Voltage Dips and Mitigation System using Dynamic Voltage Restorer
By
MD NAJIB B MD YUSOF
FINAL REPORT
Submitted to the Electrical & Electronics Engineering Programme
in Partial Fulfillment of the Requirements for the Degree
Bachelor of Engineering (Hons) (Electrical & Electronics Engineering)
Universiti Teknologi PETRONAS
Bandar Seri Iskandar
31750 Tronoh
Perak Darul Ridzuan
© Copyright 2011
. by
Md Najib b Md Yusof, 2011
CERTIFICATION OF APPROVAL
VOLTAGE DIPS AND MITIGATION SYSTEM USING DYNAMIC VOLTAGE RESTORER
Approved by,
by
Md Najib b Md Yusof
A dissertation submitted to the Electrical & Electronics Engineering Programme
Universiti Teknologi PETRONAS
in partial fulfilment of the requirement for the
Bachelor of Engineering (Hons) (Electrical & Electronics Engineering)
Assoc Prof Dr K.S. Rama Rao
Project Supervisor
UNIVERSITI TEKNOLOGI PETRONAS
TRONOH, PERAK
May 2011
ii
CERTIFICATION OF ORIGINALITY
This is to certifY that I am responsible for the work submitted in this project, that the
original work is my own except as specified in the references and acknowledgements,
and that the original work contained herein have not been undertaken or done by
unspecified sources or persons.
, MD NAJIB B MD YUSOF
iii
ABSTRACT
Quality of the output power delivered has become a major concern for heavy
duty industry for present era. The poor power quality is due to some disturbances
such as voltage sags/dips, surge, flicker, harmonics, imbalance and interruptions. It
becomes more important especially with the sophisticated devices whose
performance is very useful to the quality of power supply. Power quality problem in
industries, factories, university, residential areas etc cause failure to the equipment
and malfunction which can make the operating system stop and at the end gives a big
impact to the plant production. These issues become worse if there is no mitigation
system to counter back the problem. A voltage dip is loss of rms voltage which is a
major power quality problem. In specific term of duration and retained voltage, it can
also be representing as the lowest rms remaining voltage at the lowest point during
the dips at the industry. So, it is the responsibility of the user and customers to
identify the root cause of the problem and create a mitigation system to overcome the
problem. To overcome this abnormal problem custom power devices are connected
closer to the end of the load. One of the devices is the Dynamic Voltage Restorer
(DVR) which is the most efficient custom power device used in power distribution
networks. This paper presents modeling, simulation, and analysis of a Dynamic
Voltage Restorer (DVR) using PSCAD (Power System Computer Aided Design)
software. The main component of a DVR is voltage source converter (VSI) which is
operated by pulse width modulation (PWM) technique and a PI controller. There are
many different type of fault has been created and shown reliable result after mitigate
usingDVR.
iv
ACKNOWLEDGEMENT
I would like to thank Universiti Teknologi PETRONAS for giving me to use their
resources and work in such excellent environment.
First and foremost I take this golden opportunity to express my gratitude to my guide
Assoc Prof Dr K.S Rama Rao and Mr Bahr Eldin for their guidance during my
project work. This project would not be success without their help and the valuable
time that they given to me even though they are quite busy with their work.
I would like to extend my gratitude to my friends and technician who always
supported and encouraged me to complete my work.
v
TABLE OF CONTENTS
CERTIFICATION iii
ABSTRACT IV
ACKNOWLEDGEMENT . v
TABLE OF CONTENTS vi
CHAPTER I: INTRODUCTION . 1
1.1 Background of Study •
1.2 Problem Statement 2
1.3 Objectives and Scope of Study 2
CHAPTER2: LITERATURE REVIEW . 3
2.1 Power Quality problem 3
2.2 Classification of Voltage dips. 4
2.3 The causes 6
2.4 The effect 6
2.5 IEEE standard • 7
2.6 Custom Power Devices 8
2.7 Dynamic Voltage Restorer 9
2.7.1 Introduction . 9
2.8 Basic Structure of DVR 10
2.8.1 Energy Storage Unit 11
2.8.2 DC charging • 11
2.8.3 PWM Voltage Source Inverter 11
2.8.4 PWM Current Source Inverter 14
2.8.5 Passive filter • 15
vi
CHAPTER3:
CHAPTER4:
CHAPTERS:
REFERENCES
2.8.6 Voltage injection transformer. 16
2.9 DVR operating 17
2.9.1 Protection Mode 17
2.9.2 Standby Mode • 18
2.9.1 lrifection/Boost Mode • 18
METHODOLOGY 19
3.1 Project Identification • 19
3.2 Modeling. 21
3.3 Equation related to DVR 24
3.3.1 Mathematical model for voltage
injection by DVR system 25
3.4 Tools and Equipment Required 27
3.4.1 Power System Computer Aided Design
(PSCAD)
3.4.2 What is PSCAD
3.5 DVR structure.
3.6 Energy Storage
3.7 Pulse Width Modulation
3.8 PI controller . 3.8.1 Tuning the PI controller
RESULTS AND DISCUSSION
4.1 Result •
CONCLUSION AND RECOMMENDATION
5.1 Conclusion
5.2 Recommendations
vii
27
28
29
30
30
34
34
36
38
46
47
48
LIST OF TABLES
Table I IEEE definitions for the voltage sags and swells .................................. 6
Table 2 Comparison between UPS and DVR ................................................. 8
Table 3 Advantage and Disadvantage of Voltage Source Inverter ...................... .14
Table 4 Advantage and Disadvantage of Current Source Inverter ...................... .15
viii
LIST OF FIGURES
Figure 1: Single line diagram of power distribution system ............................... .3
Figure 2: Classification of Voltage Variations .............................................. .4
Figure 3: Sample voltage dips waveform ..................................................... 5
Figure 4: Location ofDVR ...................................................................... 9
Figure 5: Basic operation ofDVR ........................................................... .IO
Figure 6: Schematic of Dynamic Voltage Restorer ....................................... .I 0
Figure 7: The power converter structure of various PWM-VSI drives ................. .l2
Figure 8: Simplified Circuit diagram of CSI.. ............................................. .14
Figure 9: Different filter placement .......................................................... 16
Figure I 0: Connection methods for the primary side of the injection transformer .... 16
Figure II: Protection Mode .................................................................. .l8
Figure 12: Standby Mode .................................................................... .18
Figure 13: Flow diagram of project work ................................................................... 20
Figure 14: Single ine diagram ................................................................ 21
Figure 15: Timed fault configuration ........................................................ 22
Figure 16: Configuration data of the voltage transformer ................................. 23
Figure 17: Calculation for voltage sags (dips) ............................................. 25
Figure 18: Calculation for DVR injection transformer .................................... 26
Figure 19: PSCAD Software Version 4.2.1 ................................................. 27
Figure 20: DVR structure ..................................................................... 29
Figure 21: Setting mode for breaker operation ............................................. 29
Figure 22: Pulse Width Modulation generation ........................................... 30
Figure 23: Sinusoidal Pulse Width Modulation block diagram .......................... 32
Figure 24: PWM graph ........................................................................ 33
Figure 25: PI controller block diagram ...................................................... 34
Figure 26: Defining the PI controller parameter ........................................... .35
Figure 27: Complete power system network with DVR ................................. .36
Figure 28: Pulse Width Modulation ........................................................ .37
Figure 29: Switching signals for inverter leg ............................................. .37
ix
Figure 30: Three phase and load voltage at normal condition ........................... 38
Figure 31: 3 phase voltages with single phase fault without DVR .................... .39
Figure 32: Voltage at load side without DVR ............................................. 39
Figure 33: 3 phases voltage at double phase fault without DVR ....................... .40
Figure 34: Voltage at load side without DVR ............................................. .40
Figure 35: 3 phases voltage at three phase fault without DVR .......................... .41
Figure 36: Voltage at load side without DVR ............................................. .41
Figure 37: 3 phase injected voltage with DVR ............................................ .42
Figure 38: Voltage at load side with DVR for single phase fault... ............................ 43
Figure 39: Voltage at load side with DVR for double phase fault ...................... .44
Figure 40: Voltage at load side with DVR for three phase fault ............................... .45
X
Var
PSCAD
PI
EMTDC
UPS
P.U
DVR
PWM
D-Statcom
PLC
VSI
FACTs
CSI
svc Hz
IEC
IGBT
IEEE
KV
MW
ms
GTO
LIST OF ABBREVIATIONS
Volt- Amperes Reactive
Power System Computer Aided Design
Proportional Integral
Electromagnetic Transient Direct Current Software
Uninterrupted Power Supply
per unit
Dynamic Voltage Restorer
Pulse Width Modulation
Distribution Static Compensator
Programmable Logic Controller
Voltage Source Inverter
Flexible ac Technology
Current Source Inverter
Static Var Compensator
Hertz
International Electro technical Commission
Insulated Gate Bipolar Transistor
Institute of Electrical and Electronics Engineers
kilovolt
Megawatt
mili second
Gate Tum-off thyristors
xi
1.1 Background of study
CHAPTER I
INTRODUCTION
Nowadays, most of industries, universities, and utilities use modem
equipment based on the electronic devices such as PLC (Programmable Logic
Controller), laptop, washing machine, printers etc. These devices are very sensitive to
the disturbances and become less efficient to the power quality problems such as
voltage sags, swells, flicker and harmonic.
