calculation wind

Upload: wan-mohd-taufiq

Post on 05-Apr-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 Calculation Wind

    1/17

    Background

    The air flow equation is the building block of air infiltration and ventilation calculations. Every

    opening in the building fabric must be accurately represented by such an equation. Essentially there

    are two types of opening. The first are the random gaps and cracks that appear at construction joints

    or through porous material. These are ill defined and their geometry is rarely directly measurable.The second are essentially 'purpose provided' openings such as vents and windows. These are usually

    clearly defined in terms of geometry, location and flow characteristics. Openings in the former

    category require either measurement or implied knowledge about their characteristics. The

    necessary flow characteristics of the second type of opening can be inferred from the geometry of

    the opening and, therefore are easier to determine. The mathematical representation of these two

    types of opening is described in this tutorial. It is also shown that, by algebraic manipulation, both

    types of opening can be represented by an equation of identical structure. This considerable eases

    the calculation of total air flow into and out of a space.

    Volume vs. Mass Flow

    Flow rate can be expressed either in terms of 'volume' flow (e.g. m3/s, l/s, cfm) or 'mass' flow (e.g.

    kg/s). Most often fan capacity is expressed as a volume flow ,whereas calculations involving heat

    loss, for example, require that flow be expressed as a mass flow. In fundamental terms, it is more

    accurate to express flow rate as a mass flow. This is because, for a given mass of air, its volume varies

    with temperature. The Law of Continuity demands that the mass flow rate of air entering a building

    must match the mass leaving the building. Thus, in theory, a balance in mass flow does not

    necessarily mean that there is a balance in volume flow. Notwithstanding this situation, our air

    infiltration tutorials will be based on volume flow analysis. This is because for 'mild' climate

    temperature differences, where temperature differences between inside and outside peak at no

    more than 25 - 30C for a few hours at most in the year, any error will be marginal and because the

    'iterative' approach that will be introduced to calculate infiltration and ventilation rate is much more

    stable for volume flow. Any error could also be minimised by selecting an air density (to convert to

    mass flow) that is midway between the outside and inside air temperature. However, switching to

    mass flow is very straightforward (as presented at the end of this tutorial). Also 'multi-zone' models

    such as Contam96 are structured in mass flow and can be downloaded and used for precision

    analyses if needed.

    Cracks and Gaps

    Air flow through general cracks and gaps in the building fabric is a function the size and structure of

    the opening and the pressure difference acting across it. The simplest representation of a crack is

    presented in the equation below.

  • 7/31/2019 Calculation Wind

    2/17

    This equation gives the volume flow rate (e.g. m3/s).

    'C' is defined as the 'Flow Coefficient'. This is related to the size and structure of the opening. Typical

    flow coefficients are given in theAIVC Numerical Data Guide.

    'n' is the flow exponent and indicates the degree of turbulence. An 'n' value of 0.5 represents fullyturbulent flow and '1.0' represents fully laminar flow. The typical 'n' value for whole buildings is 0.66.

    'Orifice' Openings

    Clearly defined openings such as vents or windows are frequently represented as 'flat plate orifices'

    in which the volume flow is represented in the equation:

    http://www.aivc.org/http://www.aivc.org/http://www.aivc.org/http://www.aivc.org/
  • 7/31/2019 Calculation Wind

    3/17

    Thus flow can be determined directly from a geometric analysis of the opening. In the absence of

    other information, the 'discharge coefficient' is usually based on a value of 0.61. Air flow through an

    orifice is assumed to be turbulent, thus the flow exponent 'n' = 0.5.

    Making an Orifice Flow Equation Look Like a Crack Flow Equation

    For ease of infiltration and ventilation calculations it is important that the above two equations take

    on the same form. This is achieved by making the orifice equation look like a power law crack flow

    equation. To achieve this:

    Exercise: Manipulate the orifice flow equation to achieve the above 'C' and 'n' values.

