C10D and C20D HARMONIC COMPENSATOR Applications The C20D series Compensator provides a very good cost-filtering relation. It reduces the triplen harmonics (3rd, 9th, 15th), and eliminates this way the main problems in office installations, which are overloaded neutral conductors and a high neutral-earth voltage. Additionally a reduction of the remaining problems caused by harmonics is obtained. It is necessary to install the C20D always in combination with the Impedance Adaptor C10D in order to obtain the most optimised filtering and functionality. Advantages Standards Filtering levels Considerations for the installation Especially recommended for installations with a high number of single phase harmonic generating loads: Computer equipment Fluorescent illumination and discharge lamps Frequency converters Variable speed drives for DC motors Power supplies and rectifiers Elimination of overloads in neutral conductors produced by triplen harmonics (3rd, 9th, 15th), obtaining: - Reduction of construction and maintenance costs of the electrical installation as the neutral conductors don’t need to be over dimensioned. - Reduction of the electricity invoice as there are no unnecessary losses in the neutral conductors. - Prevention against fire due to overheating of the neutral conductors. - Avoid tripping of 4 pole circuit breakers. Reduction of the current consumption and improving power factor thanks to which the available power of UPS systems, transformers and generators increases. Reduction of harmonics guaranteeing a better functioning of all electrical equipment in the installation. In case the installation is already constructed and operating, it is necessary to carry out some harmonic measurements on the point where the Compensator will be installed (the best location is end of he three phase network, as close as possible to the loads). This Compensator type can be installed in case the 3rd harmonic voltage is below 2,5%. In case the 3rd harmonic voltage is higher than 2,5%, a Compensator type with galvanic isolation is necessary (models C25D and C30D). In case the installation is not yet constructed or operative or will be expanded in the future, the best solution is to install or prescribe a Compensator type with galvanic isolation (models C25D and C30D). C10D + C20D Filtering of harmonics coming from the load 3rd, 9th, 15th Reduction neutral current up to 75 % Reduction neutral-earth voltage up to 75 % Reduction phase currents up to 15 % Reduction current distortion up to 45 % Reduction voltage distortion up to 45 % Obtain Power Factor up to 0.80 IEC 60076 / HD 398 / UNE 20101 IEC 60726 / HD 464 / UNE 20178 IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) IEEE 519 - limits of voltage harmonics (USA)

Upload: others

Post on 21-Feb-2021

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C10D and C20D HARMONIC COMPENSATOR

Applications

The C20D series Compensator provides a very good cost-filtering relation. It reduces the triplen harmonics (3rd, 9th, 15th), and eliminates this way the main problems in office installations, which are overloaded neutral conductors and a high neutral-earth voltage. Additionally a reduction of the remaining problems caused by harmonics is obtained. It is necessary to install the C20D always in combination with the Impedance Adaptor C10D in order to obtain the most optimised filtering and functionality.

Advantages

Standards

Filtering levels

Considerations for the installation

Especially recommended for installations with a high number of single phase harmonic generating loads: • Computer equipment • Fluorescent illumination and discharge lamps • Frequency converters • Variable speed drives for DC motors • Power supplies and rectifiers • Elimination of overloads in neutral conductors produced by triplen harmonics (3rd, 9th, 15th), obtaining:

- Reduction of construction and maintenance costs of the electrical installation as the neutral conductors don’t need to be over dimensioned.

- Reduction of the electricity invoice as there are no unnecessary losses in the neutral conductors. - Prevention against fire due to overheating of the neutral conductors. - Avoid tripping of 4 pole circuit breakers.

• Reduction of the current consumption and improving power factor thanks to which the available power of

UPS systems, transformers and generators increases. • Reduction of harmonics guaranteeing a better functioning of all electrical equipment in the installation.

In case the installation is already constructed and operating, it is necessary to carry out some harmonic measurements on the point where the Compensator will be installed (the best location is end of he three phase network, as close as possible to the loads). This Compensator type can be installed in case the 3rd harmonic voltage is below 2,5%. In case the 3rd harmonic voltage is higher than 2,5%, a Compensator type with galvanic isolation is necessary (models C25D and C30D). In case the installation is not yet constructed or operative or will be expanded in the future, the best solution is to install or prescribe a Compensator type with galvanic isolation (models C25D and C30D).