With increasing usage of power electronics in industrial oil and gas plants,
manufacturing plants etc the issue of power quality has contributed significant
adverse effects on the plant performance. The proliferation of non-linear loads (i.e.
computers, variable speed drives, cranes, elevators, furnaces, motors, discharging
lighting, UPS (Uninterrupted Power Supply) etc ) in industries have produced
substantial voltage disturbance in Electrical Distribution System. Voltage dips can be
considered as one of the major disturbances.
Voltage dips can create unexpected and unwanted operating problems with all
types of equipments, ranging from nuisance tripping, miss-operation and failure of
electrical plant equipment (i.e. transformers, conductors, motor, generators etc.)
Plant's electrical substations experience voltage dips due to the distribution circuit
from operation of multiple large electric equipment at the plant facilities.
There are many ways to overcome the problem of voltage dips. One of the
electronic equipment that can be used to regulate the voltage is by using Dynamic
Voltage Restorer (DVR) which can provide the reliable solution to overcome the
issue of distribution power quality. The DVR mainly use for very sensitive load that
effect the efficiency of the output voltage.
I
1.2 Problem statement
Voltage dips can cause additional voltage stress to the electronic components,
electrical machines, cables, transformers, switchgears, circuit breakers, bus bars, light
sources etc also voltage dips cause reduction in equipment life span for example in
electric machines. At terminals of induction motor it causes changes in torque and
slip and consequently affects the production process. In worst case it may lead to
vibration, reducing mechanical strength and shortening the motor service life. These
uncorrected problems make process control being harder. Process variations slow
production rates, decrease product quality, increase energy consumption and the
worst thing make the plant upset. By exposing plant transformers and motors to
voltage dips may shorten their lives and increase the chances of catastrophic failure.
1.3 Objective
a. To study problems and scenarios related to the voltage dips in power quality
systems.
b. To learn about Dynamic Voltage Restorer (DVR) system that can reduce the
voltage dips problem.
c. To develop a simulation model of a distribution network incorporating the
DVR.
1.4 Scope of Study
a. Power System Computer Aided Design (PSCAD) V4 software is used for
modeling and simulations in the project. By creating large load running in a
weak power network system to create voltage dips and model the mitigation
system DVR to reduce voltage dips.
b. Understanding the Power System Computer Aided Design (PSCAD)
software.
2
CHAPTER2
LITERATURE REVIEW
2.1 Power quality problems
Step-down transformer 132/115 KV
Step-down transformer 115/11 KV
-~--1 21t.O[olm] 1
~-~ ~-w~r~---H· 2ll.O ]otrn] I
-wv----1 20.0 [Ohm]
Medium scale industries
The consumers
Figure 1: Single line diagram of power distribution system
In ideal case, power distribution system should provide a better performance
without any interrupted voltage to the customer activities. However, because of the
nonlinear loads it will affect the quality of power supplies. So due to this problem a
smooth voltage waveform cannot be achieved thus it will end up with the power
quality problem. Power Quality problem can be classified in much definition such as
voltage dips (sags), swells, flicker, harmonic distortion, transient and interruption.
3
2.2 Classification of Voltage dips
Voltage dip is change of nns voltage in short interruption at load bus. A
voltage dip means that the required energy is not being delivered to the load and this
can have serious consequences depending on the load that involved. When heavy
load are started, such as electric machine, the high starting current may drop the
voltage at certain level for a short tenn. The magnitude of the voltage usually is
below than the 10% nominal supply voltage (16]. The classification of nns voltage
variations is shown in Figure 2 as plot of voltage against duration of disturbances.
Figure 3 (a) and (b) is shown the voltage dip wavefonn.
Voltage vs duration of
Voltage (nns) I%
Voltage swells
455.5V 110%
415.0V 100% Voltage changes and fluctuations
373.5V 90%
Voltage dips
Short interruption Long interruptions
I ~ec I min 1 ho~r duration of disturbances
Figure 2: Classification of Voltage Variations
4
10.0 • ()Aput ~!l!tl4!e i
8.0 - .. - ., . - - ' ....... I -.. - . - .. i --6.0 -- . --
4.0
20 -I~Hi!HHI·IHtltiHitfjljtJljiiHI 11111111 0.0 fltlt lttt'ltttlftHtttt
IIIII Ill II -20 +I-IHl-H
1111
.. J !··
-4.0 --
-6.0 -ao -- - !
