by george a. fernandez - university of...
TRANSCRIPT
1
WIND LOAD RESISTANCE OF COMPOSITE STRUCTURAL INSULATED PANELS
By
GEORGE A. FERNANDEZ
A THESIS PRESENTED TO THE GRADUATE SCHOOL OF THE UNIVERSITY OF FLORIDA IN PARTIAL FULFILLMENT
OF THE REQUIREMENTS FOR THE DEGREE OF MASTER OF ENGINEERING
UNIVERSITY OF FLORIDA
2013
2
© 2013 George A. Fernandez
3
To my mom, Claudia, my brother, Kevin and my grandparents, Coco and Papa Mundo
4
ACKNOWLEDGMENTS
I would like to thank my advisor, Forrest J. Masters, Ph.D., P.E.; and my
committee members, Kurtis R. Gurley, Ph.D. and David O. Prevatt, Ph.D., P.E. for their
support and guidance throughout this project. I thank my colleagues, Dany Romero,
Abraham Alende, Carlos Lopez, Scott Bolton, Jimmy Jesteadt, Alex Esposito, Jason
Smith, James Austin, Johann Weekes, Sylvia Laboy, Alon Krauthammer, Anthony
Chanlee and Justin Henika, for their support and assistance throughout this project.
I would also like to acknowledge NSF CMMI for supporting this project and Dr.
Ed Sutt from Simpson Strong-Tie for their assistance.
5
TABLE OF CONTENTS
page
ACKNOWLEDGMENTS .................................................................................................. 4
TABLE OF CONTENTS .................................................................................................. 5
LIST OF TABLES ............................................................................................................ 7
LIST OF FIGURES .......................................................................................................... 8
LIST OF ABBREVIATIONS ........................................................................................... 12
LIST OF NOMENCLATURE .......................................................................................... 13
ABSTRACT ................................................................................................................... 14
CHAPTER
1 INTRODUCTION .................................................................................................... 16
Scope of Research ................................................................................................. 17 Organization of this Document ................................................................................ 17
2 BACKGROUND ...................................................................................................... 18
Traditional Light Wood Frame Construction ............................................................ 18
Applicable Standards ....................................................................................... 19 Prior Research ................................................................................................. 19
Sandwich Panels .................................................................................................... 20 Composite Beam Theory .................................................................................. 20 Structural Insulated Panels ............................................................................... 21
Composite structural Insulated Panels ............................................................. 21
3 EXPERIMENTAL DESIGN ..................................................................................... 24
4 DESIGN AND EVALUATION OF CSIP WALL CONNECTION ............................... 26
5 EVALUATION OF CSIPS WALL ASSEMBLY SUBJECTED TO WIND PRESSURE LOADING ........................................................................................... 32
Pressure step loading function ................................................................................ 33 Individual Test Results Static Step Loading 48.05 kg/m3 (3 pcf) ...................... 33
Test #1 ....................................................................................................... 33 Test #2 ....................................................................................................... 34 Test #3 ....................................................................................................... 35 Test #4 ....................................................................................................... 36
6
Individual Test Results Static Step Loading 16.02 kg/m3 (1 pcf) ...................... 37
Test #1 ....................................................................................................... 37 Time-varying pressure sequence ............................................................................ 38
Individual Test Results Dynamic Loading 48.05 kg/m3 (3 pcf) .......................... 39 Test #1 ....................................................................................................... 39 Test #2 ....................................................................................................... 40 Test #3 ....................................................................................................... 41 Test #4 ....................................................................................................... 42
Test #5 ....................................................................................................... 43 Test #6 ....................................................................................................... 44
Individual Test Results Dynamic Loading 16.02 kg/m3 (1 pcf) .......................... 44 Test #1 ....................................................................................................... 44 Test #2 ....................................................................................................... 45
Summary of Pressure Loading Results................................................................... 46 Comparison of Capacity and Failure Modes ........................................................... 48
6 EVALUATION OF CSIP WALL ASSEMBLY SUBJECTED TO SHEAR LOADING ................................................................................................................ 85
Methodology ........................................................................................................... 85 Results .................................................................................................................... 85
7 CONCLUSIONS ..................................................................................................... 90
APPENDIX
RESULTS OF LATERAL LOAD TEST .......................................................................... 93
LIST OF REFERENCES ............................................................................................... 98
BIOGRAPHICAL SKETCH .......................................................................................... 101
7
LIST OF TABLES
Table page 3-1 CSIP Panel Inventory ........................................................................................ 25
3-2 Testing Matrix .................................................................................................... 25
4-1 Fastener summary ............................................................................................. 31
4-2 T-test results for single fastener at two different temperatures .......................... 31
5-1 Static pressure step and equivalent mean wind speed ...................................... 83
5-2 Time varying basic wind speed and mean pressure .......................................... 83
5-3 Maximum pressure comparison table ................................................................ 83
5-4 Maximum deflection table .................................................................................. 84
6-1 Racking test results ........................................................................................... 89
8
LIST OF FIGURES
Figure page
2-1 SIP wall anatomy ................................................................................................ 23
2-2 CSIP cross sectional illustration ......................................................................... 23
4-1 Proposed construction assembly ........................................................................ 28
4-2 Lateral resistance testing. Photo courtesy of George Fernandez, University of Florida. ............................................................................................................... 28
4-3 Lateral capacities of nail fasteners ..................................................................... 29
4-4 Lateral capacities stratified by effective area ...................................................... 30
5-1 Two photographs of the pressure testing components A) HAPLA testing apparatus B) exterior view of testing chamber. Photo courtesy of George Fernandez and Forrest Masters, University of Florida. ....................................... 50
5-2 Strain gauge location .......................................................................................... 51
5-3 Reaction frame connection detail ....................................................................... 51
5-4 Pressure step loading function ........................................................................... 52
5-5 48.05 kg/m3 (3 pcf) CSIP Test 1 pressure time history ....................................... 52
5-6 48.05 kg/m3 (3 pcf) CSIP Test 1 deflection time history ..................................... 53
5-7 48.05 kg/m3 (3 pcf) CSIP Test 1 de-bonding and failure sketch ......................... 53
5-8 48.05 kg/m3 (3 pcf) CSIP Test 1 failure. Photo courtesy of George Fernandez, University of Florida. ........................................................................ 54
5-9 48.05 kg/m3 (3 pcf) CSIP Test 1 summary ......................................................... 54
5-10 48.05 kg/m3 (3 pcf) CSIP Test 2 pressure time history ....................................... 55
5-11 48.05 kg/m3 (3 pcf) CSIP Test 2 deflection time history ..................................... 55
5-12 48.05 kg/m3 (3 pcf) CSIP Test 2 de-bonding and failure sketch ......................... 56
5-13 48.05 kg/m3 (3 pcf) CSIP Test 2 summary ......................................................... 56
5-14 48.05 kg/m3 (3 pcf) CSIP Test 3 pressure time history ....................................... 57
9
5-15 48.05 kg/m3 (3 pcf) CSIP Test 3 deflection time history ..................................... 57
5-16 48.05 kg/m3 (3 pcf) CSIP Test 3 de-bonding and failure sketch ......................... 58
5-17 48.05 kg/m3 (3 pcf) CSIP Test 3 summary ......................................................... 58
5-18 48.05 kg/m3 (3 pcf) CSIP Test 4 pressure time history ....................................... 59
5-19 48.05 kg/m3 (3 pcf) CSIP Test 4 deflection time history ..................................... 59
5-20 48.05 kg/m3 (3 pcf) CSIP Test 4 summary ......................................................... 60
5-21 16.02 kg/m3 (1 pcf) CSIP Test 1 pressure time history ....................................... 60
5-22 16.02 kg/m3 (1 pcf) CSIP Test 1 deflection time history ..................................... 61
5-23 16.02 kg/m3 (1 pcf) CSIP Test 1 de-bonding and failure sketch ......................... 61
5-24 16.02 kg/m3 (1 pcf) CSIP Test 1 failure. Photo courtesy of George Fernandez, University of Florida. ........................................................................ 62
5-25 16.02 kg/m3 (1 pcf) CSIP Test 1 summary ......................................................... 62
5-26 Complete time-varying pressure sequence ........................................................ 63
5-27 Sample of the time-varying pressure sequence.................................................. 63
5-28 48.05 kg/m3 (3 pcf) CSIP Test 1 time varying pressure time history ................... 64
5-29 48.05 kg/m3 (3 pcf) CSIP Test 1 time varying pressure deflection time history .. 64
5-30 48.05 kg/m3 (3 pcf) CSIP Test 1 time varying pressure deflection-load plot ....... 65
5-31 48.05 kg/m3 (3 pcf) CSIP Test 1 de-bonding and failure sketch ......................... 65
5-32 48.05 kg/m3 (3 pcf) CSIP Test 2 time varying pressure time history ................... 66
5-33 48.05 kg/m3 (3 pcf) CSIP Test 2 time varying pressure deflection time history .. 66
5-34 48.05 kg/m3 (3 pcf) CSIP Test 2 time varying pressure deflection-load plot ...... 67
5-35 48.05 kg/m3 (3 pcf) CSIP Test 2 de-bonding and failure sketch ........................ 67
