c1 h3 h6 high short circuit current in medium voltage ... · pdf fileinfluencing on...
TRANSCRIPT
©A
BB
AG
-2-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Influencing on short-circuit current
� FCL
� Function of IS-limiter
� IS-limiter and circuit breaker compared
� Structure of IS-limiter
� Application examples
� Reliability
� Calculation of tripping and setting values
©A
BB
AG
-3-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Influencing on short-circuit current
� FCL
� Function of IS-limiter
� IS-limiter and circuit breaker compared
� Structure of IS-limiter
� Application examples
� Reliability
©A
BB
AG
-4-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Impedance of transformer and generator
� Splitting of busbars
� HVDC - converter
� Fault Current Limiter (FCL)
� Topology of the net
� Influencing on short-circuit current
©A
BB
AG
-5-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
i
t
� Fault Current Limiter (FCL)
Fault current limiter - type 2 (without current interruption)
Fault current limiter - type 1 (with current interruption)
©A
BB
AG
-6-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
A. Devices which are commercially available :
� Current limiting reactor (type 2)
� Fuse (type 1)
� Is-limiter (type 1)
B. Devices which are still in a stage of research:
� Superconducting Fault Current Limiter (SCFCL)
� Semiconductor Fault Current Limiter
� Hybrid Fault Current Limiter
� Fault Current Limiter (FCL)
©A
BB
AG
-7-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Overview: Commercially available
Rated current
Power losses
Voltage drop
Current interruption
<= 4000A high high No (type 2)
Current limiting reactor
<= 200A very low zero Yes (type 1)
Fuse
<= 4000A very low zero Yes (type 1)IS-limiter
©A
BB
AG
-8-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Technical data Is-limiter
RatedVoltage0,75 kV
12,00 kV17,50 kV24,00 kV36,00 kV40,50 kV
For higher rated currents IS-limiters can be connected in parallel
RatedCurrent
. . . . . 5000 A
. . . . . 4000 A
. . . . . 4000 A
. . . . . 3000 A
. . . . . 2500 A
. . . . . 2500 A
SwitchingCapability
. . .140 kA RMS. . . 210 kA RMS. . . 210 kA RMS. . . 140 kA RMS. . . 140 kA RMS. . . 140 kA RMS
©A
BB
AG
-9-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� 3000 IS-limiters in service in 78 countriesCustomers:
Industry
Town‘s utilitiesUtilities
Test-laboratories
� Paper mills� Refineries� Chemical industries� Car industries� Power stations� Steel-, Aluminium mills� On-Off-shore platforms� Ships / Vessels
©A
BB
AG
-10-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Comparison: IS-limiter – Circuit Breaker
t
i
Total operatingtime of theIS-limiter: T = 5 - 10 ms
T
T2T0 T1 T3
T1 : Operating time of the protection relais: 30 - 40 ms
T2 : Operating time of the circuit breaker: 40 - 80 ms
T3 : Arc duration: 10 - 20 ms
T0 : Response time of the protection relais: 10 - 20 ms
90 - 160 ms
©A
BB
AG
-11-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
u
t
i
� Breaking of a short-circuit current with IS-limiter
Current curve at the short-circuit location
i1
i = i1 + i2without IS-limiter
i2
i = i1 + i2with IS-limiter
160 kA
80 kA31,5kA x � x 2
©A
BB
AG
-12-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� IS-limiter components
A,B,C: three phase-separatedsystems
A: Insert holder with pulse transformer and insert
A
B: Measuring and trippingunit
B
C: Current transformerC
©A
BB
AG
-13-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� IS-limiter insert holder and insert
©A
BB
AG
-14-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Section of an IS-limiter switchgear panel17.5 kV, 1250 A – 4000 A24 kV, 1250 A – 3000 A
A Busbar compartmentB IS-limiter compartmentC CT / PT compartmentD IS-limiter measuring and
tripping device
A B D
C
©A
BB
AG
-15-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� IS-limiter in a switchgear- truck mounted -