-10.0 '-- .J ................ J. .. .. . .. ' -···-·········
0.00 0.10 0.20 0.30 0.40 0.00 0.60 0.70 0.60 0.90
(a)
0\ 5'\
0.. 4 1---1--'W----If---+--+--+--+--+-t--++--+---1--+--11---i
w 1\ ~ 3 " ~ ~ ' ~ ./BORDERLINE OF IRRITATION !z 2 1-1--' 'kc---+-+--+-f_!lloooot,_+--+'-f-'--1'1-+-'-t'-+--+-+---l w ......... ""'-- "-BORDERLINE OF VISIBILITY OF FLICKER
~ 1 r1~ ''-ri'Ff~~4~=i~~t~~~4+~t;~/1 .... ..., II _.,~~
0 1 2 5 10 20 30 1 2 5 10 20 30 1 2 5 10 20
DIPS PER HOUR DIPS PER MINUTE DIPS PER SECOND
I l I I I FREQUENCY OF ~IPS I I I I I I 3D 12 6 3 2 1 30 12 6 3 2 1 .3 .2 .1 .05
MINUTES SECONDS TIME BETWEEN DIPS
(b)
Figure 3: Sample voltage dips wavefonn
5
2.3 The causes
Voltage dip is sudden reduction between 10 % - 90 % from nominal voltage
supply [16). It happened because high current, short circuit, heavy loads and earth
faults in the grid or electric equipment. When voltage drops down below than 90 %,
the time taken for a voltage dip to occur is from millisecond up to I minute [3]. If
number of motors start at the same time or the same repeatedly start and stop, the
frequency of voltage changes may produce dips in electrical equipment that is
perceived by human eyes. The voltage dips also may cause by distribution or
transmission network fault, cable fault during the construction, lighting strike that trip
the breaker and the higher rise building without proper grounding [4]. Other causes
due to voltage dips are:
~ Storm activity -lightning, wind.
~ Object coming in contact with power line and tripping breaker - tree
branches, animals etc.
~ Utility fault.
~ Construction activity.
~ Accidents- motor vehicle, other.
~ Equipment failure.
~ Overloading.
~ Poor grounding.
~ Non-linear loads.
2.4 The effect
Voltage dip is due to high starting current that may cause the electric equipment rms
voltage drop. Due to time taken by voltage dip it may affect the process of transaction
of data and the communication system such as email and box mail system. Moreover
it may cause spurious tripping of relays and electronic equipment. In addition,
induction motor that operates at maximum torque may also damage the bearings etc.
Severe voltage dips may not allow other loads to be started due to reduction in the
supply voltage. Also major effects can occurs such as motor may not maintained the
6
required speed even for a good variable speed drive, motor contactors drop out with
around 65% of the nominal voltage and also many variable speed drives trip out when
a voltage dip is more than 15%.[4].
2.5 IEEE Standard
IEEE 446-1995, "IEEE recommended practice for emergency and standby
power system for industrial and commercial application range of sensibility loads".
The standard discusses about the effect of voltage sags on sensitive equipment such
as motor starting, etc. It shows principles and examples on how systems shall be
designed to avoid voltage sags and other power quality problems when backup
system operates.
IEEE 493-1990, "Recommended practice for design of reliable and
commercial power system"
The standard proposes different technique to predict voltage sag
characteristic, magnitude, duration and frequency. There are few important things of
interest for voltage sags. The differences can be summarized as follows:
• Calculating voltage sag magnitude by calculating voltage drop at critical load
which includes the network impedance, fault impedance and location of fault.
• By studying protection equipment and fault clearing time it is possible to
estimate the duration of voltage sag.
• Further it has been found that the voltage dips/sag with magnitude 70 % of the
nominal value is more common than complete outages [5]. Sags/ dips and
surges can be identified by the voltage magnitude and the time duration it can
sustain. IEEE 519-1992, IEEE 1159-1995 as shown in Table 1(6].
Table 1: IEEE definitions for the voltage sags and swells
Disturbance Voltage Duration
Voltage Sag 0.1- 0.9 p.u 0.5- 30 cycle
Voltage Swell 1.1-1.8 p.u 0.5- 30 cycle
7
2.6 Custom Power Devices
Nowadays, a lot of devices have been developed to mitigate voltage dips such
as Uninterrupted Power Supply (UPS), Distribution Static Compensator (D-Statcom)
and Dynamic Voltage Restorer (DVR). Among these devices UPS is well known and
most of the industries use UPS configuration for Power Distribution System
application. Previously DVR and D-Statcom are less popular devices that being used
even though they are highly efficient and in term of cost more effective. Because of
the rapid development of power electronic industry and low cost devices, DVR
becomes most popular among the industries.
DVR is used to eliminate two different types of abnormality that affect power
quality. There are two types of load situation which are linear loads and non-linear
loads. To describe that the load is linear is when the entire dependent and
independent variables changes linear with each other. Resistor is the best example to
describe as a linear device. For non-linear devices the entire dependent and
independent variables does not change with each other. Capacitors and inductors are
the best examples to describe as non-linear devices.
Among the custom power devices, UPS and DVR can be considered as the
devices that can boost up the voltage waveform of the power distribution line. The
comparison between UPS and DVR is shown in Table 2.
Table 2: Comparison between UPS and DVR
UPS( Uninterrupted Power Supply) DVR (Dynamic Voltage Restorer)
Supplying the full voltage to the load Voltage will inject during the voltage
whether there is no distortion or not. dips occur.
High power rating Low power rating
Low efficiency High efficiency
High cost Low cost
8
2.7 Dynamic Voltage Restorer
2. 7.1 Introduction
Many power quality problems such sags, swells, harmonics etc, voltage dips
are the most severe disturbances. In order to overcome the problem the concept of
custom power devices has been introduced recently. One of the devices is Dynamic
Voltage Restorer which consists of power circuit and control circuit. The DVR
provides three phase independent controlled voltage source. It controls the voltage
vectors which have magnitude and angle. These voltages are injected into the ac
distribution system at the reference voltage. DVR is the most efficient and an
effective device that has been used for power system network. DVR is a series
connection to the powers system network that injects voltage into the system that
regulates the load side voltage. Normally it is connected into a power system network
between the supply and the critical load at a common point of coupling. Other than
voltage dips, DVR also can be used for other application such as harmonic
compensation, transient in voltage and current and etc. Figure 4 and 5 show the
location ofDVR and basic operation ofDVR respectively.
A B
100.0[MV~ 0.05 [chmP.4B06 P1[
,-------1#~~-..!!.JB 11 (\ ~ B 0.05 [chmP.4805 ~I U I •
20.0[chm[ [
-H' ~_j 20.11[ohml
100.0!M'I>'l ---1#---~--'-jA tOO.O[MV~ A --~-, 0001 ~ 0.005P'[ 1 0.1 [chm[ 0.1925P'[ J'WI"--'i.,;y A A_l"------fN--~---"-1., A y., 1"--e --t--r--AII---------+-1
U U O.OG1[ahm[ 0.005[HJ U 0.1 [ohm] 0.1928[1-!]
----11'1----~----"--c 1t511<1 ---N>~-~-L-_18.7.:..,11<1'-' 0.1[chm[ 0.1928P'[ 11.001 [ohm[
Figure 4: Location ofDVR
9
Voltage wavefonns ,r'rlrirlnnn ,,, r, n .... "r ,.-. _..r,nnr'-'d!iUU\illl, + \} \1 \.! - () J J \! '"H' IJ \J \1!,;
r'\ Voltage (2-:; l.~-.AAJ sensitive
~ Load
DVR
Figure 5: Basic operation ofDVR
2.8 Basic structure ofDVR
Figure 6 shows general configuration of the DVR which consists of:
i. Booster Transformer
ii. A harmonic filter
iii. Storage device
iv. A voltage source converter
v. DC charging circuit
bl'ql E'(} al\CE!'