5-36 48.05 kg/m3 (3 pcf) CSIP Test 3 time varying pressure time history ................... 68
5-37 48.05 kg/m3 (3 pcf) CSIP Test 3 time varying pressure deflection time history .. 68
5-38 48.05 kg/m3 (3 pcf) CSIP Test 3 time varying pressure deflection-load plot ...... 69
5-39 48.05 kg/m3 (3 pcf) CSIP Test 3 de-bonding and failure sketch ........................ 69
10
5-40 48.05 kg/m3 (3 pcf) CSIP Test 4 time varying pressure time history ................... 70
5-41 48.05 kg/m3 (3 pcf) CSIP Test 4 time varying pressure deflection time history .. 70
5-42 48.05 kg/m3 (3 pcf) CSIP Test 4 time varying pressure deflection-load plot ...... 71
5-43 48.05 kg/m3 (3 pcf) CSIP Test 4 de-bonding and failure sketch ........................ 71
5-44 48.05 kg/m3 (3 pcf) CSIP Test 5 time varying pressure time history ................... 72
5-45 48.05 kg/m3 (3 pcf) CSIP Test 5 time varying pressure deflection time history .. 72
5-46 48.05 kg/m3 (3 pcf) CSIP Test 5 time varying pressure deflection-load plot ...... 73
5-47 48.05 kg/m3 (3 pcf) CSIP Test 5 de-bonding and failure sketch ........................ 73
5-48 48.05 kg/m3 (3 pcf) CSIP Test 6 time varying pressure time history ................... 74
5-49 48.05 kg/m3 (3 pcf) CSIP Test 6 time varying pressure deflection time history .. 74
5-50 48.05 kg/m3 (3 pcf) CSIP Test 6 time varying pressure deflection-load plot ...... 75
5-51 48.05 kg/m3 (3 pcf) CSIP Test 6 de-bonding and failure sketch ........................ 75
5-52 16.02 kg/m3 (1 pcf) CSIP Test 1 time varying pressure time history ................... 76
5-53 16.02 kg/m3 (1 pcf) CSIP Test 1 time varying pressure deflection time history .. 76
5-54 16.02 kg/m3 (1 pcf) CSIP Test 1 time varying pressure deflection-load plot ....... 77
5-55 16.02 kg/m3 (1 pcf) CSIP Test 1 de-bonding and failure sketch ......................... 77
5-56 16.02 kg/m3 (1 pcf) CSIP Test 2 time varying pressure time history ................... 78
5-57 16.02 kg/m3 (1 pcf) CSIP Test 2 time varying pressure deflection time history .. 78
5-58 16.02 kg/m3 (1 pcf) CSIP Test 2 time varying pressure deflection-load plot ...... 79
5-59 16.02 kg/m3 (1 pcf) CSIP Test 2 de-bonding and failure sketch ......................... 79
5-60 Deflection-load results for the 16.02 kg/m3 (1 pcf) panels .................................. 80
5-61 Deflection-load results for the 48.05 kg/m3 (3 pcf) panels .................................. 80
5-62 Observed damage. Photo courtesy of George Fernandez, University of Florida. ............................................................................................................... 81
5-63 Un-filtered mid-span deflection versus pressure................................................. 81
5-64 Filtered mid-span deflection versus pressure ..................................................... 82
11
5-65 Time-varying pressure vs. mid-span strain ......................................................... 82
6-1 Diagram of racking test setup ............................................................................. 87
6-2 Racking test load deflection interaction .............................................................. 87
6-3 Racking test face-sheet de-bonding. Photo courtesy of George Fernandez and Scott Bolton, University of Florida. ............................................................... 88
6-4 Racking test face-sheet wrinkling. Photo courtesy of George Fernandez and Scott Bolton, University of Florida. ...................................................................... 88
A-1 Lateral nail capacity failure results A-S-8d. Photo courtesy of George Fernandez, University of Florida. ........................................................................ 93
A-2 Lateral nail capacity failure results B-RS-8d. Photo courtesy of George Fernandez, University of Florida. ........................................................................ 94
A-3 Lateral nail capacity failure results C-S-6d. Photo courtesy of George Fernandez, University of Florida. ........................................................................ 95
A-4 Lateral nail capacity failure results SST-SS-6d. Photo courtesy of George Fernandez, University of Florida. ........................................................................ 96
A-5 Lateral nail capacity failure results SST-RS-6d. Photo courtesy of George Fernandez, University of Florida. ........................................................................ 97
12
LIST OF ABBREVIATIONS
ASCE AMERICAN SOCIETY OF CIVIL ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
CSIP COMPOSITE STRUCTURAL INSULATED PANELS
FEMA FEDERAL EMERGENCY MANAGEMENT AGENCY
IBHS INSTITUTE OF BUSINESS & HOME SAFETY
NOAA NATIONAL OCEANIC AND ATMOSPHERIC ADMINISTRATION
UF UNIVERSITY OF FLORIDA
UAB UNIVERSITY OF ALABAMA AT BIRMINGHAM
SIP STRUCTURAL INSULATED PANELS
13
LIST OF NOMENCLATURE
Efz Face sheet modulus of elasticity
Ecz Foam core modulus of elasticity
G Shear modulus
B Width
C Core thickness
A Cross sectional area
T Face thickness
D Distance between center-lines of opposite faces
q Distributed load per unit length
H Overall thickness
Δ Displacement at mid-span
L Span length
D Flexural rigidity of beam
𝑙 Integral length scale
𝑓 Frequency
U Mean velocity
Cp Pressure coefficient
Ρ Density of air
v Velocity (mph)
qz Velocity pressure (psf)
Kz 0.85, Velocity pressure coefficient
Kzt 1.0, Topographic factor
Kd 0.85, Wind directionality factor
14
Abstract of Thesis Presented to the Graduate School of the University of Florida in Partial Fulfillment of the
Requirements for the Degree of Master of Engineering
WIND LOAD RESISTANCE OF COMPOSITE STRUCTURAL INSULATED PANELS
By
George A. Fernandez
December 2013 Chair: Forrest Masters Major: Civil Engineering
The study evaluates the out-of-plane wind load resistance and in-plane shear
resistance of a new thermoplastic CSIP developed by the University of Alabama at
Birmingham, to address the growing demand for affordable, energy efficient building
materials. Uniaxial bending response of these panels under realistic hurricane wind load
conditions was evaluated. The panels were subjected to a step- loading pressure
sequence and a dynamic wind pressure time history sequence. The dynamic wind
pressure time history was derived from boundary layer wind tunnel model experiments.
Similar failure mechanisms were observed for both load sequences. Damage was
confined primarily to the timber connection plate, however de-bonding between the skin
and foam was observed. The pressure step loading function ranged from 0.24-6.96 kPa
and an average mid-span deflection of 9.00 cm over a 243.84 cm span was observed.
The dynamic pressure loads ranged from 0.24-5.00 kPa with an average mid-span
deflection of 7.00 cm over a 243.84 cm span. A load-deflection relationship was
established and the use of a theoretical Equation, developed by Allen (1969), was used
15
to compare the test data. Investigative testing of in-plane shear resistance was
conducted and compared with test conducted by Kermani et al. (2006).
16
CHAPTER 1 INTRODUCTION
Coastal communities have experienced an increase of 39% in shoreline county
population from 1970 to 2010 (2012 NOAA). The increase in coastal population requires
a higher demand on infrastructure (e.g. homes, apartments, high rises, roads and
bridges). Coastal communities contribute nearly $6.6 trillion dollars or half of the gross
domestic product in the United States. As engineers strive to provide improved methods
and building materials for construction to mitigate damages arising from hurricane
episodes, composite materials have received greater attention. Composite material form
parts of a pre-engineered and modular building system originally developed for cladding
(Davies 1993), and are becoming more widespread in civil, aerospace, and automotive
applications (Schnabl 2007). There are many benefits for its current use in construction.
This innovative resource is stronger than conventional wood fibers and highly resistant
to mold, mildew, and decay. Composites provide the opportunity to remove organic
material from structural components of the home, (e.g loadbearing walls and floor
systems) and make them less vulnerable to natural decay. Another benefit is its energy
efficiency. The insulation is not interrupted by studs in the wall and closed-cell
polystyrene foams have a high R-value (Cathcart 1998).
This study focuses on the out-of-plane bending behavior and in-plane shear
resistance of the CSIP described in Vaidya (2010). The results bridge the knowledge
gap and augment prior work in the characterization of CSIP mechanical properties. us
to recreate such extreme events and quantify the behavior of such components.
17
Scope of Research
The research objectives of this study are as follows:
1. Quantify the resistance for lateral nail loads, and temperature effects on CSIP thermal composite face-sheets
2. Design connection details for wall-to-foundation and wall-to-roof connections
3. Evaluates the performance of the composite panels under uniaxial bending
4. Evaluate the performance of the composite panels under shear in line with the wall
Organization of this Document
Chapter 2 provides the background to CSIP and current numerical methods for
evaluation of mechanical performance. Chapter 3 describes the experimental
methodology for structural testing and the significance of the data being collected.
Chapter 4 discusses the design and results of CSIP wall connection detail. Chapter 5
focuses on the results of the quasi static pressure loading and the time varying pressure
loading. Chapter 6 addresses the preliminary findings on shear wall behavior from
racking test. Chapter 7 concludes with recommendations for future research.
18
CHAPTER 2 BACKGROUND
Composite structural insulated panels (CSIPs) are a derivative of sandwich
panels, which were first introduced into the consumer market in the form of structural
insulated panels (SIP) in 1951 (Cathcart 1998). SIPs gained popularity in the residential
construction industry due to their competitive material costs, energy efficiency, and a
decrease in the amount of time and labor required for construction. Pre-fabricated
panels allowed for wall assemblies to be brought in assembled and offer time saving
options such as electrical pre wiring, as well as rough opening for items such as glazing
and exterior finishes.
Options for SIP skin materials include oriented strand board (OSB), plywood,
gypsum wallboard, or wafer board. A SIP panel is usually termed a ‗composite‘
structural insulated panel (CSIP) if the face-sheet material is a thermoplastic, carbon
fiber, or e-glass. This chapter discusses light-wood frame construction and sandwich
panel construction. Sandwich panel construction will encompass both SIP panels and
CSIP panels.
Traditional Light Wood Frame Construction
Light wood frame construction has seen little to no change since the 1950s with
the introduction of plywood sheathing for light frame construction. Variation in lumber
properties provided a difficult material to produce standard prediction methods (1983
Gromola). Light frame wood walls presented a unique challenge to early researchers as
the varying lumber properties and indefinite combination made it cost prohibitive to test
every wall system. The development of computer based analysis in the early 1970s
made it possible to create analytical models that would allow for the prediction of infinite
19
lumber combinations (1983 Gromola). Additional research demonstrated that a good
strength prediction for light frame wood walls was a series of composite I- joist. In his
early research, Polensek (1984) found that wall studs have the greatest effect on overall
wall capacities.
Applicable Standards
Current wood frame construction is governed by American Wood Council (AWC)
formerly ANSI / AF & PA. The standards designed focus on nail capacity as they have
been identified to be the weak point for connection to adequately transfer loads from
one member to another. Per AWC, Special Design provisions for wind and seismic
(SDPWS) wall capacity prior to design factors, for uniform load capacities (psf) for wall
sheathing resisting out of plane loads, are summarized in table 3.2.1. Sheathing
capacity is prescribed according to stud spacing, sheathing type and sheathing
thickness.