    Changing to Mass Flow

    Volumetric flow is changed to mass flow by multiplying by the air density. Since density is dependent

    on air temperature, it is not a constant. Therefore, if this approach is used, it needs to be expressed

    as a function of temperature. This will be covered in a future tutorial.

    Quadratic Formulation of the Air Flow Equation

    Some authorities prefer to express air flow in the form of a quadratic equation of the form:

    This is perceived to be dimensionally correct since the laminar and turbulent components of flow are

    separated. In essence, all the arguments and processes applied to the Power Law approach can be

    applied to the quadratic approach. In fact the single zone model, to be developed in these tutorials,

    will run just as easily in quadratic form. Again, at a later date, an equivalent analysis will beattempted.

  • 7/31/2019 Calculation Wind

    4/17

    The Next Steps

    So far we have established the Power law Equation of flow through an opening as a building block

    towards infiltration and ventilation analysis. We have also shown that the flow characteristics of

    purpose provided opening can be approximated by the geometry of the opening. We now have to:

    Introduce a method to determine the pressure difference across openings;

    Establish a 'flow network' that represents the openings in the building;

    Find 'missing' data (primarily the 'C' and 'n' values of cracks and gaps).

    Develop a mathematical model that enables us to calculate the total flow into and out of the

    building and to calculate the flow rate and flow direction through individual openings.

    Incorporate mechanical ventilation systems.

    Introduce the concept of multi-zone or multi - room networks.

    These steps will provide you with a basic design and ventilation evaluation tool that can be quickly

    established to solve 95% of pre-design and basic design steps. It will also give you the skills to apply

    more complex modelling tools that are available through the internet.

    1. The Wind Pressure Equation

    Wind striking an object induces, on that object, a spatially distributed pressure pattern (Figure

    2.1).

    Figure 2.1. Wind striking a building induces a wind induced pressure distribution.

    The value of the induced pressure at any particular point can be described by the following equation:

  • 7/31/2019 Calculation Wind

    5/17

    Equation 2.1. Wind Pressure Equation.

    A typical pattern of pressure distribution is illustrated for a simple, essentially cubed shaped building,in Figure 2.2 below.

    Figure 2.2. Example Wind Pressure Distribution.

    With respect to atmospheric pressure, wind induces a positive pressure on the upwind face of the

    object and a negative pressure on its sides and in the wake region at the rear of the building. Thewindward roof face may also be at a negative pressure unless the pitch angle exceeds about 30.

    To evaluate the wind-induced pressure, the following data are needed:

    Building dimensions and shape;

    Information about surrounding terrain and obstructions (both upwind and downwind);

    Location (e.g. city, urban, rural);

    Wind speed (and, for improved precision, direction);

    Spatial distribution of wind pressure coefficient.

    Building Dimensions and Shape: The pressure pattern is highly dependent on the shape of the

    building. Elementary and pre-design analysis is only really possible by approximating the plan-shape

  • 7/31/2019 Calculation Wind

    6/17

    of the building by a rectangle or a series of rectangles. Anything more complex may need to be

    analysed on an individual basis in a wind tunnel. computational fluid dynamic (cfd) methods are

    emerging as a potential means of analysing the pressure distribution around buildings but require

    substantial computational effort, especially if several wind speeds and directions are to be analysed.

    Surrounding Terrain and Obstructions: This again influences the pressure distribution considerably.

    The simple approach is to describe the building as being surrounded by buildings of equal height, half

    the height of completely exposed. Again, this is suitable for basic pre-design analysis. The only

    practical alternative is to consider a wind tunnel study in which a scale model of the building and the

    surrounding buildings is incorporated. Similarly this is an area where cfd analysis is emerging and will

    probably, eventually present a practical alternative.

    Location: Apart from influencing the type of surrounding obstructions, location influences the

    climatic driving forces of wind and temperature. Wind strength in an urban location, for example,

    may be considerably lower than that measured at a nearby open-site weather station. Similarly, air

    temperature may be higher in a city environment (heat island effect). A wind correction equation is

    presented below. At present a suitable temperature conversion equation is not presented but it may

    be worth increasing the open-site value, taken from the nearest meteorological station, by a degree

    or so.