Vm:a __.. LOAD I
l Vs ..AA.A.. VL l
'\.. Supply T ' T
-- Filter
control vsc system
Figure 6: Schematic of Dynamic Voltage Restorer
10
2.8.1 Energy Storage Unit
The energy storage unit is responsible to store DC voltage. It can use a super
capacitor or bank of batteries that being to storage energy. Its supply real
power to the system that is required when DVR is used for compensation.
2.8.2 DC charging
The DC charging circuit has two tasks:
• To charge back the energy that has been used after the voltage dips
compensation.
• To maintain the de voltage at the nominal de voltage.
2.8.3 PWM Voltage Source Inverter (VSI)
With the cost being the driving factor, general purpose PWM-VSI devices
with low kilowatt ratings (fractional to several tens of kilowatts) are generally
designed with minimum component count and complexity. In ac motor drive
applications, a single/three phase diode bridge circuit rectifies the AC input voltage
and a de link capacitor filters the rectified voltage forming a stiff de voltage source.
The PWM-VSI converts the de voltage to three-phase ac voltages with controllable
magnitude and frequency via a PWM method. Below about hundred volts MOSFETs
and at higher voltages IGBT power semiconductor switching devices are utilized in
the VSI, and the switching frequency can be as high as many tens of kilohertz. The
power circuit may also contain a de link capacitor pre-charging circuit, a small EMI
filter, and transient voltage suppression devices [14].
With the ac utility line power quality regulations becoming more stringent, at power
ratings higher than several tens of kilowatts the input rectifier device performance
becomes important. An inductor (de reactor) is inserted in series with the rectifier in
order to reduce the harmonic content on both the ac line and the de link capacitor. In
higher power non-regenerative applications 12-pulse rectifiers together with input
transformers with star primary and star-delta secondary windings are frequently
utilized to reduce the input current harmonic distortion. In the megawatt power range,
11
the PWM-VSI may be formed from parallel inverters, inverters with parallel devices,
or more complex inverter device structures such as the three levels VSI.[15]
c
(b)
(c)
c .-1-+----i-+-·· Va. ·VO
'""
(d)
Figure 7: The power converter structure of various PWM-VSI drives
In ac motor drive applications, shown in Figure 7 (a) a single/three-phase
diode bridge circuit rectifies the ac input voltage and a de link capacitor filters the
rectified voltage forming a stiff de voltage source.
As shown in Figure 7 (b) an inductor (de reactor) is inserted in series with the
rectifier in order to reduce the harmonic content on both the ac line and the de link
capacitor. Alternatively, a three phase reactor may be inserted in series with the ac
line to suppress the harmonics. Also a dynamic brake formed by a resistor and a gate
tum-off switch 20 is connected across the de bus capacitor in order to limit the de bus
voltage under transients and during regeneration (Figure 7(c)). In regenerative
applications with emphasis on energy efficiency back-to-back connected thyristor
12
bridges or more commonly a PWM-VSI can be utilized (Figure? (d)).
However, with the PWM-VSI a relatively large and therefore expensive three
phase reactor is required. Therefore, this solution is the most expensive approach. Up
to near a megawatt the switching device choice remains to be IGBT due to its cost
and performance advantages.
The power semiconductor devices can be IGBT's, GTO's or some of the
recently developed high voltage IGBT's and other new devices. Due to the switching
losses and the thermal issues associated with them, the switching frequency of the
PWM-VSI decreases from tens of kilohertz at lower tens of kilowatts level to less
than a kilohertz at the megawatt level. At increasing power levels, typically snubber
circuits are added to reduce the commutation losses and the peak stresses on the
devices [ 15].
13
2.8.4 PWM Current Source Inverter (CSI)
An inverter of the current source type makes it possible to convert the energy
supplied by a de source into the mains without using an auxiliary de to de converter.
The current source inverter's efficiency depends on the input de voltage of the
inverter, so the rating of the de source voltage influences the overall efficiency of the
system.
Figure 8 shows the simplified circuit of the CSI. The limited literature on the
CSI for Var compensation concentrates on the steady-state characteristic analysis and
main circuit design. These references employ a PWM switching pattern for the CSI
which is pre-calculated for harmonic elimination, where the modulation index is fixed
and the CSI is controlled by its firing angle [12]. The advantages and disadvantages
of voltage source inverter and current source inverter is shown in Table 3 and 4.
V'l'li, V:r~
AC System
Figure 8: Simplified Circuit diagram of CSI
Table 3: Advantage and Disadvantage of Voltage Source Inverter
Advantages Disadvantages
Simple and robust High switching frequency
Easy to control in the feed-forward voltage Large switching losses.
or feedback current mode
Wide ranges of frequency, magnitude of Conducted and radiated electromagnetic
fundamental output voltage are interference.
attainable.
PWM allows direct control of magnitude Hazardous over-voltage in long cables.
and phase of output space vector.
Accelerated deterioration of insulation in
bearings and supplied motors.
14
Table 4: Advantage and Disadvantage of Current Source Inverter
Advantages Disadvantages
Can transfer power in both direction Inductance slows down response to
current magnitude control commands,
can cause overvoltage if current path is
broken.
In square-wave mode is more efficient The output current is a square-wave
than a PWM VSI waveform.
Power circuit is simpler and more robust High level of low-order harmonics.
than the VSI
Lack of free-wheeling diodes, large de- When supplying a motor, can cause
link inductance, current control in the voltage spikes in the stator leakage
rectifier results in inherent protection inductance.
from over-currents.
PWM CSis are large and costly, and they
lost their efficiency advantage over VSI.
2.8.5 Passive filter
To eliminate the unwanted harmonic waveforms that are generate from VSI
process the filters can be placed on the high voltage side or on low voltage side of the
injection/booster transformer, thus higher order harmonics are eliminated from
passing through the voltage transformer. But there can be a phase shift and voltage
drop in the inverted output. This can be reduced by placing the filter on the load side.
But in the case of the higher order harmonic current passing through to the secondary
side of the transformer, a higher rating of the transformer is necessary. Figure 9
shows the different filter placement in the system.
15
. .q <j _J"' ~l~--.+ -<· -i'1 +~
.. rl' . Fi~ atlhe orimary side
Figure 9: Different filter placement
2.8.6 Voltage Injection Transformers
The booster transformer is specially designed to limit the coupling noise and
also to limit the transient energy from the primary and secondary side. Its main tasks
are:
• The DVR is connected to the power system network to H-V windings and
transforms and injects is specified voltage from supply source.
• It is also to isolate the load form the system.
The high voltage of the injection transformer is connected in series with
powers system network while the low voltage side is connected to the DVR power
circuit. The three-single phase transformers and the three-phase DVR can be
connected either star or delta open as shown in figure 10[10].
;;; >----~----r---_,__J
~====~-_j
Delta/open configuration
::;; >----'
£ Star/open configuration
Figure 10: Connection methods for the primary side of the injection transformer
16
The transformer winding ratio depends on the voltage required by the
secondary of the transformer. Normally the supply voltage must be equal to DVR
needed at the full voltage dips compensation. The higher the ratio of transformer
winding the higher current will flow at primary side which will affect the
performance of the electronic devices.
