calibration alpha-a3 elster

16
MVI_9854.AVI a las 16:08 horas 2 pulses = 1 lapso "ON" y 1 lapso "OFF" = 1 blink Modelo: FM35A Kh 1.2; P/R 24 Watt/Pulse: 0.05 C.T. V.T. 100 A 10000 V 5 A 100 V 20 100 Metering Factor 2000 60 seg 60 minutos Power = (P/s x 3600) x Factor medidor x CTR x CTV/1000 = (P/s Para medidor (FM35A) (FM5A) (FM9A) (Luz del Sur -

Upload: rockydark

Post on 11-Dec-2015

213 views

Category:

Documents


0 download

DESCRIPTION

Calibration of Alpha meterelectronic meterA1RL+

TRANSCRIPT

Page 1: Calibration Alpha-A3 Elster

MVI_9854.AVI a las 16:08 horas

2 pulses = 1 lapso "ON" y 1 lapso "OFF" = 1 blink

0123

45

678

910

111213

1415

Modelo: FM35A 16Kh 1.2; P/R 24 17

Watt/Pulse: 0.0518

C.T. V.T. 19

100 A 10000 V 20

5 A 100 V 21

20 100 22Metering Factor

2000 2324

60 seg kW

60 minutos

Power = (P/s x 3600) x Factor medidor x CTR x CTV/1000 = (P/s x 3600) x 0.05 x (C31/C32)*(E31/E32)/1000 = kW = Para medidor (FM35A) (FM5A) (FM9A) (Luz del Sur - Edelnor) =

# Active Blinks

Page 2: Calibration Alpha-A3 Elster

Para medidor FM 10A (Generación C.T.)=2 pulses = 1 lapso "ON" y 1 lapso "OFF" = 1 blink

1 26 12

12 24

V V A A PFHora 400 400 400 400 40016:08 101.9 101.7 3.810 3.230 0.550

0.525seg seg

1 lapso de activa 28.77 29.87 1.10Diferencia entre lectura y parpadeos instantáneo

1 lapso de reactiva 34.43 35.13 0.70Diferencia entre lectura y parpadeos instantáneo

aparente 55.133 56.099 0.96655.533 56.199 0.666

blinks inicio lapsos 12 blinks blinks final11 23 6 293 blinks

C.T. V.T. Metering Factor100 5 10000 100 2000 5min 30.763 seg

Cada blink de activa tiene 2 pulsos = Uno es 'On' y otro es 'OFF'Inicio (s) Final (s) tiempo pulsos on y off pulsos/seg pulsos/hr

0.067 330.763 330.696 586 1.7720 6379.27blinks desde 0

2937 40 1 488

Cada blink de reactiva tiene 2 pulsos = Uno es 'On' y otro es 'OFF'Segundos Segundos tiempo pulsos on y off pulsos/seg pulsos/hr

0 330.163 330.163 976 2.9561 10642.02blinks desde 0

488

12 blinks forman un parpadeo central

blinks ("ON" & "OFF") = pulses (1 "ON" y 1 OFF")

blinks ("ON" or "OFF") = 0.5 BlinkCentral = pulses (6 "ON" y 6 OFF")

blinks ("ON" & "OFF") =1 BlinkCentral= pulses (12 "ON" y 12 OFF")

Page 3: Calibration Alpha-A3 Elster

METER DATA (FROM VIDEO)Meter: FM(35A); Kh 1.2; P/R 24; Meter Factor = 0.05 Watts per pulse (See Meter's Manual)

# Active Pulses lap (seconds) # Reactive Pulses

0 0.0670 0.0000 0 0.4670800.00 2 0.9670 0.9000 2 1.1000771.70 4 1.9000 0.9330 4 1.7670771.70 6 2.8330 0.9330 6 2.4000

8 3.0670696.32 8 3.8670 1.0340 10 3.7000800.00 10 4.7670 0.9000 12 4.3670

14 5.0330800.00 12 5.6670 0.9000 16 5.6670771.70 14 6.6000 0.9330 18 6.3330771.70 16 7.5330 0.9330 20 6.9670

22 7.6330800.00 18 8.4330 0.9000 24 8.2670800.00 20 9.3330 0.9000 26 8.9330

28 9.5670800.00 22 10.2330 0.9000 30 10.2330863.31 24 11.0670 0.8340 32 10.8670864.35 26 11.9000 0.8330 34 11.5000