    Wind Speed and Direction: Wind induced pressure increases with the square of the wind speed,

    while the upwind and downwind faces of a structure clearly depends on the direction of the wind. A

    key problem is that the strength of the wind varies both with height above ground and the

    intervening terrain, between the nearest meteorological station (usually located in open countryside)

    and the site of the building, as illustrated in Figure 2.3.

    Figure 2.3 .Impact on wind speed of terrain and height above ground level.

    In many cases, within an urban environment, the wind speed at building height can be less than half

    of that measured at a meteorological station. Since this value is squared, failure to make the

    necessary correction to wind speed can lead to a substantial overestimate in the wind induced

  • 7/31/2019 Calculation Wind

    7/17

    pressure. A height and terrain correction approach, described in British Standard 5925 (1991) is

    presented in Table 2.1.

    Spatial Distribution of Wind Pressure Coefficient: The wind coefficient is assumed to be independent

    of wind speed but varies according to location on the building surface, the shape of the building and

    the nature of obstructions surrounding the building. Face averaged values[see Important Notes]for

    simple calculations have been tabulated (e.g. BS5925:1990 [expose buildings], Guide to Energy

    Efficient Ventilation [various degrees of shielding and two plan area aspect ratios]. Bowen and Wiren

    have both published comprehensive, spatially distributed data for various building shapes and

    shielding, based on wind tunnel studies Much of the information published in the Guide to

    Ventilation are derived from these latter sources.

    Table 2.1. Wind speed correction approach as used in BS5925.

    These datasets are suitable for more complex calculations in which faced average values do not

    provide a sufficient level of detail but where the cost of wind tunnel studies is prohibitive. Some

    illustrative, simplistic example data is presented in Figure 2.4.

    http://www.veetech.org.uk/Tutorials/disclaimer_and_important_notes.htmhttp://www.veetech.org.uk/Tutorials/disclaimer_and_important_notes.htmhttp://www.veetech.org.uk/Tutorials/disclaimer_and_important_notes.htmhttp://www.veetech.org.uk/Guide%20to%20Ventilation.htmhttp://www.veetech.org.uk/Guide%20to%20Ventilation.htmhttp://www.veetech.org.uk/Guide%20to%20Ventilation.htmhttp://www.veetech.org.uk/Guide%20to%20Ventilation.htmhttp://www.veetech.org.uk/Guide%20to%20Ventilation.htmhttp://www.veetech.org.uk/Tutorials/disclaimer_and_important_notes.htm
  • 7/31/2019 Calculation Wind

    8/17

    Figure 2.4 . Example faced averaged wind pressure coefficient data. This data was

    based on averaging and amalgamating measurement data of Bowen and Wiren. See The

    Guide to Energy Efficient Ventilationfor more data.

    A checklist summary of, and the approximations needed, for basic calculations is presented in Table

    2.2.

    Table 2.2. Checklist for simple pre design or elementary calculations.

    Parameter Simple DesignAnalysis

    (e.g. methods as described in

    the AIVC Guide to Energy

    Efficient Ventilation)

    Detailed DesignMethods andMeasurements

    (e.g. wind tunnel, cfd, specific

    local environmental

    measurements etc.)Building Shape Represent as a rectangle or

    a series of rectangles.

    Complex: Circular building,

    sections at different heights,

    courtyards etc.

    Surrounding Obstructions Represent as uniformly

    distributed equal to the height

    of the surrounding structure,

    half the height or no

    obstructions

    Complex: Not uniformly

    distributed

    Location Specify as city, urban,

    rural, open country. Use

    simple correction methods for

    wind speed and air

    temperature.

    Specific detail needed (e.g.

    about degree of urbanisation,

    heat islands, street canyons

    etc.).

    Weather Data Taken from nearest weather

    station (should be based on

    hourly records).

    (Wind speed corrected for

    terrain and building height)

    Specific on-site data needed.