C10D + C20D Filtering of harmonics coming from the load 3rd, 9th, 15th Reduction neutral current up to 75 % Reduction neutral-earth voltage up to 75 % Reduction phase currents up to 15 % Reduction current distortion up to 45 % Reduction voltage distortion up to 45 % Obtain Power Factor up to 0.80

• IEC 60076 / HD 398 / UNE 20101 • IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics (USA)

Page 2: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C10D and C20D HARMONIC COMPENSATOR

References C10D-AAA C20D-AAA AAA: Output phase current (A) AAA: Output neutral current (A)

Characteristics C10D

• Voltage .......................................................................................................................................... 400 V III • Frequency .................................................................................................................................. 50 - 60 Hz • Protection degree ............................................................................................................................ IP – 23 • Ambient temperature (ta) ............................................................................................................... + 30 ºC • Humidity (without condensation) ..................................................................................................... < 95 % • Safety class ..................................................................................................................................... Class I • Installation ......................................................................................................................................... Indoor • Service ...................................................................................................................................... Continuous • Test voltage:

- between Windings and Earth................................................................................ 3 kV (1 min, 50 Hz) • External cover .................................................................................................................................... Steel • Isolations ............................................................................................................................ Class H-180 ºC • Windings ........................................................................................... Copper HC-200 ºC (double emailed) • Cooling .......................................................................................................................... (ANAN) Natural air • Connection terminals ....................................................................................... Terminal strip (up to 100 A)

Wire terminal (as from 125 A) • Earth terminal ................................................................................................ Terminal strip (up to 100 A)

Wire terminal (as from 125 A) • Cable entries ....................................................................................................................From bottom side • Steel enclosure: Protection degree: (IP – 23).

Characteristics C20D

• Voltage .......................................................................................................................................... 400 V III • Frequency .................................................................................................................................. 50 - 60 Hz • Protection degree ............................................................................................................................ IP – 23 • Ambient temperature (ta) ............................................................................................................... + 30 ºC • Humidity (without condensation) ..................................................................................................... < 95 % • Safety class ..................................................................................................................................... Class I • Installation ......................................................................................................................................... Indoor • Service ....................................................................................................................................... Continuous • Test voltage:

- between Windings and Earth................................................................................ 3 kV (1 min, 50 Hz) • External cover .................................................................................................................................... Steel • Isolations ............................................................................................................................ Class H-180 ºC • Windings ........................................................................................... Copper HC-200 ºC (double emailed) • Cooling .......................................................................................................................... (ANAN) Natural air • Connection terminals...................................................................................... Terminal strip (up to 125 A)

Brass terminal screw (as from 160 A) • Earth terminal ................................................................................................. terminal strip (up to 125 A)

Brass terminal (as from 160 A) • Cable entries .................................................................................................................. From bottom side • Steel enclosure: Protection degree: (IP – 23). • Resin filled: Windings are resin filled for ratings as from 100 A. • Wheels and lifting eyebolts: Included.

Page 3: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C10D and C20D HARMONIC COMPENSATOR

Dimensions and weights

Impedance Adaptor C10D

Dimensions (mm) Reference A B C Weight (kg)

C10D-16 185 232 213 6.5 C10D-20 185 232 213 8.6 C10D-25 240 264 250 10.9 C10D-31.5 240 264 250 13.9 C10D-40 240 264 250 15.4 C10D-50 310 304 313 22.5 C10D-63 310 304 313 26.7 C10D-80 310 304 313 30.7 C10D-100 310 304 313 34.1 C10D-125 380 352 381 40.0 C10D-160 380 352 381 40.3 C10D-200 380 352 381 48.3 C10D-250 380 352 381 56 C10D-315 380 352 381 63 C10D-400 450 416 478 84

Compensator C20D Dimensions (mm) Reference A B C Weight (kg)

C20D-25 380 352 381 56 C20D-31.5 380 352 381 63 C20D-40 450 416 478 84 C20D-50 450 416 478 96 C20D-63 618 432 618 120 C20D-80 618 432 618 140 C20D-100 618 432 618 150 C20D-125 703 464 767 186 C20D-160 703 464 767 215 C20D-200 754 528 897 257 C20D-250 854 592 972 323 C20D-315 854 592 972 385 C20D-400 954 656 1178 572 C20D-500 1084 752 1281 703 C20D-630 1084 752 1281 841

Page 4: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C10D and C20D HARMONIC COMPENSATOR

Maximum current

Impedance Adaptor C10D

Reference Maximum phase currents (A)

C10D-16 16 C10D-20 20 C10D-25 25 C10D-31.5 31.5 C10D-40 40 C10D-50 50 C10D-63 63 C10D-80 80 C10D-100 100 C10D-125 125 C10D-160 160 C10D-200 200 C10D-250 250 C10D-315 315 C10D-400 400

