Adjustable Length 3”-10”-Galvanized N/A N/A 5DAL TC-5DLT
Adjustable Length 3”-10”-Black N/A N/A 5DALB TC-5DLTB
Adjustable Length 11”-14” -Galvanized Disc. - See 58DV-08A 5DT-AJ N/A N/A
Adjustable Length 11”-14” -Black Disc. - See 58DV-08B 5DT-AJB N/A N/A
Extension Pipe 17”-24” -Galvanized Disc. - See 58DV-16A N/A N/A N/A
Extension Pipe 17”-24” -Black Disc. - See 58DV-16AB N/A N/A N/A
Adjustable Length 8-1/2”-Galvanized 58DVA-08A - N/A from FPI N/A N/A N/A
Adjustable Length 8-1/2”-Black 58DVA-08AB N/A N/A N/A
Extension Pipe 16”-Galvanized 58DVA-16A - N/A from FPI N/A N/A N/A
Extension Pipe 16”-Black 46DVA-16AB N/A N/A N/A
45º Elbow-Galvanized 58DVA-E45 5DT-EL45 5DT-EL45 TE-5DE45
45º Elbow-Black 58DVA-E45B 5DT-EL45B 5DT-EL45B TE-5DE45B
45º Elbow Swivel-Galvanized Disc. - See 58DVA-E45 N/A N/A N/A
45º Elbow Swivel-Black Disc.-See 58DVA-E45B N/A N/A N/A
90º Elbow-Galvanized 58DVA-E90 5DT-EL90S 5DT-EL90S TE-5DE90
90º Elbow-Black 58DVA-E90B 5DT-EL90SB 5DT-EL90SB TE-5DE90B
90º Elbow, Swivel-Galvanized Disc. - See 46DVA-E45 N/A N/A N/A
90º Elbow, Swivel-Black Disc. - See 46DVA-E45 N/A N/A N/A
90º Starter Elbow, Swivel-Galvanized N/A N/A N/A N/A
Adaptor* N/A N/A N/A N/A
Ceiling Support 58DVA-DC 5DT-CS 5DSP TE-5DE45
Cathedral Support Box 58DVA-CS 5DT-CSS 5DRS TE-5DE45B
Wall Support/Band 58DVA-WS 5DT-WS/B 5DWS N/A
Offset Support 58DVA-ES - N/A from FPI 5DT-OS N/A N/A
Wall Thimble-Black 58DVA-WT 5DT-WT 5DWT TE-5DE90
Wall Thimble Support/Ceiling Support 58DVA-DC - N/A from FPI N/A N/A TE-5DE90B
Firestop Spacer 58DVA-FS 5DT-FS 5DFS N/A
Trim Plate-Black 58DAV-WFS 5DT-TP 5DCP N/A
Description SimpsonDirect Vent Pro®
SelkirkDirect Temp™
Metal-Fab™Sure Seal
ICC Excel Direct
6” Pipe Length-Galvanized 58DVA-06 5DT-6 5D6 TC-5DL6
6” Pipe Length-Black 58DVA-06B 5DT-6B 5D6B TC-5DL6B
9” Pipe Length-Galvanized 58DVA-09 5DT-9 N/A N/A
9” Pipe Length-Black 58DVA-09B 5DT-9B N/A N/A
12” Pipe Length-Galvanized 58DVA-12 5DT-12 5D12 TC-5DL1
12” Pipe Length-Black 58DVA-12B 5DT-12B 5D12B TC-5DL1B
18” Pipe Length-Galvanized 58DVA-18 5DT-18 5D18 TC-5DL18
18” Pipe Length-Black 58DVA-18B - N/A from FPI 5DT-18B 5D18B TC-5DL18B
24” Pipe Length-Galvanized 58DVA-24 5DT-24 5D24 TC-5DL2
24” Pipe Length-Black 58DVA-24B 5DT-24B 5D24B TC-4DL2B
36” Pipe Length-Galvanized 58DVA-36 5DT-36 5D36 TC-5DL3
36” Pipe Length-Black 58DVA-36B 5DT-36B 5D36B TC-5DL3B
48” Pipe Length-Galvanized 58DVA-48 5DT-48 5D48 TC-5DL4
48” Pipe Length-Black 58DVA-48B 5DT-48B 5D48B TC-5DL4B
60” Pipe Length-Galvanized 58DVA-60 N/A N/A N/A
60” Pipe Length-Black 58DVA-60B - N/A from FPI N/A N/A N/A
5” X 8” RIGID PIPE CROSS REFERENCE CHARTComponents from different Manufacturers may not be mixed. Not All Rigid Pipe components are available directly from FPI.
Regency Horizon HZ54E Gas Fireplace21
INSTALLATION
Description SimpsonDirect Vent Pro®
SelkirkDirect Temp™
Metal-Fab™Sure Seal
ICC Excel Direct
Attic Insulation Shield 12” 58DVA-IS N/A from FPI N/A N/A N/A
High Wind Vertical Cap 58DVA-VCH N/A N/A TM-5VT
High Wind Horizontal Cap N/A N/A N/A TM-5DHT
Horizontal Square Termination Cap N/A 5DT-HHC 5DHT TM-5HT
Vertical Termination Cap N/A 5DT-HVC 5DVT TM-5VT
Storm Collar 58DVA-SC 5DT-SC 5DSC TM-SC
Restrictor Disk 58DVA-RD N/A N/A TM-5DS
Colinear Flex Connectors N/A N/A N/A N/A
Adjustable Flashing 0/12-6/12 58DVA-F6 5DT-AF6 5DF TF-5FA
Adjustable Flashing 6/12-12/12 58DVA-F12 5DT-AF12 5DF1-2 TF-5FB
Vinyl Siding Standoff 58DVA-VSS 5DT-VS 5DVS TM-VSS
Vinyl Siding Shield Plate N/A 5DT-VSP N/A N/A
Snorkel Termination 14” 58DVA-SNK14 N/A N/A TM-5ST14
Snorkel Termination 36” 58DVA-SNK36 (N/A - FPI) N/A N/A TM-5ST36
Basic Horizontal Termination Kit (A) N/A 5DT-HKA N/A N/A
Horizontal Termination Kit (B) 58DVA-KHA 5DT-HKB N/A N/A
Vertical Termination Kit 58DVA-VHA 5DT-VKC N/A N/A
FPI
946-604/P Simpson Direct Vent -Vent Guard (Optional) 946-623/P AstroCap XL Horizontal Cap
770-994 Rigid Pipe Adaptor (Must use with all rigid piping) 946-506/P Vent Guard (Optional)
946-606 Starter collar reducer 5” x 8” to 4” x 6-5/8” 946-625 Vinyl Siding Standoff - AstroCap XL
Note: When using Metal-Fab Sure Seal Rigid Piping - please note that the Adaptor (4DDA) must be used in conjunction with FPI Rigid Pipe Adaptor (510-994).
Offset Pipe Selection: Use this table to determine offset pipe lengths.
Pipe Length(L)
5” x 8” Venting For specifi c instructions on venting components - visit the manufacturers website listed below.
Run (X) Rise (Y)
0” (0mm) 5-11/16” (144mm) 15-5/16” (389mm) Simpson Direct Vent Pro: www.duravent.com
6” (152mm) 8-13/16” (224mm) 18-7/16” (468mm) Selkirk Direct-Temp: www.selkirkcorp.com
9” (229mm) 10-15/16” (278mm) 20-9/16” (522mm) Metal-Fab Sure Seal: www.mtlfab.com
12” (305mm) 13” (330mm) 22-11/16” (576mm) Industrial Chimney Company: www.icc-rsf.com
24” (610mm) 21-7/16” (697mm) 31-1/16” (789mm) Note: Horizontal runs of vent must be level, or have a 1/4” rise for every 1 foot of run towards the termination. Never allow the vent to run downward - this could cause high temperatures and may present a possible fi re hazard.
36” (914mm) 29-13/16” (757mm) 39-7/16” (1002mm)
48” (1219mm) 38-1/4” (972mm) 47-7/8” (1216mm)
22Regency Horizon HZ54E Gas Fireplace
INSTALLATION
VENTING ARRANGEMENTS ALLOWABLE HORIZONTAL TERMINA-
TIONS FOR HZ54E-NG
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o (two 45o elbows equal one 90o elbow).
Note: Must use optional rigid pipe adapter (Part# 770-994) when using Rigid Pipe Venting Systems.
VENTING ARRANGEMENTS ALLOWABLE HORIZONTAL TERMINA-
TIONS FOR HZ54E-LPThe diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o (two 45o elbows equal one 90o elbow).
Note: Must use optional rigid pipe adapter (Part# 770-994) when using Rigid Pipe Venting Systems.
• Maintain clearances to combustibles as listed in "Clearances" section
• Horizontal vent must be supported every 3 feet.• Firestops are required at each fl oor level and whenever passing
through a wall.• A wall thimble is mandatory for all horizontal terminations due
to high temperatures.
• Maintain clearances to combustibles as listed in "Clearances" section• Horizontal vent must be supported every 3 feet.• Firestops are required at each fl oor level and whenever passing
through a wall.• A wall thimble is mandatory for all horizontal terminations due to
high temperatures.
VENT RESTRICTOR SETTING:Vent restrictor factory set, no adjustment required unless otherwise indicated.Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 1 to Set 2 or Set 3 if required.
VENT RESTRICTOR SETTING:Vent restrictor factory set, no adjustment required unless otherwise indicated.Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 1 to Set 3 if required.
Note: Regency® Direct Vent System (Flex) is only approved for horizontal terminations.
Note: Regency® Direct Vent System (Flex) is only approved for horizontal terminations.
2
2
0
0
12
12 20
6
6 14
4
44” (1118mm)Minimum Height
Requirement
4
14
8
8 16
10
10 1818
Ve
rtic
al H
eig
ht
(Fe
et)
Horizontal (Feet)
Vent Restrictoron Set 2
Vent Restrictoron Set 3
Vent Restrictoron Set 1
(factory setting)
16
1818
2
2
0
0
12
12 20
6
6 14
4
44” (1118mm)Minimum Height
Requirement
4
14
8
8 16
10
10 1818
Vert
ical H
eig
ht(F
eet)
Horizontal (Feet)
Vent Restrictoron Set 3
Vent Restrictoron Set 1
(factory setting)
16
1818
Regency Horizon HZ54E Gas Fireplace23
INSTALLATION
H
H1V
V1
H1
H
V
Horizontal Venting with Two (2) 90o ElbowsNG and LP
Horizontal Venting with Three (3) 90o ElbowsNG and LP
One 90o elbow = Two 45o elbows.
Option V H V + V1 H + H1 A) 2' Min. 1' Max. 3' Min. 2' Max. B) 2' Min. 2' Max. 5' Min. 4' Max. C) 3' Min. 2' Max. 7' Min. 5' Max. D) 4' Min. 3 Max. 9' Min. 6' Max. E) 5' Min. 4' Max. 10' Min. 7' Max. F) 6' Min. 6' Max. 11' Min. 9' Max.
With these options, max. total pipe length is 30 feet with min. of 11 feet total vertical and max. 9 feet total horizontal.
Please note min. 1 foot between 90o elbows is required.
VENT RESTRICTOR SETTING:Vent restrictor factory set at Set 1, no adjustment required.
One 90o elbow = Two 45o elbows.
Option V H + H1With these options, maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 10 feet total horizontal.
A) 2' Min. 4' Max.B) 3' Max. 6' Max.C) 4' Max. 8' Max.D) 5' Max. 9' Max.E) 6' Max. 10' Max.Please note minimum 1 foot between 90o elbows is required.
VENT RESTRICTOR SETTING:Vent restrictor factory set at Set 1, no adjustment required.
