Case studyHarmonic Distortion In a Steel Plant with
Induction Furnaces
Suriya TheppalukEngineer Level 4
Power Quality Analysis SectionProvincial Electricity Authority (South Area 1) Phetchaburi
![Page 2: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/2.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
Introduction Induction Furnace Instrument and Evaluate Conclusion
Outline
![Page 3: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/3.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
PEA Distribution
Network
Introduction
![Page 4: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/4.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
Introduction
THDv exceed 4% (The Harmonic Regulations for The Commercial and Industrial (PRC-PQG-01/1998) in Thailand)
Power Quality Evaluation in Distribution Network Kao Yoi (KHY) 115/22kV Substation
![Page 5: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/5.jpg)
Kao Yoi (KHY) 115/22kV Substation
Provincial Electricity Authority (South Area 1) Phetchaburi
Harmonic increase on Off Peak (10 PM-9 AM)
Introduction
![Page 6: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/6.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
AMR (Automatic Meter Reading) Via PEA Web Application
Load Profile
Introduction
![Page 7: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/7.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
Trend of THDv
Load Profile
Introduction
![Page 8: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/8.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
Induction Furnace
22/1.65kV 500 Hz 12 pulse
TR
22/ 0.95kV6300kVA
For the 12 Pulse system the input current will have theoretical harmonic components at the following multiples of fundamental frequency: 11, 13, 23, 25, etc.
![Page 9: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/9.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
Induction Furnace
22/1.65kV 500 Hz 12 pulse
Induction Furnace No.1
TR1 22/ 0.95kV 6300kVA
22/1.65kV 500 Hz 12 pulseInduction Furnace No.2
TR2 22/ 0.95kV 6300kVA
22/1.65kV 500 Hz 12 pulse
Induction Furnace No.3
TR3 22/ 0.95kV 6300kVA
Induction Furnaces in a Steel Plant:
![Page 10: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/10.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
Instrument and Evaluate
TP1
115/22kV50MVA
Kao Yoi (KHY) Substation
TP2
115/22kV50MVA
Dranetz BMI PowerVisa@PCC
![Page 11: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/11.jpg)
Harmonic Standard In Thailand : PRC - PQG - 01 / 1998 The Harmonic Regulations for The Commercial and Industrial
Provincial Electricity Authority (South Area 1) Phetchaburi
Instrument and Evaluate
Voltage at PCC.(kV)
Total harmonic distortion (%)
Total harmonic distortion in each Order (THDV%)
Odd order Even order0.4 5 4 2
22 and 24 4 3 1.7533 3 2 169 2.45 1.63 0.82
115 and above 1.5 1 0.5
Voltage at PCC.(kV)
Current distortion limits in each order (Arms)
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
0.4 48 34 22 56 11 40 9 8 7 19 6 16 5 5 5 6 4 6
11 and 12 13 8 6 10 4 8 3 3 3 7 2 6 2 2 2 2 1 1
22, 24 and 33 11 7 5 9 4 6 3 2 2 6 2 5 2 1 1 2 1 1
698.8
5.9
4.3
7.3
3.3
4.9
2.3
1.6
1.6
4.9
1.6
4.3
1.6
1 11.6
1 1
115 and above 5 4 3 4 2 3 1 1 1 3 1 3 1 1 1 1 1 1
![Page 12: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/12.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
Instrument and Evaluate
4 43.96 3.84
0
1
2
3
4
5
A CTota
l Har
mon
ic D
isto
rtio
n (%
)
THDV
PEA Limit
PCC
Results:
%THDv less than 4%
THDi order 11th , 13th , 14th , 15th , 16th , 17th, 18th
are exceed PEA limit
11
7
5
9
4
6
3
2 2
6
2
5
2
1 1
2
1 10.51
1.82
0.48
1.79
0.45
1.94
0.33 0.42 0.33
9.6
0.2
7.7
3.1
4.4
3.44.0
3.0
1.1
0
2
4
6
8
10
12
H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 H13 H14 H15 H16 H17 H18 H19
Curr
ent D
isto
rtio
n Li
mit
(Arm
s)
Harmonic Oder
PEA Limit
PCC
![Page 13: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/13.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
Solution
- Install Tuned Filter or - Detune Filter or- Active Filter
![Page 14: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/14.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
Solution
Install New 115/22kV SubstationInclude detuned filter@22kV Bus
Customer Plane:
![Page 15: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/15.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi
Conclusion
- For decrease of harmonic distortion in a steel plant with induction furnace the customer should install harmonic filter for decrease of harmonic order 11th , 13th , 14th , 15th , 16th , 17th, 18th that are exceed PEA limit
![Page 16: Case study Harmonic Distortion In a Steel Plant with Induction Furnaces 2/6_Case Study Harmonic Dis… · · 2015-05-26Case study Harmonic Distortion In a Steel Plant with Induction](https://reader035.vdocuments.us/reader035/viewer/2022062600/5aed954f7f8b9a6625902553/html5/thumbnails/16.jpg)
Provincial Electricity Authority (South Area 1) Phetchaburi