Page 1: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

By : Sagar.N (Manager – Green Initiative , Infosys)

Case Study Of Buildings with Radiant cooling

Page 2: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Infosys goals at UN:

Make Infosys Carbon neutral by 2018

Reduce per capita energy by 50% by 2018 (compared to 2008)

Source 100% of electricity from renewables by 2018

Green Initiatives team :

Specialists in respective fields: Lighting, HVAC, Building

management systems, Water, Architecture, Waste, Biodiversity,

etc.

Practice frugal engineering

Question every assumption

Validation through M&V

Green team

HVAC

Architects

Water Mgmt.

Waste Mgmt.

Automation

Lighting

2

Environmental sustainability goals

Page 3: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Increase in no.

of employees

in India

120%

13%

Absolute

Increase in

energy

Growth from 2008 to 20153

890 Million kWh avoided

0.75 Million Tons of CO2 emissions avoided

100 Million USD electricity bills avoided

Current infrastructure:

Total 40 million sq.ft. of space in India

176,000+ employees in Apr 2015

15 campuses across India

Page 4: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

46% reduction in per capita energy consumption in last 7 years

46%reduction

Energy Efficiency – kWh / employee per month4

297

266

239 230

203

178167 159

0

50

100

150

200

250

300

350

2007-08 2008-09 2009-10 2010-11 2011-12 2012-13 2013-14 2014-15

Mo

nth

ly k

Wh

/ e

mp

loye

e

Average Per capita Electricity consumption

Page 5: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

5

Performance metricInfosys design –

2007-08Infosys new

design% Improvement

1Total building energy consumption (EPI)

200 kWh/m2/year 75 kWh/m2/year 70%

2 Lighting design 1.2 W/sqft 0.48 W/sqft 60%

3Air-conditioning design (Reduction in heat load)

350 sqft per TR 750 sqft per TR 53%

4Total building electrical design

6.5 W/sqft 3.5 W/sqft 46%

5

Infosys – New design and performance benchmarks

Page 6: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Benchmarking of Infosys buildings with RMI (highest) standards

Design target Units Existing (US) Better Amory Lovins Infosys

Building energy consumption kWh/sqm-y 200 125-60 <95 <80

Lighting Power Density: Design W/sqft 1.5 0.8 0.4-0.6 0.45-0.6

Lighting Power Density: Operational W/sqft 1.5 0.6 0.1-0.3 <0.15

Installed computers/appliances.. W/sqft 4-6 1-2 <0.5 <0.7

Window glass R-value m2 K/W 0.18 – 0.35 1-1.7 ≥3.5 >1

Window glass (Light to Heat ratio) VLT/SHGC 1 1.2 >2.0 >2.0

Installed mechanical cooling sqft/ton 250-350 500-600 1200-1400+ 750 - 1000

Cooling system efficiency kW/ton 1.9 1.2-1.5 <0.6 <0.59

US India

66

*RMI :Rocky Mountain Institute

Page 7: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Sl. No. System Description Units Infosys new designs

Infosys olddesigns

Conventional

01 Total electrical load MW 3.5 6.5 10.0

02 Transformer capacity MVA 4.0 7.5 12.0

03 DG set capacity MVA 5+2.5 9+3 15+3

04 Annual energy consumption Million kWh 7.5 20 25

Infrastructure required for 1 million sqft,

7

Impact of new design on capital and operating cost7

Page 8: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Benefit of efficient design on capital and operating cost for India

Indian context:

• 2/3rd of India of 2030 is yet to be built (McKinsey report)

• For 10 billion sq.ft. of commercial space expected by 2030, Infosys

design standards can save 45,000 MW of installed capacity of power

plants

8

Page 9: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Industry leadership

5.3 million sqft of highest rated green buildings in India -

− 14 of our buildings have achieved LEED platinum rating, making us no.1 in India for office buildings. (Platinum is

highest level in LEED green building rating).

1.7 million sqft of area currently undergoing LEED/GRIHA certification

− 7 of our buildings are in different stages of LEED certification

4 of our buildings have achieved GRIHA 5-star rating (highest level in the MNRE National rating for

Green Buildings)

2.6 million sqft of Radiant cooled buildings

Infosys buildings have an annual Energy Performance Index of 80 kWh/m2/year, lowest in the

industry

Filed for a patent on a new cooling technology developed in-house (RADIFLUX)

9

Page 10: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Our approach

10

Page 11: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Integrated and goal oriented design approach

HVAC Goal Lighting Goal Water Goal

Max envelope heat gain 0.75 W/sqft

Total building @ 750-1000 sqft/TR

25 0C, 55% RH

LPD of 0.45 W/sqft

90% of building to be day lit > 110 lux

No Glare throughout the year

Architects

Facade Specialists

IT Specialists

HVAC Engineers

Lighting Specialists

Architects

Facade Specialists

Lighting Specialists

Electrical Designers

PHE Engineers

Architects

Landscape Architects

15 LPD of fresh water for

office building

Zero discharge

100% self sufficient

TEAM

GOAL

Multi disciplinary team put together to achieve common goal

1111

Page 12: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Optimization strategy

