calibration of single phase energy meter
DESCRIPTION
calibration of energy meter by direct, phantom loading, phase shifting transformerTRANSCRIPT
CALIBRATION OF SINGLE PHASE ENERGY METER BY DIRECT LOADING METHOD
AIM:
To calibrate the given energy meter by direct loading method
APPARATUS:
S.No Equipment Range Type Quantity
1 Variac,single phase 10 A AC
2 Voltmeter 300 V AC
3 Ammeter 0-10A AC
4 Rheostat AC
5 Wattmeter LPF AC
6 Single phase energy meter 10A AC
THEORY:
The calibration of energy meter may become inaccurate during its vigorous use due
to various reasons. It is necessary to calibrate the meter to determine the amount of error i.e.
its reading so that same meter can be used for correct measurement of energy.
In this method precision grade indicating instruments are used as reference standard.
These indicating instruments are connected in the circuit of meter under test. The current
and voltages are held constant during the test. The numbers of revolutions made by the test
are recorded. The time taken is also measured.
Energy recorded by meter under test = RX / KX kWh.
Energy computed from the readings of the indicating instrument = kW × t
Where RX = number of revolutions made by disc of meter under test.
KX = number of revolutions per kWh for meter under test,
kW = power in kilowatt as computed from readings f indicating
instruments t = time in hours.
Percentage Error = (RX / KX - kW × t)
------------------------- X 100
kW × t
Before conducting any of these tests on a watt hour meter its potential circuit must
be connected to the supply for one hour in order to enable the self heating of the potential
coil to stabilize.
CIRCUIT DIAGRAM:
figure:1
PROECEDURE:
1. Keep the Autotransformer at zero position.
2. Make connections as per the Circuit diagram shown below.
3. Switch on the 230 VAC, 50 Hz. power supply.
4. Increase the input voltage gradually by rotating the Auto transformer in clockwise di-
rection.
5. Adjust the load rheostat so that sufficient current flows in the circuit. Please
note that the current should be less then 4A.
6. Note down the Voltmeter, Ammeter, Wattmeter and power factor meter read-
ings for different Voltages as per the tabular column.
7. Note down the time (by using stop watch) for rotating the disc of the Energy
Meter for 10 times. Find out the percentage error by using above equations.
TABULAR COLUMN
S. No.
Voltage
(V)
Current
(I)
R = No of
revolutions
of the disc
Time
(t) in
hours
Energy meter
reading in KWh=
No. revolution
(R)/meter constant
(K)
Wattmeter
Reading in
kW × t
%
Error
RESULT:
CALIBRATION OF ENERGY METER BY PHANTOM LOADING
AIM:
To calibrate a given single phase energy meter by phantom loading.
APPARATUS:
S.NO Equipment Range Type Quantity
1
Variac, single
phase
2 A, 0-
230V
2 Voltmeter 0-300V AC
3 Ammeter 0-10A AC
4 Rheostat
5 Wattmeter
6
Single Phase
Energy Meter 300V, 10A
THEORY:
The calibration of energy meter may become inaccurate during its vigorous use
due to various reasons. It is necessary to calibrate the meter to determine the amount of
error i.e. its reading so that same meter can be used for correct measurement of energy.
In this method precision grade indicating instruments are used as reference
standard. These indicating instruments are connected in the circuit of meter under test.
The current and voltages are held constant during the test. The numbers of revolutions
made by the test are recorded. The time taken is also measured.
Energy recorded by meter under test = RX / KX kWh.
Energy computed from the readings of the indicating instrument = kW × t
Where RX = number of revolutions made by disc of meter under test.
KX = number of revolutions per kWh for meter under test,
kW = power in kilowatt as computed from readings f indicating instruments t =
time in hours.
Percentage Error =
(RX / KX - kW × t)
------------------------- X 100
kW × t
Before conducting any of these tests on a watt hour meter its potential circuit
must be connected to the supply for one hour in order to enable the self heating of the
potential coil to stabilize.
CIRCUIT DIAGRAM:
PROCEDURE
1. Keep the Autotransformer at zero position.
2. Make connections as per the Circuit diagram shown below.
3. Switch on the 230 VAC, 50 Hz. power supply.
4. Increase the input voltage gradually by rotating the Auto transformer
in clockwise direction.
5. Adjust the load rheostat so that sufficient current flows in the circuit. Please
note that the current should be less then 4A.
6. Note down the Voltmeter, Ammeter, Wattmeter and power factor meter
readings for different voltages as per the tabular column.
7. Note down the time (by using stop watch) for rotating the disc of the Energy
Meter for 10 times.
8. Find out the percentage error by using above equations.
TABULAR COLUMN:
S. No. Voltage
(V)
Current
(I)
R = No of
revolutions
of the disc
Time (t) in hours Energy meter reading
in KWh= No. revolu-
tion (R)/meter con-
stant (K)
RESULT
Expt No: CALIBRATION OF SINGLE PHASE ENERGY METERDate: USING PHASE SHIFTING TRANSFORMER
AIMTo calibrate the given single phase energy meter at unity and other power factors and to
draw the calibration curve..
