CEAG Notlichtsysteme GmbH
CEAG Notlichtsysteme GmbH
1906 2014
2
CEAG Notlichtsysteme GmbH
O. H. Chao Regional Sales Manager
(South East Asia)
3
CEAG Notlichtsysteme GmbH
A Strong Collection of Businesses With a Long History of Product Quality and Innovation
Crouse - Hinds
$500 M
(1897)
Bussmann
$400 M
(1914)
Lighting
$ 1200 M
(1956)
Power System
$800 M
(1911)
B-Line
$300 M
(1969)
Wiring Devices
$300 M
(1890)
Menvier
$400 M
(1975)
Power Tools
$300 M
(1967)
Hand Tools
$400 M
(1864)
4
CEAG Notlichtsysteme GmbH
CEAG Notlichtsysteme GmbH - the plant
• Soest
5
CEAG Notlichtsysteme GmbH
Why Not UPS
• What are the problems
– Discharge Lighting
– Heat Dissipation
– Battery Life
– Overload Capability
6
CEAG Notlichtsysteme GmbH
Discharge Lighting
• Most Discharge lighting takes a prolonged
period of time to strike the lamp and does not
comply with Standards Set at 5 seconds
• UPS manufacturers claim “NO-BREAK output
solves this, but it is WRONG
10
CEAG Notlichtsysteme GmbH
1
0
Discharge Lighting WAREHOUSE
OFFICE
MCB 1
MCB 2
230V
OUTPUT LOAD
230V
Normal Operation Fire Breaks Out
11
CEAG Notlichtsysteme GmbH
1
1
Discharge Lighting WAREHOUSE
OFFICE
MCB 1
MCB 2
SUPPLY FAIL
SHORT
CIRCUIT
OUTPUT LOAD
230V
Supply Failure
12
CEAG Notlichtsysteme GmbH
1
2
WAREHOUSE
OFFICE
MCB 1
MCB 2
SUPPLY FAIL
SHORT
CIRCUIT
OUTPUT LOAD
0V
LOSS OF EM LIGHTS DARKNESS
Discharge Lighting OVERLOAD
13
CEAG Notlichtsysteme GmbH
1
3
Discharge Lighting WAREHOUSE
OFFICE
MCB 1
MCB 2
SUPPLY FAIL
SHORT
CIRCUIT
OUTPUT LOAD
230V
MCB FAULT CLEARS (approx 5 sec’s) DISCHARGE LAMPS WARM UP
14
CEAG Notlichtsysteme GmbH
• Where discharge lighting schemes are
required, it is recommended to use separate
secondary non-maintained emergency lighting
or alternate fluorescent lighting for emergency
escape lighting.
Discharge Lighting Design
15
CEAG Notlichtsysteme GmbH
Battery Lifetime
Active stand-by operation Vs Passive Stand-by
BATTERY
CHARGER
INVERTER
(RUNNING)
BATTERY
HEAT HEAT
UPS / ACTIVE STANDBY
STSTEM
(INVERTER PERMANENTLY RUNNING)
BATTERY
CHARGER
INVERTER
(RUNNING)
BATTERY
NO HEAT
GENERATED
HEAT
STATIC INVERTER
STSTEM
(INVERTER PASSIVE STANDBY)
CONSTANT CHARGE
AND DIS-CHARGE CONSTANT TRICKLE
CHARGE ON
DEMAND
16
CEAG Notlichtsysteme GmbH
Heat Dissipation
BATTERY
CHARGER
INVERTER
(RUNNING)
BATTERY
HEAT HEAT
UPS / ACTIVE STANDBY
STSTEM
(INVERTER PERMANENTLY RUNNING)
BATTERY
CHARGER
INVERTER
(RUNNING)
BATTERY
NO HEAT
GENERATED
Negligible
HEAT
STATIC INVERTER
STSTEM
(INVERTER PASSIVE STANDBY)
UPS – STATIC INVERTER POWER LOSS
17
CEAG Notlichtsysteme GmbH
Heat Dissipation
• A 30 kW UPS system will continuously dissipate
about 3KW of heat.