24Regency Horizon HZ54E Gas Fireplace
INSTALLATION
Vertical Venting with Three (3) 90o ElbowsNG and LP
Option V H + H1 V + V1 A) 2' Min. 2' Max. 4' Min. B) 3' Min. 4' Max. 6' Min. C) 4' Min. 5' Max. 7' Min. D) 5' Min. 6' Max. 8' Min. E) 6' Min. 8' Max. 9' Min.
One 90o elbow = Two 45o elbows.
With these options, max. total pipe length is 30 feet with min. of 9 feet total vertical and max. 8 feet total horizontal.
Please note min. 1 foot between 90o elbows is required.
VENT RESTRICTOR SETTING:Vent restrictor factory set at Set 1, no adjustment required.
VH1 H
V1
Regency Horizon HZ54E Gas Fireplace25
INSTALLATION
• Vent must be supported at offsets.• Firestops are required at each fl oor level and
whenever passing through a wall.• Maintain clearances to combustibles as listed in
the "Clearances" section.• Refer to the "Vent Restrictor Position" section
for details on how to change the vent restrictor from the factory setting of Set 1 to Set 2 or Set 3 if required.
Note: Must use optional fl ue adaptor when using Rigid Pipe (Part # 770-994).
Maxi
mu
m:
40
ft.
(12.2
m)
Min
imum
8’6
”(2
.6m
)
Min
.4
4”
(111
8m
m)
Max. 10’ (3m)(centerline to centerline)Minimum length of pipe
between elbows 12” (305mm)
Maxi
mum
:27
ft.(8
.2m
)
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
Ve
rtic
alH
eig
ht
(Fe
et)
32
34
36
38
6 8
Horizontal (Feet)
20 4 10 1212 16 1814 20
Vent Restrictor on Set 2
Vent Restrictor on Set 3
Vent Restrictor on Set 1(factory setting)
VENTING ARRANGEMENTS ALLOWABLE VERTICAL TERMINATIONS FOR HZ54E-NG
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90o elbows, with Rigid Pipe Venting Systems for Natural Gas. Two 45o elbows equal to one 90o elbow. Maximum of four 45o elbows allowed.
Please note min. 1 foot between 90o
elbows is required.
26Regency Horizon HZ54E Gas Fireplace
INSTALLATION
• Vent must be supported at offsets.• Firestops are required at each fl oor level and
whenever passing through a wall.• Maintain clearances to combustibles as listed in
the "Clearances" section.• Refer to the "Vent Restrictor Position" section
for details on how to change the vent restrictor from the factory setting of Set 1 to Set 3 or Set 4 if required.
Note: Must use optional fl ue adaptor when using Rigid Pipe (Part # 770-994).
Maxi
mum
:40
ft.
(12.2
m)
Min
imum
8’6
”(2
.6m
)
Min
.4
4”
(111
8m
m)
Max. 10’ (3m)(centerline to centerline)
Maxi
mum
:27
ft.(8
.2m
)
0
2
4
6
40
8
10
12
14
16
18
20
22
24
26
28
30
Ve
rtic
alH
eig
ht
(Fe
et)
32
34
36
38
6 8
Horizontal (Feet)
20 4 10 1212 16 1814 20
Vent Restrictor on Set 3
Vent Restrictor on Set 4
Vent Restrictor on Set 1(factory setting)
Minimum length of pipebetween elbows 12” (305mm)
VENTING ARRANGEMENTS ALLOWABLE VERTICAL TERMINATIONS FOR HZ54E-LP
The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90o elbows, with Rigid Pipe Venting Systems for Propane. Two 45o elbows equal to one 90o elbow. Maximum of four 45o elbows allowed.
Please note min. 1 foot between 90o
elbows is required.
Regency Horizon HZ54E Gas Fireplace27
INSTALLATION
Diagram 7
Diagram 5
7) Ensure that the pipe clearances to combustible materials are maintained (Diagram 5). Install the termination cap.
Note: If installing termination on a vinyl siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.
The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.
8) Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble over the vent pipe. The wall thimble is required for all horizontal terminations.
9) Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. It is important that the vent pipe extends into the vent cap suffi cient distance so as to result in a minimum pipe overlap of 1-1/4 inches (32mm). Secure the connection between the vent pipe and the vent cap.
10) Install wall thimble in the center of the 11" (279mm) square and attach with wood screws (Diagram 7).
UNIT INSTALLATION WITH HORIZONTAL
TERMINATION(Rigid Vent Systems)
A top clearance of 3"(76mm) and side & bottom clearance of 2"(51mm) must be maintained; except when passing through a wall, ceiling, or at the termination where the use of a fi restop or wall thimble reduces the required clearance to 1-1/2" (38mm). We recommend framing a 11"(279mm) x 11"(279mm) (inside dimensions) hole to give structural rigidity for mounting the termination.
Install the vent system according to the manufacturer's instructions included with the components.
1) Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit.
2) Direct Vent pipe and fi ttings are designed with special twist-lock connections to connect the venting system to the appliance fl ue outlet. A twist-lock appliance adaptor is required.
3) In conjunction with the Simpson Direct Vent Pro system, install the adaptor after the unit is set in its desired location. Put a bead of high temperature silicone inside the outer section of the adapter and a bead of Mill Pack on the inner collar. Slip the adapter over the existing inner and outer fl ue collar. Fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier).
4) Level the fi replace and fasten it to the framing using nails or screws through the top and side nailing strips.
5) Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.
Note: For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. Silicone (red RTV) is optional.
Diagram 1
6) Mark the wall for a 11" x 11" (279mm x 279mm) square hole. The center of the square hole should line up with the center-line of the horizontal pipe. Cut and frame the 11 inch (279mm) square hole in the exterior wall where the vent will be terminated. See diagram 2 for center line requirements.
If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, an 8" (203mm) diameter hole is acceptable.
Diagram 2
Note: a) The horizontal run of vent must be level, or
have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fi re.
b) The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. See "Exterior Vent Termination Locations" section for more details.
Horizontal runs of vent must be supported every 3 feet (0.9meter). Wall straps are available for this purpose.
28Regency Horizon HZ54E Gas Fireplace
INSTALLATION
6) Continue to assemble pipe lengths.
Note: If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3 feet (0.9 meter), to avoid excessive stress on the elbows, and possible separation. Wall straps are available for this purpose
(Diagram 2). Galvanized pipe is desirable above the roofl ine
due to its higher corrosion resistance. Continue to add pipe sections through the fl ashing until the height of the vent cap meets the minimum height requirements specifi ed in Diagram 5 or local codes. Note that for steep roof pitches, the vertical height must be increased.
Diagram 3
Note:For best results and optimum performance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant to every inner pipe connection. Failure to do so may result in drafting or performance issues not covered under warranty. Silicone (red RTV) is optional.
UNIT INSTALLATION WITH VERTICAL TERMINATION
(Rigid Vent Systems)Note: A clearance of 2"(51mm) must be
maintained; except when passing through a wall, ceiling, or at the termination where the use of a fi restop or wall thimble reduces the required clearance to 1-1/2" (38mm). We recommend framing a 11"(279mm) x 11"(279mm) (inside dimensions) hole to give structural rigidity for mounting the termination.
1) Maintain the 1-1/2" (38mm) clearances (air spaces) to combust ib les when passing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfaces, ensuring that the use of a firestop or wall thimble is used as noted above. Do not pack air spaces with insulation. Check "Venting Arrangement - Vertical Termination" section for the maximum vertical rise of the venting system and the maximum hor izontal offset limitations.
2) Set the gas appliance in its desired location. Drop a plumb bob down from the ceiling to the position of the appliance fl ue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at his point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, and mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters or other framing will obstruct the venting system. You may wish to relocate the appliance or to offset, as shown in Diagram 2 to avoid cutting load bearing members.
3) A Firestop spacer must be installed in the fl oor or ceiling of every level.
4) Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed.
Diagram 4: The upper half of the fl ashing is installed under the roofi ng material and not nailed down until the chimney is installed.
This allows for small adjustments.
5) Cut a hole in the roof centered on the small drilled hole placed in the roof in Step 2. The hole should be of suffi cient size to meet the minimum requirements for clearance to combustibles of 1-1/2"(38mm). Slip the fl ashing under the shingles (shingles should overlap half the fl ashing) as per Diagram 4.
Offset Chart
A poor draft, or down drafting can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the vent height may solve the problem.
7) Ensure vent is vertical and secure the base of the fl ashing to the roof with roofi ng rails, slide storm collar over the pipe section and seal with a mastic.
8) Install the vertical termination cap by twist-locking it.
Note: Any closets or storage spaces, which the vent passes through must be enclosed.
Diagram 5
Roof PitchMinimum Vent
HeightFeet Meters
fl at to 7/12 2 0.61
over 7/12 to 8/12 2 0.61
over 8/12 to 9/12 2 0.61
over 9/12 to 10/12 2.5 0.76
over 10/12 to 11/12 3.25 0.99
over 11/12 to 12/12 4 1.22
over 12/12 to 14/12 5 1.52
over 14/12 to 16/12 6 1.83
over 16/12 to 18/12 7 2.13
over 18/12 to 20/12 7.5 2.29
over 20/12 to 21/12 8 2.44
Diagram 2
Diagram 1
Regency Horizon HZ54E Gas Fireplace29
INSTALLATION4) Separate the 2 halves of the wall thimble and
securely fasten the one with the tabs to the outside wall making sure that the tabs are on top and bottom. Fasten the other thimble half to the inside wall. The thimble halves slip inside each other and can be adjusted for 2 x 4 or 2 x 6 walls.
5) Slip the assembled liner and termination assembly through the thimble making sure the termination cap faces up (there are markings on the cap that show which way is up). This will position the termination cap with proper down slope for draining water. Fasten the cap to the outer wall with the 4 supplied screws.
6) Pull the centre 5"(127mm) liner and outer 8"(203mm) liner out enough to slip over the fl ue
collars of the fi replace. (You may wish to cut the liner shorter to make it more workable.) Do not bend liner more than 90o. The liners must slip over the collars a minimum of 1-3/8".
7) Apply Mill Pac over the fi replace inner collar and slip the 5"(127mm) liner down over it and attach with 3 supplied screws.
8) Do the same with the 8"(203mm) liner.
9) Apply a bead of silicone between the thimble and termination and around the outer edge of the terminal at the wall in order to keep the water out.
UNIT INSTALLATIONHORIZONTAL TERMINATIONWITH FLEX VENT SYSTEM
Note: A top clearance of 3"(76mm) and side & bottom clearance of 2"(51mm) must be maintained; except when passing through a wall, ceiling, or at the termination where the use of a fi restop or wall thimble reduces the required clearance to 1-1/2" (38mm). We recommend framing a 11"(279mm) x 11"(279mm) (inside dimensions) hole to give structural rigidity for mounting the termination.
1) Locate the unit in the framing, rough in the gas (preferably on the right side of the unit). Locate the centerline of the termination and mark wall accordingly. Cut an 11"(279mm) hole in the wall (inside dimension).
Note: If installing termination on a siding cov-ered wall, a vinyl siding standoff or vinyl furring strips must be used to ensure that the termination is not recessed into the siding.
2) Level the fi replace and fasten it to the framing using nails or screws through the nailing strips.
3) Assemble the vent assembly by applying Mill Pac to the 5"(127mm) inner collar of the termina-tion and slipping the 5"(127mm) liner over it at least 1-3/8" (35mm). Fasten with the 3 screws (drilling pilot holes will make this easier). Ap-ply Mill Pac or high temperature silicone to the 8"(203mm) fl ex pipe and slip it over the 8" outer collar of the vent terminal at least 1-3/8"(35mm) and fasten with the 3 screws.
NOTE: Horizontal sections must be supported at intervals not exceeding 3 feet (0.9 meter). (Flame picture and performance will be affected by sags in the liner).