    Wind Pressure Coefficient

    Data

    Tabular data for simple

    building shapes or, for

    slightly more complex

    structures, spatially

    distributed data as published

    by Bowen and Wiren.

    Wind tunnel data from

    individual scale model of the

    building and its surroundings.

    2. The Stack Pressure Equation

    Stack flow is driven by the difference between the inside and outdoor air temperature. Assuming

    that the indoor temperature is above the outdoor value, the inside air is less dense and therefore

    lighter than the outside air. As a consequence, the vertical pressure gradient, exerted by the indoor

    air, is steeper, resulting in a pressure imbalance. If the enclosed space is penetrated by openings at

    different heights, air flows through openings at the lowest level and escapes through the upper

    http://www.veetech.org.uk/Guide%20to%20Ventilation.htmhttp://www.veetech.org.uk/Guide%20to%20Ventilation.htmhttp://www.veetech.org.uk/Guide%20to%20Ventilation.htmhttp://www.veetech.org.uk/Guide%20to%20Ventilation.htmhttp://www.veetech.org.uk/Guide%20to%20Ventilation.htm
  • 7/31/2019 Calculation Wind

    9/17

    openings (Figure 2.5). This flow process is reversed if the indoor temperature is less than the outdoor

    temperature. The location at which the indoor and outdoor pressures are in balance is called the

    neutral pressure plane. If an opening were present at this opening, there would be no airflow

    through it.

    Figure 2.5. The principle of stack flow.

    Stack pressure is calculated directly by the application of the Ideal Gas Laws. The temperature

    difference or stack induced pressure at an opening with respect any arbitrary datum height (e.g.surface level) is given by Equation 2.2, where h is the height of the opening above (or below) the

    chosen datum. Usually, the datum is taken as the surface or floor level of the building. With basic

    hand calculations, or very elementary networks, however, there can be an advantage in taking the

    datum as the level of the lowest open. This is because the relative stack pressure at this level will be

    zero, thus saving the effort of a calculation for each opening assigned to this level. In applying the

    stack flow equation, it must be remembered that the temperature is given in Kelvins (degrees

    absolute) and not in Centigrade.

  • 7/31/2019 Calculation Wind

    10/17

    Equation 2.2. The stack flow equation.

    3. Combining Wind Pressure with Stack Pressure

    The pressures calculated using Equations 2.1 and 2.2 are additive (Figure 2.6) i.e. they can be

    summed directly together. This is not the same, however, as adding together the airflow rates

    calculated individually for wind and stack pressure.

    Figure 2.6. Combining wind and stack pressure.

    Introduction

    In Tutorial 1, the various formulations of airflow equations were introduced. This was followed, in

    Tutorial 2, by the formulation of the wind and stack pressure equations. In this tutorial, the flow

    network, i.e. the system of openings in the building fabric, through which air exchange between the

    inside and outside of a building takes place, is described.

    The flow equation of Tutorial 1 must be applied to every opening in the building envelope. If any are

    ignored (e.g. unidentified cracks and gaps in the building fabric) then the calculations will be in error.

    Typically, the number of leakage openings is underestimated because openings are unwittingly

    ignored. This results in underestimating the potential air change rate and, almost certainly,incorrectly predicting airflow patterns. The leakier the building, the more likely underestimates will

  • 7/31/2019 Calculation Wind

    11/17

    occur. It should also be noted that a building is leaky unless specific measures have been introduced

    during the construction to ensure that it is not. Usually, only if required by legislation of if specified

    by the building owner, will the building be anything other than leaky. The only possible exception

    might be poured concrete structures with few junction elements.

    Incorporating all openings is usually undertaken by defining:

    A network to represent background or air infiltration paths;

    A network of purpose provided openings such as windows, air vents etc;

    A network of mechanical ventilation fans.

    A Network to Represent Background Openings

    Figure 3.1. Background leakage networks.