ASTM E 72 is used to conduct strength testing of panels for building
construction. ASTM E 72 p section 12 describes the method for the transverse loading
of a vertical wall with either a uniform pressure in a chamber or, a uniform load with a
bag or, loading the wall specimen at its quarter points. The significance of this testing is
to quantify the resistance of the wall subjected to out of plane loads. Section 14 of
ASTM E 72 refers to racking test for shear walls.
Prior Research
The forestry and paper group has been conducting and publishing research on wood
products as early as the 1970s. Several models presently exist to estimate the
capacities of wood wall.
20
Sandwich Panels
Composite Beam Theory
The first approaches to composite beam theory were developed in the early 20th
century (e.g, Timoshenko 1921; Newmark 1951). Most studies assume linear elastic
behavior and perfect bonding between different layers to estimate mechanical behavior,
however, these assumptions are simplifications of complex behavior that was difficult to
quantify during this time period. Recent research on composite sandwich panels
includes Baehre (1994), Roberts (2002), Girhammar (2008a, 2008b, 2009), Manalo
(2010), Uddin (2010), Fam (2010), Vaidya (2010) and Mohammed (2011). Perhaps the
most accepted method to account for an imperfect bond can be found in Newmark
(1951); Girhammer and other researchers developed closed-form solutions with the
advancement of computer algorithms and technology. (Girhammer et al., 1993, 2008,
2009).
This analysis herein applies classical beam theory to benchmark results. Euler-
Bernoulli beam theory with a shear deformation term is shown to match the load
deflection relationship within an acceptable tolerance (5%). The closed form solution
developed by Allen (1969) Equation 2-1 and 2-2 appear to be good predictors of load
deflection relationship for uniaxial bending of CSIP panels. Ultimately Equations 2-3 and
2-4 were used to estimate deflection.
(2-1)
(2-2)
(
)
(2-3)
21
(2-4)
Structural Insulated Panels
Since introduced in the 1950s, SIP research and development was primarily
done by private companies and most of the advancements were considered proprietary.
Figure 2-1 shows the cross-section of a typical SIP wall. SIP panels consist of a foam
core sandwiched between two wood fiber skins. The wood fiber skins are primarily
oriented strand board but are also made out of plywood, gypsum wallboard, or wafer
board. These materials are susceptible to organic decay and can foster various types of
mold if left unattended.
Composite structural Insulated Panels
The panels in this study (Figure 2-2) consist of a low-cost thermoplastics
orthotropic glass/ propylene (glass-PP) laminate exterior face-sheet and expanded
polystyrene foam (EPS) for the core material (Mousa 2010). With recent developments
in cost effective textile including, hot-melt impregnation, direct reinforced thermoplastics
(DRIFT), vacuum thermoforming, and long fiber thermoplastics (LFTs), it is now
possible to combine various high strain-energy fibers with a wide variety of
thermoplastic polymers to produce very low cost composite product, such as the
aforementioned test subject. Advantages of these CSIP panels include:
1. Faster construction: CSIPS can be constructed in one-third of the time of conventional light wood frame construction.
2. Environmental consciousness: The use of this product causes waste reduction and allows the recycling of any remaining material.
3. Design flexibility: These panels can be used for the construction of a simple storage building or even a large office building.
22
4. High thermal performance: It maintains a high R-value ~3.85-5.50/in of thickness
5. Corrosion resistance: E-glass and EPS foam exhibit resistance to mold and corrosion.
CSIP construction can have a potential impact beyond the coastal United States.
Its low manufacturing cost and the ease of shipping worldwide make it an excellent
candidate to address some of the needs of many underdeveloped coastal communities.
Neither cost effective, nor fortified construction form part of the methodology for building
construction for many underdeveloped countries (Prevatt et al., 1994). As a result,
modular construction can have a positive impact by providing an alternative method of
construction and aid in mitigation of home loss in coastal communities around the world.
Limitations do exist for this type of composite assembly, which were highlighted
in the research conducted by Vaidya et al. (2010). He found that delamination occurred
between the foam and the exterior skin during axial loading of the wall assembly.
Similar results were observed in this study that applied uniaxial bending. Delamination
and its contribution to the findings of this research is further delineated in chapter 5
however it is important to note that delamination may have contributed to the nonlinear
strain behavior observed in the compression face-sheet.
Part of the research initiative was to quantify the performance characteristics of
such panels and compare test results to analytical results. A classical beam theory will
be applied to the analysis of the test results. This research applies closed form
composite beam theory approach.
23
Figure 2-1. SIP wall anatomy
Figure 2-2. CSIP cross sectional illustration
24
CHAPTER 3 EXPERIMENTAL DESIGN
The principal objective of this study was to develop a testing framework to
evaluate CSIP wall assemblies subjected to uniaxial bending caused by pressure
loading and in-plane shear transferred from the diaphragm to the foundation through the
shear wall. Table 3-1 provides a summary of CSIP panel inventory provided by UAB.
Table 3-2 identifies the testing matrix of the panels that will be subjected to uniaxial
bending caused by pressure loading and racking.
The study was conducted in three phases.
Phase one studied the interaction and failure modes of five different nail type fasteners (see Table 4-1), subjected to single shear to design the optimal connection.
Phase two subjected the completed wall assembly and connection to a pressure step loading function and a time-varying pressure sequence.
Phase three consisted of the preliminary investigation of shear resistance with two complete wall assemblies.
The pressure data was derived from wind load tests conducted on a model of a
low-rise rectangular building at the University of Western Ontario (UWO) Boundary
Layer Wind Tunnel. (Ho et al., 2003) The final stage of the research applied in-plane
shear loads to two wall assemblies using the racking procedure described in ASTM
E72. The connection details were identical to the bending test configuration.
25
Table 3-1. CSIP Panel Inventory
Table 3-2. Testing Matrix Panel Type Test type A B C Sum Static 1 4 0 5 Dynamic step-loading 2 6 0 8 Racking 0 0 4 4
Total 17
Panel type Panel Dimension Core Density Panels #
A 139.7 x 1219.2 x 2438.4 mm
(5.5‖ x 4‘ x 8‘) 16.02 kg/m3 (1 pcf) 4
B 139.7 x 1219.2 x 2438.4 mm
(5.5‖ x 4‘ x 8‘) 48.05 kg/m3 (3 pcf) 11
C 254.0 x 1219.2 x 2438.4 mm
(10‖ x 4‘ x 8‘) 48.05 kg/m3 (3 pcf) 8
D 139.7 x 1219.2 x 1828.8 mm
(5.5‖ x 4‘ x 6‘) 48.05 kg/m3 (3 pcf) 1
E 254.0 x 1219.2 x 2438.4 mm
(10‖ x 4‘ x 8‘) 48.05 kg/m3 (3 pcf) 1
26
CHAPTER 4 DESIGN AND EVALUATION OF CSIP WALL CONNECTION
The objective of this phase was to design an easily constructible connection
detail for the implementation in the field as depicted in Figure 4-1. Ease of construction
will help to promote the use of such panels in under developed regions.
The lateral capacities of five nail type fasteners, presented in Table 4-1, were
quantified using a modified lateral resistance ASTM D 1761 test performed on a Tinius
Olson 400 Super ―L‖ Hydraulic Test Machine. Thermoplastic material constitutive
properties are temperature dependent, thus face-sheets were tested at two ambient
temperatures: 21.1˚C and 32.2˚C (70˚F, 90˚F). ASTM D 1761 loading rates were
modified to 30-40 times faster than prescribed to minimize temperature effects on
cooling of the face-sheets. The thermoplastic composite face-sheets were first
separated from the foam core and cut into 38.1 cm x 8.8 cm (15 in x 3.5 in) specimens,
then stored in a temperature controlled room. Samples were assembled in two stages.
Stage one prepared a southern yellow pine (SYP) 2 x 4 on edge with a steel bar at one
end. Stage two, immediately preceded testing, attached a face-sheet specimen to the
opposite end of the SYP 2 x 4 with a single fastener. The single fastener was driven in
by a Bostitch Magnesium Model No. F21PL nail gun 620 at 53 kPa (90 psi). The Bostich
nail gun was calibrated to a pressure that set the fastener flush. The modified ASTM D
1761 loading was required to maintain the face-sheets at prescribed temperature for the
duration of the test with surface cooling kept to less than 0.9 ˚C (0.5 ˚F).
Figure 4- shows a photo of a sample and an illustration of the individual
components of the test sample. Figure 4-3 and Figure 4-4 provide a summary of the
initial test conducted to aid in the selection of a fastener that would provide the greatest
27
lateral resistance. A single fastener was chosen based on the results. Thirty additional
tests were performed on the chosen fastener to quantify dependency on the lateral
capacity as a function of specific gravity and moisture content. Specific gravity and
moisture content were obtained using ASTM standards, ASTM 2395 and ASTM 4442
respectively. From each of the samples tested multiple sections of timber member were
taken and evaluated for specific gravity and moisture content and then recorded. This
provided a direct comparison to NDS lateral capacity of sheathing to main members.
Connection Testing Results: Tests were performed under two temperatures:
21.1˚C (70˚F) and 32.2˚C (90˚F), and a student‘s t-test was performed to compare the
results (Table 4-2). All but one fastener failed to reject the null hypothesis, which
indicates that temperature did not play a significant role in the determination of the
lateral capacity of a face-sheet attached with a single nail. The only nail that failed to
reject the null hypothesis was B-RS-8d, which is a ring shank common 8d nail. Figure 4-
4 groups the results per effective area. All of the fasteners were found to be suitable for
assembling the CSIP systems. The stainless steel ring shank 6d common nail (SST-SS)
was selected for its resistance to rusting in corrosive coastal environments.
28
Figure 4-1. Proposed construction assembly
Figure 4-2. Lateral resistance testing. Photo courtesy of George Fernandez, University
of Florida.
