cable_solutions_firealarm

Upload: walsarissa

Post on 09-Apr-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/7/2019 Cable_Solutions_FireAlarm

    1/2

    CABLE SOLUTIONS

    Fire Alarm Cable

    Plenum - FPLP Fire Alarm Cables

    Riser - FPLR Fire Alarm Cables

    Fire/Clad Armored Fire Alarm Cables

    Shielded / Cabled

    Part# Description Rating Part# Description Rating

    85802 18/2 solid BC OAS FPLP 81802 18/2 solid BC FPLP

    85804 18/4 solid BC OAS FPLP 81804 18/4 solid BC FPLP

    85602 16/2 solid BC OAS FPLP 81602 16/2 solid BC FPLP

    85604 16/4 solid BC OAS FPLP 81604 16/4 solid BC FPLP

    85402 14/2 solid BC OAS FPLP 81402 14/2 solid BC FPLP

    85404 14/4 solid BC OAS FPLP 81404 14/4 solid BC FPLP

    81202 12/2 solid BC FPLP

    Shielded / Cabled Unshielded / Cabled

    Part# Description Rating Part# Description Rating

    98300 18/2 solid BC OAS FPLR 98820 18/2 solid BC FPLR

    98831 18/4 solid BC OAS FPLR 98804 18/4 solid BC FPLR

    98630 16/2 solid BC OAS FPLR 98620 16/2 solid BC FPLR

    98631 16/4 solid BC OAS FPLR 98604 16/4 solid BC FPLR

    98430 14/2 solid BC OAS FPLR 98420 14/2 solid BC FPLR

    98431 14/4 solid BC OAS FPLR 98404 14/4 solid BC FPLR

    98230 12/2 solid BC OAS FPLR 98200 12/2 solid BC FPLR

    Unshielded / Parallel

    Part# Description Rating98204 22/4 solid BC FPLR

    98844 18/4 solid BC FPLR

    Part# Description Rating

    92852 18/2 solid BC FPL

    92854 18/4 solid BC FPL

    92652 16/2 solid BC FPL

    92654 16/4 solid BC FPL

    92452 14/2 solid BC FPL

    92454 14/4 solid BC FPL

    92252 12/2 solid BC FPL

    LT543-06-01 re

    Unshielded / Cabled

    Coleman Cable Inc. 1530 Shields Drive Waukegan, IL 60085 800.323.9355 www.colemancab

  • 8/7/2019 Cable_Solutions_FireAlarm

    2/2

    CABLE SOLUTIONS

    Fire Alarm Cable

    Review of Cable Requirements:All installations must follow guidelines established by the

    National Electric Code. Below are some basic practices to

    remember when installing power-limited fire alarm systems.

    For a more in-depth review of requirements and installation

    guidelines, refer to the NEC code book.

    1. All cables must be listed by a Nationally Recognized

    Testing Lab (UL, ETL, CSA, etc). Check all cables for the

    proper markings. Refer to NEC Article 760.

    2. Comply with local wiring requirements.

    3. Only use conductors made of copper.

    4. Test wiring for grounds, short circuits, and open faults

    before the system is placed in operation.5. Always use the proper gauge of wire to avoid line loss.

    6. Avoid interference when routing wire.

    7. Installation to prevent the spread of fire from floor to floor.

    8. A minimum of 6 inches of free conductor is required in each

    electrical box to facilitate termination.

    9. All wiring must be terminated with listed devices.

    Plenum CMP FPLP

    Riser CMR FPLR

    General Purpose CMGCM

    FPL

    Type CM - Communications wire & cable

    Type FPL - Power-limited fire alarm cables

    Cable A shall be permitted to be used in place of Cable BA B

    NEC Article 760Fire Alarm Systems

    Applies to the installation of wiring & equipment of the fire alarm

    systems including all circuits controlled and powered by the fire

    alarm system

    Cable Substitution Hierarchy

    LT543-06-01 SEPT10 R3Coleman Cable Inc.

    1530 Shields Drive

    Waukegan, IL 60085

    800.323.9355

    www.colemancable.com

    Identify the Application

    Type of system: Fire detection & alarm notification, guard'stour, sprinkler water flow or sprinkler supervisory systems.

    Where the cable will be installed: Ducts & plenums, conduit?

    Distance cable will be run.

    Whether the system is addressable, may need to meet

    specific capacitance.

    What Really Matters in Selecting the

    RIGHT Fire Alarm Cable

    Where the Cable will be installed:Cable rating is important, the NEC has 3 ratings FPLP, FPLR and FPL.

    These ratings designate where and how the cable can be installed based on

    the ability of the wire to reduce the spread of smoke and fire.

    FPLP (Plenum): Type FPLP power-limited fire alarm plenum cable is listed

    by the NEC as being suitable for use in ducts, plenums and other space used

    for environmental air. All FPLP cables are listed as having adequate fire-

    resistant and low-smoke producing characteristics and must pass both UL

    test 1424 and NFPA 262.

    FPLR (Riser): Type FPLR power-limited fire alarm riser cable is listed as

    being suitable for use in a vertical run in a shaft or from floor to floor. All

    FPLR cables are listed as having fire-resistant characteristics capable of pre-

    venting fire from traveling floor to floor. Riser cables must pass both UL test

    1424 and the vertical riser flame test UL 1666.FPL (General Purpose): Type FPL power-limited fire alarm cable is listed

    by the NEC as being suitable for general purpose fire alarm use. This listing

    excludes installation in riser, ducts, plenums and other space used for

    environmental air unless the cable is installed in conduit. All FPL cables are

    listed as being resistant to the spread of fire and must pass both UL test

    1424 and vertical flame test UL 1685 or CSA vertical flame test.

    Type of SystemIs the system microprocessor based and therefore sensitive to EMI and RFI?

    If the system is computer based, a SHIELDED cable will protect the circuits

    from this outside interference and keep the signal constant.

    SHIELDED: Offers excellent protection against interference (EMI & RFI).

    EMI (Electro Magnetic Interference): Electrostatic sparks or spiking

    from motors, neon or fluorescent lighting ballasts or any other sources that

    cause noise. Shielded cables should be considered for installations in

    areas near dimmer panels and light switches, in parallel runs, near neon orfluorescent lights and near power cables.

    RFI (Radio Frequency Interference): Some frequencies used for radio

    communications have a tendency to become coupled onto conductors to

    produce RFI.

    UNSHIELDED: Cost effective where interference is not a concern.Distance the cable will run

    Voltage drop should be calculated or refer to equipment manufacturers

    recommendations. Knowing the distance the cable will run also helps

    identify the right gauge size cable to select. Larger gauge for longer runs.

    CapacitanceThe capacity of the insulation to hold an electric charge. Often, lower

    capacitance (Picofarrads/foot = pF/ft.) translates to a higher performance

    cable. May need to meet requirements for specific hardware systems.

    Cabled (Twisted) vs. Straight-Lay (Zip or Parallel)

    CABLED: Most common for fire alarm cable. Reduces crosstalk

    interference from other signals (inside or outside the cable), especially over

    longer runs.

    STRAIGHT-LAY: Cost effective where interference is not a concern.

    Solid vs. StrandedSOLID: Industry standard for most fire alarm cable. Solid conductors are

    easier to terminate, often lower cost and have less attenuation/signal loss.