Compensator C20D

Reference Maximum neutral current (A)

C20D-25 25 C20D-31.5 31.5 C20D-40 40 C20D-50 50 C20D-63 63 C20D-80 80 C20D-100 100 C20D-125 125 C20D-160 160 C20D-200 200 C20D-250 250 C20D-315 315 C20D-400 400 C20D-500 500 C20D-630 630

Maximum harmonic level

The compliance to following standards about harmonics is obtained:

IEC61000, IEEE519

Maximum residual voltage distortion in the output(1): THD%V ≤ 5% V3<1%; V5=V7...V13 ≤ 3%

(1) This distortion is generated by the impedance of the Compensator. Harmonic voltages produced by other loads or

coming from the mains are not considered in these values.

Page 5: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C10D and C20D HARMONIC COMPENSATOR

Recommended protections

Impedance Adaptor C10D Reference Rating

(A) Type

C10D-16 16 aM,D C10D-20 20 aM,D C10D-25 25 aM,D C10D-31.5 32 aM,D C10D-40 40 aM,D C10D-50 50 aM,D C10D-63 63 aM,D C10D-80 80 aM,D C10D-100 100 aM,D C10D-125 125 aM,MCCB C10D-160 160 aM,MCCB C10D-200 200 aM,MCCB C10D-250 250 aM,MCCB C10D-315 315 aM,MCCB C10D-400 400 aM,MCCB

(1) Protections against short circuits and overloads.

Compensator C20D Reference Rating

(A) Type

C20D-25 10 D C20D-31.5 12.5 D C20D-40 16 D C20D-50 20 D C20D-63 25 D C20D-80 32 D C20D-100 40 D C20D-125 50 D C20D-160 63 D C20D-200 80 D C20D-250 100 MCCB C20D-315 125 MCCB C20D-400 160 MCCB C20D-500 200 MCCB C20D-630 250 MCCB

(1) Protections against short circuits and overloads. C : MCB C curve. D : MCB D curve. aM : aM type fuse. gG : gG type fuse. MCCB : Molded case circuit breaker.

Page 6: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C10D and C22D HARMONIC COMPENSATOR

Applications

Advantages

Filtering levels

Considerations for the installation

Division of the loads

The C22D Compensator offers an elevated filtering of the harmonics of the 3rd, 5th, 7th, 9th, 15th, 17th, 19th order, solving therefore all possible problems that harmonics can cause in the installation. The C22D Compensator is used in combination with the C20D Compensator. In order to obtain the most optimised filtering and functionality it is necessary to install a C10D Impedance Adapter which each Compensator.

Especially recommended for installations with a high number of single phase harmonic generating loads: • Computer equipment • Fluorescent illumination and discharge lamps • Frequency converters • Variable speed drives for DC motors • Power supplies and rectifiers • Elimination of overloads in neutral conductors produced by triplen harmonics (3rd, 9th, 15th), obtaining:

- Reduction of construction and maintenance costs of the electrical installation as the neutral conductors don’t need to be over dimensioned.

- Reduction of the electricity invoice as there are no unnecessary losses in the neutral conductors. - Prevention against fire due to overheating of the neutral conductors. - Avoid tripping of 4 pole circuit breakers.

• Reduction of the current consumption and improving power factor thanks to which the available power of

UPS systems, transformers and generators increases. • Reduction of harmonics guaranteeing a better functioning of all electrical equipment in the installation.

In case the installation is already constructed and operating, it is necessary to carry out some harmonic measurements on the point where the Compensator will be installed (the best location is end of he three phase network, as close as possible to the loads). This Compensator type can be installed in case the 3rd harmonic voltage is below 2,5%. In case the 3rd harmonic voltage is higher than 2,5%, a Compensator type with galvanic isolation is necessary (models C25D and C30D). In case the installation is not yet constructed or operative or will be expanded in the future, the best solution is to install or prescribe a Compensator type with galvanic isolation (models C25D and C30D).

C10D + C22D + C20D

Filtering of harmonics coming from the load 3rd, 5th, 7th, 9th, 15th, 17th, 19th

Reduction neutral current up to 80 % Reduction neutral-earth voltage up to 80 % Reduction phase currents up to 40 % Reduction current distortion up to 75 % Reduction voltage distortion up to 75 % Obtain Power Factor up to 0.95

The C22D Compensator is used in combination with the C20D Compensator. Each of these supplies 50% of the load to be filtered. The 5th, 7th, 17th and 19th harmonics are compensated between the two loads and the triplen harmonics (3rd, 9th, 15th) are filtered in the windings of the Compensators. In order to obtain the most optimised filtering and functionality it is necessary to install a C10D Impedance Adapter which each Compensator.