IMPORTANT: Do not locate termination hood where excessive snow or ice buildup may occur. Be sure to check vent termination area after snow falls, and clear to prevent accidental blockage of venting system. When using snow blowers, make sure snow is not directed towards vent termination area.
ASTROCAP XLDIMENSIONS (946-623/P)
30Regency Horizon HZ54E Gas Fireplace
INSTALLATION
GAS PIPE PRESSURE TESTING
The appliance must be isolated from the gas sup-ply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator built into the gas control, and should be checked at the pressure test point.
Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a
1/8" wide fl at screwdriver.
3) Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON" position.
5) The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.
6) When fi nished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver. Note: Screw should be snug, but do not over tighten.
HIGH ELEVATIONThis unit is approved for altitude 0 to 4500 ft. (CAN1 2.17-M91).
GAS LINE INSTALLATION
Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation code.
For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1.
When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.
NOTE: A shutoff / dante valve should be supplied in or near the unit (or as per local codes) for ease of servicing this appliance.
IMPORTANT: Always check for gas leaks with a soap and water solution or gas leak detec-tor. Do not use open fl ame for leak testing.
HZ54E-NG SYSTEM DATAMin. Supply Pressure 5" WC (1.25 kpa)
Low Setting Man. Pressure
1.6" WC (0.40kpa)
Max. Manifold Pressure
3.5" WC (0.87 kpa)
Orifi ce Size #30 DMS
Minimum Input 29,000 Btu/h (8.50 kW)
Maximum Input 41,500 Btu/h(12.16 kW)
HZ54E-LP SYSTEM DATAMin. Supply Pressure 12" WC (2.98 kpa)
Low Setting Man. Pressure
6.4" WC (1.59kpa)
Max. Manifold Pressure
10" WC (2.49 kpa)
Orifi ce Size #49 DMS
Minimum Input 30,000 Btu/h (8.79 kW)
Maximum Input 37,000 Btu/h(10.84 kW)
Note: If you have an incorrect fl ame pattern, contact your Regency® dealer for further instructions.
Incorrect fl ame pattern will have small, probably yellow fl ames, not coming into proper contact with the rear burner or fl ame sensor.
Burner
Flame Sensor
Pilot Ignitor
PILOT ADJUSTMENT
Periodically check the pilot fl ames. Correct fl ame pattern has two strong blue fl ames: 1 fl owing around the fl ame sensor and 1 fl owing across the burner (it does not have to be touching the burner).
886 S.I.T. VALVE DESCRIPTION
1) Manual high/low adjustment2) Pilot adjustment3) Outlet Pressure Tap4) Inlet Pressure Tap5) Pilot Outlet6) Main Gas Outlet7) Main Gas Inlet
1
3
2
4
5
6
7
Regency Horizon HZ54E Gas Fireplace31
INSTALLATION
VALVE COVER REMOVAL
The valve cover will need to be removed to access the valve tray (see valve tray replacement) and also to access the DBFC (see Battery + ON/OFF switch installation).
1) Remove Faceplate and glass door if installed.
2) The valve cover is located on the right side underneath the glass door - loosen 2 screws securing the valve cover (see Diagram 1 below).
Valve cover Diagram 1
Diagram 2
Diagram 3
3) Slide the valve cover upward.
4) Lift the cover up off the screws and out of the unit.
5) To install - reverse steps.
32Regency Horizon HZ54E Gas Fireplace
INSTALLATIONAERATION ADJUSTMENT
The burner aeration is factory set but may need adjusting due to either the local gas supply or altitude. Open the air shutter for a blue fl ame or close for a more yellow fl ame.
For instructions to remove the burner for access to the ventury cap, see pages 46-47 in this manual.
Minimum Air Shutter Opening:
NG 1/2"LP 1/2"LP w/Logs = Full Open
CAUTION: Carbon will be produced if air shutter is tightly closed.
Note: Any damage due to carboning resulting from improperly setting the aeration controls is NOT covered under warranty.
Venturi Cap
WIRING DIAGRAM
This heater does not require a 120V A.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/thermostat will continue to operate. However, a 120V A.C. power supply is needed for the fan/blower operation.
(Do not cut the ground terminal off under any circumstances.)
NOTE: Even if the fan is not purchased with the unit, it is still a good idea to bring power to the receptacle box (provided with the unit) in case the fan is installed at a later date.
0.886.001Proflame Valve
Standard Main On/Off Switchor Optional Wall Switch
SureFire™ Switch
Regency Horizon HZ54E Gas Fireplace33
INSTALLATION
GroundGreen
Neutral
Live
Black Black
Black
Fan Thermodisc(normally open)
Ground
120V AC60 Hz
Fan
WhiteBlack
Black
Proflame SystemConfiguration886 GTMFWire Diagram
PROFLAME SYSTEM GTMF WITH OPTIONAL FAN
SureFire™ Switch
885
34Regency Horizon HZ54E Gas Fireplace
INSTALLATION
NOTE: Wiring schematics for HZ54E (120 Volts),plug-in fan circuit with speed control switch on wall.
Lockwasher
Fanground wire
Nut
#8 Ground Lug(for mobile home)
Star washer
GroundGreen
Neutral
Live
Black Black
Black
Fan Thermodisc(normally open)
Ground
120V AC60 Hz
Fan
WhiteBlack
Black
OPTIONAL FAN WIRING DIAGRAM WITHOUT PROFLAME GTMF SYSTEM
Electrical Connection Alternative Scheme "A",Power at Stove
Wall Junction Box
*Speed ControlSwitch withlead wires(Regency)
Wire Nuts
Wire Nuts
14 AWG wire
14 AWG wire
*Wire Clamp
*Receptacle Boxinside stove
*Receptacle(dedicated use
by stove fan only)
120 Volts60 Hz
Copper Ground
White (Neutral)
Black (Hot)
~
Wall Junction Box
*Speed ControlSwitch with lead wires
Wire Nuts
14 AWG wire
*Wire Clamp
120 Volts60 Hz Copper Ground
White (Neutral)Black (Hot)
Wire
BlackWhite
Ground
*Receptacle Boxinside stove
~
*Receptacle(dedicated use
by stove fan only)
* = supplied with fan kit
Other parts are to be suppliedby electrician or installer
Electrical Connection Alternative Scheme "B"Power at Switch
Regency Horizon HZ54E Gas Fireplace35
INSTALLATION
WALL SWITCH (Included with Unit)
1) Run the supplied 10' of wire through the right or left side gas inlet opening. Be careful not to damage wire.
Note: We recommend a maximum of 10' of wire but if you wish to go with a longer run, use the Thermostat Wire Table.
2) Connect the wire to the wall switch and install into the receptacle box (supplied). Also attach wires to the valve as shown below.
CAUTIONDo not wire millivolt
wall switch wire to 120V wire.
Optional WALL THERMOSTAT
A wall thermostat may be installed if desired, connect the wires as per the wiring diagram. Use table below to determine the maximum wire length.
Note: Preferable if the thermostat is installed on an interior wall.
Regency® offers an optional programmable thermostat but any 250-750 millivolt rated non-anticipator type thermostat that is CSA, ULC or UL approved may be used.
CAUTIONDo not wire millivolt
wall thermostat wiresto 120V wire.
Thermostat Wire Table
Optional REMOTE CONTROL
Use the Regency® Remote Control Kit approved for this unit. Use of other systems may void your warranty.
The remote control kit comes with a hand held transmitter, a receiver and a wall mounting plate.
1) Choose a convenient location on the wall to install the receiver and the receptacle box (protection from extreme heat is very important). Run wires from the fi replace to that location. Use Thermostat Wire Table.
CAUTIONDo not wire millivolt remote control wires
to 120V wire.
2) Connect the two wires to the IPI wire harness .See wiring diagrams. Optional wall switch GT/GTM suing wire 0.584.907.
3) Install 3 AAA alkaline batteries in the transmit-ter and 4 AA alkaline batteries in the receiver. Install the receiver and it's cover in the wall. Switch the remote receiver to "remote" mode. The remote control is ow ready for operation.
14 GA.16 GA.18 GA.20 GA.22 GA.
50 Ft.32 Ft.20 Ft.12 Ft.
9 Ft.
Recommended Maximum Lead Length (Two-Wire) When Using Wall Thermostat (CP-2 System)
Wire Size Max. Length
36Regency Horizon HZ54E Gas Fireplace
INSTALLATION
584 Proflame GT Series Feature Sheet
(X) Indicates Included Feature
Note 1 ~ Profl ame Flame Modulator for GTM & GTMF Remote Controls are sold seperately. Choice of NG or LP fl ame modulator (to match unit fuel type). See Regency Retail Price pages for complete details
Note 2 ~ FPI Profl ame Remote Controls come standard with white wall mount switch & cover plate.
1 1 1
Regency Horizon HZ54E Gas Fireplace37
INSTALLATIONBATTERY & ON | OFF SWITCH INSTALLATION
DFBC = digital fi replace burner control
1) Remove glass door and valve cover (see valve cover removal section in this manual) to access to DFBC & battery pack.
2) Lift DFBC and battery pack up and out.
3) Disconnect connector from battery holder and remove from tray – (battery holder is attached by Velcro to tray).
4) Install - 4 AA batteries, reconnect the connector to the battery pack and put back onto Velcro strip
5) Locate the Green and White from the DFBC module wire harness; connect the spade connectors from the On/Off switch. Green to Black and White to White.
6) Reinstall the module and battery pack tray into the holder
38Regency Horizon HZ54E Gas Fireplace
INSTALLATION
DFBC = digital fi replace burner control
1) Remove glass door to access to DFBC & battery pack tray.
2) Lift DFBC and battery pack up and out.
GT REMOTE INSTALLATION
3) Disconnect connector from battery holder and remove from tray – (battery holder is attached by Velcro to tray).
4) Remove the 4 AA batteries if installed, reconnect the connector to the battery pack and put back onto Velcro strip
5) Locate the Green and White wires from the DFBC module wire harness; connect the spade connectors from the receiver wire harness, (TH) Green to (DFBC) Green and (TH/TP) White to (DFBC) White
Note: DO NOT USE 4 AA batteries in the battery pack on the tray - the DFBC is now powered by the receiver batteries in the wall.
6) Locate the DFC wire from the receiver wire harness and connect to the DC supply wire from the DFBC.
Regency Horizon HZ54E Gas Fireplace39
INSTALLATION
Note: DO NOT USE 4 AA batteries in the battery pack on the tray - the DFBC is now powered by the receiver batteries in the wall.
GTM REMOTE INSTALLATIONDFBC = digital fi replace burner control
1) Remove the faceplate and glass door to access to DFBC & battery pack tray.
2) Lift DFBC and battery pack up and out.
3) Disconnect connector from battery holder and remove from tray – (battery holder is attached by Velcro to tray).
4) Remove the 4 AA batteries if installed, reconnect the connector to the battery pack and put back onto Velcro strip
5) Locate the Green and White wires from the DFBC module wire harness; connect the spade connectors from the receiver wire harness, (TH) Green to (DFBC) Green and (TH/TP) White to (DFBC) White
6) Locate the DFC wire from the receiver wire harness and connect to the DC supply wire from the DFBC.
7) Remove the hi/lo knob from the valve head, if installed, by removing 2 screws as shown below.
8) Install the stepper motor in the same location the hi/lo knob was removed from - with 2 screws as shown below.
40Regency Horizon HZ54E Gas Fireplace
INSTALLATION
12) Program Receiver and transmitter (refer to manual)
Note: DO NOT USE 4 AA batteries in the battery pack on the tray; the DFBC is now powered by the receiver batteries in the wall.
11) Connect GTM motor wire from the stepper motor to the wire connector from the receiver wire harness.