Results in ‘4x’

reduction in air

conditioning

energy

HVAC Optimization

Reduce Heat Gain

Energy simulation

Efficient heat

transfer mechanism

Efficient system

Equipment configuration

Efficient equipment

Control strategy

Continuous monitoring

10%

5%

10%

15%

7%

8%

10%

10%

12

Page 13: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Passive design: Right orientation - Restricted building span to 18 m

Window-wall ratio < 30%

13

Building shape and orientation13

Page 14: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Envelope heat gain < 0.75 W/sq.ft

External heat gain in building to be less than 0.75 W/sq.ft

- Wall insulation with R value of 10

- Roof insulation with R value of 15

• Window-wall ratio < 30%

– Low SHGC of 0.2 with low e glass. Double glazed unit with

argon gas to achieve R value of 5.5

– Glazing completely shaded

14

35 0C 25 0C

Heat ingress through standard wall

35 0C 25 0C

Heat ingress through insulated wall

5 times more efficient

2.0 W/m2 deg K

0.40 W/m2 deg K

Outdoor

Outdoor

Indoor

Indoor

High performanceHigh tech

14

Page 15: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Day light pane

View pane

External shading

Smart glazing

Interior light shelf

15

Day lighting and Glare control – Glass and shading15

Page 16: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Day lighting – shading strategy implementation

West façade

with no windows

16

SDB-1, Infosys Hyderabad campus

16

Page 17: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

17

To take daylight deeper into floors

Daylight panel

Vision panel

Light shelves for deeper penetration of day light

Day lighting – Interior light shelf17

Page 18: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

18

• Provides pleasant office space

• Improves employee health

• Improves employee productivity

• Addresses Vitamin D deficiency

Natural light in offices18

Page 19: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Use of simulation software for designs

Daylight analysis Shading and glare analysis Building envelope analysis

N-S oriented. Building floor plate : 16m Master plan analysis

19

Page 20: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

1. Use automated energy saving strategies/logics

- every single electrical motor in the building uses an energy saving strategy

2. Manage energy by detail – for lighting, computing and plug loads

- floor-wise and wing-wise energy monitoring for lighting, computing and plug

loads for granular energy control, identification of wastage

3. Continuous M&V, continuous commissioning

- measures energy as well as efficiency for all hvac and ups for continuous

verification and improvement

4. Deliver highest standards of indoor air quality (IAQ)

- Demand controlled ventilation to maintain IAQ with minimal energy

consumption

20

Example of demand controlled ventilation.Building only uses as much fresh air as

required based on occupancy / CO2 sensing

Smart building systems20

Page 21: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

5. Provides data to optimize future building designs- records peak value of W/sqft on hvac, lighting, computing and main incomer to migrate from thumb rule

engineering to performance data driven engineering

6. Allow equipment and system level diagnostics and corrections

e.g extensive measurement on ahus allow identification of low flows, malfunctioning valves, fans, coils,

filters, etc.

7. Enables trending and data analytics

- e.g. trends to analyze historical operation of VAVs, AHUs, Chiller plants.

8. Water efficiency

- monitors water consumption on hourly, daily and monthly basis for optimization

2121

Smart building systems

Page 22: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Managing wastage by granular energy monitoring

Helps manage

floor wise energy

wastage

22

Working on SMS alerts for energy wastage

22

Page 23: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Continuous verification, continuous auditing- Design Vs Actual

Constant monitoring to

get design efficiencies

23

Allows performance based management for maintenance contracts

23

Page 24: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

SMS Gateway

in cloud

Alert condition Preconfigured SMS alerts in BMS

DDC

Controller

2424

SMS alerts for critical alarms

Page 25: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Command center at Infosys Bangalore to monitor, manage and optimize resources usage

Remote monitoring through Command Center25

Page 26: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

• Building: Software Development Block (SDB) -1, Hyderabad

• Total area: 240,000 sqft (excluding central wing, which is not occupied)

− Conventional side: 120,000 sqft

− Radiant side: 120,000 sqft

− Total occupancy: 2600

− Conventional side: 1340

− Radiant side: 1260

Analysis

26

Page 27: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

HYDERABAD SDB-1First radiant cooled commercial building in India

Page 28: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Heat Capacity of this volume of air

=

Heat Capacity of this volume of water

Water has 3400 times more heat carrying

capacity than air for the same volume Pumping cost is 7.5 times lower

Pumping Air Vs. Water for

same cooling capacity

28

Efficient Heat transfer mode and medium28

Page 29: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Requires 75% less air compared to conventional systems

30% more efficient than conventional HVAC systems

Higher thermal comfort on account of better mean radiant

temperature

Highest indoor air quality

Radiant system equipment requires lesser space

29

Radiant pipes

Radiant slab

Efficient system - Radiant cooling29

Page 30: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Infosys case study - Radiant cooling• Radiant cooling for the first time in India