Page 7: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C10D and C22D HARMONIC COMPENSATOR

Standards

• IEC 60076 / HD 398 / UNE 20101 • IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics (USA)

References C10D-AAA C22D-SSS AAA: Output phase current (A) AAA: Output rating (kVA)

Characteristics C10D

• Voltage .......................................................................................................................................... 400 V III • Frequency .................................................................................................................................. 50 - 60 Hz • Protection degree ............................................................................................................................ IP – 23 • Ambient temperature (ta) ............................................................................................................... + 30 ºC • Humidity (without condensation) ..................................................................................................... < 95 % • Safety class ..................................................................................................................................... Class I • Installation ........................................................................................................................................ Indoor • Service ...................................................................................................................................... Continuous • Test voltage:

- between Windings and Earth................................................................................ 3 kV (1 min, 50 Hz) • External cover .................................................................................................................................... Steel • Isolations ............................................................................................................................ Class H-180 ºC • Windings ........................................................................................... Copper HC-200 ºC (double emailed) • Cooling .......................................................................................................................... (ANAN) Natural air • Connection terminals ....................................................................................... Terminal strip (up to 100 A)

Wire terminal (as from 125 A) • Earth terminal ................................................................................................ Terminal strip (up to 100 A)

Wire terminal (as from 125 A) • Cable entries ....................................................................................................................From bottom side • Steel enclosure: Protection degree: (IP – 23).

Characteristics C22D

• Input voltage .......................................................................................................................... 400 V III +N • Output voltage ....................................................................................................................... 400 V III +N • Frequency .................................................................................................................................. 50 - 60 Hz • Protection degree ............................................................................................................................ IP – 23 • Ambient temperature (ta) ............................................................................................................... + 30 ºC • Humidity (without condensation) ..................................................................................................... < 95 % • Safety class ..................................................................................................................................... Class I • Installation ......................................................................................................................................... Indoor • Service ...................................................................................................................................... Continuous • Test voltage:

- between Windings and Earth................................................................................ 3 kV (1 min, 50 Hz) • External cover .................................................................................................................................... Steel • Isolations ............................................................................................................................ Class H-180 ºC • Windings ........................................................................................... Copper HC-200 ºC (double emailed) • Cooling .......................................................................................................................... (ANAN) Natural air • Connection terminals................................................................................. Terminal strip (up to 31.5 kVA)

Brass terminal screw (as from 40 kVA) • Earth terminal ........................................................................................... Terminal strip (up to 31.5 kVA)

Brass terminal (as from 40 kVA) • Cable entries ................................................................................................................... From bottom side • Steel enclosure: Protection degree: (IP – 23). • Resin filled: Windings are resin filled for ratings as from 20 kVA. • Wheels and lifting eyebolts: Included.

Page 8: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C10D and C22D HARMONIC COMPENSATOR

Impedance Adaptor C10D

Dimensions (mm) Reference A B C Weight (kg)

C10D-16 185 232 213 6.5 C10D-20 185 232 213 8.6 C10D-25 240 264 250 10.9 C10D-31.5 240 264 250 13.9 C10D-40 240 264 250 15.4 C10D-50 310 304 313 22.5 C10D-63 310 304 313 26.7 C10D-80 310 304 313 30.7 C10D-100 310 304 313 34.1 C10D-125 380 352 381 40.0 C10D-160 380 352 381 40.3 C10D-200 380 352 381 48.3 C10D-250 380 352 381 56 C10D-315 380 352 381 63 C10D-400 450 416 478 84

Compensator C22D Dimensions (mm) Reference A B C Weight (kg)

C22D-10 450 416 478 96 C22D-12.5 618 432 618 120 C22D-16 618 432 618 140 C22D-20 618 432 618 150 C22D-25 703 464 767 186 C22D-31.5 703 464 767 215 C22D-40 754 528 897 257 C22D-50 854 592 972 323 C22D-63 854 592 972 385 C22D-80 954 656 1178 493 C22D-100 954 656 1178 572 C22D-125 1084 752 1281 841 C22D-160 1204 832 1421 1174

Dimensions and weights

Page 9: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C10D and C22D HARMONIC COMPENSATOR

