CAISO Workshop on Reactive Power Requirements and Financial Compensation Jason MacDowell
![Page 2: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/2.jpg)
Wind Turbines and Reactive Power Control
![Page 3: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/3.jpg)
3
GE 1.5 MW Reactive Capability
• Full leading and lagging range over full power range
• Faster reactive response than synch. generator
• Capability of reactive compensation with no wind
• No need for FACTS devices
![Page 4: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/4.jpg)
4
WTG Reactive Power Capability
Terminal Bus
P gen
Q gen
WTG
Reactive Power for Voltage Support
• Steady-state PF range - 0.90 under-excited/0.90 over-excited
• Dynamic range meets or exceeds steady-state range
• WTG reactive capability often sufficient to satisfy PF requirements at POI
• VAR capability reduced at low power due to units cycling off-line
Rating Point
Active Power
![Page 5: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/5.jpg)
5
WindCONTROL
QWTG
PWTG
QWTG
PWTG
QWTG
PWTG
QWTG
PWTG
QWTG
PWTG
QWTG
PWTG
QL
QC
HV Bus
LV Bus
Reactive Compensation
(if required)
PWP
QWP
Substation
Point of Interconnection
(POI)
Reactive
Power
Controller
LTC
Plant Level Control System
• Coordinated turbine and plant supervisory control structure
• Voltage, VAR, & PF control
• PF requirements primarily met by WTG reactive capability, but augmented by mechanically switched shunt devices if necessary
• Combined plant response eliminates need for SVC, STATCOM, or other expensive equipment
• Integrated with substation SCADA
![Page 6: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/6.jpg)
6 /
Wind Plant vs. Wind Turbine Reactive Capabilities
Wind Plant pf capability wind turbine pf spec
Reactive Losses
• I2X of unit transformer
• I2X of collector lines and cables
• I2X of substation transformer
• V2BL of shunt reactors
• QL of dynamic compensator
Reactive Gains
• V2BC of collector cables
• V2BC of harmonic filters
• V2BC of shunt cap banks
• QC of dynamic compensator
Extra compensation provided to make up the difference
• Switched caps and reactors all step-wise compensation
• Dynamic compensation needed for smooth control unless WTG has variable reactive capability
![Page 7: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/7.jpg)
7 /
Voltage-Dependent Power Factor Spec From UK grid code
Assumes less reactive power injection when grid voltage is above nominal
![Page 8: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/8.jpg)
8 /
System Strength
What is it?
• Usually measured in short circuit MVA
• MVAsc = kVb2/Xsc = 3½kVbkIsc
Why is it the single most important factor?
• Maximum short circuit (I.e. max kIsc or min Xsc) dictates breaker duties, many equipment ratings (later lecture)
• Minimum short circuit (I.e. min kIsc or max Xsc) dictates worst sensitivities, e.g. dV/dC, dV/dP, etc. (we’ll look at this some more below)
![Page 9: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/9.jpg)
9 /
Wind Farm P, Q, V Relationship
E n tire F a rm
-3 5
-3 0
-2 5
-2 0
-1 5
-1 0
-5
0
0 5 0 1 0 0 1 5 0 2 0 0 2 5 0
P (M W )
Q (
MV
Ar)
Fixed PF Fixed V
E n tire F a rm
-3 5
-3 0
-2 5
-2 0
-1 5
-1 0
-5
0
0 5 0 1 0 0 1 5 0 2 0 0 2 5 0
P (M W )
Q (
MV
Ar)
Fixed PF Fixed V
Voltage Control Takes Advantage of Reactive Power Capability
![Page 10: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/10.jpg)
10 /
• System Response
• Voltage, P & Q Flows at POI
• Input Wind Speed
Voltage Regulation
![Page 11: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/11.jpg)
11 /
• Individual WTG Response
• Selected Variables
Voltage Regulation
![Page 12: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/12.jpg)
Wind Turbine Fault Tolerance
![Page 13: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/13.jpg)
13 /
Ride-Thru Capabilities
Remains on-line and feeds reactive power through system disturbances
Meets present and emerging grid requirement with Low/Zero Voltage Ride Through (LVRT/ZVRT) capability
Meets transmission reliability standards similar to thermal generators
Active Power
Reactive Power
Voltage
Apparent Power
Zero Voltage Event
GE's Standard WindRIDE-THRU Offerings
0
20
40
60
80
100
120
-1.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0
Time (seconds)
Vo
lta
ge
at
Po
int
of
Inte
rco
nn
ec
tio
n (P
erc
en
t)
200 ms
LVRT
ZVRT
![Page 14: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/14.jpg)
14 /
FAULT RIDE-THROUGH NERC PRC-024: Generator Frequency and Voltage Protective Relay Settings
Requirement 1: Frequency Ride-Through
• Each Generator Owner (GO) shall:
– Set in service frequency protective relaying so that it does not operate to trip the generating unit during frequency excursions within the band described in Attachment 1
– Conditions and exceptions: – Must operate between 59.5 and 60.5 Hz continuous – May trip if rate of change >2.5 Hz/sec (Aurora exclusion)
Requirement 2: Voltage Ride-Through
• Each Generator Owner (GO) shall:
– Set in service voltage protective relaying so that it does not operate to trip the generating unit during voltage excursions within the specified band
– Conditions and Exceptions: – Consider 3-phase Zone 1 faults with normal clearing – Site-specific clearing time may be used – Generator tripping for SPS, RAS or to clear the fault allowed
![Page 15: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/15.jpg)
15 /
NERC PRC-024: Voltage Ride-Through
HVRT DURATION LVRT DURATION
Time (Sec) Voltage
(p.u.) Time (Sec)
Voltage
(p.u.)
