case histories john w. martyny, ph.d., cih tri-county health department
TRANSCRIPT
Building Characteristics Community college occupied in
October, 1986. 1 Building with 3 floors and about
1,000,000 sq.ft. Has had IAQ complaints since it was
occupied. Odors, stuffiness, upper respiratory complaints. Complaints have increased as of late.
Complaints are primarily from staff. Building has the following areas:
Registration area Teaching areas Automotive and diesel repair areas Veterinary Technician area Print shop area Chemistry laboratories Farm equipment repair area
Building layout is a 3 story main building with three 1 story wings.
Ventilation System Evaluation
Visual Inspection Cleanliness
Filter Replacement
Moisture
Damper Functioning
Ventilation Evaluation Results
Generally good condition Clean Good filters (return and outside) Fiberglass lining in good condition
Moisture Problems Moisture in drain pans Biocide use
Carbon Dioxide Sampling
Actually a tracer gas method. Acceptable levels depend upon:
population density Outside levels Contamination (CO)
Generally accepted levels 1000 ppm 800 ppm
Carbon Dioxide Results
Ranged from 340 ppm to 637 ppm in all areas tested.
Outside levels were approximately 300 ppm.
Complaints Distributed to all staff in the staff room.
Take home questionnaire 90% return rate
Concerns: Congestion and stuffiness - 37% Too hot or cold - 35% Dryness - 44% Eye irritation - 30% Headache - 24%
Comparison Complaint Levels
NIOSH HEDGE School
Headache 25% 44% 24%
Congest. 22% 45% 37%
Eye Irrit. 33% 42% 30%
Fatigue 26% 46% 28%
Tests Conducted at Building
Tracer Gas Testing Bioaerosol Testing Particulate Sampling Comfort Factors
Bioaerosol Results
Outside Levels 1200 - 1500 CFU/m3 Mostly Cladosporium
Inside Levels ND - 59 CFU/m3 Mostly Cladosporium Some Penicillium but low.
Particulate Levels Standards
None
Measurements Outside vs. inside Particle size - PM 2.5 and PM 10
Meaning of elevated levels Poor filtration Bioaerosols Particulate Source
Particulate Results
Highest levels in Rm 159 PM 2.5 = 9ug/m3 PM 10 = 14 ug/m3
Other Areas PM 2.5 = 0.5 - 3 ug/m3 PM 10 = 1 - 10 ug/m3
Meaning Activity and Processes
Temperature and Humidity Results
Temperatures ranged from a mean of 70 degrees to a mean of 76 degrees.
Highest levels ranged from 70 to 78 Highest levels in 214 and 159 Chiller operation a problem
Humidity levels ranged from 47% to 79%. High humidity can cause microbial problems and
comfort problems.
Tracer Gas Sampling
Uses of Tracer gas Decay Studies Migration Studies
Methodology Sulfur hexafluoride Injection Results
Tracer Gas Results
Rm. 159 air exchange rates. 0.76 to 1.1 ACH Lowest in morning
Other Areas 1.27 to 1.9 ACH
Standards ASHRAE - 15 - 20 cfm/person Actual unknown
Conclusions
Need to clean air handlers, improve drainage, and take out biocides.
Improve outside air in some areas. Stop migration of odors. Control temperature and humidity.
Case History #2The Government Building.
Broken water lines due to freezing of Air handlers.
Extensive water damage Hot temperatures Moldy odors Visible mold
Question: Sample or Not Sample???
Case #2 Airborne Sampling Results
Room TotalFungi
Penicil.Sp.
Clad.Sp.
Outside 495 18 272B 147 36 12 18A 107 77 41 12B 122 89 24 30C 113 2915 2037 7D 107 259 41 42
Case #2: Bulk Sample Results
Bulk sample from one room contained
Stachybotrys chartarum.
Bulk samples indicated Penicillium and
Aspergillus sp. with fungal hyphae.
Lesson Learned
Sampling may or may not correctly answer the question.
Sampling may not support visual observations.
The more samples the better. The variability between samples may be
great.
Case #3: Same Place, Different Time
What were the results of the remediation?
All water damage was repaired. All water damaged material was removed. Ventilation system was repaired and observed. People were moved out of the facility.
Should sampling be conducted?
Case #3Airborne Sampling Results
Location Tot.Fungi
Aspergil.Sp.
Cladosp.Sp.
Outside 251 3 150
A127 356 238 53
A113 131 78 36
A117 148 0 106
A106 18 12 6
Case #4Institution
Prison where workers had hypersensitivity pneumonitis.
Workers worked in several areas. Old barn with sever pigeon use. Old slaughter house Potato storage area
Sample or not sample?
Case #4Airborne Sampling Results
Location Tot.Fungi
Penicil.Sp.
Aspergil.Sp.
Outside 813 80 0
Old Barn 1095 100 500
SlaughterHouse
85,760 85,760 0