29
Figure 4-3. Lateral capacities of nail fasteners
30
Figure 4-4. Lateral capacities stratified by effective area
31
Table 4-1. Fastener summary
ID Shank Shank diameter Head diameter Shank length Aeff
mm in mm in mm in mm2 in2
A-S Smooth 3.33 0.131 7.19 0.283 63.50 2.500 31.612 0.049
B-RS Ring 3.33 0.113 6.99 0.275 60.33 2.375 31.612 0.049
C-S Smooth 3.33 0.113 7.19 0.283 50.80 2.000 34.193 0.053
SST-RS Ring 3.33 0.113 6.99 0.275 50.80 2.000 31.612 0.049
SST-SS Spiral 3.33 0.113 6.71 0.264 50.80 2.000 29.032 0.045
Table 4-2. T-test results for single fastener at two different temperatures
Paired test 32.22⁰C
A-S-8d B-RS-8d C-S-6d SST-SS-6d SST-RS-6d
21.1
1⁰C
A-S-8d 0
B-RS-8d 1
C-S-6d 0
SST-SS-6d 0
SST-RS-6d 0
0=Failed to reject null hypothesis
1=Rejected null hypothesis
32
CHAPTER 5 EVALUATION OF CSIPS WALL ASSEMBLY SUBJECTED TO WIND PRESSURE
LOADING
Phase two experiments used the High Airflow Pressure Loading Actuator
(HAPLA Figure 5-1 A), which is based on the Pressure Loading Actuator system (PLA)
developed by UWO (Kopp et al., 2010). This system was used to apply time-varying
pressure to surfaces of buildings and other structures. The HAPLA consists of two 75
hp centrifugal blowers connected to a valve with a rotating central disk actuated by a
servo motor. The servo controls the disk‘s position, which in turn regulates the system
pressure with a three chamber design. Custom LabVIEW 8.5 software operating on a
National Instruments PXI system, controls the pressure in the chamber through a 100
Hz PID loop that receives feedback from an Ashcroft XLdp transducer attached to the
test chamber. Currently, the HAPLA can simulate up to a 3Hz sinusoidal waveform and
a peak pressure of ±7 kPa. Time-varying pressure sequences with the HAPLA are
limited to frequency components as high as 2Hz in the target pressure time history. Mid-
span deflections were recorded with a Balluff BOD63M photoelectric distance sensor.
The reaction frame consisted of two similar attachment points to represent the
floor and roof connection seen in Figure 4-1. Complete test assembly walls were
instrumented with six TML model PFL-30-11-3L strain gauges on the exterior face-
sheets. Additionally, three were installed on the compression face and three on the
tension face at the third points along the mid-section of the wall, as illustrated on Figure
5-2. Figure 5-3 is a detail for both the top and bottom connection for the out of plane test
frame.
33
Pressure step loading function
The step loading pressure time history was applied to determine the peak static
load at failure (Figure 5-4). The function was generated using an initial pressure of 0.24
kPa (5 psf) and increasing by 0.48 kPa (10 psf) up to 6.96 kPa (145 psf) with duration of
ninety seconds per pressure step. The pressures were chosen based on the capabilities
of the system. Table 5-1 shows the fifteen unique pressures tabulated in the center
column, the right column was determined by solving for the equivalent design wind
speed based on ASCE7-10.
Equation 5-1 from section 27.3.2 ASCE 7-10 Main Wind Force Resisting System
(MWFRS) envelope was used to find the equivalent wind velocity for the static pressure
step. This equation required certain assumptions to be made about the velocity
pressure coefficient, topographic factors, and the wind directionality factor. The
equivalent basic wind speeds are presented in Table 5-1.
qz 0.000256* z* zt d*v
2 (5-1)
Individual Test Results Static Step Loading 48.05 kg/m3 (3 pcf)
Test #1
Test one demonstrated the need for adjustment to the PID parameters at loads
greater than 3.60 kPa for subsequent test. Figure 5-5 is a time history plot presenting a
target and measured pressure sequence for visual comparison. This figure shows that
the PID parameters were not correctly calibrated above 2.5 kPa pressure target. Figure
5-6 represents the deflection time history for this test. The specimen was still able to
obtain a max pressure of 6.45 kPa. Figure 5-7 is a sketch of the de-bonding that was
observed at the conclusion of the test. The large de-bonding that was observed on the
bottom of the panel‘s interior factsheet was not caused by mechanical failure and can
34
be attributed to manufacturing error. The top timber split longitudinally into three
segments however, de-bonding between the top section of the interior face-sheet was
measured to be less than the bottom where the connection remained without fracture.
Though the ultimate load of the system was approximately 6.45 kPa, the plot on
Figure 5-9 shows the limit state was exceeded at approximately at 1 kPa. The blue line
represents a deflection limit state of L/180. This pressure corresponds to a wind speed
between 40 and 51 m/s (90 and 100 mph). The theoretical deflection was validated with
the data collected as can be seen on Figure 5-9. Figure 5-9 confirms the equation used
accurately predicted the mid-span deflection.
The strain profile exhibit a linear behavior up to approximately 2 kPa when they
begin to show nonlinear trends. The center strain gauge SG5 on the tension face
reported the highest strain, as expected, and SG2 on the compression face had the
largest compression strains. The panel, however, was not performing as a perfectly
bonded composite beam evidenced by the unequal opposite strains. At 3 kPa the
compression strain gauges begin to lose their compression, leading the author to
conclude the face-sheet is slipping from the core and no longer behaving as an ideal
composite system.
Test #2
Test two pressure sequence demonstrates the corrections to the PID parameters
have improved the tracking of the system to the pressure sequence. Figure 5-10
presents a target and measure pressure sequence. Figure 5-11 represents the
deflection time history for this test. Failure is evident at approximately 4.6 kPa with a
sudden drop in the measure pressure; at this point failure of the top timber plate
occurred. Figure 5-12 is a sketch of the de-bonding that was observed at the end of the
35
testing. Based on the failure, it was difficult to quantify the de-bonding along the inside
face.
Though the ultimate load of the system was approximately 4.6 kPa, the plot on
Figure 5-13 shows the limit state was exceeded approximately at 1 kPa. The blue line
represents a deflection limit state of L/180. This pressure corresponds to a wind speed
between 40 and 51 m/s (90 and 100 mph). Nonetheless the theoretical deflection was
substantiated by the data, as shown in Figure 5-13. As with the initial test, Figure 5-13
validates the equation used does predict the mid-span deflection accurately.
The strain profile exhibited linear behavior up to approximately 3.5 kPa on the
tension face and SG5 and 2 kPa for the compression face SG2 just before failure when
they begin to show nonlinear trends. As anticipated, the largest strains for both the
tension and compression face were located at the center with SG5 on the tension face
and SG2 on the compression face. The unequal opposite strains prove the panel is not
behaving as a perfectly bonded composite beam. At 2.5 kPa the compression strain
gauges begin to lose their compression, which suggests the face-sheet is slipping from
the core and no longer behaving as an ideal composite system.
Test #3
Maintaining the same PID parameters from test two, the HAPLA was able to
maintain the accurate pressure throughout the fifteen different pressure steps. Figure 5-
14 presents a target and measure pressure sequence. The panel and timber
connections were exposed to all fifteen quasi static pressure steps reaching an ultimate
pressure of approximately 6.9 kPa without failure. Figure 5-15 shows the deflection time
history for this test. Figure 5-16 depicts the de-bonding. At the completion of the
36
pressure test, the panel was examined for de-bonding and the inside bottom left corner
showed no signs of de-bonding between the face-sheets and the foam core.
The limit state was exceeded at approximately at 1.5 kPa and that the ultimate
pressure was 6.9 kPa (Figure 5-17). The blue line represents a deflection limit state of
L/180. This pressure corresponds to a wind speed between 40 and 51 m/s (90 and 100
mph). However the theoretical deflection in this test overestimated the actual deflection
as can be seen in the plot on Figure 5-17. This plot also shows the wall system
deflection not behaving linearly with pressure in contrast to the other tests described in
this section.
The strain profile exhibited linear behavior up to approximately 3.5 kPa on the
tension face with SG5 and 2 kPa for the compression face with SG2 just before failure,
which is when they begin to show nonlinear trends. As expected, the center strain
gauge SG5 on the tension face reported the highest strain, yet the SG2 on the
compression face had the largest compression strains. The panel however is not
behaving as a perfectly bonded composite beam and is evident with the unequal
opposite strains. At 2.5 kPa the compression strain gauges begin to lose their
compression strain which leads the author to believe the face-sheet is slipping from the
core and no longer behaving as an ideal composite system.
Test #4
Maintaining the same PID parameters from test two, the HAPLA was able to
maintain the accurate pressure throughout the eleven different pressure stages. The
pressure sequence shown in Figure 5-18 depicts the target and the measured pressure
sequences. The panel and timber connections were able to withstand all fifteen quasi
static pressure steps and failed at the eleventh stage of the pressure sequence. Figure
37
5-19 shows the deflection time history. This panel did not have data for de-bonding at
the conclusion of testing.
Though the ultimate load of the system was approximately 4.9 kPa, the plot on
Figure 5-20 shows the limit state was exceeded approximately at 1 kPa, indicated by
the blue line. The blue line represents a deflection limit state of L/180. This pressure
corresponds to a wind speed between 40 and 51 m/s (90 and 100 mph). The theoretical
deflection in this test was an accurate predictor of the actual deflection, as can be seen
in the plot on Figure 5-20. This plot also shows the theoretical deflection is
underestimating the true wall system deflection.
The strain profile exhibited linear behavior up to approximately 3 kPa on the
tension face and SG5 and 2 kPa for the compression face SG2 when they begin to
show nonlinear trends. The center strain gauge SG5 on the tension face reported the
highest strain, which was expected, and SG2 on the compression face had the largest
compression strains. The panel did not behave as a perfectly bonded composite beam
as proven by the unequal opposite strains. At 2.5 kPa the compression strain gauges
begin to lose their compression strain, leading the author to believe the face-sheet is
slipping from the core and no longer behaves as an ideal composite system.
Individual Test Results Static Step Loading 16.02 kg/m3 (1 pcf)
Test #1
Maintaining the same PID parameters from test two, the HAPLA was able to
maintain the accurate pressure throughout the ten different pressure stages. The
pressure sequence on Figure 5-21 presents a target and the measured pressure
sequence for panel test number one.The measured pressure sequence begins to show
evidence of not achieving the target pressure at the fifth pressure step. The panel and
38
timber failed at the eleventh stage of the pressure sequence. Figure 5-22 represents the
deflection time history for this test. Figure 5-23 is a sketch of the de-bonding that results
at the end of the testing. At the completion of the pressure test the panel was examined
for de-bonding. Separation of the wall assembly from the timber connection hindered
the ability to collect de-bonding data.