    Networks representing background leakages are illustrated in Figure 3.1. The basic procedure is as

    follows:

    Determine the total surface area of exposed building surface (m2);

    Separate into the area of each face and the roof (or ceiling) area;

    Separate each face into a lower half and an upper half (single storey) or upper and lower half

    for each storey (multi storey building);

    Identify the C value of each of each path by multiplying its area by the building porosity (as

    determined by pressurisation test or as specified in design);

    Check that units are set to a common value (e.g. L/s or m3/s at 1 Pa).

    A Network to Represent Purpose Provided Openings

    This is determined by identifying for each opening:

    The face of the building in which it is located;

  • 7/31/2019 Calculation Wind

    12/17

    The height of opening;

    Its dimensions;

    For large openings (e.g. open windows) divide the area into an upper and lower section so

    that two way flow can be simulated.

    A Network to Represent Mechanical Ventilation Fans

    A simple representation of mechanical ventilation can be achieved by establishing a constant flow

    path for each fan. This is only permissible if the induced flow has no more than a few Pascals

    influence on pressure drop. The easiest method is to set the flow exponent to the value 1 and the C

    value to the desired ventilation flow rate (in L/s or m3/s).

    The flow network comprises the location and flow characteristics of ALL the above openings.

    Assuming a total of j openings, the flow rate through each opening is solved by determining theinternal pressure of the space or (in the case of a multi-zone building) each internal zone. This is

    determined by applying the Law of Conservation of Mass (i.e. the mass of flow into the building

    equals the mass of flow out or the sum of the flow equals zero). Thus the mass balance equation (and

    volume flow approximation) for j flow paths is given by:

    These generally have to be solved by iteration using a model such a s PHPAIDA. The user must

    supply the pressure (due to stack and wind) for each flow path and the flow coefficient and flow

    exponent for each path. This leaves the internal pressure as the only unknown.

    Direct solution is possible for very simple networks. Examples are given in Tutorial 5.

    http://phpaida.veetech.org.uk/phpaida.phphttp://phpaida.veetech.org.uk/phpaida.phphttp://phpaida.veetech.org.uk/phpaida.php
  • 7/31/2019 Calculation Wind

    13/17

    This completUse the tutorials to calculate the ventilation rates for the configurations shown below.

    These may all be calculated by hand. Once completed usePHPAIDAto verify the calculated values.

    The Building Volume is 250 m3

    The size of each opening is 1000 cm2 The wind speed at a nearby met station is 4.5 m/s

    The outside air temperature is 0 Deg C

    The inside air temperature is 20 Deg C

    For each of the above figures calculate by hand:

    Ventilation Rate (L/s);

    Air Change Rate;

    For:

    Open Terrain;

    Shielded (Urban Terrain).

    Compare the results using .

    http://phpaida.veetech.org.uk/phpaida.phphttp://phpaida.veetech.org.uk/phpaida.phphttp://phpaida.veetech.org.uk/phpaida.phphttp://phpaida.veetech.org.uk/phpaida.php
  • 7/31/2019 Calculation Wind

    14/17

    IntroductionPHPAIDA may be accessed at the link below:

    http://phpaida.veetech.org.uk/phpaida.php

    The purpose of this tutorial is to highlight the powerful solutions that can be achieved. This

    algorithm is intended as an early stage tool for sizing natural ventilation openings and basic

    mechanical systems. It can also be used in the development of control systems to adjust ventilation

    openings according to weather conditions.

    Starting ConditionsFor simplicity consider a building such as a dwelling in which the inside air is well mixed (e.g. open

    plan space or internal doors open). Assume that good air quality is needed and that there are 4

    occupants. Based on a ventilation rate of 15 Litres/s (L/s) for each occupant the required ventilation

    rate is 60 L/s.