The winding configuration of the transformer depends on the power system. If
the transformer uses delta/star ( /1 - Y ) connection with the grounded neutral, during
the fault, earth fault happens on the high voltage side, no zero sequence current flows
to the secondary and only positive and negative sequence components will flow. So
the DVR can only compensate with the positive and negative sequence components
and for the open configuration it will be used to compensate the positive and negative
sequence. Similarly for other winding configuration such as delta/ delta connection of
the transformer, during the fault, earth fault occur, the positive, negative and zero
sequence components flow through the secondary side [8].
2.9 DVR operating system
The basic function of DVR is to control the voltage, V DVR generated by the
voltage source converter to the booster transformer. If there is a different voltage that
is caused by power system network, the DVR will compensate by injecting to the
distribution line from voltage source converter through the injection/booster
transformer.
The DVR has three modes of operation which are: protection mode, standby
mode and injection! booster mode.
2.9.1 Protection mode
If the load current exceeds the limit of the winding transformer current, the
DVR is isolated from the system by using bypass switches whereby S2 and S3 will
open and S 1 will close to supply another path to the current to flow as shown in
Figure 11.
17
S'
Sl
lll'"P.l.~f>'
!<'\\UC'III!.'
n ~I!iSJTIU WAD
Figure 11: Protection Mode
2.9.2 Standby Mode (VnVR = 0)
In the standby mode the injection/booster transformer low winding will not
inject voltage to the system. In this case the voltage source converter is not switched
on and the full load current will pass through the primary as shown in Figure 12.
j~:QTJRJ'.'F 1;'Emnt\"E L(l.-'.D w BCH!STER TR~NSFORI">IF£
l 1• IIINJ:!Ntl yyy
.! 1- l
lt\"P.-\.~;; }.'WITt.'HFS (('~)N~ 'IRU a.
.....
I r!LTER I l!:\IT
Figure 12: Standby Mode
2.9.3 Injection/ Boost Mode: (V DVR > 0)
In this case, the DVR injects a voltage trough the booster transformer due to
the disturbances on the power system network
18
CHAPTER3
METHODOLOGY
3.1 Procedure Identification
The project is carried out according to the flow chart as shown in Figure 13. It
is started with study of the voltage dips and the mitigation system using dynamic
voltage restorer. Then data is collected on DVR part by gathering the information
from internet resources, technical papers and also books. During this phase, voltage
dip fundamental also must be studied in order to achieve expected result at the end of
the research. Current technology also needs to be taken into account so that a clear
understanding on the operation ofDVR can be obtained.
In addition, the control system also needs to be studied to get better
understanding on DVR and its application. Preparing weak power system network
with load need also to be studied in order to apply and enhance the knowledge of this
type of power quality problem. Next, simulate the weak power network system and
analyze the voltage dip in order to get voltage dip graph. In this stage, collecting data
of varies type of fault is needed.
After all the data have been taken, the next phase is designing the structure of
DVR and mitigates the poor voltage using DVR. After that, the controller part needs
to apply to the system so that the voltage can be control automatically. After doing all
the simulation and achieve the data for every parameter needed, analysis the result
will conducted.
19
Study power quality problem in term of voltage dip
Study on Dynamic Voltage Restorer to mitigate the voltage dips problem
! Recognize and design part of Dynamic Voltage Restorer
l Preparing weak power system network with load
! Simulate the system and analyze the voltage dip
l Collect the data with several type of fuult
! Mitigate the voltage dips using Dynamic Voltage Restorer
! Design the controller part to control the Dynamic Voltage
Restorer
• Analyze the result
Conclusion
Figure 13: Flow diagram of project work
20
~vv'
-g .Q ..c .-=: :;: § !;))
"' ::a ~w 1000 !MVAI
~ ib = ·;;;
l"v'N'---'Y~Y !J. 63 ~Vv ~ 132!k'll 115!kVJ 115!kVJ ~Vv
<I> .;;
~ 0
-fii .:!!
ell ~ = -= e .. "C §l, = ::s li:
"! ..,
20~1 w.--H
20.0 !ohrq [
Wr--20.0 !ohrq
Vfa 0.1!ohml 019~6~ .-H
A
Vfb 0.1Johrt1 0.1926~
'" 0.1Johrq 0.1926!HI
115!kl'l IC · 1 lie 1B.71kVI • I I ' "' _,,,- ~
8 .> --<)
Vrms
c FAULTS
':"
~ _::g
""' <I>
:§ <I> bh -.s '"" "' ~ .... f! = ~
Single line diagram shown in Figure 14 of the system is composed by a
132kV, 50 Hz generation system, feeding two transmission lines through a 3-
winding transformer connected in star/delta/delta, 132/115/115 kV. Such transmission
line feed two distribution networks through two transformers in delta/star, 115/ 18.7
kV and 115/llkV. The DVR is simulated to be in operation only when the fault
occurs. The duration of fault considered to be is 300 ms. The Figure 15 show the
timed fault configuration and Figure 16 (a), (b) and (c) show the transformer voltage
configuration.
Transformer Name
3 Ph8se Transformer MVA
Base opermon frequency
-11Type
-#2Type
-#3Type
Delta lagS or leads v
[tfaultn] Timed Fault Logic L8::J
Time to Apply Fault
Duration of F au1t
Jo.3(s]
Jo.3(s]
OK Cancel Help ...
Figure 15: Timed fault configuration
Jr1 _, LretoUnovoftage(RMS)
J1 00.0 (MVA] """"ng 2 Uno to Line vollege (RMS)
Jso.O (Hz] """"ng 3 Lreto Uno volloge (RMS)
Jv iJ
Pos. seq.lefi<age reactance (#1-*2)
Pos. seq.leakage react&nce (#1-13)
Pos. seq. --ce (#2-I'J)
Joello iJ Joelo iJ JLogs iJ J0.2(pu]
[O:liPu-1 --10.1 (pu]
~--il'~
Jon(puJ Copper lOSses Jo.o(puJ Tap changer on winding
Concel Help ...
(a)
22
Cancel
J132(kV]
J115(kV]
Help ...
-
xfmr Jplw] J Phase J Winding I ransformer ~
Transformer Name IT1 3 Phase Transformer 'ttfiiA 1100.0 [MVA)
Base operation frequency I so O(HZJ
~11Type ro;; 3 ~12Type IV .:J Dele Lags or L~ Y I Lags ::J Posllve seQI8'lCe leek1lge reectn:e I o.2 (pu)
Ideal Transformer Model ~ ~ No Iced loss8s 0.0 (pu)
Copper losses 0.0 (pu)
TlltJ clw1ger on wirdng !N;;;" ~ Grll)hlcs Display 13 phase view ~ Display Detells? 3
Cancel ..... (b)
xfmr Jplw] J Phase 7 Wmdmg I ransformcr rsi ----r,rrf•.ll j' -,t "
Transformer Name rn 3 ~Transformer 'ttfiiA I 100.0(MVA)
Base operation~ l soo IHZI ~11Type l0e1a -:::J ~12Type fY .:J Dele Lags or Leeds Y I Leads 3 Poslive ~ leekage reectence 1 o.1 (pu)
Jdeel Transformer Model ~ 3 Noloedmses 1 o.o (pu)
--Copper losses l oo[puJ
TlltJ changer on~ jt;;; 3 OrepNcs Display 13 phase view ..:J Display Detels? 3
OK Cancel .. .. (c)
~ 1l.ile lo lile YIUJe (RMS) lm[kVJ --~ 21.i'le lo l.ile wtage (RillS) 118 7!kVl --
C.-eel I ~ ...