Though the ultimate load of the system was approximately 5.05 kPa, the plot on
Figure 5-25 shows the limit state, which is the blue line, was exceeded approximately at
1 kPa. The blue line represents a deflection limit state of L/180. This pressure
corresponds to a wind speed between 40 and 51 m/s (90 and 100 mph). The theoretical
deflection in this test was an accurate predictor of the actual deflection as can be seen
in the plot on Figure 5-25. This plot also shows the theoretical deflection is under
estimating the true wall system deflection.
The strain profile exhibited linear behavior up to approximately 3 kPa on the
tension face and SG5 and 2 kPa for the compression face SG2 when they begin to
show nonlinear trends. The center strain gauge SG5 on the tension face reported the
highest strain, which was expected, and SG2 on the compression face had the largest
compression strains. The panel however is not behaving as a perfectly bonded
composite beam and is evident with the unequal opposite strains.
Time-varying pressure sequence
The time varying pressure sequence was derived from a ‗worst case‘ scenario on
a 12.19 m W x 19.05 m L x 7.32 m H (40 ft W x 62.5 ft L x 24 ft H) building in the NIST
Aerodynamic Database (Ho et al., 2003). The NIST database provides time histories of
Cp values for all taps from a particular wind tunnel model along with other prudent
information. For the time-varying pressure sequence the Cp values taken from the NIST
39
database must be converted from model scale to full scale values using the reduced
frequency relationship Equation 5-2, f is the frequency of the data, l is the integral length
scale, U is the mean wind speed. Equation 5-3 was used to obtain the full-scale
pressure time history from converted Cp time history.
(fl
U)model
(fl
U)full-scale
(5-2)
P(t) 1
2 U̅
2Cp(t) (5-3)
Each segment was filtered to 2 Hz using a low pass filter to improve
controllability. The mean of the record was increased by 10% to account for internal
pressurization (1994 Vickery). For this pressure sequence, segments of full records
were concatenated to form a full record length of 10394 sec (173.2 min). The basic wind
speed was incremented in steps of 4.47 m/s beginning with 44.7 m/s, a total of eleven
basic wind speeds were used to formulate the pressure sequence. Mechanical
limitations of the HAPLA prevented peak pressure in stage 11 from being achieved;
Figure 5-26 is a full-time history of the target pressure. Figure 5-27 is a narrow segment
of time to show the reduction in peak pressure gain and the fidelity of the HAPLA. Table
5-2 show the basic wind speed used with Equation 5-2 to compute the pressure time
history. The mean pressure in Table 5-2 is the measured mean pressure from the data
recorded.
Individual Test Results Dynamic Loading 48.05 kg/m3 (3 pcf)
Test #1
The pressure sequence in the following figure presents the data that was
recorded from subjecting the CSIP panel to the time varying pressure sequence. The
plot on Figure 5-28 is the target and measured pressure vs. time. The HAPLA system
40
was unsuccessful at achieving the higher peaks on the final stage of the sequence,
however, the system was able to reproduce smaller amplitude fluctuations with
accuracy. Figure 5-29 is the displacement vs. time; this plot has a disjunction in the data
at approximately the 7500 second mark due to the movement of the displacement
traducer for safety reasons.
Figure 5-30 shows the deflection vs. pressure relationship. The red line
represents the theoretical equation previously used in the quasi static pressure results
plots. The blue line once again represents the deflection limit state of L/180 for light
wood frame construction. Equation 2-4 was an accurate predictor of the mean deflection
for this CSIP wall. The limit state line, unlike that of the static walls, is exceeded at
approximately 0.4 kPa. Figure 5-31 is a sketch of the de-bonding and failure observed
after the pressure sequence was completed and the wall removed from the test frame.
Test #1 had no visual de-bonding at the conclusion of the test and both the top and
bottom plate remain undamaged.
Test #2
The pressure sequence in Figure 5-32 presents the data that was recorded from
subjecting the second CSIP panel to the same time varying pressure sequence
described in the previous chapter. The plot on Figure 5-32 is the target and measured
pressure vs. time. The HAPLA system was unsuccessful at achieving the higher peaks
on the final stage of the sequence, however the system was able to reproduce smaller
amplitude fluctuation with accuracy. Figure 5-33 is the displacement vs. time, this plot
has a disjunction in the data at approximately the 10,500 second mark, due to a large
movement of the wall assembly. Inspection after completion of the sequence yielded no
visual evidence for failure and timber connection remained intact.
41
Figure 5-34 shows the deflection vs. pressure relationship. The red line
represents the theoretical equation previously used in the quasi static pressure results
plots. The blue line again represents the deflection limit state of L/180 for light wood
frame construction. Equation 2-4 was an accurate predictor of the mean deflection for
this CSIP wall, yet it slightly over predicts loads below 1.4 kPa and under predicts
deflection for higher loads. The limit state line, unlike that of the static walls, is exceeded
at just above 0.4 kPa based on the theoretical deflection line and at 0.6 kPa based on
the measured data. Figure 5-35 is a sketch of the de-bonding and failure observed after
the pressure sequence was completed and the wall removed from the test frame. Test
#2 had no visual de-bonding at the conclusion of the test and both the top and bottom
plate remain undamaged.
Test #3
The pressure sequence in Figure 5-36 presents the data that was recorded from
subjecting the third CSIP panel to the same time varying pressure sequence described
in this chapter. The plot on Figure 5-36 is the target and measured pressure vs. time.
The HAPLA system was unsuccessful at achieving the higher peaks on the final stage
of the sequence, however the system was able to reproduce smaller amplitude
fluctuation with accuracy. Figure 5-37 is a plot of the displacement vs. time. This plot
has a jump in the data at approximately 10,000 seconds. After inspection of the wall
assembly, at the completion of the sequence, the cause of the discontinuity was partial
cracking of the bottom timber plate.
Figure 5-38 plots the deflection vs. pressure. The red line represents the
theoretical equation previously used in the quasi static pressure results plots. The blue
line represents the deflection limit state of L/180 for light wood frame construction.
42
Equation 2-4 was an accurate predictor of the mean deflection for this CSIP wall, yet it
slightly over predicts loads below 1.4 kPa and under predicts deflection for higher loads.
The limit state line, unlike that of the static walls, is exceeded at just above 0.4 kPa
based on the theoretical deflection line and at 0.6 kPa based on the measured data.
Figure 5-39 is a sketch of the de-bonding and failure observed after the pressure
sequence was completed and the wall removed from the test frame. Test #3 had no
visual de-bonding at the conclusion of the test and only the top plate remained
undamaged. The bottom plate had visual evidence of partial cracking.
Test #4
The pressure sequence in Figure 5-40 presents the data that was recorded from
subjecting the fourth CSIP panel to the same time varying pressure sequence described
in this chapter. The plot on Figure 5-40 is the target and measured pressure vs. time.
The HAPLA system was unsuccessful at achieving the higher peaks on the final stage
of the sequence, however the system was able to reproduce smaller amplitude
fluctuation with accuracy. Figure 5-41 is the displacement vs. time. This plot shows that
the system exhibits a non-linear behavior at lower loads that was not seen in previous
test. This change in slope on Figure 5-41 indicates a change in the load deflection
response because it is occurring during the fourth repetition of the final stage segment.
Figure 5-42 shows the deflection vs. pressure relationship. The red line
represents the theoretical equation previously used in the quasi static pressure results
plots. The blue line represents the deflection limit state of L/180 for light wood frame
construction. Equation 2-4 was an accurate predictor of the mean deflection for this
CSIP wall, there was an over prediction of loads below 1.4 kPa and under prediction of
deflection for loads higher than 1.4 kPa. The limit state line, unlike that of the static
43
walls, is exceeded at just above 0.4 kPa based on the theoretical deflection line and at
0.6 kPa based on the data. Figure 5-43 is a sketch of the de-bonding and failure
observed after the pressure sequence was completed and the wall removed from the
test frame. Test #4 had no visual de-bonding at the conclusion of the test and only the
top plate was damaged with visual evidence of partial cracking.
Test #5
The pressure sequence in Figure 5-44 presents the data that was recorded from
subjecting the fifth CSIP panel to the same time varying pressure sequence described
in this chapter. The plot on Figure 5-44 is the target and measured pressure vs. time.
This wall sample was successful sustaining loads until the eleventh stage, but only
completed two repetitions of the stage before failing. Figure 5-45, which is the deflection
vs. time plot, illustrates at approximately 5000 seconds there was either some de-
bonding or failure based on the CSIP walls deflection response.
Figure 5-46 shows the deflection vs. pressure relationship. The red line
represents the theoretical equation previously used in the quasi static pressure results
plots. The blue line represents the deflection limit state of L/180 for light wood frame
construction. Equation 2-4 was an accurate predictor of the mean deflection for this
CSIP wall. It slightly over predicts loads below 1.4 kPa and under predicts deflection for
higher loads. The limit state line, unlike that of the static walls, is exceeded at just above
0.4 kPa based on the theoretical deflection line and at 0.6 kPa based on the data.
Figure 5-47 is a sketch of the de-bonding and failure observed after the pressure
sequence was completed and the wall removed from the test frame. Test #5 had no
visual de-bonding at the conclusion of the test and neither the top plate nor bottom plate
had any visual signs of damage.
44
Test #6
The pressure sequence in Figure 5-48 presents the data that was recorded after
subjecting the sixth CSIP panel to the same time varying pressure sequence described
in the previous chapter. The plot on Figure 5-48 is the target and measured pressure vs.
time. This wall sample was successful sustaining loads through the sixteenth stage
before failing. Figure 5-49, which is the deflection vs. time plot, illustrates at
approximately 5,000 seconds and 9,000 seconds that there was some form of either de-
bonding or failure based on the CSIP walls deflection response.
Figure 5-50 shows the deflection vs. pressure relationship. The red line
represents the theoretical equation previously used in the quasi static pressure results
plots. The blue line represents the deflection limit state of L/180 for light wood frame
construction. Equation 2-4 was an accurate predictor of the mean deflection for this
CSIP wall. It does over predict for loads below 1.4 kPa and under predicts deflection for
higher loads. The limit state line, unlike that of the static walls, is exceeded at just above
0.4 kPa based on the theoretical deflection line and at 0.6 kPa based on the data.