36 12.1670771.70 28 12.8330 0.9330 38 12.8330830.45 30 13.7000 0.8670 40 13.4670

800.00 32 14.6000 0.9000 42 14.1330

800.00 34 15.5000 0.9000 44 14.8330

46 15.5670

800.00 36 16.4000 0.9000 48 16.3330

831.41 38 17.2660 0.8660 50 17.1330

863.31 40 18.1000 0.8340 52 17.8660

745.34 42 19.0660 0.9660 54 18.6330

674.79 44 20.1330 1.0670 56 19.4000

58 20.2000

654.55 46 21.2330 1.1000 60 20.9660

674.79 48 22.3000 1.0670 62 21.7330781.55 777.22 Sec/2pulses 0.9264 Sec/2pulses

Pulses/sec = 2.1590 Pulses/sec = 2.1590 Pulses/sec = Pulses per hour = Pulses/sec x 3600 7772.23 pulses/60min

Power = (P/s x 3600) x Factor medidor x CTR x CTV/1000 = (P/s x 3600) x 0.05 x (C31/C32)*(E31/E32)/1000 = kW = 777.223 kW0.050 1943.06 pulses/15min

kW each ON-OFF

Seconds of video

Seconds of video

<---- P/s ---->

Page 4: Calibration Alpha-A3 Elster

0.075 1943.00 complete pulses/15min194.3058 Total energy in 15 min

194.3000 Registered Energy (Meter)

0.0058 kWh without registration reduces

777.223 kW, Power absorbed-0.003% 777.200 kW, Power regist -0.035%

0.595 PF

64.7712 =Factor directo = kW/blink

400 400 400 Factor de Medición0.3242 0.5117 0.6172 Lecturas

kW kVAR kVA129.7 204.7 246.9 Lectura x Factor

654.55 cálculo de potencia con blinks (parpadeos) en el medidor404.7% Las lecturas son instantáneas y no sin medidas de un solo instante.

1028.6 1219.2Diferencia entre lectura y parpadeos instantáneo 402.5% 393.8%

745.34 1081.1 1313.1 Potencia aparente, contando el lapso en activa y reactiva 0.537 431.9% por separado

166 kVAR faltantes, Banco condensadores (instantáneo)

5min 30.763 seg1.5948 2.6605 3.1019 5min30.763seg - 0.067seg

kW kVAR kVA es igual a 330.696seg637.9 1064.2 1240.8 promedio en 330.696 seg

PF 0.514872.8 kVAR banco condensadores

kVAR1064.20

pulses (1 "ON" y 1 OFF")

pulses (6 "ON" y 6 OFF")

pulses (12 "ON" y 12 OFF")

blinks/minuto

Page 5: Calibration Alpha-A3 Elster

METER DATA (FROM VIDEO)

lap (seconds)

0.0000 00.6330 1137.44 10.6670 1079.46 20.6330 1137.44 30.6670 1079.46 40.6330 1137.44 50.6670 1079.46 60.6660 1081.08 70.6340 1135.65 80.6660 1081.08 90.6340 1135.65 100.6660 1081.08 110.6340 1135.65 120.6660 1081.08 130.6340 1135.65 140.6660 1081.08 150.6340 1135.65 160.6330 1137.44 170.6670 1079.46 180.6660 1081.08 190.6340 1135.65 20

0.6660 1081.08 210.7000 1028.57 22

0.7340 980.93 230.7660 939.95 24

0.8000 900.00 25

0.7330 982.26 26

0.7670 938.72 27

0.7670 938.72 280.8000 900.00 29

0.7660 939.95 300.7670 938.72 310.6860 1056.03 kVAR

2.9155 Pulses/sec = 2.915510495.63 pulses/60min1049.56 kVAR 0.595 P.F. 13/10/2011 16:08 hrs

2623.91 pulses/15min

kVAR each ON-OFF

# Reactive Blinks

Page 6: Calibration Alpha-A3 Elster

2623.00 complete pulses/15min262.3907 Total energy in 15 min

262.3000 Registered Energy (Meter)

0.0907 kWh without registration reduces kW of Max. Demand registered in 15 minutes

1049.563 kVAR, Power absorbed1049.200 kVAR, Power registered as Maximum Demand by ALPHA meter

0.595 PF

87.4612 Factor directo = kVAR/blink

cálculo de potencia con blinks (parpadeos) en el medidorLas lecturas son instantáneas y no sin medidas de un solo instante.