©A
BB
AG
-16-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Reliability
Self monitoringRedundancy (for each phase one independent system)
©A
BB
AG
-17-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
1 phase fault
2 phase fault
� Redundancy IS-limiter
Is-limiter
L1
L2
L3
CB
G
©A
BB
AG
-18-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Reliability
Self monitoringRedundancy (for each phase one independent system)
Protection against EMI- special current transformators
(low impedance shield between primary and secondary winding)
- filters for incoming / outgoing wires
- special tripping and measuring wires(each pair tightly twisted and protected by steel conduit)
Test equipment(quick, complete and easy test by user)
©A
BB
AG
-19-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
IS-limiter insert holder with test insert
Test equipment
� Test set for IS-limiter
©A
BB
AG
-20-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Safety related reliability of IS-limiter
1-phase 3-phase
Safety Integrity Level (SIL)
- Average Probability of Failure on demand 4,9E-5 1,02E-4
- Hardware Failure Tolerance 0 1
- Safe Failure Fraction 96,1 96,1
- % of SIL 3 4,9 10,2
- MTTF: 196 years
©A
BB
AG
-21-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Detection of the Short-circuit current
didt( )3
3didt( )2
i
t
ilimit
2
1
1 Short-circuit currentwithout IS-limiter
2 Short-circuit current– IS-limiter tripped –
3 Over current– IS-limiter not tripped –
ilimit ^ (di/dt)^ = logical „and“
4 4 Peak value of service current
©A
BB
AG
-22-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Schedule for tripping
T1T2
T0: Reaching time for tripping criteria (instantaneous value and di/dt).
T4T0t
i
T3
.
T1: Response time of the electronic approx. 15 µs
T2: Time for opening the bursting bridge and for commutating the current to the fuse element approx. 85 µs
T3: Melting time of the fuse element approx. 500 µs
T4: Arc duration
iA: Tripping criteria are reached (instantaneous value and di/dt).
iB: Current at beginning of fuse element's melting
iC: Let-through current
iC
iB
iA
©A
BB
AG
-23-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
L1
L2
L3
Circuit-breaker
Measuringand trippingdevice
Tripping-unitL1
L2L3
* further voltages on request
Alarms:- Is - limiter tripped- Is - limiter not ready- Supply voltage failure- Is - limiter blocked
Main supply-voltage
95 VAC - 250 VAC*
Auxiliary supply-voltage
95 VAC - 250 VAC*
DC supplyvoltage
24 VDC - 250 VDC*
Blocking
TrippingIndication
Power-supply
Self-monitoringIndication
ReadinessIndication
Power-unit Indication-unit
Tripping
Tripping ClosingInterlocking
� Interface of IS-limiter measuring and tripping device
Measurement Input
©A
BB
AG
-24-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� IS-limiter mounted in bus sectionAdvantages:
� Improving „powerquality“
� Increasing the relia-bility of the system
� Reduction of thenetwork-impedance
� Optimal load flow
� Existing busbarsystem has not to be changed
©A
BB
AG
-25-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� IS-limiter in generator feederAdvantages:
� Generator can be connected indepen-dent on the short-circuit capability of the system
� Existing busbarsystem has not to be changed
� No need of expensive generator breaker
©A
BB
AG
-26-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� IS-limiter in parallel to reactorAdvantages:
� Avoid copper losses of the reactor
� Avoid voltage drop of the reactor
� No electro-magnetical field of the reactor
©A
BB
AG
-27-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Calculation of the lossesTechnical Data: Ur = 13.8 kV, Ir = 4000 AReduction: 50 kA to 40 kA
(L = 0.172 mH, P = 42.5 kW/phase)
Copper losses per year: 42.5 kW * 3 *24h *330T = 1.009.800 kWh (Iservice = 4000 A)
10.625 kW * 3 * 24h * 330dT = 252.450 kWh (Iservice = 2000 A)
©A
BB
AG