9) Install 4 - AA batteries into the receiver, ensure correct polarity.
10) Plug receiver wires into the back of the receiver and bundle wires with the wire clip as shown below.
Wire Clip
Regency Horizon HZ54E Gas Fireplace41
INSTALLATION
GTMF REMOTE INSTALLATION
DFBC = digital fi replace burner control
1) Remove the faceplate and glass door to access to DFBC & battery pack tray.
2) Lift DFBC and battery pack up and out.
3) Disconnect connector from battery holder and remove from tray – (battery holder is attached by Velcro to tray).
4) Remove the 4 AA batteries if installed, reconnect the connector to the battery pack and put back onto Velcro strip
5) Locate the Green and White wires from the DFBC module wire harness; connect the spade connectors from the receiver wire harness, (TH) Green to (DFBC) Green and (TH/TP) White to (DFBC) White
6) Locate the DFC wire from the receiver wire harness and connect to thDC supply wire from the DFBC. (insert pictures
7) Remove the hi/lo knob from the valve head, if installed, by removing 2 screws as shown below.
8) Install the stepper motor in the same location the hi/lo knob was removed from - with 2 screws as shown below.
42Regency Horizon HZ54E Gas Fireplace
INSTALLATION
13) Install the heat shield onto the fan control module - then install onto the velcro pad located on the fl oor of the unit located left of the receiver.
Fan Control Module
12) From the wire harness, plug the FCM wire into the fan control mule.
9) Install 4 - AA batteries into the receiver.
11) Install the heat shield to the receiver with two screws and attach to the fl oor of the unit with a velcro pad.
14) Plug fan control module into receptacle located on the left hand side ofunit.
15) Match the remote control to the receiver - see remote control instructions.
16) Reverse steps 2 and 1.
17) Check to ensure there are no gas leaks..
Heat shield
FCM wire
10) Plug ‘motor’ wires into the back of the receiver and bundle wires with the wire clip - as shown below.
10) Before installing the fan control module, install the heat shield on thecontrol module by securing with 2 screws.
Regency Horizon HZ54E Gas Fireplace43
INSTALLATIONOPTIONAL REFLECTIVE PANEL INSTALLATION
1) Position the left side panel in place - top of panel in fi rst, then fi t the bottom tab into the slot at the bottom of the fi rebox as shown below. Repeat for right side panel.
Fit side panel tab into slot
Left Side PanelShown
Left side panel in position
2) Fit the back panel into position by clearing the pilot shield - bottom of panel goes in fi rst.
Then fi t the tabs on the bottom left and right side of the back panel into the slots at the base of the fi rebox.
Secure the back panel in place by placing the brackets over the screws on the top of the inside left and right side of the fi rebox and tighten the screw to hold the bracket against the back panel shown below.
Right side back panel tab fi tted into slot
Bracket shown in place on right side of the fi rebox
Right side panel in position
Before installation, panels must be handled and cleaned as per instructions noted below:
Stainless Steel Panels Black Enamel Panels
• Stainless panels must be inspected for scratches and dimples prior to installation. All claims to be recorded at this time. Claims for damage after installation will not receive consideration.
• Black Enamel panels must be inspected for scratches and dimples prior to installation. All claims to be recorded at this time. Claims for damage after installation will not receive consideration.
• Use a hair dryer to remove the protective coating from the panels.
• To protect the fi nish during installation and handling - cotton gloves MUST be worn at all times while handling the panels.
• Stainless panels will discolor a little during normal operation. This is normal and should not be considered a defect.
• Black Enamel panels will discolor a little during normal operation. This is normal and should not be considered a defect.
* All hand and fi nger marks MUST be cleaned off with a soft cloth and a stainless steel cleaner. Most stainless steel cleaners leave a fi lm/residue on the surface of the panels. Use an ammonia based cleaner (ie. glass cleaner) to remove this fi lm before applying heat to the unit.Failure to do this will result in burn stains on panels which you will be unable to remove. Not protected by product warranty.
* All hand and fi nger marks MUST be cleaned off with a soft cloth. Use an ammonia based cleaner (ie. glass cleaner) to remove any fi ngerprints before applying heat to the unit.Failure to do this will result in burn stain on panels which you will be unable to remove. Not protected by product warranty.
90 degree bend faces
towards center of unit on both left and right side panels
Left Side Bracket
44Regency Horizon HZ54E Gas Fireplace
INSTALLATIONGLASS CRYSTALS OR OPTIONAL CERAMIC STONES
INSTALLATION ON BURNER
Glass Crystals shown on BurnerFor Units HZ54E, HZ30E, HZ42ST, HZ42, HZO42 only
Optional Ceramic Spa Stones + Glass Crystals shown on burner.For Units HZ54E, HZ30E, HZ42ST, HZ42 only
Optional Garden Stones + Glass Crystals shown on burner.For the HZO42 only
Glass Crystals shown on BurnerFor units P33S,P33SE L676S, U32S, U32SE,E33S,only
Optional Ceramic Spa Stones shown on burner.For units P33S,P33SE L676S, U32S, U32SE, E33S only
Burner PackagesUnit Glass Crystals Ceramic Spa Stones Garden StonesHZ54E 3 Bags 1 Bag Glass + 2 packages (140 spa stones)
HZ42 2 Bags 1 Bag Glass + 1 package (70 spa stones)
HZ42 ST 2 Bags 1 Bag Glass + 1 package (70 spa stones)
HZO42 3 Bags N/A 1 package (50 stones)
*HZ30E 1 bag 1 Bag Glass + 1 package (70 spa stones)
L676S 1 Bag 1 package = (70 spa stones)
**P33S/P33SE 1 Bag 1 package = (70 spa stones)
U32S / U32SE 1 Bag 1 package = (70 spa stones)
E33S 1 Bag 1 package = (70 spa stones)
NOTE: 1 Ceramic spa stone package contains 70 stones 1 Garden stone package contains 50 stones *Recommended - use only 40 of the 70 ceramic stones on the HZ30E burner.**Recommended - use only 50 of the 70 ceramic stones on the P33S/P33SE burner.
Evenly spread the supplied Glass Crystals or optional Ceramic Spa or Garden Stones over the burner. Ensure the crystals (or stones) do not overlap too much as this will effect the fl ame pattern.
IMPORTANT NOTE:
Only the supplied approved Cobalt Glass, Ceramic Spa Stones or Garden Stones are to be used with these fi replaces. Use of any other type oglass crystals or stones can alter the unit's performance, any damage caused by the use of any unapproved glass or stones will not be coveredunder warranty.
When using Ceramic or Garden Stones, DO NOT cover burner ports that lead to pilot fl ame. Ensure the crystals or stones do not overlap excessivelyas this will effect the fl ame pattern.
Regency Horizon HZ54E Gas Fireplace45
INSTALLATION
White River Pebbles shown surrounding the Burner Natural River Pebbles shown surrounding the Burner
There are 3 optional packages to choose from to cover the fi rebox base:
1) White River Pebbles2) Natural River Pebbles3) Glass Crystals (4 colors available)
Spread the pebbles / crystals evenly on the exposed base of the fi rebox. Pebbles are NOT to be placed anywhere on the burner or over top of the Glass Crystals or optional Ceramic Spa Stones.
NOTE: Only the supplied and approved pebbles / crystals are to be used. Use of any other type of pebbles or material can create a danger and will void warranty.
Glass Crystals shown surrounding the Burner
Firebox PackagesUnit Glass Crystals Pebbles
HZ54E 6 Bags 2 packages (6 x bags pebbles)
HZ42 5 Bags 2 packages (6 x bags pebbles)
HZ42 ST 5 Bags 1 package (6 x bags pebbles)
HZO42 4 Bags 1 package (3 x bags pebbles)
HZ30E 2 bags 1 package (3 x bags pebbles)
L676S 3 Bags 1 package (3 x bags pebbles)
P33S/P33SE 3 Bags 1 package (3 x bags pebbles)
U32S/U32SE 3 Bags 1 package (3 x bags pebbles)
E33S 3 Bags 1 package (3 x bags pebbles)
White River Pebbles shown surrounding the Burner
GLASS CRYSTALS OR OPTIONAL PEBBLESINSTALLATION ON FIREBOX BASE
46Regency Horizon HZ54E Gas Fireplace
INSTALLATION
Installation of Refl ective Panels must be completed before installing the log set.
Read the instructions below carefully and refer to the images. If the logs are broken do not use the unit until they are replaced. Broken logs can interfere with pilot operation.
Improper positioning of the logs may create carbon build-up and can alter the unit's performance which is not covered under warranty.
Log kit # 476-930 contains the following pieces:
Part # DescriptionA x 2 Log B x 2 LogC x 2 Log D x 2 Log476-103 x 12 Pin Clips 946-669 Platinum Embers
1) Remove the following if already installed: a) Faceplate b) Glass Door c) Pebbles d) Glass Crystals e) Stones
Note: Aeration Setting is set at 1/2" from the factory. The following are recommended settings for NG and LP units when using the log set : NG = 1/2" LP = Full Open
2) Attach the 12 pin clips to the bottom cover (not the burner) in the exact locations indicated by an X, as shown in Diagram 2 below.
Note: Front and back measurements originate from the centre line of burner.Side measurements originate from front edge of the bottom cover (see Diagram 3).
Note: Units may have dimples on the burner to indicate pin clip installation points. If dimples are not present on the burner, follow the above directions.
20-5/8”
5-5/8”
19-1/2”19”
xx7-1/2” 11-3/8”8-3/4”
4-3/4”7-3/4”15-3/4”
xxx
x
x x x1-1/2” 2”
17”6”
x xxLC
20-5/8”
v
19-3/16”19-3/16”
Diagram 2
Diagram 1
A
B
CDDC
B
A
Di 4
3) Pin clips are attached to the lip edge of the bottom cover (not the burner) see diagrams 3 & 4.
Bottom Cover Side measurements from corner edge.
Lip Edge
Burner
All measurements along the front and back edge originate from centre line.Centerline indicated by "V" cut out on the rear edge of the burner.
Measurements to centre of pins.
Back
Front
OPTIONAL LOG SET INSTALLATION
Regency Horizon HZ54E Gas Fireplace47
INSTALLATION
Diagram 5
4) Install the glass crystals (see glass crystal installation section in this manual).
Pin clips installed - dots indicate dimple locations.*Actual dimples/pin clips are black - not white as shown
Diagram 6
Diagram 8
Diagram 7
6) If installing optional pebbles - install pebbles before log installation.
5) Place platinum embers on glass crystals as shown in diagram 7.
48Regency Horizon HZ54E Gas Fireplace
INSTALLATION
8) Place logs C + D on logs A + B, as shown in diagram 10.
Note: Logs should be oriented exactly as shown in diagram 10.
9) Install the following:
a) *Glass door b) *Faceplate and door frame *Refer to these sections in the HZ54 manual for detailed instructions.
Diagram 9
Diagram 10
Diagram 11Log Set Installed (shown with optional pebbles)
7) Place logs A + B on the burner, rest logs on the pin clips, as shown in diagram 9.
Note: Logs should be oriented exactly as shown in diagram 9.
AB
BA
C
D
DC
Regency Horizon HZ54E Gas Fireplace49
INSTALLATION
FACEPLATE &DOOR FRAME OVERLAY INSTALLATION
1) Install the door frame overlay by hooking the top fl ange over top of the glass door, push in the bottom of the door frame overlay to secure in place.
Door Frame Overlay
Glass Door
3) Secure the left side mounting bracket to the backside of the faceplate as shown below. Use 3 screws supplied to secure the mounting bracket in place. Repeat for right side.