Figure 5-51 is a sketch of the de-bonding and failure observed after the pressure
sequence was completed and the wall removed from the test frame. Test number six
had visual de-bonding on the top of the inside face-sheet. At the conclusion of the test
the top plate had no signs of damage, but the bottom plate had a partial crack as a
visual sign of damage.
Individual Test Results Dynamic Loading 16.02 kg/m3 (1 pcf)
Test #1
The pressure sequence in Figure 5-52 presents the data that was recorded from
subjecting the sixth CSIP panel to the same time varying pressure sequence described
45
in the previous chapter. The plot on Figure 5-52 is the target and measured pressure vs.
time. This wall sample successfully sustained loads through the seventh stage before
failing. Figure 5-53, the deflection vs. time plot, illustrates at approximately 5500
seconds there was some form of either de-bonding or failure based on the CSIP walls
deflection response.
Figure 5-54 shows the deflection vs. pressure relationship. The red line
represents the theoretical equation previously used in the quasi static pressure results
plots. The blue line represents the deflection limit state of L/180 for light wood frame
construction. Equation 2-4 was an accurate predictor of the mean deflection for this
CSIP wall; it under predicts loads above 0.5 kPa. The limit state line, unlike that of the
static walls, is exceeded at just above 0.5 kPa as per the theoretical equation and the
measured data. Figure 5-55 is a sketch of the de-bonding and failure observed after the
pressure sequence was completed and the wall removed from the test frame. Test
number one of the light core density did show visual de-bonding on the bottom of the
inside face-sheet and the top right of the outer face-sheet. At the conclusion of the test,
the top plate had no signs of damage but the bottom plate was damaged in the process
of removal from the test frame. As a result, it could not be determined whether it was a
partial crack or a full failure of the member.
Test #2
The pressure sequence in Figure 5-56 presents the data that was recorded from
subjecting the sixth CSIP panel to the same time varying pressure sequence described
in the previous chapter. The plot on Figure 5-56 is the target and measured pressure vs.
time. This wall sample was successful sustaining loads through the eighth stage before
failing. Figure 5-57, which is the deflection vs. time plot, illustrates at approximately
46
6,000 seconds there was some form of either de-bonding or failure based on the CSIP
walls deflection response.
Figure 5-58 shows the deflection vs. pressure relationship. The red line
represents the theoretical equation previously used in the quasi static pressure results
plots. The blue line represents the deflection limit state of L/180 for light wood frame
construction. Equation 2-4 was not an accurate predictor of the mean deflection for this
CSIP wall. The limit state line, unlike that of the static walls, is exceeded at just above
0.4 kPa based on the theoretical deflection line and the data. Figure 5-59 is a sketch of
the de-bonding and failure observed after the pressure sequence was completed and
the wall removed from the test frame. Test number two of the light core density did
show visual de-bonding on the bottom of the inside face-sheet and the top of the outer
face-sheet. At the conclusion of the test, the top plate had partial cracking but the
bottom plate was damaged and had complete failure.
Summary of Pressure Loading Results
The pressure step loading sequence provided a reference for load deflection
relationship for a complete wall assembly and verification of theoretical equations
presented in Equation 2-4. A total of five CSIP wall assemblies were tested, by
subjecting them to the pressure step load sequence. The results of the five CSIP walls
are given in Table 5-3 and Table 5-4 for the 16.02 kg/m3 (1 pcf) and four 48.05 kg/m3
(3pcf) wall assemblies. The plots on Figures 5-55 and 5-56 indicate the summary of the
load vs. deflection data for each of the two density groups tested with the step pressure
loading sequence. The summary results show that the wall assemblies have a linear
relationship between load and deflection. The solid line was computed using Eq. 2.
Though currently only prudent to the state of Florida, both the International Residential
47
Code (IRC 2009) and Florida Building Code (FBC 2010) Section R613 makes reference
to max deflection of SIP type walls to be L/254. The blue line presented in chapter five
corresponded to a deflection limit state of L/180 for standard light wood frame stud
walls. It was determined from analyzing the load deflection data that the mid-span
deflection was exceeded at a pressure load of 0.72 kPa and 1 kPa which correspond to
the L/254 and L/180 deflection limit state respectively.
When analyzing the strain data, it was observed, as shown in Figure 5-9, Figure
5-13, Figure 5-17, Figure 5-20, and Figure 5-25, - a strain vs. load plot, that the
compressive strain exhibits a form of strain release. This type of behavior was also
observed in research performed by Roberts et al. (2002). This strain behavior was
observed in all tested panels, with some being more prominent than others. This strain
behavior has a possibility indicative of active de-bonding. When de-bonding initiates it
would cause the compressive sheet to alter its behavior from a composite material to a
single membrane in tension. Figure 5-62 presents four photographs of failures observed
during testing. Within both parts of phase two all but one wall assembly did not fail.
Failure was primarily observed in the connection plates with splitting of the timber
parallel to grain.
Morrison (2011) conducted a study focused on fasteners in wood that
emphasized the importance of understanding a) the ultimate capacity under static
loading and b) the failure load under cyclic loading. This study conducted tests similar to
those described by Morrison et al. (2011). The results exhibit a decrease of
approximately 70% in the capacity of the CSIP panel subjected to time varying ―realistic‖
loading rather than static loading conditions, even though average peak loads reflected
48
a lower difference of approximately 26%. Figure 5-63 is a load vs. deflection plot of one
test with minimal filtering that shows a high variability, making it difficult to predict the
dynamic behavior. However, as shown in the individual results discussion, with limited
filtering it is possible to predict mean deflection vs mean pressure per stage of the
dynamic sequence. Figure 5-64 is a summary of both 48.05 kg/m3 (3 pcf) and 16.02
kg/m3 (1 pcf) CSIP wall subjected to the dynamic pressure sequence. It was observed
that the wall, although flexible, had difficulty returning to a natural state after load was
removed. Therefore, it is concluded that this scatter is difficult to predict because current
equation used do not take previous conditions into consideration. It could be possible to
correct some uncertainty using a coefficient of restitution to account for some of the
variability. Results shown in Figure 5-65 also suggest that shear deformation in the core
may have a larger influence in dynamic loading.
As first introduced with the pressure step-loading, the strain behavior may be a
sign of de-bonding (not visible during testing). Figure 5-65 is a representation of similar
behavior observed on all CSIP walls subjected to dynamic loading. It demonstrates that
while tensile behavior is linear with regard to applied load, mid-span strain compression
does not follow any particular pattern and almost demonstrates a plateau effect at
approximately 100 micro strains.
Comparison of Capacity and Failure Modes
Table 5-3 tabulates the results for the maximum pressure through the duration of
a specific test and provides a mean with one standard deviation. The maximum
pressure a 48.05 kg/m3 (3 pcf) and a16.02 kg/m3 (1 pcf) CSIP panel was able to resist
was 6.90 kPa 5.05 kPa, respectively, during the Pressure step loading sequence. As
49
per the results, prior to failure during the dynamic pressure sequence, the mean
maximum pressure for both core densities was approximately 25% less than the mean
maximum measured pressure observed in the step loading, whose mean was 5.71 kPa
compared to 4.21 kPa. Table 5-4 provides a summary of the maximum deflection and
compares the results and means of both the step loading test and the dynamic test.
When comparing the mean max deflection between step loading and dynamic test
results, we find a difference of approximately 30%.
50
Figure 5-1. Two photographs of the pressure testing components A) HAPLA testing
apparatus B) exterior view of testing chamber. Photo courtesy of George Fernandez and Forrest Masters, University of Florida.
51
Figure 5-2. Strain gauge location
Figure 5-3. Reaction frame connection detail
52
Figure 5-4. Pressure step loading function
Figure 5-5. 48.05 kg/m3 (3 pcf) CSIP Test 1 pressure time history
0 200 400 600 800 1000 12000
1
2
3
4
5
6
7
Time (Seconds)
Pre
ssu
re (
KP
a)
Target
Measured
53
Figure 5-6. 48.05 kg/m3 (3 pcf) CSIP Test 1 deflection time history
Figure 5-7. 48.05 kg/m3 (3 pcf) CSIP Test 1 de-bonding and failure sketch
0 200 400 600 800 1000 1200
10
20
30
40
50
60
70
80
90
100
110
Time (Seconds)
Deflection (
mm
)
CSIP Static -06-2011
T cf.t
54
Figure 5-8. 48.05 kg/m3 (3 pcf) CSIP Test 1 failure. Photo courtesy of George Fernandez, University of Florida.
Figure 5-9. 48.05 kg/m3 (3 pcf) CSIP Test 1 summary
55
Figure 5-10. 48.05 kg/m3 (3 pcf) CSIP Test 2 pressure time history
Figure 5-11. 48.05 kg/m3 (3 pcf) CSIP Test 2 deflection time history
0 100 200 300 400 500 600 700 8000
1
2
3
4
5
Time (Seconds)
Pre
ssu
re (
KP
a)
Target
Measured
0 100 200 300 400 500 600 700 800
10
20
30
40
50
60
70
80
90
100
110
Time (Seconds)
Deflection (
mm
)
CSIP Static -11-2011
T cf.t
56
Figure 5-12. 48.05 kg/m3 (3 pcf) CSIP Test 2 de-bonding and failure sketch
Figure 5-13. 48.05 kg/m3 (3 pcf) CSIP Test 2 summary
57
Figure 5-14. 48.05 kg/m3 (3 pcf) CSIP Test 3 pressure time history
Figure 5-15. 48.05 kg/m3 (3 pcf) CSIP Test 3 deflection time history
0 200 400 600 800 1000 1200 14000
1
2
3
4
5
6
7
Time (Seconds)
Pre
ssu
re (
KP
a)
Target
Measured
0 200 400 600 800 1000 1200
10
20
30
40
50
60
70
80
90
100
110
Time (Seconds)
Deflection (
mm
)
CSIP Static -12-2011
T cf.t
58
Figure 5-16. 48.05 kg/m3 (3 pcf) CSIP Test 3 de-bonding and failure sketch
Figure 5-17. 48.05 kg/m3 (3 pcf) CSIP Test 3 summary
59
Figure 5-18. 48.05 kg/m3 (3 pcf) CSIP Test 4 pressure time history
Figure 5-19. 48.05 kg/m3 (3 pcf) CSIP Test 4 deflection time history
0 100 200 300 400 500 600 700 800 9000
1
2
3
4
5
6
Time (Seconds)
Pre
ssu
re (
KP
a)
Target
Measured
0 100 200 300 400 500 600 700 800 900
10
20
30
40
50
60
70
80
90
100
110
Time (Seconds)
Deflection (
mm
)
CSIP Static -13-2011
T cf.t
60
Figure 5-20. 48.05 kg/m3 (3 pcf) CSIP Test 4 summary
Figure 5-21. 16.02 kg/m3 (1 pcf) CSIP Test 1 pressure time history
0 100 200 300 400 500 600 700 800 9000
1
2
3
4
5
6
Time (Seconds)
Pre
ssu
re (
KP
a)
Target
Measured
61
Figure 5-22. 16.02 kg/m3 (1 pcf) CSIP Test 1 deflection time history
Figure 5-23. 16.02 kg/m3 (1 pcf) CSIP Test 1 de-bonding and failure sketch
0 100 200 300 400 500 600 700 800 900
10
20
30
40
50
60
70
80
90
100
110
Time (Seconds)
Deflection (
mm
)
CSIP Static -11-2011
T cf.t
62
Figure 5-24. 16.02 kg/m3 (1 pcf) CSIP Test 1 failure. Photo courtesy of George
Fernandez, University of Florida.