Maximum current

Impedance Adaptor C10D

Reference Maximum phase currents (A)

C10D-16 16 C10D-20 20 C10D-25 25 C10D-31.5 31.5 C10D-40 40 C10D-50 50 C10D-63 63 C10D-80 80 C10D-100 100 C10D-125 125 C10D-160 160 C10D-200 200 C10D-250 250 C10D-315 315 C10D-400 400

Compensator C22D

Reference Rating (kVA)

I rms (A)

C22D-10 10 14.5 C22D-12.5 12.5 18 C22D-16 16 23 C22D-20 20 29 C22D-25 25 36 C22D-31.5 31.5 46 C22D-40 40 58 C22D-50 50 72 C22D-63 63 91 C22D-80 80 115 C22D-100 100 144 C22D-125 125 180 C22D-160 160 231

Maximum harmonic level

The compliance to following standards about harmonics is obtained:

IEC61000, IEEE519

Maximum residual voltage distortion in the output(1): THD%V ≤ 5% V3<1%; V5=V7...V13 ≤ 3%

(1) This distortion is generated by the impedance of the Compensator. Harmonic voltages produced by other loads or

coming from the mains are not considered in these values.

Page 10: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C10D and C22D HARMONIC COMPENSATOR

Recommended protections

Input protection (1) Output protection (2)

Reference Rating (A) Type Rating

(A) Type

C22D-10 20 aM,D 16 gC,C C22D-12.5 25 aM,D 20 gC,C C22D-16 32 aM,D 25 gC,C C22D-20 40 aM,D 32 gC,C C22D-25 50 aM,D 40 gC,C C22D-31.5 63 aM,D 50 gC,C C22D-40 80 aM,D 63 gC,C C22D-50 100 aM,D 80 gC,C C22D-63 160 aM,MCCB 100 gC,C C22D-80 200 aM,MCCB 125 gC,C C22D-100 250 aM,MCCB 160 gC,MCCB C22D-125 400 aM,MCCB 200 gC,MCCB C22D-160 630 aM,MCCB 250 gC,MCCB

(1) Protection against short circuits. (2) Protection against overloads. These protections provide protections for the C22D Compensator as well as for the C10D Impedance Adaptor. C : MCB C curve. D : MCB D curve. aM : aM type fuse. gG : gG type fuse. MCCB : Molded case circuit breaker.

Page 11: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C25D HARMONIC COMPENSATOR WITH GALVANIC ISOLATION

Applications

• The C25D series is totally eliminating the triplen harmonics (3rd, 9th, 15th), avoiding any type of overload in the neutral as well as a high neutral-earth voltage produced by harmonics.

• The galvanic isolation of the C25D Compensator provides additional advantages such as: reduction of the electromagnetic disturbances coming from the supply network, optional voltage adaptation and the possibility to use independent earths as the neutral is isolated from the mains.

Advantages

Filtering levels

Using several Compensators

Especially recommended for installations with a high number of single phase harmonic generating loads: • Computer equipment • Fluorescent illumination and discharge lamps • Frequency converters • Variable speed drives for DC motors • Power supplies and rectifiers • Elimination of overloads in neutral conductors produced by triplen harmonics (3rd, 9th, 15th), obtaining:

- Reduction of construction and maintenance costs of the electrical installation as the neutral conductors don’t need to be over dimensioned.

- Reduction of the electricity invoice as there are no unnecessary losses in the neutral conductors. - Prevention against fire due to overheating of the neutral conductors. - Avoid tripping of 4 pole circuit breakers.

• Reduction of the current consumption and improving power factor thanks to which the available power of

UPS systems, transformers and generators increases. • Reduction of harmonics and electromagnetic disturbances guaranteeing a better functioning of all

electrical equipment in the installation.

The C25D Compensator is available in two versions offering different phase shifts (0º and 180º) for the 5th and 7th harmonic. By combining both versions, elimination of the 3rd, 5th, 7th, 9th, 15th 17th and 19th is obtained, filtering all harmonics that can appear in an installation. This configuration is also very suitable for installations where due to technical prescriptions or standards and legislations a high level of filtering is required.