Instantaneous 1.20 Instantaneous 0.00
0.20 1.175 0.15 0.45
0.5 1.15 0.30 0.65
1.0 1.10 2.0 0.75
3.0 0.9
Generators / Plant must not trip for credible faults inside the zone unless:
•SPS / RAS requires it
•Generator critical clearing time requires it (synchronous generators)
![Page 16: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/16.jpg)
16 /
NERC PRC-024: Frequency Ride-Through QUEBEC
High Frequency Low Frequency
Time (Sec) Frequency (Hz) Time (Sec) Frequency (Hz)
0 - 5 66 0 – 0.35 55.5
5 -90 63 0.35 - 2 56.5
90 - 660 61.5 2 - 10 57
> 660 60.6 10 - 90 57.5
90 - 660 58.5
> 660 59.4
EASTERN INTERCONNECTION
High Frequency Low Frequency
Time (Sec) Freq. (Hz)
Time (Sec) Freq. (Hz)
0 – 10(90.935-1.45713*f) 61.8 0 – 10(1.7373*f-100.116) 57.8 10(90.935-1.45713*f)
- Continuous 60.5
10(1.7373*f-100.116) - Continuous
59.5
Continuous 60.5 Continuous 59.5
WECC
High Frequency Low Frequency
Time (Sec) Frequency (Hz) Time (Sec) Frequency (Hz)
0 – 30 61.7 0 – 0.75 57
30 – 180 61.6 7.5 - 30 57.3
>180 60.6 7.5 - 30 57.8
30 - 180 58.4
>180 59.4
ERCOT
High Frequency Low Frequency
Time (Sec) Frequency (Hz) Time (Sec) Frequency (Hz)
0 - 30 61.8 0 – 2 57.5
30 - 540 61.6 2 - 30 58
>540 60.6 30-540 58.4
>540 59.4
![Page 17: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/17.jpg)
Transient Stability
![Page 18: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/18.jpg)
18 /
Transient Stability
DFAG wind farms are more stable than conventional synchronous generators.
![Page 19: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/19.jpg)
19 /
Transient Stability
In fact, wind farms will survive some disturbances that trip conventional synchronous generators.
![Page 20: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/20.jpg)
Plant reactive coordination problems and solutions
![Page 21: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/21.jpg)
21 /
WTG terminal Voltage with Uncoordinated PI regulators with PT error
![Page 22: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/22.jpg)
22 /
WTG terminal Voltage with Uncoordinated PI regulators with PT error
![Page 23: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/23.jpg)
23 /
Thermal
Plant
Thermal Plant Voltage Regulator
WF3
Grid
Several Miles
Several Miles
Connecting nodes
X1 X2 Wind Plant
Voltage Control
PT2
WF1 WF2
Wind Plant Voltage Control
Wind Plant Voltage Control
PT1
Multi-Plant Topology is Complex
![Page 24: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/24.jpg)
24 /
Volt/Var Control (simplified block diagram)
Voltage Reference
Measured Voltage PI Control:
(Kpv, Kiv gains)
Voltage Error
Reactive Command to Wind Turbines
Droop: %, LPF
Reactive Power delivered from wind plant to grid
+ -
-
![Page 25: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/25.jpg)
Study results demonstrating voltage droop
![Page 26: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/26.jpg)
26 /
Where are we? Six Wind Plants in a region with relatively little load and a couple large thermal plants that normally anchor system voltage. Local penetration is high. Voltage management is significant challenge.
20% change in power from Wind causes ~4% dV at 230kV
![Page 27: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/27.jpg)
27 /
Response of One Plant to a major line outage
Reactive Power Output
Point-of-regulation Voltage
Terminal Voltage Behavior
![Page 28: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/28.jpg)
28 /
Wind Plant Droops Field and Tuned Gains
Wind Plant Droop %
(on plant MVAr base)
Proportional
Gain
Integral Gain
Plant 1 5 6.0 1.5
Plants 2 1.3 1.5 0.5
Plants 3 1.3 3.5 0.83
Plant 4 2.0 0.18 0.09
Plant 5 1.3 1.5 0.5
Plant 6 1.5 0.4 0.2
![Page 29: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/29.jpg)
Field test results
![Page 30: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/30.jpg)
30 /
Voltage Behavior – 5 Uncoordinated Wind Plants
System
conditions
moving
System conditions
moving
Grid capacitor
switching
Voltage Limit
overrides power factor control
![Page 31: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/31.jpg)
31 /
Voltage Behavior – 5 Coordinated Wind Plants
System conditions
moving
System
conditions
moving
Grid capacitor
switching
![Page 32: CAISO Workshop on Reactive Power Requirements … · • Capability of reactive compensation with no wind ... Remains on-line and feeds reactive power through ... Meets transmission](https://reader031.vdocuments.us/reader031/viewer/2022022017/5b8297b57f8b9a54278e9437/html5/thumbnails/32.jpg)
32 /
Thank You