c264 barres 225kv exist
TRANSCRIPT
-
7/29/2019 C264 Barres 225kv Exist
1/2
5 6 7 8 9 10 1 1 12 1 3 14 1 5 16 1 7 18 1 9 20 2 1 22 2 3 24 2 5 26 2 7 28 2 9 30
Modular Bay Computer L B 0 I 6 8 1 0 0 0 2 2 0 0 0 0 0 0 A 1 1 1 1 N 1 0
L
Note: 15 boards maximum in the rack type 'L'
B
0
I
6
8
1
0
0
0
2
Note: No cable needed
Factory Setted Legacy Ports N1/2 on BIU board
For CPU with 2 serial links: Factory Setted Legacy Ports N3/4
Note: With rack 'L' & Wetting Voltage = 110/125 Vdc, 10 x DIU 210 boards maximum
Harsh Environmental Coating
Nominal wetting voltage for digital inputs (DIU200(-) or DIU211(+) or CCU200(-) or DSP210(-))
Digital Input Module (16 DI), each with 16 digital inputs (DIU200A0x)
Multi Tension-Peak-Current Digital Input Module (16 DI), each with 16 digital inputs DIU211
Note: Additional board count must not exceed 13
Digital Output Module (10 DO), each with 10 digital outputs (DOU200)
0
Manufacturing Process
CPU and Base Communication
Note: Additional board count must not exceed 13
Transducerless Measurements Unit - Direct measuring value acquisition: 4 CT + 5 VT
1 - 4
C264
2
Package Rack 4U (CAS2xx) + FBP2xx
Front Panel (GHU2xx)
Language (including: Front Panel Labels, HMI)
Power Supply and Legacy Ports (BIUxxx)
Case 40 T for use with CT/VT (Compact size), IP52, pin-terminal connection, 4 slots
Case 40 T for use without CT/VT (Compact size), IP52, pin-terminal connection, 6 slots
Case 80 T for use with CT/VT (Medium size), IP20, pin-terminal connection, 14 slots
Case 80 T for use without CT/VT (Medium size), IP20, pin-terminal connection, 15 slots
Front Panel Leds and L/R switch - IP52 protection -GHU210 (40TE) or GHU211(80TE)Front Panel with Leds + Graphic Display LCD +L/R switch -GHU200(40TE) or GHU201(80TE) - IP52 prot.
Simple Blind front panel : GHU220 (40TE ) or GHU 221(80TE)Detachable Front Panel with Graphic Display 40TE (GHU200) + Simple Blind Front panel (GHU22x)
Detachable Front Panel with Graphic Display 80TE (GHU201) + Simple Blind Front panel (GHU22x)Detachable Front Panel with Leds 40TE (GHU210) + Simple Blind Front panel (GHU22x)Detachable Front Panel with Leds 80TE (GHU211) + Simple Blind Front panel (GHU22x)
French ( English)
English (English)
Spanish (English)
German (English)
BIU241-A01 : VA,nom: 24 VDC / Nominal wetting voltage for 2DI: 24 VDC
BIU241-A02 : VA,nom: 48 to 60 VDC / Nominal wetting voltage for 2DI: 48/60 VDC
BIU241-A03 :VA,nom: 110 to 125 VDC / Nominal wetting voltage for 2 DI: 110/125 VDC
BIU241 A04 : VA,nom: 220 VDC and 115 to 230VAC / Nominal wetting voltage for 2 DI: 220 VDC
Port N2: RS232 ; Port N1: RS232
Port N2: RS232 ; Port N1: RS485
Port N2: RS485 ; Port N1: RS485
CPU270(Type3), with 2*Ethernet RJ45, 64Mb FlashMemory, 1 ppm Oscillator accuracy (Ref CPU270 = 2071590A02 )
CPU270(Type3), with 2*Ethernet RJ45, 64Mb FlashMemory, 50ppm Oscillator accuracy (Ref CPU270 = 2071590A01)
Port N3: RS232 (non isolated) ; Port N4: RS232 (non isolated)
Port N3: RS485(ECU201) ; Port N4: RS485(ECU201)
Port N3: Optical(ECU200) ; Port N4: Optical(ECU200)
Automatic affectation (as standard) of the I/O modules in the basic rack
No
Yes
Without
VA,nom: 24 V DC (- to earth) DIU200-A01 board or CCU200-A01 board or DSP210-A01
VA,nom: 48/60 V DC (- to earth) - DIU200-A02 board or CCU200-A02 board or DSP210-A02
VA,nom: 110/125 V DC (- to earth) - DIU200-A03 board or CCU200-A03 board or DSP210-A03
VA,nom: 220 V DC (- to earth) : DIU200-A04 board or CCU200-A04 board or DSP210-A04
VA,nom: 110-125 VDC (-to earth) - DIU200-A03 board or CCU200-A07 board (input setted if > 68% Vn)