• If electricity costs HK$0.9 per unit then the running
costs will be:
$0.9 X 3 x 24 x 365 = HK$23,652 per year
• For a static inverter costs will negligible
18
CEAG Notlichtsysteme GmbH
Summary
• Designed for emergency lighting requirement
• >10 yrs
• Negligible
• 200% for 10 seconds, 125% for 20 minutes
• Adapted for emergency lighting requirement
• ~ 3-5 years
• Loss Energy
• 125-150% momentary only
• Design
• Lifetime
• Heat Dissipation
• Overlaod Capability
CBS Typical UPS
19
CEAG Notlichtsysteme GmbH
t
I U
Battery Charger
Self contained luminaires - construction
Mains
20
CEAG Notlichtsysteme GmbH
Battery
6
3 9
6
3 9
12 12
18 month
32 month 24 month
36 month
28 month
21
CEAG Notlichtsysteme GmbH
OGi-V batteries
Influence of temperature, life expectancy
Life expectancy as a function of the battery
temperature
0
10
20
30
40
50
60
1 2 3 4 5 6 7 8 9 10 11 12 13 [years]
[°C]
22
CEAG Notlichtsysteme GmbH
Our Philosophy
Each safety luminaire is important -
it can save human´s health and life
monitor each luminaire
automatic testing
connection to BMS
use the advantages of central-
battery systems.
Innovation in Emergency-Lighting is increasing
safety in buildings
37
CEAG Notlichtsysteme GmbH
38
CEAG Notlichtsysteme GmbH
CBS : AC CBS : DC
39
CEAG Notlichtsysteme GmbH
DC SYSTEM
Cable entry from the bottom
Cable entry from the top
3-pole terminals with
neutral disconnector
Change - over module
24 x SKU 2 x 3 A CG-S
Controller,DC/DC converter,
charger, 2 x SKU 2 x 3 A CG-S
Load break switch, mains
Load break switch, battery
AC fuses for substations
DC fuses for substations
2,5A boost charger
40
CEAG Notlichtsysteme GmbH
-Higher initial cost (Product, Space)
System Disadvantage
CBS
- Battery service life time up to 10 years (at 20oC)
- All relevant tests are carried out automatically
- Suitable for high and low luminaires power
- Low maintenance work and follow-up cost
- Software user friendly
- Maintain, Non-Maintain & Switching Mode in ONE circuit
- Individual Circuit Protection (with SKU fuse relay)
- No need Converter from DC to AC (Less Battery Capacity)
System Advantage
CBS DC SYSTEM
41
CEAG Notlichtsysteme GmbH
Cost of Emergency - Lighting DC SYSTEM
42
CEAG Notlichtsysteme GmbH
Conventional Installation
Maintained mode c1
Maintained mode c1
Non-maint. mode c2
Non-maint. mode c2
Switched maintained mode c3
Switched maintained mode c3
3 final circuits !
DC SYSTEM
43
CEAG Notlichtsysteme GmbH
S = Switching
T = Technology
A = Advanced
R = Revision
Z B - S
DC SYSTEM
44
CEAG Notlichtsysteme GmbH
Only 1outgoing
circuits
necessary !
Non - maintained mode
Maintained mode
Switch maintained
mode
the STAR Technology
(Switching Technology Advanced Revision)
• Savings in installation
• Easy planning
• Full flexibility
• Easy programming
• Connection to BMS and LON
• Visualitzation by computer
(CG Vision.)
DC SYSTEM
45
CEAG Notlichtsysteme GmbH
Compact system Non - Compact system Substation
46
CEAG Notlichtsysteme GmbH
Internal modules and wiring DC SYSTEM
47
CEAG Notlichtsysteme GmbH
Change Over Relay 1x6A / 2x3A
/ 4x1.5A • intelligent switch over relays
• separate AC and DC fuses
• emergency operation even without controller
Control unit: ST-S • Programming
• Monitoring
• Logbook
Charger • 2.5A charging current
• temperature controlled charging method
48
CEAG Notlichtsysteme GmbH
Display of 4 x 20 characters lines, contrast and brightness are adjustable through the program
Display of: - date / time - charging fault - deep discharge protection - battery voltage - battery charge current (+) - battery discharge current during test or failure (-) - manual reset - function test - time-delayed emergency light on mains return (remaining time in minutes) - luminaire fault with specific location data. - insulation fault stating faulty circuit - failure MDB (location data) - fault information - programming information
ZB-S: Control module
49
CEAG Notlichtsysteme GmbH
STAR - Technology
0
ZB - S
220V
1111111...