    Assume the following building dimensions and weather conditions:

    Urban Location

    Building Height = 8 m

    Building Volume = 240 M3

    Outdoor Temperature = 0 C

    Indoor temperature = 20 C

    Windspeed from a nearby met station = 3 m/s

    Sizing Openings for Natural VentilationBy entering the above data into PHPAIDA the opening areas of the 9 available flow paths can be

    varied to obtain a ventilation rate of approximately 60 L/s. There is no unique solution but the

    http://phpaida.veetech.org.uk/phpaida.phphttp://phpaida.veetech.org.uk/phpaida.phphttp://phpaida.veetech.org.uk/phpaida.phphttp://phpaida.veetech.org.uk/phpaida.php
  • 7/31/2019 Calculation Wind

    15/17

    following is an example:

    Flow Path Height (m)Opening

    Area (cm2

    )

    1 - 4 1.5 50

    5 - 8 5.0 100

    9 8.0 550

    The opening areas were quickly derived in three manual iterations and gave a total ventilation flow

    rate of 59.6 L/s combined with a fairly uniformly inflow through openings 1 to 8 combined with

    extract from the chimney opening. This approach can be applied to a variety of weather conditions,for example to derive a control strategy for openings to provide a uniform ventilation rate over a

    wide range of conditions.

    Extract Only and Supply Only Mechanical VentilationAn alternative approach is to consider a mechanical extract or mechanical supply system. By keeping

    the same openings as above, the result using PHPAIDA is:

    Extract at 60 L/s gives a total ventilation rate of: 85.27 L/s

    Supply at 60 L/s gives a total ventilation rate of: 90.61 L/s

    Although the weather conditions and opening areas are the same as for the natural ventilation case,

    it is seen that the total ventilation rate is less than the sum of the natural and mechanical rates. This

    is an advantage of mechanical extract or supply only systems. The natural openings are actually

    needed to provide the supply air for an extract system or to provide an exhaust route for a supply air

    system. It is possible to reduce the opening sizes so that weather has a much reduced impact. This

    means that a certain amount of building leakage can be accommodated. However, when the

    opening size is reduced, the pressure difference between the inside and outside of the building

    increases. This means that the mechanical system has to work harder, resulting in higher energy use.Also the fan must be capable of overcoming any increased pressure difference while providing the

    required airflow rate.

    Under many instances, natural driving forces tend to be in the low Pascal range, thus an optimum

    internal pressure to overcome the influence of weather would be:

    -10 Pa (i.e. 10 Pa below atmospheric) for extract systems;

    +10 Pa (i.e. 10 Pa above atmospheric for supply systems.

  • 7/31/2019 Calculation Wind

    16/17

    For low rise buildings this will result in a uniform ventilation flow rate over a wide range of normal

    weather conditions.

    A solution can be found by adjusting the opening areas in PHPAIDA until the internal pressure is

    approximately 10 Pa. A suitable solution is:

    Flow PathOpening

    Area (cm2

    )

    1-8 40

    9 0

    Differential areas between the upper and lower openings are no longer important because flow wasdominated by the mechanical ventilation rather than natural forces. Also the roof stack is not

    required.

    For extract ventilation this gave an under pressure of: -9.13 Pa.

    For supply ventilation this gave an over pressure of ; +2.98 Pa.

    In both cases the flow rate was exactly 60 L/s (i.e. flow is dominated entirely by the mechanical

    system.)

    Of course it is possible to reduce the opening area further for the supply approach since the 10 Pa

    target has not been reached. This is left as an exercise along with explaining why the pressures for

    the extract and supply systems are numerically different.

    Balanced VentilationBalanced Ventilation consists of mechanically providing both Supply and Extract Ventilation to the

    space. Thus the design ventilation rate of 60 L/s must be applied to both the Extract and Supply

    inputs of the PHPAIDA data input section.

    When entering the mechanical balanced data to the original natural ventilation example, the over all

    ventilation rate becomes:

    Balanced at 60 L/s gives a total ventilation rate of: 119.59 L/s.

    This is exactly the sum of the natural ventilation rate and the mechanical ventilation rate. Thus to

    avoid over ventilation the building must be completely airtight. This is the major disadvantage of

    balanced systems.

    ConclusionsBy understanding and experimenting with these simple examples, the potential of PHPAIDA can be

  • 7/31/2019 Calculation Wind

    17/17

    quickly understood. It is not possible to guarantee any results but PHPAIDA enables basic design

    guidance to be obtained to assist in more advanced design tools.