• SDB-1 (Hyderabad SEZ) has 2 identical halves, one with radiant

cooling and the other with conventional air conditioning

• This building is today the biggest demonstration of cooling

technology comparison

Radiant slab

AIR-CONDITIONING RADIANT COOLING 100

3525

0

20

40

60

80

100

120

Standard Air-conditioning

Efficient Air-conditioning

Radiant cooling

Cooling energy consumption (kWh/m2/year)

30

Page 31: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Live Energy Data 31

Page 32: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

HVAC energy breakup

32

Chillers60%

Pumps7%

Cooling towers3%

Air Handlers30%

Chillers / DX unit71%

Pumps13%

Cooling towers3%

Air Handlers13%

Conventional side

Total HVAC energy: 428,000 kWh

HVAC Energy index: 38.4 kWh/SQM

Radiant side

Total HVAC energy: 267,000 kWh

HVAC Energy index: 26.1 kWh/SQM

Page 33: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Conventional system Radiant system

Chiller 3145200 3145200

Cooling tower 1306400 1306400

HVAC low side 22838756 15310396

AHUs, DOAS, HRW 5118200 2878900

Radiant piping, accessories, installation, etc. 0 9075760

BMS 6184000 6584000

Total cost (Rs.) 38592556 38300656

Area (sq.ft.) 120000 120000

Rs./sq.ft. 322 319

Cost comparison (Conventional Vs. Radiant)

33

Page 34: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Key Points in Implementing Radiant Slab34

• No condensation has happened in last 5 years.

a) Average water temp to control the manifolds

b) Room dew point is over ride for manifold control

c) Space temp to control PIBCV

d) Condensation sensor installed in the shaft override

e) Dehumidified air to control the dew point in space with

VAV/thermafusers/slot diffusers

• Only 2 Punctures recorded in last 5 years. (Initial period)

• Capex and Opex is lower.

Page 35: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Learnings - Radiant Slab35

• Radiant pipes to be kept under pressure of 3 – 4 kg/cm2 always during installation

• Manifolds to be preferably at the peripheral area

• Two separate controls for peripheral area near glass and work station area

• No radiant slab for meeting rooms/cabins – Design with air

• Not very Flexibile - All services to be planned during designed stage

• Additional drilling is difficult.

• Acoustics is a challenge - Infosys has no issues since there is no voice based operations

Page 36: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Radiant Panels cooling our Buildings36

Published in Construction World Vol 17

Page 37: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

37

• We are the first in India to implement the

radiant panel based cooling system.

• Pipes are embedded in panels of modular

sizes like ceiling tiles,

• These panels are interconnected to allow

chilled water flow .

• Cooling is achieved when the Hot source

radiate directly to the cold ceiling.

• Fresh air is supplied through an air

system that maintains pleasant indoor air

quality.

Radiant Panel Based Cooling

Page 38: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Learnings - Radiant Panels38

• Flexible in design when compared to slab.

• Piping/ joints/ pressure drops are very high

• Acoustics is a challenge

• Expensive when compared with Slab

Page 39: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

DIY Approach by Infosys39

• Panels should be very flexible

• Piping and joints should be minimal

• Acoustics is addressed

• Should not be expensive than Slab.

• Ease of installation and maintenance

Page 40: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

DIY Integrated Design Approach by Infosys40

• Indoor air quality

• Thermal comfort

• Visual comfort

• Acoustic comfort

• Sustainable solution

Page 41: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Infosys in-house radiant panels4141

Developed by Infosys in-house team

Tested and certified for its performance as per international standards in WSP

lab Germany

Produces twice the capacity and less cost , compared to current solutions in

the market

Produces 193 W/m2 at 10 K delta T as per EN14240 standards

Radiant cooling is 30% more efficient than conventional system

Patent filed in US, Europe and India

Page 42: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

Capacity Graph – EN14240 standards42

Page 43: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

RADIFLUX43

Page 44: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

KEY Features of RADIFLUX44

Monolithic and flexible in design

Gives architects liberty in Ceiling designs – Ceilings can be designed with different

shapes and colors

Highest capacity in class

Highest Air quality

Lesser connections in the system

Ease of Installation and maintenance

Page 45: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

45

Any questions ???

Page 46: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

46

Contact Details:

Sagar.N

E mail : [email protected]

Phone : +91 7829918739

Page 47: Case Study Of Buildings with Radiant cooling - BEEP - Case study on radiant... · Case Study Of Buildings with Radiant cooling. ... (Light to Heat ratio) ... Daylight analysis Shading

© 2013 Infosys Limited, Bangalore, India. All Rights Reserved. Infosys believes the information in this document is accurate as of its publication date; such information is subject to changewithout notice. Infosys acknowledges the proprietary rights of other companies to the trademarks, product names and such other intellectual property rights mentioned in this document. Exceptas expressly permitted, neither this documentation nor any part of it may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, printing,photocopying,recording or otherwise, without the prior permission of Infosys Limited and/ or any named intellectual property rights holders under this document.

Thank You