Figure 5-25. 16.02 kg/m3 (1 pcf) CSIP Test 1 summary
63
Figure 5-26. Complete time-varying pressure sequence
Figure 5-27. Sample of the time-varying pressure sequence
64
Figure 5-28. 48.05 kg/m3 (3 pcf) CSIP Test 1 time varying pressure time history
Figure 5-29. 48.05 kg/m3 (3 pcf) CSIP Test 1 time varying pressure deflection time
history
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
1
2
3
4
5
6
Time (Seconds)
Pre
ssu
re (
KP
a)
CSIP Dynamic 09-12-2011 3pcf
Target
Measured
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
10
20
30
40
50
60
70
80
90
100
Time (Seconds)
Def
lect
ion
(m
m)
CSIP Dynamic 09-12-2011 3pcf
Measured
65
Figure 5-30. 48.05 kg/m3 (3 pcf) CSIP Test 1 time varying pressure deflection-load plot
Figure 5-31. 48.05 kg/m3 (3 pcf) CSIP Test 1 de-bonding and failure sketch
0 10 20 30 40 50 60 70 80 90 1000
0.5
1
1.5
2
2.5P
ress
ure
(K
Pa)
Deflection (mm)
CSIP Dynamic 09-12-2011 3pcf
Experimental
Theoretical Deflection
66
Figure 5-32. 48.05 kg/m3 (3 pcf) CSIP Test 2 time varying pressure time history
Figure 5-33. 48.05 kg/m3 (3 pcf) CSIP Test 2 time varying pressure deflection time
history
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
1
2
3
4
5
6
Time (Seconds)
Pre
ssu
re (
KP
a)CSIP Dynamic 09-21-2011 3pcf
Target
Measured
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
20
40
60
80
100
120
140
Time (Seconds)
Def
lect
ion
(m
m)
CSIP Dynamic 09-21-2011 3pcf
Target
67
Figure 5-34. 48.05 kg/m3 (3 pcf) CSIP Test 2 time varying pressure deflection-load plot
Figure 5-35. 48.05 kg/m3 (3 pcf) CSIP Test 2 de-bonding and failure sketch
0 20 40 60 80 100 1200
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2P
ress
ure
(K
Pa)
Deflection (mm)
CSIP Dynamic 09-21-2011 3pcf
Experimental
Theoretical Deflection
68
Figure 5-36. 48.05 kg/m3 (3 pcf) CSIP Test 3 time varying pressure time history
Figure 5-37. 48.05 kg/m3 (3 pcf) CSIP Test 3 time varying pressure deflection time
history
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
1
2
3
4
5
6
Time (Seconds)
Pre
ssu
re (
KP
a)CSIP Dynamic 10-25-2011 3pcf
Target
Measured
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
10
20
30
40
50
60
70
80
Time (Seconds)
Def
lect
ion
(m
m)
CSIP Dynamic 10-25-2011 3pcf
Target
69
Figure 5-38. 48.05 kg/m3 (3 pcf) CSIP Test 3 time varying pressure deflection-load plot
Figure 5-39. 48.05 kg/m3 (3 pcf) CSIP Test 3 de-bonding and failure sketch
0 10 20 30 40 50 60 700
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2P
ress
ure
(K
Pa)
Deflection (mm)
CSIP Dynamic 10-25-2011 3pcf
Experimental
Theoretical Deflection
70
Figure 5-40. 48.05 kg/m3 (3 pcf) CSIP Test 4 time varying pressure time history
Figure 5-41. 48.05 kg/m3 (3 pcf) CSIP Test 4 time varying pressure deflection time
history
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
1
2
3
4
5
6
Time (Seconds)
Pre
ssu
re (
KP
a)
CSIP Dynamic 11-01-2011 3pcf
Target
Measured
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
5
10
15
20
25
30
35
40
Time (Seconds)
Def
lect
ion
(m
m)
CSIP Dynamic 11-01-2011 3pcf
Target
71
Figure 5-42. 48.05 kg/m3 (3 pcf) CSIP Test 4 time varying pressure deflection-load plot
Figure 5-43. 48.05 kg/m3 (3 pcf) CSIP Test 4 de-bonding and failure sketch
0 5 10 15 20 25 30 350
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2P
ress
ure
(K
Pa)
Deflection (mm)
CSIP Dynamic 11-01-2011 3pcf
Experimental
Theoretical Deflection
72
Figure 5-44. 48.05 kg/m3 (3 pcf) CSIP Test 5 time varying pressure time history
Figure 5-45. 48.05 kg/m3 (3 pcf) CSIP Test 5 time varying pressure deflection time
history
0 1000 2000 3000 4000 5000 6000 7000 8000 90000
1
2
3
4
5
6
Time (Seconds)
Pre
ssu
re (
KP
a)
CSIP Dynamic 11-02-2011 3pcf
Target
Measured
0 1000 2000 3000 4000 5000 6000 7000 8000 90000
10
20
30
40
50
60
70
Time (Seconds)
Def
lect
ion
(m
m)
CSIP Dynamic 11-02-2011 3pcf
Measured
73
Figure 5-46. 48.05 kg/m3 (3 pcf) CSIP Test 5 time varying pressure deflection-load plot
Figure 5-47. 48.05 kg/m3 (3 pcf) CSIP Test 5 de-bonding and failure sketch
0 10 20 30 40 500
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2P
ress
ure
(K
Pa)
Deflection (mm)
CSIP Dynamic 11-02-2011 3pcf
Experimental
Theoretical Deflection
74
Figure 5-48. 48.05 kg/m3 (3 pcf) CSIP Test 6 time varying pressure time history
Figure 5-49. 48.05 kg/m3 (3 pcf) CSIP Test 6 time varying pressure deflection time
history
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
1
2
3
4
5
6
Time (Seconds)
Pre
ssu
re (
KP
a)CSIP Dynamic 11-03-2011 3pcf
Target
Measured
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 100000
10
20
30
40
50
60
70
80
90
100
Time (Seconds)
Def
lect
ion
(m
m)
CSIP Dynamic 11-03-2011 3pcf
Measured
75
Figure 5-50. 48.05 kg/m3 (3 pcf) CSIP Test 6 time varying pressure deflection-load plot
Figure 5-51. 48.05 kg/m3 (3 pcf) CSIP Test 6 de-bonding and failure sketch
0 10 20 30 40 50 60 70 800
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2P
ress
ure
(K
Pa)
Deflection (mm)
CSIP Dynamic 11-03-2011 3pcf
Experimental
Theoretical Deflection
76
Figure 5-52. 16.02 kg/m3 (1 pcf) CSIP Test 1 time varying pressure time history
Figure 5-53. 16.02 kg/m3 (1 pcf) CSIP Test 1 time varying pressure deflection time
history
0 1000 2000 3000 4000 5000 60000
0.5
1
1.5
2
2.5
3
3.5
4
4.5
Time (Seconds)
Pre
ssu
re (
KP
a)
CSIP Dynamic 09-26-2011 1pcf
Target
Measured
0 1000 2000 3000 4000 5000 60000
20
40
60
80
100
120
Time (Seconds)
Def
lect
ion
(m
m)
CSIP Dynamic 09-26-2011 1pcf
Measured
77
Figure 5-54. 16.02 kg/m3 (1 pcf) CSIP Test 1 time varying pressure deflection-load plot
Figure 5-55. 16.02 kg/m3 (1 pcf) CSIP Test 1 de-bonding and failure sketch
0 20 40 60 80 1000
0.5
1
1.5P
ress
ure
(K
Pa)
Deflection (mm)
CSIP Dynamic 09-26-2011 1pcf
Experimental
Theoretical Deflection
78
Figure 5-56. 16.02 kg/m3 (1 pcf) CSIP Test 2 time varying pressure time history
Figure 5-57. 16.02 kg/m3 (1 pcf) CSIP Test 2 time varying pressure deflection time
history
0 1000 2000 3000 4000 5000 60000
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
Time (Seconds)
Pre
ssu
re (
KP
a)
CSIP Dynamic 10-03-2011 1pcf
Target
Measured
0 1000 2000 3000 4000 5000 60000
20
40
60
80
100
120
140
160
180
Time (Seconds)
Def
lect
ion
(m
m)
CSIP Dynamic 10-03-2011 1pcf
Measured
79
Figure 5-58. 16.02 kg/m3 (1 pcf) CSIP Test 2 time varying pressure deflection-load plot
Figure 5-59. 16.02 kg/m3 (1 pcf) CSIP Test 2 de-bonding and failure sketch
0 50 100 1500
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6P
ress
ure
(K
Pa)
Deflection (mm)
CSIP Dynamic 10-03-2011 1pcf
Experimental
Theoretical Deflection
80
Figure 5-60. Deflection-load results for the 16.02 kg/m3 (1 pcf) panels
Figure 5-61. Deflection-load results for the 48.05 kg/m3 (3 pcf) panels
81
Figure 5-62. Observed damage. Photo courtesy of George Fernandez, University of
Florida.