1
2
3
4
5
6
20
0101000...1
Non-maintained mode
Maintained mode
Switched non-maintained
mode
L N PE
5A
230 V 50 Hz
2 x 5A
DC SYSTEM
50
CEAG Notlichtsysteme GmbH
Function Test / Battery Mode
1
2
3
4
5
6
20
0
Battery supply
220V
2 x 5A
L N PE
5A
230 V 50 Hz
Address / location
51
CEAG Notlichtsysteme GmbH
ZB-S
DALI EVG 0
D
U
D
2L-CG-SB U
O
U D1
D2
O
D1
D2
Switch / dimmer
Daylight sensor
DALI-Controller
Features :
- New, with Tridonic DALI/DSI function !
- Unique selling proposition against competitors !
- Due to integration in a high design light management,
especially for design buildings, like museums
New development: DALI-module 2L-CG-SB
Application
DC SYSTEM
52
CEAG Notlichtsysteme GmbH
L6
L5
L4
L3
L2
L1
ZB-S 26C6, battery inside the cabinet; 90Ah battery, for the load of 240 luminaires, each of 2x28W and
60 EXIT signs of 10W, dimension per cabinet: H x W x D 2000 x 800 x 600
80 x (2x28)W + 20 x 10 W EXIT sign
80 x (2x28)W + 20 x 10 W EXIT sign
80 x (2x28)W + 20 x 10 W EXIT sign
ZB-S 26C6, battery inside the cabinet; 90Ah battery, for the load of 240 luminaires, each of 2x28W and
60 EXIT signs of 10W, dimension per cabinet: H x W x D 2000 x 800 x 600
80 x (2x28)W + 20 x 10 W EXIT sign
80 x (2x28)W + 20 x 10 W EXIT sign
80 x (2x28)W + 20 x 10 W EXIT sign
53
CEAG Notlichtsysteme GmbH
L6
L5
L4
L3
L2
L1
ZB-S 26C6, battery inside the cabinet; 90Ah battery, for the load of 240 luminaires, each of 2x28W and
60 EXIT signs of 10W, dimension per cabinet: H x W x D 2000 x 800 x 600
L6: 80 x (2x28)W + 20 x 10 W EXIT sign
80 x (2x28)W + 20 x 10 W EXIT sign
ZB-S 26C6, battery inside the cabinet; 90Ah battery, for the load of 240 luminaires, each of 2x28W and
60 EXIT signs of 10W, dimension per cabinet: H x W x D 2000 x 800 x 600
80 x (2x28W) + 20 x 10 W EXIT sign
80 x (2x28)W + 20 x 10 W EXIT sign
80 x (2x28)W + 20 x 10 W EXIT sign
80 x (2x28)W + 20 x 10 W EXIT sign
54
CEAG Notlichtsysteme GmbH
L2 - L23
PC monitoring software:
CG Vision
L6
L5
L4
L3
L2
L1
55
CEAG Notlichtsysteme GmbH
DC SYSTEM
Sub-station
16mm2 of
AC & DC Cable
CBS & Battery
1.5mm2 cable to lighting
HK Science Park
56
CEAG Notlichtsysteme GmbH
Tamar HK Gov.天馬艦政府總部
57
CEAG Notlichtsysteme GmbH
New development: CGVision
Features :
- Implementation of new CGLine !
- Constant implemantation of
new features to save the
unique selling advantages
New Features :
- Extensive print menu
- Timer menu
- Extensive logbook function
- Building layout as option
58
CEAG Notlichtsysteme GmbH
Dubai 1994
EML - Market
100 % Self Contained luminaires
0 % Central Battery Systems
EML - Market
2004 - 80 % Central Battery Systems
End 2007 – 100% must use in CBS
Dubai 2004
59
CEAG Notlichtsysteme GmbH
Dubai Tower
2008 Water Cube
New Bangkok International Airport
7 Star Hotel
60
CEAG Notlichtsysteme GmbH
Allianz Arena, Munich,
Germany (2006 World Cup)
Veltins Arena, Schalke, Germany
61
CEAG Notlichtsysteme GmbH
Athens International Airport Düsseldorf International Airport
New Bangkok International Airport Dubai International Airport