Potencia aparente, contando el lapso en activa y reactiva

kVAR faltantes, Banco condensadores (instantáneo)

5min30.763seg - 0.067seges igual a 330.696seg

blinks/minuto

Page 7: Calibration Alpha-A3 Elster

ELSTER CALIBRATION

ALPHA METER STATISTICS REPORT

Customer Name: Gen Order # :

Meter:Style:Form: TA: Kh: Metering FactorSerial:

Test Bench used:Manufacturer:Model (Type): Serial Number: Accuracy Class:

Local Sales Office: Av. La Marina 842 - 846 La Perla Callao - PERU Phone:(511) 4575533 Fax: (511) 4575686

Certified by this document: FILE N°:

SET-POINT IN TEST BENCH:Manufacturer

MEASUREMENTS REGISTERED BY THE METER:N° Meter5501308

L = fase R M = fase S R = fase T Temperatura de prueba = 23°C±5°CFL = Full Load, Carga total equivalente a la corriente de prueba TA (2.5 A) PF = Factor de potencia 0.5 inductivo a la corriente de prueba LL = Light Load, Carga ligera equivalente al 10% del TA

CONDICIÓN 1 LFLCONDICIÓN 2 LPFCONDICIÓN 3 MFLCONDICIÓN 4 MPF

Page 8: Calibration Alpha-A3 Elster

CONDICIÓN 5 RFLCONDICIÓN 6 RPFCONDICIÓN 7 FLCONDICIÓN 8 PFCONDICIÓN 9 LL

Para medidor (FM35A) (FM5A) (FM9A) (Luz del Sur - Edelnor) = Para medidor FM 10A (Generación C.T.)=

Page 9: Calibration Alpha-A3 Elster

ELSTER CALIBRATION US$ 150

ALPHA METER STATISTICS REPORT

ELSTER MEDIDORES S.A, PERU Date: 05/01/201510000000XXX-000XXX Mfg Order # : M86XXXX Customer Order # :

A3 ALPHAZA2B0-XXXXXX Type: A1RL+ 35A Class: CL202.5 Volts: 2201.2 PR: 240.05 Watts per pulseXX XXX XXX

WECO

0.04

ELSTER MEDIDORES S.AAv. La Marina 842 - 846 La Perla Callao - PERU Phone:(511) 4575533 Fax: (511) 4575686

Certified by this document:

SET-POINT IN TEST BENCH:Model (Type) Serial LFL LPF

100 100.000

MEASUREMENTS REGISTERED BY THE METER:BarCode Serial LFL LPF

AADTN303/5501308 04 565 328 100 100.007

FL = Full Load, Carga total equivalente a la corriente de prueba TA (2.5 A) PF = Factor de potencia 0.5 inductivo a la corriente de prueba LL = Light Load, Carga ligera equivalente al 10% del TA

Left Full Load 100.005Left Power Factor 100.007Medium Full Load 100.005Medium Power Factor 100.005

Page 10: Calibration Alpha-A3 Elster

Right Full Load 100.005Right Power Factor 100.007

Full Load 100.009Power Factor 100.004Light Load 100.007

0.0500.075

Page 11: Calibration Alpha-A3 Elster

Customer Order # :

MFL MPF RFL RPF FL I PF I LL100.000 100.000 100.000 100.000 100.000 100.000 100.000

MFL MPF RFL RPF FL PF LL100.005 100.005 100.005 100.007 100.009 100.004 100.007

Left Full Load (100% Carga Izquierda) = 2.5A y 1.0 PF

Medium Full Load (100% Carga Medio) = 2.5A y 1.0 PFLeft Power Factor (100% Carga Izquierda) = 2.5A y 0.5 PF = Power Factor = Factor de Potencia

Medium Power Factor (100% Carga Medio) = 2.5A y 0.5 PF = Power Factor = Factor de Potencia

Page 12: Calibration Alpha-A3 Elster

Right Full Load (100% Carga Derecha) = 2.5A y 1.0 PF

Combined Full Load (100% Carga en 3 fases) = 2.5A y 1.0 PFRight Power Factor (100% Carga Derecha) = 2.5A y 0.5 PF = Power Factor = Factor de Potencia

Combined Power Factor (100% Carga en 3 fases) = 2.5A y 0.5 PF = Power Factor = Factor de PotenciaCombined Light Load (10% Carga en 3 fases) = 0.25A y 1.0 PF

Page 13: Calibration Alpha-A3 Elster

= Power Factor = Factor de Potencia

= Power Factor = Factor de Potencia

Page 14: Calibration Alpha-A3 Elster

= Power Factor = Factor de Potencia

= Power Factor = Factor de Potencia