APPARATUS REQUIRED
S.No Apparatus Name Type Range Qty
1 Single phase energy meter Induction type 1
2 Standard wattmeter 300 V; 10A, UPF
1
3 Voltmeter MI (0-300) V 1
4 Ammeter MI (0-10) A 1
5 Lamp Load 230 V, 5 Kw 1
6 Phase Shifting transformer 1
7.Single phase auto
transformer 230/(0-270 V 1
8 Stop watch
9 Connecting wires
FORMULAE
Energy meter specification rev/kwh=
True energy (Pt) =
Measured energy =
(Power Time ) / 36001000
n , n Number of revolutions750
% Error = Measured True 100
True
THEORY
The energy meter is an integrated type of instrument where the speed of rotation of the aluminum disc is directly proportional to power consumed and the number of revolution per minute is proportional to the energy consumed by the load. The ratings associated with the energy meter are
1. Voltage rating2. Current rating3. Frequency rating4. Meter constants
The driving system of the meter provides the rotational torque for the moving system, which in turn activates the energy registration system for reading purposes. The energy meter is operated on induction principle, in which the eddy current induced in the aluminum disc interacts with the main field and creates the driving torque.
This system employs phantom loading. Here, the phase shifting transformer to supply the voltage of varying power factor to the potential coil of energy meter. The system phase supply is used to supply current of energy required value to the current coil of energy meter. Thus energy meter is tested under various power factor loads without applying any actual load. This is called phantom loading.
PROCEDURE
1. Give the connections as per the circuit diagram.2. Switch on the three phase supply through phase shifting transformer. Also switch on the
single phase supply through autotransformer. The autotransformer should be kept in mini-mum position before switching on.
3. Set the 5A current in ammeter with the help of auto transformer.4. Now note down the voltage, current and power from the respective meters. Also note the
time required for the disc to rotate hundred times.5. Repeat step 3 for various power factors The power factor is set with the help of phase
shifting transformer.6. Tabulate the readings and do the necessary calculations.
Circuit Diagram
Sl No
Wattmeter PowerTime for n rev Seconds
Power Factor
Measured Energy KwH
True Energy KwH
%Error
Observed Reading (Watts)
Actual Reading (Watts)
Model Calculation
RESULT:
CALIBRATION OF SINGLE PHASE DIGITAL ENERGY METER BY DIRECT LOADING METHOD
AIM:
To calibrate the given energy meter by direct loading method
APPARATUS:
S.No Equipment Range Type Quantity
1 Variac,single phase 10 A AC
2 Voltmeter 300 V AC
3 Ammeter 0-10A AC
4 Rheostat AC
5 Wattmeter LPF AC
6 Single phase energy meter 10A AC
THEORY:
The calibration of energy meter may become inaccurate during its vigorous use
due to various reasons. It is necessary to calibrate the meter to determine the amount of
error i.e. its reading so that same meter can be used for correct measurement of energy.
In this method precision grade indicating instruments are used as reference
standard. These indicating instruments are connected in the circuit of meter under test.
The current and voltages are held constant during the test. The numbers of revolutions
made by the test are recorded. The time taken is also measured.
Energy recorded by meter under test = RX / KX kWh.
Energy computed from the readings of the indicating instrument = kW × t
Where RX = number of impulse of meter under test.
KX number of revolutions per kWh for meter under
kW =
power
kilowatt as
computed
from
readings f
indicating
instrument
s t = time
in
Percentage Error = (RX / KX - kW × t)
------------------------- X 100
kW × t
Before conducting any of these tests on a watt hour meter its potential circuit
must be connected to the supply for one hour in order to enable the self heating of the
potential coil to stabilize.
CIRCUIT DIAGRAM:
PROECEDURE:
1. Keep the Autotransformer at zero position.
2. Make connections as per the Circuit diagram shown below.
3. Switch on the 230 VAC, 50 Hz. power supply.
4. Increase the input voltage gradually by rotating the Auto transformer in clockwise
direction.
5. Adjust the load rheostat so that sufficient current flows in the circuit.
P
l
e
a
s
e
n
o
t
e
t
h
a
t
t
h
e
c
u
r
r
e
n
t
s
h
o
u
l
d be less then 4A.
6. Note down the Voltmeter, Ammeter, Wattmeter and power factor meter
readings for different Voltages as per the tabular column.
7. Note down the time (by using stop watch) for rotating the disc of the En-
ergy Meter for 10 times. Find out the percentage error by using above
equations.
TABULAR COLUMN
S. No.
Voltage
(V)
Current
(I)
R = No of
revolutions
of the disc
Time
(t) in
hours
Energy meter
reading in KWh=
No. revolution
(R)/meter constant
(K)
Wattmeter
Reading in
kW × t
%
Error
RESULT:
MEASUREMENT OF RESISTANCE USING WHEATSTONE BRIDGE
AIMTo measure the given medium resistance using Wheatstone bridge.
Apparatus Required
Sl.No. Apparatus Range Quantity
1 Wheatstone bridge kit -- 1
2 Unknown resistance -- 1
3 Galvanometer -- 1
4 Patch card -- 6
Theory
It is used for the measurement of medium resistances. Very high degrees of accuracy can
be achieved with the Wheatstone bridge. It has four resistive arms, consisting of resistances R1,
R2, R3 and R4 together with a battery source and a null detector usually a galvanometer or other
sensitive current meter. The current through the galvanometer depends on the potential
difference between points C and D. The bridge is said to be balanced when there is no current
through the galvanometer or when the potential difference across the galvanometer is zero.
For bridge balance we can write,
I1 R1 = I2 R2 (1)
For galvanometer current to be zero, the following conditions also exist:
Procedure
The unknown resistance is connected to the kit. Ratio arm is set to some value.
By adjusting the resistance R1 the galvanometer is made to indicate null position or
zero, indicating balanced condition.
The values of resistance are noted using multimeter.
The unknown resistance is calculated from these values.
WHEASTONE BRIDGE METHOD
Tabulation
Sr.No. Value marked R2 Rm Unknown resistance Rx
Unit
1 1000 1000 1000 1000
2
3
4
MODEL CALCULATION
RESULT