. . I xfmr lplwj l PhdSc I W1nd1np, I rdn~formcr &'I
Mllq 11.ile to Lne volage (RillS) 115 [kV)
Mllq 21.ile to l.ile volage (RillS) j 11[kV) -
OK c.lC8I ~·~
Figure 16: Configuration data of the voltage transformer
23
3.3 Equation related to DVR
Referring to Figure 17, for normal operation (no fault) current will flow
through the balanced load A and B. Both 2 load is balance load. When there is fault
occur for example at load A, a high current will flow into the feeder A. So based on
the Kirchhoff's Law current will flow into feeder B. A voltage drop occurs at feeder
B.
For example:
Load A impedance = Zload A
Load B impedance = Zload B
Feeder A reactance = X1
Feeder B reactance = X2
Current flow from power supply = I
Current flow from feeder A = h
Current flow from feeder B = I2
Therefore, I = I 1 + I 2
In normal condition (without any fault)
Vz I = =--=-Xz+ ZLOADB
(1)
When fault occurs at feeder A, because of the short circuit occur, the high
current will flowing through feeder B as well as through the source. At this moment
voltage at feeder B will decease due to the voltage drop across source reactance X,.
So from this condition voltage at feeder B will decrease from nominal voltage.
During fault, the source current,
(2)
24
FaDit A
V•8p.u..
V• I. p.IL
v~ o~s p.u. r Sag
Figure 17: Calculation for voltage sag (dip).
3.3.1 Mathematical model for voltage injection by DVR system.
Consider the schematic diagram shown in Figure 18. The impedance
represented Zth where the real part of the impedance Rth and the imaginary part in
reactance X th.
(1)
(2)
Where
V1 = The desired voltage magnitude
Zth = Load impedance
h = Load current
Vth =System voltage during the fault
Thus, when the voltage drop occurs at feeder B, DVR will inject a voltage through
the transformer so that the magnitude of the voltage is same as the load voltage.
(3)
25
The load current h is given by,
h= (4)
Where
PL = Real power
QL = Reactive power
When V L is a voltage reference,
VvvR < VvvR < a = VL < 0 + Zth h < (fJ - fJ) - Vth < a (5)
a,p and a are angles of VvvR and fJ is load angle.
The complex power injection of the DVR can be describe as
DVR
Voltage source converter
Figure 18: Calculation for DVR injection transformer
26
(6)
(7)
3.4 Tools and Equipment Required
The simulation and analysis uses the Power System Computer Aided Design
software.
3.4.1 Power System Computer Aided Design (PSCAD)
In this project PSCADIEMTDC software as shown in Figure 19 is used to
model, simulate and analyze voltage dips and mitigation using DVR. The student
version is used to familiarize with the software. This student edition is limited but
provides examples and tutorial is important to understand the software functionality.
To have more knowledge about this software, liaise with Simulation Research and
Support Engineer, Manitoba HVOC Research Center, Canada or access to the
website PSCAD such as www.pscad.com
AboutPSCAD ~
PSCAD v4 2 .1
Copyrigtt (C) 2006
Manloba HVOC Research Certre
a.ild Version 42.1 (Aug 11 2006)
Operefilg System \o"Mdows XP (Service Pack 2)
License Host locatlost
License I 1
Expiratial Date <Never>
OK
Figure 19: PSCAD Software Version 4.2.1
27
3.4.2 What is PSCAD?
PSCAD (Power System computer aided design) is software used to perform
the modeling analysis of such controller for a wide range of operating conditions.
PSCAD also enables the user to construct the circuit schematically, run simulation,
analyze the result and imaging the data in completely integrated in graphical
environment. Online plotting function, control meters are also included so that the
user can alter the system parameters during a simulation run and view the result
directly. PSCAD comes completely with a library of pre-programmed and tested
models, ranging from simple passive elements and control functions. It is easy to the
user to do any type of modeling such as FACTS devices. transmission line, breakers,
transformers etc. If a particular model does not exist, PSCAD provides the flexibility
of simple custom model either by assembling those graphically using existing models
or by utilizing an intuitively designed from Design Editor.
The following are some common models found in system studied using
PSCAD:
I. Resistors, inductors, capacitors
11. Mutually coupled windings, such as transformers.
III. Frequency dependent transmission lines and cables(including the most
accurate time domain line model)
IV. Current and voltage source.
V. Switches and breakers.
VI. Protection and relaying
VII. Diodes, thyristors and GTO's
VJJI. Analog and digital control functions
JX. AC and OC machines, exciters, governors, stabilizers and inertial model
X. Meters and measuring functions.
XI. Generic OC and AC controls
XII. HVDC,SVC and other FACTS controllers
XIII. Wind source, turbines and governor.
28
3.5 DVR structure
The power circuit of DVR consists of Energy Storage (DC supply), PWM
(Pulse Width Modulation) inverter and injection transfonner and is shown in Figure
20. Figure 21 is shown the setting mode for breaker operation.
Gn 2
g1
0 II
a:
Gb ' 2
g4
Timed Bleaker
()
~~ BRKA Gn G b
2 "' 2 g3 gS
c If',
B d1C
.. If',
A \t1c r If', BRKA
~c
-* ' G I Gt 2 1 ° 1 2
g6 g2
Figure 20: DVR structure
, Pbredkn] Timed Hredker I ogic ~)
I of Breaker Operltiol.s r.liel State
r 1 - Close
r. 2 r;" Open
Time of Fi'st Breaker Operation I 0.3 [s)
Time of 2nd Breaker Operation I O.S(s)
OK - Help ... J
Figure 21: Setting mode for breaker operation
29
I ..I I .. ~ I .. ~ ~~
- .. -..., ..., ..., •
3.6 Energy Storage
The de (direct current) voltage is used to provide the real power during the
voltage dips compensation.
3. 7 Pulse Width Modulation (PWM)
Pulse Width Modulation is one of the techniques of controlling the voltage
within de-de converter. With this technique the converter output voltage involves a
pulse modulated wave and the voltage is controlled by varying the duration of the
output voltage pulses. The control voltage will be achieved by comparing the
triangular wavefonn with a switching frequency. The reference control voltage output
obtained from the sinusoidal wave is compared with a high frequency triangular wave
of 5000 Hz with 50 % duty cycle. The high value of the switching frequency is
required for voltage dips compensation. Figure 22 to 24 represents the generation of
SPWM (Sinusoidal Pulse Width Modulation) signal for the VSI (Voltage Source
Inverter).
(a)
I ,;igndlgcn I '>•gndl Lcncr<>lor lw Inter pold .. IRJ
Fr~y Of Signal
Initial Phase of Slgnel
OK Cencet J
(b)
30
jsooo.o IH%1
~~--
'Triangle 3 j SOI%1
~ 1·1
- Help .•• _j
g1
[compar] Two Input Comparator ~,
OUpj when A>8 fht OCCIIS 11 OUpj when no translictl OCCIIS ro-()UpJ when A<-8 trst OCCli'S I ' 1 _ _ _ _
Help ... J (c)
Figure 22: PWM generation
a) The comparator generate an output equal to I when the magnitude of the
triangular waveform higher than sine wave/ control waveform.
b) The comparator generates an output equal to 0 when the magnitude of the
triangular waveform lowers or equal than sine wave/ control waveform.
