case project - control system in labview - telemark...
TRANSCRIPT
Telemark University College Department of Electrical Engineering, Information Technology and Cybernetics
Faculty of Technology, Postboks 203, Kjølnes ring 56, N-3901 Porsgrunn, Norway. Tel: +47 35 57 50 00 Fax: +47 35 57 54 01
Case Project
Control System in LabVIEW HANS-‐PETTER HALVORSEN, 2013.08.16
ii
Table of Contents Table of Contents .................................................................................................................................... ii
1 Modeling ........................................................................................................................................... 3
1.1 Air Heater .................................................................................................................................. 3
1.2 Level Tank .................................................................................................................................. 4
2 Simulation ......................................................................................................................................... 6
2.1 DAQ Device ............................................................................................................................... 6
2.1.1 DAQ Assistant .................................................................................................................... 6
2.2 Model Implementation ............................................................................................................. 8
2.2.1 Model Adjustment ............................................................................................................. 9
3 Control System ............................................................................................................................... 11
3.1 Discrete Low-‐pass Filter .......................................................................................................... 11
3.2 Discrete PI Controller .............................................................................................................. 12
3.3 Control System ........................................................................................................................ 12
3.4 Controller Tuning .................................................................................................................... 13
3
1 Modeling
1.1 Air Heater
Below we see the Air Heater.
Heater: The air is heated by an electrical heater. The supplied power is controlled by an external voltage signal in the range 𝟎 − 𝟓 𝑽 (min power, max power).
Temperature sensors: Two Pt100 temperature elements are available (some of the Air Heaters have only one). You can use Temperature sensor 1 in this assignment. The range is 𝟏 − 𝟓 𝑽, and this voltage range corresponds to the temperature range 𝟐𝟎 − 𝟓𝟎℃ (with a linear relation).
A simple mathematical model of the system could be:
𝑇!"# =1𝜃!
−𝑇!"# + 𝐾!𝑢 𝑡 − 𝜃! + 𝑇!"#
Where:
• 𝑇!"# ℃ is the air temperature at the tube outlet • 𝑢 [𝑉] is the control signal to the heater • 𝜃! [𝑠] is the time-‐constant • 𝐾! [𝑑𝑒𝑔 𝐶 / 𝑉] is the heater gain • 𝜃! [𝑠] is the time-‐delay representing air transportation and sluggishness in the heater
4 Modeling
Control System in LabVIEW
• 𝑇!"# ℃ is the environmental (room) temperature. It is the temperature in the outlet air of the air tube when the control signal to the heater has been set to zero for relatively long time (some minutes)
The following values can be used:
𝜃! = 22 𝑠𝑒𝑐
𝜃! = 0 𝑠𝑒𝑐
𝐾! = 3.5 ℃𝑉
𝑇!"# = 21.5 ℃
Note! All of the devices are slightly different. It is necessary to run som experiments in order to find the optimal values for your device. The procedure is described later.
1.2 Level Tank
The LM-‐900 Level Tank equipment will be used in this Lab Work:
Control Signal: A pump fills the tank with water from the reservoir. The pump speed can be controlled by a voltage signal in the range 0 − 5𝑉. The pump can be controlled by an external voltage signal at the “FROM PC” connector.
Measurement Signal: The measurement is a voltage signal in the range 0 − 5𝑉 available at the “TO PC” connector. This voltage range corresponds to a level range of 0 − 20 𝑐𝑚, approximately (unless you need a more accurate relation, you can assume this range in your applications).
5 Modeling
Control System in LabVIEW
Scaling: You need to scale the signal 0 − 5𝑉 to 0 − 20𝑐𝑚. The following linear relationship applies:
𝑦 = 𝑎𝑥 + 𝑏
A very simple (linear) model of the water tank is as follows:
𝐴!ℎ = 𝐾!𝑢−𝐹!"#
or
ℎ =1𝐴!
𝐾!𝑢−𝐹!"#
Where:
• ℎ [𝑐𝑚] is the level in the water tank • 𝑢 [𝑉] is the pump control signal to the pump • 𝐴! [𝑐𝑚2] is the cross-‐sectional area in the tank • 𝐾! [(𝑐𝑚3/𝑠)/𝑉] is the pump gain • 𝐹!"# [𝑐𝑚3/𝑠] is the outflow through the valve (this outflow can be modeled more
accurately taking into account the valve characteristic expressing the relation between pressure drop across the valve and the flow through the valve).
The following values can be used:
𝐾! = 15(𝑐𝑚!/𝑠)/𝑉
𝐴! = 80𝑐𝑚!
𝐹!"# = 10𝑐𝑚!/𝑠
𝑇! = 0.1𝑠
Note! All of the devices are slightly different. It is necessary to run som experiments in order to find the optimal values for your device. The procedure is described later.