Mounting Bracketshown in place
Left SideMounting Bracket
NOTE: Ensure that the faceplate is positioned correctly when installing the mounting brackets to the faceplate. There is a top and bottom, the top of the faceplate has 4 tabs whereas the bottom only has 2 as shown in the diagram below.
2) Place 2 of the supplied magnets on the lower corners of the Door Frame Overlay, this will keep the Faceplate in postion after it has been installed.
Magnet Position
50Regency Horizon HZ54E Gas Fireplace
INSTALLATION
Completed Faceplate & Door Frame Overlay Installation
IMPORTANT NOTE
To ensure the gap between the door frame and the faceplate are equal from side to side you may need to slide the faceplate slightly to the left or right accordingly.
Also if necessary, the faceplate may be adjusted up and down by loosening the top screw as shown in the diagram below and sliding the plate up or down as required.
Faceplate Mounting Slots
4) Install the faceplate to the unit by hooking the left and right side mounting brackets into the mounting slots at the side of the fi rebox as shown below. It is recommended that you use the fi rst mounting slot (the one closest to the door frame overlay) out of the 5 so that the faceplate and door frame overlay are fl ush with one another. See diagram below.
NOTE: There are 5 mounting slots available, this is to accomodate any fi nishing that protrudes slightly beyond the faceplate.
First Mounting Slot (recommended)
Regency Horizon HZ54E Gas Fireplace51
INSTALLATION
OPTIONAL FAN INSTALLATION
1) Turn the unit off and allow it to cool down to room temperature.
2) Turn off the gas supply to the unit.
3) Remove the faceplate by lifting it up off the hinges on the sides of the fi rebox.
4) Remove the door frame overlay by swinging out 45o from the bottom and lift up and out.
5) Remove the glass door.
a) Remove the 3 screws shown below at the bottom of the glass door.
b) Swing the door out 45o from the bottom and lift up and out.
6) Remove the burner tray by undoing the 2 screws in between the bot-tom cover and burner on the fi rebox. Carefully lift the burner up and out ensuring not to spill the glass crystals.
Aerial View of the inside of the unit shown.
7) Remove bottom cover by undoing 3 screws securing it to the fi rebox base, lift up and out.
Aerial View of the inside of the unit shown.
8) Loosen 6 screws that secure the burner extenders. on burner tray, located behind the burner on either side of the pilot assembly.
9) Lift out the 2 burner tray extenders.
Burner tray extenders
Burner tray extenders
Burner tray
Steps 6 & 7 for NG units only:
Steps 8 -10 for LP units only:
52Regency Horizon HZ54E Gas Fireplace
INSTALLATION
13) Secure the fan to the fl oor of the unit with 2 screws.
14) Attach the ground wire from the fan to the ground lug in the unit. The ground lug is located just in front of the receptacle box on the left side on the fl oor of the unit
15) Attach the receiver to the unit with the velcro strip. Place the receiver in front of the ground lug on the left side of the unit - inside the bottom frame of the unit
Ground Lug
11) Remove 8 screws to remove the fan access panel cover - located on the left hand side fl oor of the fi rebox.
12) Manoeuvre the fan into position on the fl oor of the unit. Tilt the fan to get through the fan access panel and into position.
Fan Access Panel
9) After extenders have been removed. Remove the 2 screws that secure the burner tray, at the base of the fi rebox.
10) Slide the burner to the left and lift it out.
Location of screws securing burner
Regency Horizon HZ54E Gas Fireplace53
INSTALLATION
16) Install the fan control module into the unit through the open fan access panel. Plug the fan control module into the receptacle in the unit (left side - fl oor of unit). Plug the fan into the fan control module and connect
GTMF remote (see GTMF installation instructions in this manual).
17) Slide the thermodisc into the bracket on the bottom side of the fan access panel.
18) Reverse Steps 8 through 5.
19) Install the fan air defl ector - it hooks to 2 brackets on to the bottom lip of the unit, to the right of the receiver.
17) Reverse Steps 4 through 1.
Air defl ector
TO REMOVE THE FAN
1) Turn the power off.2) Reverse the above instructions.
Maintenance: The sealed bearings are lubricated, there is no need to lubricate them further. (Extra lubricant will cause more lint and dust buildup - causing the bearings to prematurely fail).Regular cleaning and vacuuming of the fan area will add to the life of the motor.
IMPORTANT:These fans collect a lot of dust from within your home. Ensure you maintain these fan motors on a regular basis by vacuumingthe fan blades and housing using a soft brush nozzle.
Air defl ector
Bracket
54Regency Horizon HZ54E Gas Fireplace
54
OPERATING INSTRUCTIONS
OPERATING INSTRUCTIONS
1) Read and understand these instructions before operating this appliance.
2) Check to see that all wiring is correct and enclosed to prevent possible shock.
3) Check to ensure there are no gas leaks.
4) Make sure the glass in the glass door frame is properly positioned. Never operate the appliance with the glass removed.
5) Verify that the venting and cap are unobstructed.
6) The unit should never be turned off, and on again without a minimum of a 60 second wait.
LIGHTING PROCEDURE
1) Turn on the wall switch or press and release on ON/OFF button once on the remote control.
2) After approximately 4 seconds the spark ignition system will spark for 60 seconds to light the main burner.
3) The unit will turn on.
Note: The fi rst try for ignition will last approxi-mately 60 seconds. If there is no fl ame ignition (rectifi cation) the board will stop sparking for approximately 35 seconds. After wait time , the board will start second try for ignition by sparking for approximately 60 seconds . If there is still no positive ignition the board will go into lock out.
The system will need to be reset as follows:
a) Turn the system off using ON/OFF switch or press ON/OFF button - if using optional remote.
b) After approximately 2 seconds turn on ON/OFF switch or press ON/OFF button if using optional remote.
c) Repeat step 2.
SHUTDOWN PROCEDURE
1) Turn ON/OFF switch or press and release the ON/OFF button once if using optional Remote Control.
2) If service is to be performed - you must disconnect the battery.
During the fi rst few fi res, a white fi lm may develop on the glass front as part of the curing process. The glass should be cleaned after the unit has cooled down or the fi lm will bake on and become very diffi cult to remove. Use a non-abrasive cleaner and DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS HOT.
The FIRST FIRE in your heater is part of the paint curing process. To ensure the paint is properly cured, it is recommended you burn your fi replace for at least four (4) hours the fi rst time with the fan on.
When fi rst operated, the unit will release an odour caused by the curing of the paint and the burning off of any oils remaining from manufac-turing. Smoke detectors in the house may go off at this time. Open a few windows to ventilate the room for a couple of hours. The glass may require cleaning.
NOTE: When the glass is cold and the appliance is lit, it may cause condensation and fog the glass. This condensation is normal and will disappear in a few minutes as the glass heats up.
DO NOT ATTEMPT TO CLEAN THE GLASS WHILE IT IS STILL HOT!
DO NOT BURN THE UNIT WITHOUT THE GLASS DOOR IN PLACE.
FIRST FIRE
NORMAL OPERATING SOUNDS OF
GAS APPLIANCESIt is possible that you will hear some sounds from your gas appliance. This is perfectly normal due to the fact that there are various gauges and types of steel used within your appliance. Listed below are some examples. All are normal operating sounds and should not be considered as defects in your appliance.
Burner Tray: The burner tray is positioned directly under the burner and is made of a different gauge material from the rest of the fi rebox and body. Therefore, the varying thicknesses of steel will expand and contract at slightly different rates which can cause "ticking" and "cracking" sounds. You should also be aware that as there are temperature changes within the unit these sounds will likely re-occur. Again, this is normal for steel fi reboxes.
Pilot Flame:While the pilot fl ame is on it can make a very slight "whisper" sound.
Gas Control Valve: As the gas control valve turns ON and OFF, a dull clicking sound may be audible, this is normal operation of a gas regulator or valve.
Unit Body/Firebox: Different types and thicknesses of steel will expand and contract at different rates resulting in some "cracking" and "ticking" sounds will be heard throughout the cycling process.
Blower Thermodisc: When this thermally activated switch turns ON it will create a small "clicking" sound. This is the switch contacts closing and is normal.
Regency Horizon HZ54E Gas Fireplace5555
OPERATING INSTRUCTIONS
COPY OF LIGHTING PLATE INSTRUCTIONS
918-628b
A) This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand.B) BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the fl oor because some gas is heavier than air and will settle on the fl oor. WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance.- Do not touch any electric switch, do not use any phone in your building.- Immediately call your gas supplier from a neighbours phone. Follow the gas supplier’s instructions.- If you cannot reach your gas supplier, call the fi re department.
C) Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and replace any part of the control system and any gas control which has been underwater.A) Cet appareil est muni d’un dispositif d’allumage qui allume automatiquement la veilleuse. Ne tentez pas d’allumer la veilleuse manuellement. B) AVANT DE FAIRE FONCTIONNER, renifl ez tout autour de l’appareil pour déceler une odeur de gaz. Renifl ez près du plancher, car certains gaz sont pluslourds que l’air et peuvent s’accumuler au niveau du sol. QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ : • Ne pas tenter d’allumer d’appareil • Ne touchez à aucun interrupteur; ne pas vous servir des téléphones se trouvant dans le bâtiment. • Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur. • Si vous ne pouvez rejoindre le fournisseur, appelez le service des incendiesC) N’utilisez pas cet appareil s’il a été plongé dansl’eau, même partiellement. Faites inspecter l’appareil par un tech-
nicien qualifi é et remplacez toute partie du système de contrôle et toute commande qui ont été plongés dans l’eau.
DO NOT REMOVE THIS INSTRUCTION PLATE
TO TURN OFF GAS APPLIANCE
This appliance must be installed in accordance with local codes, if any;if none, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or
Natural Gas and Propane Installation Codes, CSA B149.1.
CAUTION: Hot while in operation. Do not touch. Severe Burns may result. Due to high surface temperatures keep children, clothing and furniture, gasoline and other liquids having fl ammable vapors away. Keep burner and control compartment clean. See installation and operating instructions accompanying appliance.
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s information manual provided with this appliance. For assistance or additional information consult a qualified installer, service agency or gas supplier.AVERTISSEMENT. Quiconque ne respecte pas à la lettre les instructions dans la présente notice risquede déclencher un incendie ou une explosion entraînant des dommages, des blessures ou la mort.Une installation, d'ajustement, de modifi cation, de service ou d'entretien peut provoquer des blessures ou des dommages matériels. Reportez-vous au manuel du propriétaire de l'information fournie avec cet appareil. Pour obtenir de l'aide ou des informations supplémen-taires consulter un installateur qualifi é, une agence de service ou fournisseur de gaz.
1) Turn on ON/OFF switch 2) After approximately 4 seconds the spark ignition system will spark for 60 seconds to light the main
burner.3) The unit will turn on.Note: The fi rst attempt to ignition will last approximately 60 seconds. If there is no fl ame ignition (rectifi ca-tion) the board will stop sparking for approximately 35 seconds. After this wait time, the board will start a second try for ignition by sparking for approximately 60 seconds. If there is still no positive ignition after the second attempt the board will go into lock out.The system will need to be reset as follows (after going into lock out mode): a) Wait 5 minutes - turn the system off using ON/OFF switch. b) After approximately 2 seconds turn on ON/OFF switch or press ON/OFF button if using optional
remote. c) Unit will repeat step 2.1) Appuyez le bouton ON / OFF 2) Attendre 4 secondes. Le système d’allumage produira des étincelles pendant 60 secondes afi n d’amorcer
le brûleur principal.3) Les fl ammes s’allumeront.Remarque : Au premier allumage, le système tente d’allumer les fl ammes pendant 60 secondes. Si l’essai est infructueux, le système fait une pause de 35 secondes. C’est ce qu'on appelle l'étape de rectifi cation. Ce délai écoulé, le système tente à nouveau d'allumer les fl ammes en produisant des étincelles pendant 60 secondes. Si les fl ammes ne s’allument toujours pas, le système se met en mode verrouillage. Il faut alors le réinitialiser en suivant les étapes ci-dessous (pour le déverrouiller) : a) Attendre 5 minutes et éteindre l’appareil en réglant l’interrupteur à la position « OFF »; b) Attendre 2 secondes et rallumer le système à l’aide de l’interrupteur ou de la télécommande. c) L'unité répétera l'étape 2.