Installing one Compensator

Installing several Compensators combining 0º and 180º versions

Filtering of harmonics coming from the load 3rd, 9th, 15th 3rd, 5th, 7th, 9th, 15th, 17th, 19thFiltering of voltage harmonics coming from the mains or other loads 3rd, 9th, 15th 3rd, 9th, 15th Reduction neutral current up to 90 % 90 % Reduction neutral-earth voltage up to 90 % 90 % Reduction phase currents up to 15 % 45 % Reduction current distortion up to 45 % 85 % Reduction voltage distortion up to 40 % 65 % Obtain Power Factor up to 0.80 0.96

Page 12: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C25D HARMONIC COMPENSATOR WITH GALVANIC ISOLATION

Standards

• IEC 60076 / HD 398 / UNE 20101 • IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics (USA)

References C25D-SSS-AAA SSS: Output rating (kVA) AAA: Phase shift angle harmonic 5 and 7 (0 or 180)

Characteristics

• Input voltage ................................................................................................ 400 V III+N (C25D-SSS-180) 400 V III (C25D-SSS-0) • Output voltage ....................................................................................................................... 400 V III + N • Frequency ................................................................................................................................... 50 - 60 Hz • Protection degree ............................................................................................................................. IP – 23 • Ambient temperature (ta) ................................................................................................................ + 30 ºC • Humidity (without condensation) ..................................................................................................... < 95 % • Safety class ..................................................................................................................................... Class I • Installation ......................................................................................................................................... Indoor • Service ....................................................................................................................................... Continuous • Test voltage:

- between Primary and Secondary........................................................................... 3 kV (1 min, 50 Hz) - between Primary and Earth.................................................................................... 3 kV (1 min, 50 Hz) - between Secondary and Earth............................................................................... 3 kV (1 min, 50 Hz)

• External cover .................................................................................................................................... Steel • Isolations ............................................................................................................................ Class H-180 ºC • Windings ........................................................................................... Copper HC-200 ºC (double emailed) • Cooling .......................................................................................................................... (ANAN) Natural air • Connection terminals................................................................................. Terminal strip (up to 31.5 kVA)

Brass terminal screw (as from 40 kVA) • Earth terminal ........................................................................................... Terminal strip (up to 31.5 kVA)

Brass terminal (as from 40 kVA) • Cable entries ................................................................................................................... From bottom side • Steel enclosure: Protection degree: (IP – 23). • Resin filled: Windings are resin filled for ratings as from 16 kVA. • Wheels and lifting eyebolts: Included.

Dimensions and weights

Dimensions (mm) Reference A B C

Weight (kg)

C25D-10-0 C25D10-180 618 432 618 120 C25D-12.5-0 C25D-12.5-180 618 432 618 140 C25D-16-0 C25D-16-180 618 432 618 150 C25D-20-0 C25D-20-180 703 464 767 186 C25D-25-0 C25D-25-180 703 464 767 215 C25D-31.5-0 C25D-31.5-180 754 528 897 257 C25D-40-0 C25D-40-180 854 592 972 385 C25D-50-0 C25D-50-180 954 656 1178 493 C25D-63-0 C25D-63-180 954 656 1178 572 C25D-80-0 C25D-80-180 1084 752 1281 703 C25D-100-0 C25D-100-180 1084 752 1281 841 C25D-125-0 C25D-125-180 1204 832 1421 999 C25D-160-0 C25D-160-180 1418 968 1571 1451

Page 13: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C25D HARMONIC COMPENSATOR WITH GALVANIC ISOLATION

Maximum harmonic level

Admissible harmonics for obtaining output voltage compliant with IEC61000,IEEE519 Reference Rating

(kVA) I rms (A) I3 (0.80⋅I1)

(A) I5 (0.30⋅I1)

(A) I7 (0.22⋅I1)

(A) I9 (0.15⋅I1)

(A) I11 (0.10⋅I1)

(A) I13 (0.07⋅I1)

(A) C25D-10-0 C25D10-180 10 14.5 8.7 3.2 2.3 1.6 1.1 0.7 C25D-12.5-0 C25D-12.5-180 12.5 18 10.8 4 2.9 2 1.4 0.9 C25D-16-0 C25D-16-180 16 23 14 5 3.7 2.5 1.7 1.2 C25D-20-0 C25D-20-180 20 29 17.5 6.4 4.6 3.2 2.2 1.5 C25D-25-0 C25D-25-180 25 36 21.6 8 5.8 4 2.7 1.8 C25D-31.5-0 C25D-31.5-180 31.5 46 27.6 10 7.4 5 3.5 2.3 C25D-40-0 C25D-40-180 40 58 35 12.8 9.3 6.4 4.4 2.9 C25D-50-0 C25D-50-180 50 72 43 16 12 8 5.5 3.5 C25D-63-0 C25D-63-180 63 91 55 20 14.6 10 6.8 4.6 C25D-80-0 C25D-80-180 80 115 69 25 18 13 9 6 C25D-100-0 C25D-100-180 100 144 86 32 23 16 10.8 7.2 C25D-125-0 C25D-125-180 125 180 108 40 29 20 13.5 9 C25D-160-0 C25D-160-180 160 231 139 51 37 26 17 11.6