6
2 Simulation
2.1 DAQ Device
We we will use a USB-‐6008 DAQ unit in order to read data from the process (𝑦) to the PC, and write data (𝑢) from the PC to the process.
2.1.1 DAQ Assistant
In order to communicate with the USB-‐6008 DAQ device within LabVIEW, we can use the DAQ Assistant. Note! The NI-‐DAQmx software needs to be installed.
The DAQ Assistant is located from the Functions palette: “Measurement I/O → NI-‐DAQmx → DAQ Assist”.
Analog In Example:
Below we see a typical example in LabVIEW where we read from the “Analog Input” port of the DAQ device:
Analog Out Example:
Below we see a typical example in LabVIEW where we read from the “Analog Output” port of the DAQ device:
7 Simulation
Control System in LabVIEW
Loopback Test (Analog Out connected to Analog In):
Front Panel Example:
8 Simulation
Control System in LabVIEW
2.2 Model Implementation
The model (Level Tank or Air Heater) should be implemented using the blocks (Integrator, Transport Delay, Summation, Multiplication, etc.) from the Simulation palette in LabVIEW:
Air Heater: The Air Heater model can be implemented as a Simulation Sub System:
Level Tank: The Level Tank model can be implemented as a Simulation Sub System:
9 Simulation
Control System in LabVIEW
2.2.1 Model Adjustment
The model parameters should be adjusted by some simple experiments where you run the simulator in parallel with the real process. Use the “Trial and Error” method in order to find the unknown parameters.
The LabVIEW program for adjusting the parameters could be like this:
This means that we plot the output of the model and the process and compare them after a change in the control signal. If they are “almost” identical, we have found good model parameters, if not, we need to adjust the modelparameters and try again.
LabVIEW Example:
11
3 Control System This is a typical block diagram of the system:
Since LabVIEW is a graphical development environment, this can easly be implemented in LabVIEW.
3.1 Discrete Low-pass Filter
Transfer function for a first-‐order low-‐pass filter may be written:
𝐻 𝑠 =1
𝑇!𝑠 + 1
Where 𝑇! is the time-‐constant of the filter.
Create a discrete low-‐pass filter in LabVIEW using the Formula Node in LabVIEW. Create a SubVI of the code. The user needs to be able to set the time constant of the filter 𝑇! from the outside, i.e., it should be an input to the SubVI. The simulation Time-‐step 𝑇! needs also to be set from the outside.
Use the Euler Backward method:
𝑥 =𝑥! − 𝑥!!!
𝑇!
Perform simulations to make sure the filter works as expected. Explain/Show how you do this. Why do we use a low-‐pass filter?
12 Control System
Control System in LabVIEW
3.2 Discrete PI Controller
A continuous time PI controller may be written:
𝑢 𝑡 = 𝑢! + 𝐾!𝑒 𝑡 +𝐾!𝑇!
𝑒𝑑𝜏!
!
Where u is the controller output and e is the control error:
𝑒 𝑡 = 𝑟 𝑡 − 𝑦(𝑡)
Create a discrete PI controller in LabVIEW using the Formula Node. Create a SubVI of the code.
-‐ Typical Inputs to the controller: 𝐾!, 𝑇! , 𝑦, 𝑟
-‐ Typical Outputs from the controller: 𝑢
Use the Euler Backward method:
𝑥 =𝑥! − 𝑥!!!
𝑇!
Make sure the PI controller works as expected.
3.3 Control System
Implement a control system using the discrete PI controller created. Use the mathematical model of the system in the simulations.
You should also test our control system on the real process (Level Tank or Air Heater).
Note! You need to install the NI-‐DAQ-‐mx driver that makes it possible to use the USB-‐6008 device together with LabVIEW.
Set up hardware and software according to the sketch below:
13 Control System
Control System in LabVIEW
Make sure to use your low-‐pass measurement filter created in a previous task.
3.4 Controller Tuning
Use the, e.g., Skogestad’s method in order to find proper PI parameters for the system.
Skogestad’s method:
In this task we assume the following process:
𝐻 𝑠 =𝑇!"#(𝑠)𝑢(𝑠)
=𝐾
𝑇𝑠 + 1𝑒!!"
The Skogestad’s method assumes you apply a step on the input (𝑢) and then observe the response and the output (𝑦), as shown below:
14 Control System
Control System in LabVIEW
If we have a model of the system (which we have in our case), we can use the following Skogestad’s formulas for finding the PI(D) parameters directly:
Tip! In this task we can e.g., set 𝑇! = 10 𝑠 and 𝑐 = 1.5 (or try with other values if you get poor PI parameters).