T
Figure 23: Sinusoidal Pulse Width Modulation block diagram
31
<> g5
~:r -1 - ~ r I I
.. ill l l ~ li ...
~1
1 ~ ~ r1n~:r:r1 r: .. l ! l . . ·1 l. d ~~~~
Figure 24: Sinusoidal Pulse Width Modulation signal
32
3.8 PI controller
For the control system part, a Proportional Integration (PI) controller was used
to regulate the error between the supply voltage (measured) to the reference voltage
as shown in Figure 25. The reason PI controller being chosen is because the function
of the proportional itself will respond quickly toward the changes of error occurs. The
integration function is used to remove the offsets of the reference of steady state with
the input. Before DVR start to inject the voltage to the system, the timed
consideration is allowed for the synchronization process. The synchronization process
was made according to the possible system frequency deviation. The system is not
much deviated from 50 Hz frequency. Hence, it will help the load voltage without
phase jumps.
Vrg;s----
litt-~ _, p
PI comoler pererneters : Cortr ... -
rtegral gat! Pr~ lei gat! -100 -10
--0
5.17284 --0
0.493627
Figure 25: PI controller block diagram
33
Delta
3.8.1 Tuning the PI controller
Figure 26 show the interface to key in the parameter for the PI controller.
(pi _c tlr] PI Controller \w lnterpoldtion ~
Proportional Gail
lrtegral Tme Const.ert
Maxint.ln Linit
MlniTun Linl
r.ial ~ of lrtejJ'ator
lrtegration h4ethod
lOp IGi rw.o--1-10.0
lo.o
~lletpotatioll ~y
r. r
OK - ~-·· J
(a)
~, , [var] Variable Input Shder ~ 1 [vdr] Var1able Input Shder ~
Tile (for c1sp1ey n panel and meter) I ~I!!J'ai gail Tile (tor c1sp1ey n panel and meter) I Proportional gail
~ l PI cortroler pera Gr~ I PI cortroler pera
Display tile on icon? r;;- _:j Display tile on icon? I No .:] MaxilunVu roo- MaxilunVu f10 --hhlunVu lo.o hhlunVu ro.o --ra~vu 15.17283950317 rlial Vak.Je 1 0.493827160494
l.tis (eg: kA, kV, pu) r l.tis (eg: kA, kV, pu) I oa colediln (TtuNI c:uVa> leriulus 3 o.a colediln (TtuNI coma) leriulus 3
OK ~-·· OK ~ ... - .
(b)
Figure 26: Defining the PI controller parameter
34
The PSCAD simulation diagram ofthe proposed distribution network together
with the DVR and with control circuit is presented in Figure 27.
1 0 0 ~· • }
lkma •F
lv.£ " · 1 ooe 8 ~~-
? •
I --· 18'1531
I . ,. 1- .... I I
- :.. OlfiiJifZI
(a)
0.1. '"""' (• +~ CD 0
(b)
""-{ ~ 1.0 ,J~f
so.rf~
Figure 27: Complete power system network with DVR
35
CHAPTER4
RESULTS AND DISCUSSIONS
The simulation is carried out and the results are analyzed for different voltage
dip and fault condition.
Different voltage dip conditions
(i) No fault
(ii) Single line to ground fault without DVR
(iii) Double line to ground fault without DVR
(iv) Three phase to ground fault without DVR
(v) Injection voltage with DVR
(vi) Single line to ground fault with DVR
(vii) Double line to ground fault with DVR
(viii) Three phase to ground fault with DVR
Besides that, the graph of the output voltage VSC will shows as one of the
DVR part to generate 3-phase signals from de to ac voltage. Also the injection
transfonner graph will shows to see the changes before and after voltage dip occurs.
36
PSCAD simulation diagram of the proposed PWM is presented in Figure 28.
The signal (here the red, yellow and blue) is compared with the triangular waveform
(green) to generate ac waveform. Figure 29 shows the ac signal. Each of the signal is
120 degree a part each others.
1.50 • Vlri Vred Vyf!loN -~
1.00
0.50
0.00
-0.50
-1.00
-1.50 r---~--~--~----r---~---r--~----~--~---.
O.IXX> 0.010 O.ao!O O.<XJl 0.040 0.000 O.IB> 0.070 0.(8) O.ca> 0.100
Figure 28: Pulse Width Modulation
500 • fa
«X)
:m 200 100
~ 0
>- -100
-200
-D)
-400
-500
O.IXX> 0.010 O.ao!O O.<XJl 0.040 O.CB:l O.IB> 0.070 0.(8) O.ca> 0.100
Figure 29: Switching signals for inverter leg
37
4.1 Result
Case l : No fault
This section shows the simulation and results when no fault occurred at the system.
Voltage dip created at t = 0 s
Figure 30 shows the injected voltage and load voltage during normal condition.
:llOO • VII> ·- •lt!!l
I.J&I\hn~ :~
till ·~
1Bl
1.«1
~ O.IJJ >-
Q.Bl
0.<10
Q.2l
0.00
0.00 0.10 Q.2l 0.«1 O.!il
Figure 30: Three phase and load voltage at normal condition
38
Case 2: Single phase to ground fault without DVR
This section shows the simulation and results when single phase fault occurred at the
system.
Voltage dip created at t = 0.3 - 0.6 s
Figure 31 shows the red voltage phase drop during the voltage dip. Figure 32 shows
the load voltage drop during the voltage dip.
•'180
Figure 31: 3 phase voltages with single phase fault without DVR
ttl •YI!!I
tm
QID
... 0.110
Qt)
O.tl 100
Figure 32: Voltage at load side without DVR
39
Case 3: Double phase to ground fault without DVR
This section shows the simulations and results when double phase fault occurred at
the system.
Voltage dip created at t = 0.3 - 0.6 s
Figure 33 shows the blue and green voltage phase drop from 9.0 p.u to 3.0 p.u during
the voltage dip. Figure 34 shows the load voltage drop from 0.9 p.u to 0.6 p.u during
the voltage dip.
15.0 • VSI
10.0
5.0
~ 00 >.
-6.0
-10.0
-15.0
0.3) O.«l O.!iO 0.8> 0.10
Figure 33: 3 phases voltage at double phase fault without DVR
"""vu. cn.n 1.3> • Y!!!!
100
0.80
08) >.
O.«l I 0.3)
0.00
0.00 0.10 0.30 O.«l O.!iO 0.8> 0.10 0.8> 0.9J
Figure 34: Voltage at load side without DVR
40
Case 4 : Three phase to ground fault without DVR
This section shows the simulations and results when three phase fault occurred at the
system.
Voltage dip created at t = 0.3 - 0.6 s
Figure 35 shows all voltage phase drop from 9.0 p.u to 3.0 p.u during the voltage dip.
Figure 36 shows the load voltage drop from 0.9 p.u to 0.15 p.u during the voltage dip.