In case above values for the harmonics and currents are respected, the compliance to following standards about harmonics is obtained:

IEC61000, IEEE519

Maximum residual voltage distortion in the output(1): THD%V ≤ 5%

V3=V5...V13 ≤ 3% (1) This distortion is generated by the impedance of the Compensator. Harmonic voltages produced by other loads or

coming from the mains are not considered in these values.

Recommended protections

Input protection (1) Output protection (2)

Reference Rating (A) Type Rating

(A) Type

C25D-10-0 C25D10-180 32 aM,D 16 gC,C C25D-12.5-0 C25D-12.5-180 40 aM,D 20 gC,C C25D-16-0 C25D-16-180 50 aM,D 25 gC,C C25D-20-0 C25D-20-180 63 aM,D 32 gC,C C25D-25-0 C25D-25-180 80 aM,D 40 gC,C C25D-31.5-0 C25D-31.5-180 100 aM,D 50 gC,C C25D-40-0 C25D-40-180 160 aM,MCCB 63 gC,C C25D-50-0 C25D-50-180 200 aM,MCCB 80 gC,C C25D-63-0 C25D-63-180 250 aM,MCCB 100 gC,C C25D-80-0 C25D-80-180 315 aM,MCCB 125 gC,C C25D-100-0 C25D-100-180 400 aM,MCCB 160 gC,MCCB C25D-125-0 C25D-125-180 500 aM,MCCB 200 gC,MCCB C25D-160-0 C25D-160-180 800 aM,MCCB 250 gC,MCCB

(1) Protection against short circuits. (2) Protection against overloads. C : MCB C curve. D : MCB D curve. aM : aM type fuse. gG : gG type fuse. MCCB : Molded case circuit breaker.

Page 14: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C30D HARMONIC COMPENSATOR WITH GALVANIC ISOLATION

Applications

The C30D is the Compensator that achieves the highest level of harmonic filtering in office installations. It eliminates the 3rd, 5th, 7th, 9th, 15th, 17th and 19th harmonic avoiding therefore all possible problems that harmonics can cause in the installation. The C30D is also suitable for installations where due to standards and legislations a high level of filtering is required.

Advantages

Standards

Filtering levels

Division of the loads

• It provides additional advantages such as: reduction of electromagnetic disturbances coming from the mains, optional voltage adaptation between input and output and the possibility to use independent earths as the neutral is isolated from the mains

Especially recommended for installations with a high number of single phase harmonic generating loads: • Computer equipment • Fluorescent illumination and discharge lamps • Frequency converters • Variable speed drives for DC motors • Power supplies and rectifiers • Elimination of overloads in neutral conductors produced by triplen harmonics (3rd, 9th, 15th), obtaining:

- Reduction of construction and maintenance costs of the electrical installation as the neutral conductors don’t need to be over dimensioned.

- Reduction of the electricity invoice as there are no unnecessary losses in the neutral conductors. - Prevention against fire due to overheating of the neutral conductors. - Avoid tripping of 4 pole circuit breakers.

• Reduction of the current consumption and improving power factor thanks to which the available power of

UPS systems, transformers and generators increases. • Reduction of harmonics and electromagnetic disturbances guaranteeing a better functioning of all

electrical equipment in the installation.

The C30D Compensator consists of two secondary windings. Each secondary should supply 50% of the load to be filtered. The filtered harmonics are compensated in the secondary windings and do not circulate through the rest of the installation.

Filtering of harmonics coming from the load 3rd, 5th, 7th, 9th, 15th, 17th, 19thFiltering of voltage harmonics coming from the mains or other loads 3rd, 9th, 15th Reduction neutral current up to 90 % Reduction neutral-earth voltage up to 90 % Reduction phase currents up to 45 % Reduction current distortion up to 85 % Reduction voltage distortion up to 85 % Obtain Power Factor up to 0.96

• IEC 60076 / HD 398 / UNE 20101 • IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics (USA)

Page 15: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C30D HARMONIC COMPENSATOR WITH GALVANIC ISOLATION

References C30D-SSS SSS: Total output rating (kVA)