1) Turn off ON/OFF switch 2) If service is to be performed - you must disconnect power to the unit, from the battery pack, refer to
manual.1) Appuyez sur le bouton ON / OFF 2) Si le service est effectuée, vous devez débrancher l'appareil, du bloc-piles, voir le manuel d'instruction
pour plus de détails.
LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
56Regency Horizon HZ54E Gas Fireplace
MAINTENANCEMAINTENANCE INSTRUCTIONS
1) Always turn off the gas valve before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year.
2) Clean appliance and door with a damp cloth (never when unit is hot). Never use an abrasive cleaner. The glass should be cleaned with a gas fi replace glass cleaner. The glass should be cleaned when it starts looking cloudy.
3) The faceplate is fi nished in a heat resistant paint and should only be refi nished with heat resistant paint. Regency® uses StoveBright Paint - Metallic Black #6309.
Note: Faceplates and inner panels made from stainless steel will naturally change color over time.
4) Make a periodic check of burner for proper position and condition. Visually check the fl ame of the burner periodically, making sure the fl ames are steady; not lifting or fl oating. If there is a problem, call a qualifi ed service person.
5) The appliance and venting system must be inspected before use, and at least annually, by a qualifi ed fi eld service person, to ensure that the fl ow of combustion and ventilation air is not obstructed.
Note: Never operate the appliance without the glass properly secured in place.
6) Do not use this appliance if any part has been under water. Immediately call a qualifi ed service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
7) In the event this appliance has been serviced check that the vent-air system has been properly resealed & reinstalled in accordance with the manufacturer's instructions.
8) Verify operation after servicing.
GENERAL VENT MAINTENANCE
Conduct an inspection of the venting system semi-annually. Recommended areas to inspect as follows:
1) Check the Venting System for corrosion in areas that are exposed to the elements. These will appear as rust spots or streaks, and in extreme cases, holes. These components should be replaced immediately.
2) Remove the Cap, and shine a fl ashlight down the Vent. Remove any bird nests, or other foreign material.
3) Check for evidences of excessive condensation, such as water droplets forming in the inner liner, and subsequently dripping out the joints, Continuous condensation can cause corrosion of caps, pipe, and fi ttings. It may be caused by having excessive lateral runs, too many elbows, and exterior portions of the system being exposed to cold weather.
4) Inspect joints, to verify that no pipe sections or fi ttings have been disturbed, and consequently loosened. Also check mechanical supports such as Wall Straps, or plumbers' tape for rigidity.
GLASS GASKET If the glass gasket requires replacement use a tadpole glass gasket (Part # 936-159).
CAUTION: Wear gloves when removing damaged or broken glass.
WARNING: Do not operate the appliance with the glass panels removed, cracked or broken. Replacement of the glass panels should be done by a licensed or qualifi ed service person.
GLASS DOORYour Regency® fi replace is supplied with high temperature 5mm-Ceramic glass. If your glass requires cleaning, we recommend using an approved glass cleaner available at all authorized dealers. Do not use abrasive materials.
CAUTION & WARNINGS:
* Do not clean when the glass is hot.* The use of substitute glass will void all product
warranties.* Care must be taken to avoid breakage of the
glass.* Do not strike or abuse the glass.* Do not operate this fi replace without the glass
front or with a cracked or broken glass front.* Wear gloves when removing damaged or broken
glass.* Replacement of the glass panel(s) should be
done by a licensed or qualifi ed service per son.
GLASS REPLACEMENT
In the event that you break your glass by impact, purchase your replacement from an authorized Regency® dealer only.
Replacement glass is shipped already installed into the door frame.
Regency Horizon HZ54E Gas Fireplace57
MAINTENANCE
1) Turn the unit off and allow it to cool down to room temperature.
2) Turn off the gas supply to the unit.
3) Remove the faceplate by lifting it up off the hinges on the sides of the fi rebox.
4) Remove the door frame overlay by swinging out 45o from the bottom and lift up and out.
5) Remove the glass door.
a) Remove the 3 screws shown below at the bottom of the glass door.
b) Swing the door out 45o from the bottom and lift up and out.
GLASS DOOR REMOVAL
6) Remove valve cover - (see valve cover removal section in this manual).
58Regency Horizon HZ54E Gas Fireplace
MAINTENANCE
1) Turn the unit off and allow it to cool down to room temperature.
2) Turn off the gas supply to the unit.
3) Remove the faceplate by lifting it up off the hinges on the sides of the fi rebox.
4) Remove the door frame overlay by swinging out 45o from the bottom and lift up and out.
5) Remove the glass door.
a) Remove the 3 screws shown below at the bottom of the glass door.
b) Swing the door out 45o from the bottom and lift up and out.
VALVE TRAY REPLACEMENT
Note: See next pages for specifi c instructions for NG / LP units.
Prior to removing burner - remove the following (if installed): -crystals -pebbles -spa stones -logs -Inner panels
Regency Horizon HZ54E Gas Fireplace59
MAINTENANCE
1) Remove the burner tray by undoing the 2 screws in between the bot-tom cover and burner on the fi rebox. Carefully lift the burner up and out ensuring not to spill the glass crystals.
Aerial View of the inside of the unit shown.
Green Wire Orange Wire
3) Disconnect the green and orange wires from the valve.
7) Remove the valve tray by undoing 12 screws.
8) Partially lift out valve tray.
9) Disconnect the inlet gas line.
10) Replace valve and reverse steps.
2) Remove bottom cover by undoing 3 screws securing it to the fi rebox base, lift up and out.
Aerial View of the inside of the unit shown.
4) Disconnect the green ground wire from the valve bracket.
5) Lift out the DFBC and battery pack.
6) Disconnect the CN4 and CN3 wires from the DFBC.
Green ground wire
DFBC
CN4
CN3
Battery pack
HZ54E-NG UNIT
60Regency Horizon HZ54E Gas Fireplace
MAINTENANCEHZ54E-LP UNIT
1) Loosen 6 screws that secure the burner extenders. on burner tray, located behind the burner on either side of the pilot assembly.
2) Lift out the 2 burner tray extenders.
4) After extenders have been removed. Remove the 2 screws that secure the burner tray, at the base of the fi rebox.
5) Slide the burner to the left and lift it out.
6) With burner removed - lift out burner tray.
Burner tray extenders
Burner tray extenders
Burner tray
Gas Inlet Line
Burner Bracket
Location of screws securing burner
10) Partially lift out valve tray.
11) Disconnect the inlet gas line.
12) Replace valve and reverse steps.
9) Remove the valve tray by undoing 12 screws.
Green Wire Orange Wire
7) Disconnect the green and orange wires from the valve.
8) Disconnect the green ground wire from the valve bracket.
Green ground wire
Regency Horizon HZ54E Gas Fireplace61
PARTS LIST
MAIN ASSEMBLY
2
34
6 1
5
7
8
HEAT WAVE DUCT KIT
HEAT RELEASE DUCT KIT
Part # Description 1) 476-151 Bottom Cover (False Tray) NG 476-152 Bottom Cover (False Tray) LP2) 476-525 Burner Assembly -NG 476-530 Burner Assembly-LP3) 476-574E/P Valve Assembly -NG 476-576E/P Valve Assembly-LP
4) 911-004 886 SIT Valve - NG 911-005 886 SIT Valve - LP5) 911-006 Pilot Assembly - NG 911-007 Pilot Assembly - LP
910-363 White Wall Switch 910-366 White Switch Plate Wire
Part # Description
6) 904-660 Burner Orifi ce # 30 (NG) 904-431 Burner Orifi ce # 49 (LP) 904-658 Inlet Gas Flex Line SS7) 476-101 Burner Extenders (LP unit only) 476-042f LH / RH Nailing Strips8) 476-915 Optional Fan
370-055 Flue Collar Gasket 476-023 Plate Relief Gasket 476-055 Valve Tray Gasket 521-035 Inner Flue Collar Gasket
940-359/P Flush Glass 476-011 Flush Door 911-019 Wire (Valve to Burner ON/OFF) 948-409 Flue Collar 476-080 Lifting Handle 946-556 Heatwave Kit 946-570 Heatrelease Kit
918-883 Manual
62Regency Horizon HZ54E Gas Fireplace
PARTS LIST
Part # Description 30) 476-907 Refl ective Stainless Steel Panels 476-908 Black Enamel Inner Panels
31) 476-924 Faceplate & Door Frame Overlay - Black 476-927 Faceplate & Door Frame Overlay - Stainless Steel 476-926 Faceplate & Door Frame Overlay - Sunset Bronze
946-671 Cobalt Blue Glass Crystals 946-672 Natural River Pebbles 946-673 White River Pebbles 946-674 Stones 476-930 Log Set 946-690 GT remote 946-691 GTM remote 946-692 GTMF remote 910-576 Cover Wall Mount 910-572 Receiver GTM SIT w/Batt & Cover
ACCESSORIES
30
31
Regency Horizon HZ54E Gas Fireplace63
WARRANTY
Regency® Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our facility. Regency Fireplace Products is pleased to extend this limited lifetime warranty to the original purchaser of a Regency® Product. This warranty is not transferable.
The Warranty: Limited Lifetime The combustion chamber, heat exchanger, burner tubes/pans, logs, glass crystals, ceramic spa stones, pebbles, brick panels and gold plating (against defective manufacture only) are covered under the Limited Lifetime Warranty for fi ve (5) years for parts and subsidized labour* and parts only thereafter.
Glass is covered for lifetime against thermal breakage only, parts and subsidized labour* for fi ve (5) years and parts only thereafter from date of purchase.
External casting, surrounds and grills are covered against cracks and warps resulting from manufacturer defects, parts and subsidized labour* for three (3) years from the date of purchase and parts only thereafter.
Special Finishes - One year on stainless steel panels, nickel overlays,nickel faceplates, brushed nickel and antique copper full screens and doors. You can expect some changes in color as the product "ages" with constant heating and cooling. FPI warranties the product for any manufacturing defects on the original product. However, the manufacturers warranty does not cover changing colors and marks, ie. fi nger prints, etc applied after the purchase of the product. Damage from the use of abrasive cleaners is not covered by warranty.
Electrical and mechanical components such as blowers, switches, wiring, thermodiscs, FPI remote controls, spill switches, thermopiles, thermocouples, pilot assembly components, and gas valves are covered for two years parts and one year subsidized labour* from the date of purchase. Blowers and valves replaced under warranty are considered repairs and continue as if new with appliance. ie. twelve (12) months from original purchase date of appliance with a minimum of three (3) months coverage from date of replacement.
FPI venting components are covered parts and subsidized labour* for three (3) years from date of purchase.
Simpson Dura-Vent venting components (Direct Vent units) are covered by Simpson Dura-Vent Inc. warranty.
Repair/replacement parts purchased by the consumer from FPI after the original coverage has expired on the unit will carry a 90 day warranty, valid with a receipt only. Any item shown to be defective will be repaired or replaced at our discretion. No labor coverage is included with these parts.
Conditions:Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced at FPI's option, through an accredited distributor or agent provided that the defective part be returned to the distributor or agent Transportation Prepaid, if requested.
Porcelain/Enamel - Absolute perfection is either guaranteed nor commercially possible. Any chips must be reported and inspected by an authorized dealer within three days of installation. Reported damage after this time will be subject to rejection.