10.0 • V&l -~
ao 6.0
40 2.0
~ 0.0 >- -2.0
-4.0
~0
.a.o -10.0
02) 0.~ 0.«> 050 0.00 0.70
Figure 35: 3 phases voltage at three phase fault without DVR
VnT6 vu. ~ 1.20 • .Ym:l
1.00
O.!Kl ~. f 0.00
I >-
0.40 \
0.20 \_ 0.00
0.00 0.10 0.~ 0.40 0.50 0.00 0.70 O.!Kl O.!K>
Figure 36: Voltage at load side without DVR
41
Case 5 : Injected voltage with DVR
This section shows the simulations and results when fault occurred at the system.
Voltage dip created at t = 0.3- 0.6 s
Figure 37 shows the injection voltage from DVR system during the fault occurred.
•.w. • liSt
040 QlO
Figure 37: 3 phase injected voltage with DVR
42
Case 6 : Single phase to ground fault witb DVR
This section shows the simulations and results improvement of load voltage when
single phase to ground fault occurred at the system.
Voltage dip created at t = 0.3- 0.6 s
Figure 38 shows the improvement ofload voltage when DVR connected to the
system.
tal
noo --nm Ul Oll till
Figure 38: Voltage at load side with DVR for single phase fault
43
Case 7 : Double phase to ground fault with DVR
This section shows the simulations and results improvement of load voltage when
double phase to ground fault occurred at the system.
Voltage dip created at t = 0.3- 0.6 s
Figure 39 shows the improvement of load voltage from 0.15 p.u up to 0.9 p.u when
DVR connected to the system.
1.2) •VmB
1.00
, .. --... ---IIWNW'NtNW,Wl'fiN~WJ#:~\ ~ o.oo r- ·- , v -
{
o.ro I
O.«l f
021
0.00
Figure 39: Voltage at load side with DVR for double phase fault
44
Case 8 : Three phase to ground fault with DVR
This section shows the simulations and results improvement of load voltage when
three phase to ground fault occurred at the system.
Voltage dip created at t = 0.3 - 0.6 s
Figure 40 shows the improvement of load voltage from 0.6 p.u up to 0.9 p.u when
DVR connected to the system.
Vmsvu:QcdB
121 •Vms
1.00
'1/>fWNA\~Wt/MW##I'#N.J'v./,.---O.lll ,...,.-
1/
O.En I t - j
0.40 I I I
021
0.00
0.00 0.10 O.al O.ll 0.40 O.fn O.En 0.10 O.lll 0.00
Figure 40: Voltage at load side with DVR three phase fault
45
CHAPTERS
CONCLUSION AND RECOMMENDATION
5.1 Conclusion
Voltage dips are most common problems faced by the consumer. Many
industries face the problem of voltage dips problem leading to loss in production cost.
The common solution for this problem is to use full UPS system but it is more costly.
This project describes a solution to the voltage dip problem and the
compensation technique using custom power electronic device DVR which was
designed by using PSCAD software. The design and also the application of DVR for
voltage dip and the simulation results for different fault were presented. A PWM
based control scheme was implemented to generated 3-phases signal and this PWM
scheme only require voltage measurement. To control the voltage, PI controller has
been developed to control the voltage automatically. It uses a closed loop control
system to detect the phase difference and magnitude error between the voltage during
and before the voltage dip. In addition to mitigation of voltage dip, the simulation
result indicates that DVR provides additional benefit of output voltage improvement.
The DVR injects appropriate voltage component to correct rapidly any voltage dip to
keep the load voltage balanced and constant at the nominal value. The efficiency and
effectiveness in voltage dip compensation is demonstrated by the simulation results
ensuring high quality in power supply.
46
5.2 Recommendation
In order to verify the simulation results, understanding the behavior of the
Dynamic Voltage Restorer is important to mitigate the voltage dips by selecting the
right configuration of DVR. This project mainly concentrated on about mitigation of
the output voltage whereas the other power quality issues are not taken into account.
So in future work, voltage and current harmonics also need to be considered as one of
the power quality issues and DVR is to be designed to mitigate the voltage and
current harmonics.
47
REFERENCES
[1] David Chapman, "Voltage dips", Copper Development Association, pg 1-6,
2001.
[2] C.Benachaiba and B.Ferdi, "Power Quality Improvement using DVR", American
Journal of Applied Sciences (6), vol3, p.p 396-400, 2009.
[3] C. DiPerna, P.Verde, A.Sannino, M. H.J. Bollen, "Static series compensator for
voltage dips mitigation with zero sequence injection capability", Bologna Power
Tech Conference, p.p 23-26, June 2003.
[4] K.W.E.Cheng, Y.L.Ho, S.L.Ho, K.P.Wong, NCCheung and T.K.Cheung,"
Investigation of Voltage Dips Restorer Using Square Wave Inverter" the 30'h
Annual Conference of the IEEE Industrial Electronics Society, Busan, Korea, p.p
2-6, November 2004.
[5] C. S. Chang, Zhemin Yu, "Distributed Mitigation of Voltage Sag by Optimal
Placement of Series Compensation Devices Based on Stochastic Assessment",
IEEE transactions on Power Systems, Vol.19, No.2, May 2004, pg.788-795.
[6] A.EI Mofty, K.Youssef,"Industrial power quality problems," Alexandria
Electricity Company, Alexandria, Egypt, pg.18-21, June 2007.
[7] C.Zhan, V.K. Ramachandaramurty, A Arulampalam, C.Fitzer, S.Kromlidis,
M.Bames, N.Jenkins, "Dynamic Voltage Restorer bassed on Voltage Space
vector PWM control", lEE transactions on Industry Apllication, Vol. 37 (No. 6)
Nov/Dec 200l,pg. 1855-1863.
[8] C.Zhan, V.K. Ramachandaramurty, A Arulampalam, C.Fitzer, S.Kromlidis,
M.Bames, N.Jenkins," Control of a battery supported dynamic voltage restorer",
lEE proceedings on transmission and distribution, Vol 149 ( No 5), Sep.2002, pg.
533-542.
[9] Ned Mohan, Tore M. Undeland, Willian P.Robbins, " Power Electronic
Converters, Application and design", (book), Chapter 8- Switch- Switch mode dc
ac inverters, John Wiley and sons, Inc, 2-3,p.g 200-248.
[10] P.T Nguyen, Tapan K.Saha, "Dynamic voltage restorer against balanced and
unbalanced voltage sags: Modelling and Simulation", IEEE transactions on Power
Delivery, 2004, pg.l-6.
48
[11] Kasumi Perera, Arulampalam, Sanath Alahakoon, Daniel Salomonsson
"Automated Control Technique for a Single Phase Dynamic Voltage Restore",
Proceedings of the International Conference and Automated, December 2006,
p.g 103-108
[12] M. Haberberger and F. W. Fuchs, (no year stated), Protection Strategies for
IGBT Current Source Inverters. pp. 1-7.
[13] P. Pillay, E. I. Odendal and R. G. Harley. (1984). Torque and Speed Harmonic
Analysis of a PWM CSI-Fed Induction Motor Drive, pp. 1-7.
[14] Jos Arrillaga and Neville R. Watson, (2003), Power System Harmonics, 2"d
Edition. John Wiley & Sons, Ltd., England.
[15] M. Lafoz and I.J. Iglesias, C. Veganzones, (2002), Three-Level Voltage Source
Inverter with Hysteresis-Band Current Control, pp.l-1 0
[16] IEEE recommended practice for evaluating electric power
system compatibility with electronic process equipment, IEEE
Standard 1346-1998. 1998.
49