Characteristics

• Input voltage .......................................................................................................................... 400 V III +N • Output voltage ..................................................................................................................2 x 400 V III + N • Frequency .................................................................................................................................. 50 - 60 Hz • Protection degree ............................................................................................................................ IP – 23 • Ambient temperature (ta) ............................................................................................................... + 30 ºC • Humidity (without condensation) ..................................................................................................... < 95 % • Safety class ..................................................................................................................................... Class I • Installation ......................................................................................................................................... Indoor • Service ....................................................................................................................................... Continuous • Test voltage:

- between Primary and Secondary.......................................................................... 3 kV (1 min, 50 Hz) - between Primary and Earth................................................................................... 3 kV (1 min, 50 Hz) - between Secondary and Earth.............................................................................. 3 kV (1 min, 50 Hz)

• External cover .................................................................................................................................... Steel • Isolations ............................................................................................................................ Class H-180 ºC • Windings ........................................................................................... Copper HC-200 ºC (double emailed) • Cooling .......................................................................................................................... (ANAN) Natural air • Connection terminals................................................................................. Terminal strip (up to 31.5 kVA)

Brass terminal screw (as from 40 kVA) • Earth terminal ........................................................................................... Terminal strip (up to 31.5 kVA)

Brass terminal (as from 40 kVA) • Cable entries ................................................................................................................... From bottom side • Steel enclosure: Protection degree: (IP – 23). • Resin filled: Windings are resin filled for ratings as from 12.5 kVA. • Wheels and lifting eyebolts: Included.

Dimensions and weights

Dimensions (mm) Reference A B C Weight (kg)

C30D-10 618 432 618 140 C30D-12.5 618 432 618 150 C30D-16 703 464 767 186 C30D-20 703 464 767 215 C30D-25 754 528 897 257 C30D-31.5 854 592 972 323 C30D-40 854 592 972 385 C30D-50 954 656 1178 493 C30D-63 954 656 1178 572 C30D-80 1084 752 1281 703 C30D-100 1084 752 1281 841 C30D-125 1204 832 1421 999 C30D-160 1204 832 1421 1174

Page 16: C10D and C20D - 3.imimg.com• IEC 60726 / HD 464 / UNE 20178 • IEC 61000 / EN 61000 - limits of voltage harmonics (EUROPE, international) • IEEE 519 - limits of voltage harmonics

C30D HARMONIC COMPENSATOR WITH GALVANIC ISOLATION

Maximum current

Reference Rating (kVA)

I rms Secondary 1

(A)

I rms Secondary 2

(A)

C30D-10 10 7.3 7.3 C30D-12.5 12.5 9.0 9.0 C30D-16 16 12 12 C30D-20 20 15 15 C30D-25 25 18 18 C30D-31.5 31.5 23 23 C30D-40 40 29 29 C30D-50 50 36 36 C30D-63 63 46 46 C30D-80 80 58 58 C30D-100 100 72 72 C30D-125 125 90 90 C30D-160 160 116 116

Maximum harmonic level

The compliance to following standards about harmonics is obtained:

IEC61000, IEEE519

Maximum residual voltage distortion in the output(1): THD%V ≤ 5% V3=V5...V13 ≤ 3%

(1) This distortion is generated by the impedance of the Compensator. Harmonic voltages produced by other

loads or coming from the mains are not considered in these values.

Recommended protections

Input protection (1) Output protection (2)

Reference Rating (A) Type Rating

(A) Type

C30D-10 40 aM,D 2 x 8 gC,C C30D-12.5 50 aM,D 2 x 10 gC,C C30D-16 63 aM,D 2 x 12 gC,C C30D-20 80 aM,D 2 x 16 gC,C C30D-25 100 aM,D 2 x 20 gC,C C30D-31.5 125 aM,MCCB 2 x 25 gC,C C30D-40 160 aM,MCCB 2 x 32 gC,C C30D-50 200 aM,MCCB 2 x 40 gC,C C30D-63 250 aM,MCCB 2 x 50 gC,C C30D-80 315 aM,MCCB 2 x 63 gC,C C30D-100 400 aM,MCCB 2 x 80 gC,C C30D-125 500 aM,MCCB 2 x 100 gC,C C30D-160 630 aM,MCCB 2 x 125 gC,C

(1) Protection against short circuits. (2) Protection against overloads. Each output of the Compensator has to be protected. C : MCB C curve. D : MCB D curve. aM : aM type fuse. gG : gG type fuse. MCCB : Molded case circuit breaker.