It is the general practice of FPI to charge for larger, higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for manufacturer defect.
The authorized selling dealer is responsible for all in-fi eld service work carried out on your Regency® product. FPI will not be liable for results or costs of workmanship from unauthorized service persons or dealers.
At all times FPI reserves the right to inspect product in the fi eld which is claimed to be defective.
All claims must be submitted to FPI by authorized selling dealers. It is essential that all submitted claims provide all of the necessary information including customer name, purchase date, serial #, type of unit, problem, and part or parts requested, without this information the warranty will be invalid.
Exclusions:This limited Lifetime Warranty does not extend to or include paint, door or glass gasketing or trim.
At no time will FPI be liable for any consequential damages which exceed the purchase price of the unit. FPI has no obligation to enhance or modify any unit once manufactured. ie. as products evolve, fi eld modifi cations or upgrades will not be performed.
FPI will not be liable for travel costs for service work.
Installation and environmental problems are not the responsibility of the manufacturer and therefore are not covered under the terms of this warranty policy.
Embers, rockwool, gaskets, door handles and paint are not covered under the terms of this warranty policy.
Any unit which shows signs of neglect or misuse is not covered under the terms of this warranty policy.
The warranty will not extend to any part which has been tampered with or altered in any way, or in our judgment has been subject to misuse, improper installation, negligence or accident, spillage or downdrafts caused by environmental or geographical conditions, inadequate ventilation, excessive offsets, negative air pressure caused by mechanical systems such as furnaces, fans, clothes dryer, etc.
Freight damage to stoves and replacement parts is not covered by warranty and is subject to a claim against the freight carrier by the dealer.
FPI will not be liable for acts of God, or acts of terrorism, which cause malfunction of the appliance.
Performance problems due to operator error will not be covered by this warranty policy.
Products made or provided by other manufacturers and used in conjunction with the operation of this appliance without prior authorization from FPI, may nullify your warranty on this product.
Any alteration to the unit which causes sooting or carboning that results in damage to the interior / exterior facia is not the responsibility of FPI.
* Subsidy according to job scale as predetermined by FPI.
64Regency Horizon HZ54E Gas Fireplace
Installer: Please complete the following information
Dealer Name & Address: ______________________________________________
___________________________________________________________________
Installer: ___________________________________________________________
Phone #: ___________________________________________________________
Date Installed: ______________________________________________________
Serial No.: __________________________________________________________
___________________________________________________________________
Printed in Canada
Regency Horizon and SureFire™ are trademarks of FPI Fireplace Products International Ltd.
Register your Regency® online athttp://www.regency-fi re.com
© Copyright 2010, FPI Fireplace Products International Ltd. All rights reserved.
Regency® fi replaces are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our door.
Regency Fireplace Products is pleased to extend this Limited Lifetime Warranty to the original purchaser of a Regency® Product.
See the inside back cover for details.
University of Denver HOLLOW METAL DOORS AND FRAMES Centennial Halls Main Level Renovation Project Manual 08 11 13
SECTION 08 11 13 - HOLLOW METAL DOORS AND FRAMES
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Non-fire-rated steel doors and frames.
B. Sound-rated steel doors and frames.
1.02 RELATED REQUIREMENTS
A. Section 08 71 00 - Door Hardware.
B. Section 08 80 00 - Glazing: Glass for doors and borrowed lites.
C. Section 09 90 00 - Painting and Coating: Field painting.
1.03 REFERENCE STANDARDS
A. ANSI/ICC A117.1 - American National Standard for Accessible and Usable Buildings andFacilities; International Code Council; 2003.
B. ANSI A250.8 - SDI-100 Recommended Specifications for Standard Steel Doors and Frames;2003.
C. ANSI A250.10 - Test Procedure and Acceptance Criteria for Prime Painted Steel Surfaces forSteel Doors and Frames; 1998 (R2004).
D. ASTM E 90 - Standard Test Method for Laboratory Measurement of Airborne SoundTransmission Loss of Building Partitions and Elements; 2009.
E. ASTM E 413 - Classification for Rating Sound Insulation; 2004.
F. ASTM E 1408 - Standard Test Method for Laboratory Measurement of the Sound TransmissionLoss of Door Panels and Door Systems; 1991 (Reapproved 2000).
G. BHMA A156.115 - Hardware Preparation in Steel Doors and Steel Frames; 2006.
H. NAAMM HMMA 840 - Guide Specifications for Installation and Storage of Hollow Metal Doorsand Frames; The National Association of Architectural Metal Manufacturers; 2007.
1.04 SUBMITTALS
A. See Section 01 30 00 - Administrative Requirements for submittal procedures.
B. Product Data: Materials and details of design and construction, hardware locations,reinforcement type and locations, anchorage and fastening methods, and finishes; and onecopy of referenced grade standard.
C. Shop Drawings: Details of each opening, showing elevations, glazing, frame profiles, andidentifying location of different finishes, if any.
1.05 QUALITY ASSURANCE
A. Maintain at the project site a copy of all reference standards dealing with installation.
1.06 DELIVERY, STORAGE, AND HANDLING
A. Store in accordance with NAAMM HMMA 840.
B. Protect with resilient packaging; avoid humidity build-up under coverings; prevent corrosion.
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. Steel Doors and Frames:1. Assa Abloy Ceco, Curries, or Fleming: www.assaabloydss.com.
2. Windsor Republic Doors: www.republicdoor.com.
3. Steelcraft: www.steelcraft.com.
4. Substitutions: See Section 01 60 00 - Product Requirements.
University of Denver HOLLOW METAL DOORS AND FRAMES Centennial Halls Main Level Renovation 2 of 3 08 11 13
2.02 DOORS AND FRAMES
A. Requirements for All Doors and Frames:
1. Accessibility: Comply with ANSI/ICC A117.1.
2. Door Top Closures: Flush with top of faces and edges.
3. Door Edge Profile: Beveled on both edges.
4. Door Texture: Smooth faces.
5. Glazed Lights: Non-removable stops on non-secure side; sizes and configurations asindicated on drawings.
6. Hardware Preparation: In accordance with BHMA A156.115, with reinforcement welded inplace, in addition to other requirements specified in door grade standard.
7. Galvanizing for Units in Wet Areas: All components hot-dipped zinc-iron alloy-coated(galvannealed), manufacturer's standard coating thickness.
8. Finish: Factory primed, for field finishing.
B. Combined Requirements: If a particular door and frame unit is indicated to comply with morethan one type of requirement, comply with all the specified requirements for each type; forinstance, an exterior door that is also indicated as being sound-rated must comply with therequirements specified for exterior doors and for sound-rated doors; where two requirementsconflict, comply with the most stringent.
2.03 STEEL DOORS
A. Interior Doors , Non-Fire-Rated:
1. Grade: ANSI A250.8 Level 1, physical performance Level C, Model 1, full flush.
2. Thickness: 1-3/4 inches.
B. Interior Doors , Sound-Rated:1. Grade: ANSI A250.8 Level 2, physical performance Level B, Model 2, seamless.
2. STC Rating of Assembled Door, Frame, and Seals: 35, calculated in accordance withASTM E 413, tested in accordance with ASTM E 90 or ASTM E 1408.
3. Sound Seals: Integral, concealed in door or frame.
4. Force to Open and Close and Latch: Not more than 5 pounds.
2.04 STEEL FRAMES
A. General:1. Comply with the requirements of grade specified for corresponding door.
a. Frames for Sound-Rated Wood Doors: Comply with frame requirements specified inANSI A250.8 for Level 1, 16 gage
2. Finish: Same as for door.
B. Interior Door Frames , Non-Fire-Rated: Knock-down type.
C. Sound-Rated Door Frames: Knock-down type.
2.05 ACCESSORY MATERIALS
A. Glazing: As specified in Section 08 80 00 , factory installed.
B. Silencers: Resilient rubber, fitted into drilled hole; 3 on strike side of single door, 3 on centermullion of pairs, and 2 on head of pairs without center mullions.
C. Temporary Frame Spreaders: Provide for all factory- or shop-assembled frames.
2.06 FINISH MATERIALS
A. Primer: Rust-inhibiting, complying with ANSI A250.10 , door manufacturer's standard.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify existing conditions before starting work.
B. Verify that opening sizes and tolerances are acceptable.
University of Denver HOLLOW METAL DOORS AND FRAMES Centennial Halls Main Level Renovation 3 of 3 08 11 13
3.02 INSTALLATION
A. Install in accordance with the requirements of the specified door grade standard and NAAMMHMMA 840.
B. Coordinate frame anchor placement with wall construction.
C. Coordinate installation of hardware.
D. Coordinate installation of glazing.
3.03 TOLERANCES
A. Maximum Diagonal Distortion: 1/16 in measured with straight edge, corner to corner.
3.04 ADJUSTING
A. Adjust for smooth and balanced door movement.
B. Adjust sound control doors so that seals are fully engaged when door is closed.
C. Test sound control doors for force to close, latch, and unlatch in accordance with ASTM E1408; adjust as required to comply.
