Fire Alarm Cable for Addressable Fire Alarm System Specification: Twisted pair of bare copper conductor. Color coded insulation, black and red. Shield with aluminum - mylar tape 100% coverage. Tinned copper drain wire. Low smoke and no halogen LSZH jacket. Rated temp. 105 o C, rated voltage 600V. Note: For GST fire alarm system, non-shield twisted pair cable can be used. The minimum size is 18AWG Standard Standard Weight Conductor Cross section area DC resistance Insulation Jacket Jacket Length No./mm Part No. Cable Type No.of pairs or triple AWG mm 2 /Km OD. (mm) OD. (mm) Color (m/reel) (kg/km) 1/ 0.643mm 55100 P/N-9022(lszh) 1 22AWG 0.324 59.1 /Km 1.5 4.52 Orange 1000 29.1 1/ 0.813mm 55101 P/N-9020(lszh) 1 20AWG 0.519 36.4 /Km 1.67 4.82 Orange 1000 34.6 1/ 1.02mm 55102 P/N-9018(lszh) 1 18AWG 0.823 21.4 /Km 1.88 5.32 Orange 1000 43.2 1/1.29mm 55103 P/N-9016(lszh) 1 16AWG 1.31 13.5 /Km 2.15 5.82 Orange 1000 55.5 1/1.63mm 55104 P/N-9014(lszh) 1 14WG 2.08 8.45 /Km 2.75 7.1 Orange 1000 90.4 1/ 2.05mm 55105 P/N-9012(lszh) 1 12AWG 3.31 5.31 /Km 3.17 8 Orange 1000 119.3 Local supplier: KP Trading, Bangkok Thailand, Tel. 02 735-2500, Fax 02 8735-2509. Cable brand name is Hosiwell.

Upload: noonbcc130

Post on 11-Apr-2015

98 views

Category:

Documents


4 download

DESCRIPTION

Fire Alarm Cable for Addressable Fire Alarm SystemSpecification: Twisted pair of bare copper conductor. Color coded insulation, black and red. Shield with aluminum - mylar tape 100% coverage. Tinned copper drain wire. Low smoke and no halogen LSZH jacket. o Rated temp. 105 C, rated voltage 600V. Note: For GST fire alarm system, non-shield twisted pair cable can be used. The minimum size is 18AWG Cross section area mm2Part No. 55100 55101 55102 55103 55104 55105Cable Type P/N-9022(lszh) P/N

TRANSCRIPT

Page 1: Cable for Addressable Fire Alarm System

Fire Alarm Cable for Addressable Fire Alarm System

Specification: Twisted pair of bare copper conductor. Color coded insulation, black and red. Shield with aluminum - mylar tape 100% coverage. Tinned copper drain wire. Low smoke and no halogen LSZH jacket. Rated temp. 105oC, rated voltage 600V. Note: For GST fire alarm system, non-shield twisted pair cable can be used. The minimum size is 18AWG

Standard Standard Weight

Conductor

Cross section

area DC

resistance Insulation Jacket Jacket Length No./mm Part

No. Cable Type

No.of pairs or

triple AWG mm2 Ω/Km OD. (mm) OD. (mm)

Color (m/reel) (kg/km)

1/ 0.643mm 55100 P/N-9022(lszh) 1 22AWG

0.324 59.1 Ω/Km 1.5 4.52 Orange 1000 29.1

1/ 0.813mm 55101 P/N-9020(lszh) 1 20AWG

0.519 36.4 Ω/Km 1.67 4.82 Orange 1000 34.6

1/ 1.02mm 55102 P/N-9018(lszh) 1 18AWG

0.823 21.4 Ω/Km 1.88 5.32 Orange 1000 43.2

1/1.29mm 55103 P/N-9016(lszh) 1 16AWG

1.31 13.5 Ω/Km 2.15 5.82 Orange 1000 55.5

1/1.63mm 55104 P/N-9014(lszh) 1 14WG

2.08 8.45 Ω/Km 2.75 7.1 Orange 1000 90.4

1/ 2.05mm 55105 P/N-9012(lszh) 1 12AWG

3.31 5.31 Ω/Km 3.17 8 Orange 1000 119.3