-28-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� IS-limiter versus reactorProblem:
� Reactor is not able to limit the short-circuit current to zero
� There is still a contribution to the peak value of the short-circuit current
G
Grid IndustrialSystem
10 kA �
1 MVA14 %
415 V
IK reactor''
1250 A
2,37 kA2,9 kA3,8 kA4,5 kA5,5 kACurrent Ik reactor''through reactor
uk = 40 %uk = 30 %uk = 20 %uk = 15 %uk = 10 %
©A
BB
AG
-29-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Short-circuit contribution with reactor
Situation:
� 4 industrial generators behind reactors will fully load the grid in sight of short-circuit currents
Technical data of the Reactor:IR = 1250 AuK= 15 %
Technical data of generator:1 MVA, 14 %IK’’ = 10 kA
Grid Industrial System
0 kA(no contribution)
G1
4,5 kA
G2
4,5 kA
G3
4,5 kA
G4
4,5 kA
18 kA �
415 V
©A
BB
AG
-30-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� Connection of a generator to a network with current-direction comparison Advantages:
� Private / industrial generator feeder can be connected to the fully loaded grid
� Selective tripping of the IS-limiter (IS-limiter will operate only for short-circuit faults in the grid 1 ; will not operate in the grid 2 )
©A
BB
AG
-31-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� IS-limiters with summation of currents
©A
BB
AG
-32-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
� IS-limiter installations
- Chartered Semiconductor Mfg Ltd / Singapore- Shell - Windparks in Germany / Spain- Aluminium works in Australia- Oil/Gas platforms world-wide- Refineries world-wide- Utilities / Town-Utilities in Germany, Scandinavia, …- Los Alamos National Laboratories / USA- MIT / Bosten USA- Rolls Royce / Great Britain- Deutsche Bundesbank (German state bank)- …
©A
BB
AG
-33-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
Solves short-circuit problems in new and extended systems
Optimum solution for interconnection of switchgear installations
Tried and tested in thousands of installations
Worldwide in service
The peak short-circuit current cannot be reached
� Conclusion
Reduces costs of switchgear installations
The short-circuit current is limited at the first current rise
©A
BB
AG
-34-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
Advantage of IS-limiter
- Tripping criteria:
instantaneous current and di/dt of current
- Additional tripping criteria can be used
- No cooling time to replace tripped inserts
- Automatic connection of tripping wires to inserts
- Type tested enclosure
©A
BB
AG
-37-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
IS-limiter insert holder with test insert
Test equipment
� Test set for IS-limiter
©A
BB
AG
-39-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
A 4
Q 6 L 1 T 1 L 1 Q 6 L 2 T 1 L 2 Q 6 L 3 T 1 L 3
L1 L2 L3
Block diagram of the IS-limiter device Power unit
Tripping units
Anti-interference unit
Indication unit
Miniature circuit-breaker forsupply voltage
IS-limiter (insert holder and insert)
IS-limiter tripping transformer
Flag-type relay to monitorsupply voltage
Flag-type relay to monitorreadiness for operation
Flag-type relay to indicatetripping
G1:
A2:
A3:
A4:
F116:
Q6:
T1:
H106:
H116:
H1:
H106 H116IS-limiternot ready
H1L1Phase L1tripped
H1L2Phase L2tripped
H1L3Phase L3tripped
Anti-interference unit A3
F116
Powerunit
G1
Trippingunit
Phase L1A2L1
Trippingunit
Phase L2A2L2
Trippingunit
Phase L3A2L3
+ 150V
©A
BB
AG
-40-
08.0
9.20
05–
Is-li
mite
r.ppt
–P
TP
M-B
Is-limiter
Schematic diagram of a tripping unitof the tripping device type QR3S . . . / standard design
IS-limiter tripping transformerIntermediate transformer oftripping unitPulse transformerMeasuring inductanceSetting resistorsTripping capacitorDischarge resistorCharge
T1:T2:
T3:L1:R1...R6:C1:RS:RZ:
+ 150 V
C+ -
RZ
T3
T2
L1
U1 U2
T1
15
R5
R6
R3
R2
R1
R4
RS144
1
236
5
7
10
U3 U5
U4
Re
b1
Test socketconnector
Meteringelement 1
Trippingpulseemitter
Meteringelement 2