DIU200 quantity = 0DIU200 quantity = 1DIU200 quantity = 2DIU200 quantity = 3DIU200 quantity = 4DIU200 quantity = 5DIU200 quantity = 6DIU200 quantity = 7DIU200 quantity = 8DIU200 quantity = 9DIU200 quantity = 10
DIU200 quantity = 11DIU200 quantity = 12DIU200 quantity = 13DIU200 quantity = 14DIU200 quantity = 15
DIU200 & DIU211 cannot be used in the same rack
DOU200 quantity = 0DOU200 quantity = 1DOU200 quantity = 2DOU200 quantity = 3DOU200 quantity = 4DOU200 quantity = 5DOU200 quantity = 6DOU200 quantity = 7
-
7/29/2019 C264 Barres 225kv Exist
2/2
5 6 7 8 9 10 1 1 12 1 3 14 1 5 16 1 7 18 1 9 20 2 1 22 2 3 24 2 5 26 2 7 28 2 9 30
Modular Bay Computer L B 0 I 6 8 1 0 0 0 2 2 0 0 0 0 0 0 A 1 1 1 1 N 1 0
1 - 4
C264
0
0
0
A
1
1
1
1
N
1
0
DC 8 Analog Input Module (Current), with 8 analogue inputs (AIU211)
Legacy IED communication protocols (To lower levels: Relays, PLC, RTU, etc)
User Application
Note: Additional board count must not exceed 13 : CCU cannot be adjacent to TMU
DC 4 Analog Input Module (C or V transducer connection) each with 4 analogue inputs (AIU201)
Note: Additional board count must not exceed 13
Note: Additional board count must not exceed 13
Mixed Module (8 DI + 4 DO), each with 8 digital inputs and 4 digital outputs (CCU20x)
Note: Additional board count must not exceed 13
Analog output module (Currents) ,with 4 analogue ouputs (AOU200)
Cable Lenght for Detachable Front Panel
Note: Additional board count must not exceed 13
OK
Ethernet-based SCADA Communication Protocol ( to upper levels SCADA, DCS, Master Station,
...)
Legacy Serial SCADA Communication Protocol (to upper levels: SCADA, DCS, Master station,
etc)
Ethernet-based Switch Unit (SWU20x) 0R Redundant Unit (SWR20x) OR Dual Humming Unit
(SWD20x)
Specific Software Version
Built in Application
0
0
DOU200 quantity = 7DOU200 quantity = 8DOU200 quantity = 9DOU200 quantity = 10DOU200 quantity = 11DOU200 quantity = 12DOU200 quantity = 13
CCU200 quantity = 0CCU200 quantity = 1CCU200 quantity = 2CCU200 quantity = 3CCU200 quantity = 4CCU200 quantity = 5CCU200 quantity = 6CCU200 quantity = 7CCU200 quantity = 8CCU200 quantity = 9CCU200 quantity = 10CCU200 quantity = 11CCU200 quantity = 12CCU200 quantity = 13CCU200 quantity = 14CCU200 quantity = 15
AIU201 quantity = 0
AIU201 quantity = 1AIU201 quantity = 2AIU201 quantity = 3AIU201 quantity = 4
AIU201 quantity = 5AIU201 quantity = 6
AIU211 quantity = 0AIU211 quantity = 1AIU211 quantity = 2
AIU211 quantity = 3AIU211 quantity = 4AIU211 quantity = 5AIU211 quantity = 6
AOU200 quantity = 0
AOU200 quantity = 1AOU200 quantity = 2
AOU200 quantity = 3AOU200 quantity = 4
Without
SWU200 - With four 10/100BaseT Ethernet ports (RJ45)SWU202- With two 100BaseF MultiMode Ethernet ports (ST) and four 10/100BaseT Ethernet ports (RJ45)SWU204- With two 100BaseF MonoMode Ethernet ports (SC) and four 10/100BaseT Ethernet ports (RJ45)SWR202 or SWR212 -With two 100BaseF MultiMode Ethernet ports (ST) + four 10/100BaseT Ethernet ports (RJ45)
SWR204 or SWR 214 -With two 100BaseF MonoMode Ethernet ports (SC) + four 10/100BaseT Ethernet ports (RJ45)SWD202 or SWD212 - With two 100BaseF MultiMode Ethernet ports (ST) + four 10/100BaseT Ethernet ports (RJ45)
IEC 60870-5-104
Up to two SCADA links in: IEC 60870-5-101, DNP3, Modbus
Up to 4 IEDs links in: DNP3, MODBUS, IEC 60870-5-103, IEC 60870-5-101
Disabled
Enabled ISaGRAF run-time for Programmable Logic, Automation, etc.
No Software loaded
Option CD3: No Software loaded, delivered with one CD-ROM inc. the C264 software(PACIS V3) - Consult Marketing
Option CD4: No Software loaded, delivered with one CD-ROM inc. the C264 software(PACIS V4) - Consult Marketing
Disabled
Synchrocheck/Voltage Regulation/ Autorecloser enabled
No cable