END OF SECTION
University of Denver Centennial Halls Lighting Equipment Schedule
Current TypeDescription Location/ Application
Dimensions/
Aperture Manufacturer Approved Alternates Style/Part Number Lamp
No. of
Lamps
Ballast
Factor
System
Watts
Dimmin
g See
Note ? Volts Mounting
Mounting
Height Notes
Legend _G = Ground-mount or In-
Ground
_L = Linear
_M = Movable/Portable (lamp,
task)
_P = Pendant Mount
_R = Recessed
_T = Theatrical Lighting
_S = Surface Ceiling
_W = Surface Wall
Pendant Lighting
AP Decorative/Ambient Pendant Study Area 23.75"
Square
Neidhardt Shaper 472 Craftsman Series, 4 Bar, 26W
CFL lamping
RPD01 Pendant, White Finish 55W T5 FPC with 21W
2D
1
1
1.0 82 N Pendant 8'-0" Notes 1, 2
BP Not Used 7'-0"
CP Luminous Cylinder Pendant
with Bronze Finish
Hearth Room Counter Amerlux Shaper 422-CFL/1/26-XX(voltage)-BM-24"
Philips Omega Len 8 Pendant LEN8-
26PLT-BR-OPF-C-C-U;
Neidhardt Form Cylinder Pendant
Pari Pendant PARI-3R-20-
T4GU6.5-E-SO-AMBZ-CC-120
CMH T4GU6.5 20W
3000K (Philips or Osram
Sylvania ONLY)
1 24 N Pendant TBD
±6'-6"
Notes 1, 2
Recessed Lighting
AR Recessed Performance
Ambient with Diffuse Optics
and Door Frame Access
Back of House
Spaces
2' x 2' Philips Daybrite Corelite Z2 Recessed Lensed
Axis Day Curved DAYC-2'X2'-S-T5-2-W-
UNV-E-1-XX;
Litecontrol Litewave G-D-LHE222T5-HE-
CWL-LP/ELB-xx(voltage)
Softtrace 2ST-G-2-14-DS-
XX(voltage)-2-EB115
T5 14W 3000K 85CRI 2 1.15 35 N Ceiling
Recessed
Note 6
BR not used
CR4 Ceiling+Wall Recessed
Lensed Lightline with Outside
Corner
Stair Entry Soffits Nominal 2'
(ceiling) +
Nominal 2'
(wall)
a-Light Architectural Lighting Work Lightplane
Axis
NeoRay Straight and Narrow
Accolade 5 1-D5L-2-2-2-
XX(voltage)-A-C(Gyp. Ceiling W/
Outside Corner)-O(BR52)(brown
fine texture semi-gloss)
T5 14W 3000K 85CRI 2 1.0 32 N Ceiling / Wall
Recessed
Note 6
CR6 Ceiling+Wall Recessed
Lensed Lightline with Outside
Corner
Entry Soffits Nominal 4'
(ceiling) +
Nominal 2'
(wall)
a-Light Architectural Lighting Work Lightplane
Axis
NeoRay Straight and Narrow
Accolade 5 1-D5L-2-4-2-
xx(voltage)-A-C(Gyp. Ceiling W/
Outside Corner)-O(BR52) (brown
fine texture semi-gloss)
T5 28W 3000K 85 CRI +
T5 14W 3000K 85CRI
1
1
1.0 49 N Ceiling / Wall
Recessed
Note 6
CR8 Ceiling Recessed Lensed
Lightline with Staggered
Lamps
Entry Soffits Nominal 8' a-Light Architectural Lighting Work Lightplane
Axis
NeoRay Straight and Narrow
Accolade 5 1-D5-8-2-xx(voltage)-
A-G-O(BR52)(brown fine texture
semi-gloss)
T5 28W 3000K 85 CRI 2 1.0 64 N Ceiling
Recessed
Note 6
DR Recessed Lensed Wall WashHearth Room 2.9" Aperture Amerlux Lightolier Calculite Solid State 4" Square
Aperture 500 lm package wall wash;
RSA/Iris/Portfolio 3" - 4" Square Lensed
Wall Wash, T4GU6.5 20W
Evoke 2.9" Square Lensed Wall
Wash E2.9SLW-20-T5GU6.5-
xx(voltage)-GOLD/E2.9SLW-
MWW
CMH T4GU6.5 20W
3000K (Philips or Osram
Sylvania ONLY)
1 24 N Ceiling
Recessed
Note 6
ER not used
FR Square Glass Downlight Reception Desk 2.9" Aperture Amerlux Lightolier Lytepoints LED or T4GU6.5 20W
with Square Glass Trim;
RSA/Iris/Portfolio 3" - 4" Square
Downlight with Decorative Trim, T4GU6.5
Evoke 2.9" Square Downlight
E2.9SD-20-T4GU6.5-xx(voltage)-
NF-GRID-GOLD/E2.9SG-SONA
CMH T4GU6.5 20W
3000K (Philips or Osram
Sylvania ONLY)
1 24 N Ceiling
Recessed
Note 6
Surface Ceiling
AS Surface Mount (or semi-
recessed) LED or Compact
Fluorescent Decorative
Hallway and Lounge
Zone Clouds
6" x 7"
Rectangle
Spectrum Lighting Amerlux Evoke 2.9" Square Downlight
Evoke 2.9" Square Downlight E2.9SD-20-
T4GU6.5-xx(voltage)-NF-GRID-
GOLD/E2.9SG-SONA;
Neidhardt Holiday Inn Fixture (custom
size), 6x6, 26W CFL lamp
CY0607SQFA-LED-14w3K-
XX(voltage)-SM
LED 3000K 14 N Ceiling Surface Note 6
LES DU_Halls_LES_2011.05.13_Add1.xls 1
University of Denver Centennial Halls Lighting Equipment Schedule
Current TypeDescription Location/ Application
Dimensions/
Aperture Manufacturer Approved Alternates Style/Part Number Lamp
No. of
Lamps
Ballast
Factor
System
Watts
Dimmin
g See
Note ? Volts Mounting
Mounting
Height Notes
BS Surface Mount Decorative
Ambient Fixture
Hearth Room 18" Square Shaper Neidhardt RPD01 Ceiling, White Finish 271-18"-CFL/2/26-xx(voltage)-
OBZ-5P
26W CFL 3000K 2 1.0 56 N Ceiling Surface Notes 2, 6
CS Surface Mount Performance
Ambient with Diffuse Optics
and Door Frame Access
Back of House
Spaces, Restrooms
2' x 2' Philips Daybrite Corelite Z2 Surface Lensed
Axis Day Curved DAYC-2'X2'-
mod(surface)-T5-2-W-UNV-E-1-XX;
Softtrace 2ST-SM(surface)-2-14-
DS-XX(voltage)-2-EB115
T5 14W 3000K 85CRI 2 1.15 35 N Ceiling Surface Notes 2, 6
DS Decorative/Ambient Ceiling
Mount
Study Area 23.75"
Square
Neidhardt Shaper 271 Craftsman Square Surface, 4
Bar, 26W CFL lamping, Bronze Finish
RPD01 Ceiling, White Finish 55W T5 FPC with 21W
2D
1
1
1.0 82 N Ceiling Surface Notes 2, 6
ES Surface Mount 1'x1' Ambient
Fixture
Hallways 1'x1' Shaper Philips Daybrite Softrace 1x1 LED Surface
Mount, 3000K;
ALM 1055C-03 Flush Mount
698 Series, 698-SQ-
CFL/2/13/xx(voltage)-xx(bronze)-
TBC
13W CFL 2 1.00 29 N Ceiling Surface Notes 2, 6
Surface Wall
AW4 Linear Fluorescent Wall
Asymmetic Indirect with
Sawtooth Reflector
Hallways 4' Ametrix Insight Visio;
aLight Accolade 4 D4 Series 4-H-U-T-D-
XX(mounting)-T0-BR52(brown fine texture
semi-gloss)
Arrowlinear AC-SI-A-1-LF-T5-1C-
XXX-B-AK6
Osram Sylvania T5HO
47W Supersaver 3000K
1 47 N Surface Wall Top course
of masonry
Notes 1, 2
AW8 Linear Fluorescent Wall
Asymmetic Indirect with
Sawtooth Reflector
Hallways 8' Ametrix Insight Visio;
aLight Accolade 4 D4 Series 8-H-U-T-D-
XX(mounting)-T0-BR52(brown fine texture
semi-gloss)
Arrowlinear A08-SI-A-2-LF-054-
XXX-B-AK6
Osram Sylvania T5HO
47W Supersaver 3000K
2
(1 in
section)
94 N Surface Wall Top course
of masonry
Notes 1, 2
AW12 Linear Fluorescent Wall
Asymmetic Indirect, Bronze
Finish
Hallways 12' Ametrix Insight Visio;
aLight Accolade 4 D4 Series 12-H-U-T-D-
XX(mounting)-T0-BR52(brown fine texture
semi-gloss)
Arrowlinear A04-SI-A-1-LF-054-
XXX-B-AK6
Osram Sylvania T5HO
47W Supersaver 3000K
3
(1 in
section)
141 N Surface Wall Top course
of masonry
Notes 1, 2
BW Decorative Metal and Glass
Sconce with Bronze Finish
Screen Walls
(Vertical Mount);
Restrooms
(Horizontal Mount);
Reception Display
Wall (Horizontal
Mount)
24" T5 Shaper Architectural Lighting Works TriPlane
Wall;
OCL Illusion-mod (diffuse front)
600-24"-T5/2/14-xx(voltage)-BM T5 14W 3000K 85 CRI 2 1.0 32 N Surface Wall Notes 1, 2, 7
CW Linear Fluorescent Wall
Asymmetic Direct/Indirect
Hallways 4' aLight Corelite Class A Perf Wall;
Litecontrol V3 Wall Valance
Arcature 4 4-S-U-A-D-R-T032-
BR52(brown fine texture semi-
gloss)
T5 28W 3000K 85 CRI 1 1.0 32 N Surface Wall 7'-0" Notes 1, 2
Linear Lighting
AL Asymmetric Architectural
Cove Luminaire with Sawtooth
Reflector
TBD in Field Nulite Birchwood Lighting Ashley
Corelite Solo
Dayolite ITG26
CSV-1-54T5HO-xx(voltage) Osram Sylvania T5HO
47W Supersaver 3000K
1 1 12w/l.f. N Surface Cove Note 3
BL Linear LED Tape Lighting with
Rigid Aluminum Mounting
Channel for Heat Dissipation
Screen Walls Spike Lighting ParadigmLED Flex500 Interior, 5000K
(Paradigm Systems 303.399.0386);
ET2 Starstrand Ultima 24
Sonic Glow (164 lm / l.f.) with
Aluminum Mounting Channel for
Heat Dissipation
3500K LED, 120-degree 5w/l.f. N Recessed into
Woodwork
Notes 4, 5
General Notes:
1.) Should a product from one of the listed Approved Alternate manufacturers be bid, and subsequently submitted for Shop Drawing Approval, it must meet all functional and aesthetic aspects of the manufacturer's product that is listed as the prime with a specific
catalog number. These attributes shall include, but not necessarily be limited to the following:
a.) Lamp, ballast, transformer, and/or power supply as applicable.
b.) Approximate physical dimensions (In the case of overall depth of recessed units, submitted fixture must not exceed the prime specified product by more than 1/2 inch)
c.) Optical performance, including: efficiency, beam distribution, center beam candlepower, etc.
d.) Metal gauge or thickness, material content and finish of all visible surfaces.
e.) Mounting mechanisms and technique.
Acceptability of compliance is the final decision of the Lighting Designer. Operable samples, with 120 volt cord and plug, shall be provided if requested.
LES DU_Halls_LES_2011.05.13_Add1.xls 2
University of Denver Centennial Halls Lighting Equipment Schedule
Current TypeDescription Location/ Application
Dimensions/
Aperture Manufacturer Approved Alternates Style/Part Number Lamp
No. of
Lamps
Ballast
Factor
System
Watts
Dimmin
g See
Note ? Volts Mounting
Mounting
Height Notes
2.)
Project Notes:
1.)
2.)
3.)
4.)
5.)
6.)
7.) Type BW Luminaire is vertically mounted at modular and screen walls. It is mounted horizontally in bathrooms and at the Reception Display Wall.
Contractor is responsible for verifying ceiling materials and thickness prior to ordering luminaire and ordering appropriate trim as needed to accommodate varying ceiling conditions such as acoustical ceiling grid, 9/16" or 5/16" grid widths, gypsum board, plaster or specialty
ceilings.
Contractor responsible for a level, orthogonally aligned installation of all pendant, sconce, and ceiling surface mount fixtures.
For all pendants, chandeliers, bracket lights, sconces, and wall recessed area lights, contractor shall verify exact suspension/mounting heights with Architect and Lighting Designer prior to final installation. Contractor responsible for verifying stem/cable lengths
based on ceiling height.
Contractor shall supply full range of manufacturer's standard colors for metal, glass, and trim for fixtures where finish is not specified.
Contractor responsible for determination and procurement of all necessary boxes, leader cables, jumper cables, control cables, connector and interconnector devices, required to provide a complete, code compliant installation consistent with recommendation of the
manufacture. The LED manufacturer's basic 12" LED module is listed in the fixture schedule. Contractor shall be responsible for providing the required quantity of manufacturer's standard leader cables, jumper cables, wiring blocks/boxes, data enablers, and other
miscellaneous parts and pieces; to ensure a complete, operational and code compliant system. Provide driver, power supply and/or transformer of appropriate size for this application. Locate devices in accessible, concealed-from-view, ventilated location in conformance with
manufacturer's requirements and consistent with Contract Documents.
Fixture is mounted and concealed within architectural cove, consistent with all applicable architectural/lighting details. No part of this fixture or its constituent lamp(s) shall be directly visible from normal viewing angles. Interior details are supplied for the mounting
of this fixture which provide specific guidance, however, if any modification of those details are necessary in order to fulfill this concealment requirement, it should be brought to the attention of the Lighting Designer or Interior Designer prior to proceeding with
electrical rough-in or architectural framing. When made necessary by cove construction, fixture mounting shall be shimmed upward such that the lamp and/or reflector is just below the top of the cove, while still maintaining concealment, in order to maximize
distribution and efficiency.
Provide shop drawing that shows complete assembly and configuration of all parts and pieces for this fixture's specific application.
LES DU_Halls_LES_2011.05.13_Add1.xls 3