Figure 5-63. Un-filtered mid-span deflection versus pressure
0 10 20 30 40 50 60 70 80 90 1000
0.5
1
1.5
2
2.5
3
3.5
4
Pre
ssu
re (
Kp
a)
Deflection (mm)
CSIP Dynamic 11-03-2011 3pcf
Measured
82
Figure 5-64. Filtered mid-span deflection versus pressure
Figure 5-65. Time-varying pressure vs. mid-span strain
83
Table 5-1. Static pressure step and equivalent mean wind speed Step # Mean Pressure kPa (psf) Mean Wind Velocity m/s (mph)
1 0.24 (5) 23.24 (52) 2 0.72 (15) 40.23 (90) 3 1.20 (25) 51.85 (116) 4 1.68 (35) 61.24 (137) 5 2.16 (45) 69.73 (156) 6 2.64 (55) 76.89 (172) 7 3.12 (65) 83.59 (187) 8 3.60 (75) 89.85 (201) 9 4.08 (85) 95.66 (214)
10 4.56 (95) 101.03 (226) 11 5.04 (105) 106.39 (238) 12 5.52 (115) 111.31 (249) 13 6.00 (125) 115.78 (259) 14 6.48 (135) 120.70 (270) 15 6.96 (145) 125.17 (280)
Table 5-2. Time varying basic wind speed and mean pressure Step # Basic Wind Velocity m/s (mph) Mean Pressure kPa (psf)
1 44.71 (100) 0.409 (8.5) 2 49.17 (110) 0.496 (10.4) 3 53.69 (120) 0.593 (12.4) 4 58.11 (130) 0.697 (14.5) 5 62.58 (140) 0.811 (16.9) 6 67.05 (150) 0.933 (19.48) 7 71.52 (160) 1.064 (22.22) 8 75.99 (170) 1.204 (25.24 9 80.46 (180) 1.352 (28.23)
10 84.93 (190) 1.509 (31.51) 11-16 89.40 (200) 1.675 (34.98)
Table 5-3. Maximum pressure comparison table Foam core density
Maximum step loading pressure (kPa) Maximum dynamic pressure (kPa) Sample Mean ± Std Sample Mean ± Std
48.05 kg/m3 (3 pcf)
6.45
5.71 ± 1.13
4.42
4.21 ± 0.28
4.60 4.63
6.90 4.22 4.90 3.89
--- 4.13 --- 3.96
16.02 kg/m3 (1 pcf)
5.05 5.05
3.78 3.81
--- 3.84
84
Table 5-4. Maximum deflection table Foam core density
Maximum quasi-steady deflection (mm) Maximum dynamic deflection (mm) Sample Mean ± Std Sample Mean ± Std
48.05 kg/m3 (3 pcf)
101.0
90.4 ± 22.2
53.0
62.1 ± 17.1
64.0 77.1 114.7 69.8
81.9 36.4
--- 55.0
--- 81.5
16.02 kg/m3 (1 pcf)
95.0 95.0
46.1 76.5
--- 106.9
85
CHAPTER 6 EVALUATION OF CSIP WALL ASSEMBLY SUBJECTED TO SHEAR LOADING
Methodology
Racking loads were applied to two separate CSIP wall assemblies in accordance
with ASTM E72. The panels tested had a core thickness of 25.4 cm (10 in), however
their density was 48.05 kg/m3 (3 pcf). Two separate tests were conducted. Each test
used two CSIP wall segments of dimension 254.0 x 1219.2 x 2438.4 mm (10‖ x 4‘ x 8‘)
joined along the top and bottom with a reduced timber member. The bottom connection
was the same as the connection detail in the pressure loading wall assembly. The top
connections consisted of a timber member affixed to the wall and resting on fixed roller
to prevent vertical translation. Loads were applied using an Enerpac 10,000 psi
hydraulic hand pump connected to a 12 ton Enerpac hydraulic bottle jack model number
RCH123. The loads were measured using an Omega 2,267.96 Kg (5,000 lb) load cell
model number LCH-5k. The data was recoded using a NI-PXI at 50 Hz. Displacement
was measured using two Unimeasure Linear Position Transducers (JX-P420-25-N11-
11S-31N and JX-PA-80-N11-11S-321) and one Balluff BOD63M photoelectric distance
sensor measured displacements. Figure 6-1 is a diagram of the test set up per ASTM
E72. The location of instrumentation, supports, and restrains of the wall assembly are
labeled in Figure 6-1.
Results
The racking tests were completed at the University of Florida (UF) Weil Hall
structural engineering test laboratory. Table 6-1 presents a summary of the data
collected during these two tests. Figure 6-2 Panel 1 performed with a 38% higher
capacity than panel two. This difference in load capacity between both wall assemblies
86
highlights the requirement for further testing. It is evident from Figure 6-3 that de-
bonding could be a possible explanation for the difference between the performances of
the two test setups. Figure 6-3 and Figure 6-4 present the failure observed at the
completion of test 1. Comparing the data from this study with results observed by
Kermani et al. (2006) our study can be recognized as conservative. The test
configuration exceeded SIP panels with a core of 95 mm with no vertical load by 77%
and performed equivalent to a solid OSB SIP wall with 25 kN (5620.22 lb) of vertical
load. The panel assemblies, tested at the UF, were only fastened with a top plate and
bottom plate.
87
Figure 6-1. Diagram of racking test setup
Figure 6-2. Racking test load deflection interaction
0 1 2 3 4 5 6 7 80
5
10
15
20
25
30
Displacement (cm)
Load
(kN
)
Test 1
Test 2
88
Figure 6-3. Racking test face-sheet de-bonding. Photo courtesy of George Fernandez
and Scott Bolton, University of Florida.
Figure 6-4. Racking test face-sheet wrinkling. Photo courtesy of George Fernandez and
Scott Bolton, University of Florida.
89
Table 6-1. Racking test results
Test # Vertical Loads
kN (lb) Test Ultimate Load
kN (lb)
Maximum displacement
cm (in) Failure observed
1 0 27.9 (6271.4) 7.06 (2.78) Wrinkling of the
face-sheet 2 0 20.1 (4519.8) 7.80 (3.07)
90
CHAPTER 8 CONCLUSIONS
An experimental study was performed to characterize the out-of-plane bending
and shear capacity of composite structural insulated panels. This experimental work
was conducted to evaluate adequacy of a connection detail and to improve the
understanding of CSIP wall assemblies subjected to uniaxial bending caused by
pressure loading and shear response to racking loads.
Phase one of the testing investigated the design of the connection detail. The
investigation of the connection design began with the selection of five nail type, though
all fasteners were found to be suitable for the connection ultimately a stainless steel 6d
nail was chosen. A conservative approach was taken when specifying the nail spacing
of 76.2 mm (3 in) on center for interior nails and 38.1 mm (1.5 in) for the end nails.
Unlike timber construction nails are only placed along the top and bottom edge of face
sheets to connect to the timber members. With the elimination of studs the quantity of
nails required diminishes. Typical perimeter spacing for timber walls may vary from 51
mm (2 in) to 153 mm (6 in) and 305 mm (12 in) for field nails. (Lindt et al., 2005)
Following the design of the connection, the two core densities of CSIP walls were
subjected to wind pressures using the HAPLA, a total of 19 walls were tested. The wall
assemblies were tested with both increasing step loading and time varying pressures.
The walls with a step loading condition were able to obtain an average peak load
capacity of 5.71 kPa (119 psf). In comparison the wall tested with a time varying
pressure averaged a maximum load of 4.21 kPa (88 psf). These pressures correspond
to instantaneous wind velocities of approximately 110 m/s (246 Mph) and 100 m/s (223
Mph) respectively, exceeding the highest wind observed by only 20 m/s (46 Mph).
91
Though the likelihood of exposure to sustained winds of that magnitude due to a tropical
cyclone is minimal, the possibility does seem to be plausible in a tornado.
Ultimate loads comprise only part of the criteria for building materials, another
facet of the material designers must concern themselves with would be the
serviceability. The walls subjected to step pressure and time varying pressure failed to
meet deflection limit states of L/254 at the design pressure. (FBC, 2010) The wall
assemblies exceeded the deflection limit state at approximately 0.72 kPa equivalent to a
wind velocity of 40 m/s (90 mph) during the step loading. The walls exceeded the
deflection limit state at 0.4 kPa during the time varying pressure sequence, which would
be equivalent to a mean 60 sec wind speed of 44 m/s (100 mph). However, most
coastal communities require a design wind speed of 58 m/s (130 mph) or greater.
(ASCE 7, 2010)
Delamination was observed at the conclusion of 7 of the 14 pressure tests. The
step loaded walls experience delamination in 4 of the 5 test in contrast to the time
varying pressure loaded walls experiencing delamination in 3 of the 9 walls. The
difference in the observed delamination suggests that the walls may vary in
performance based on load time exposure and perhaps be susceptible to creep.
In plane loads are also a consideration for design. Based on a limited sample
size only two wall assemblies were tested for their in plane shear capacities.
Consequent to the vertical timber end members and a joint between two individual wall
segments not being installed, the racking test setup can be considered to be a
conservative approach to the racking capacities of such wall assemblies. It is the
author‘s opinion that this facet of the testing program should be revisited to include
92
timber connection around the perimeter and having the two panels joined at the center.
However, the two shear walls tested did exceed comparable timber shear walls tested
by 77% with no vertical load. (Kermani et al., 2006)
CSIP walls have been introduced to aid in the advancement of building materials
and technologies. Based on the small sample size, the ability to conduct statistical
comparison between core densities and loading conditions for this study was limited.
The recommendation for future testing are as followed:
Select one core density and one thickness to allow for larger sample size, enabling probabilistic modeling.
Alternative adhesives should be explored to prevent delamination between face sheets and core to maximize potential composite behavior.
Testing of shear walls with varying location and size of openings and vertical load to compare with equivalent timber wall studies.
93
APPENDIX A RESULTS OF LATERAL LOAD TEST
Figure A-1. Lateral nail capacity failure results A-S-8d. Photo courtesy of George Fernandez, University of Florida.
94
Figure A-2. Lateral nail capacity failure results B-RS-8d. Photo courtesy of George Fernandez, University of Florida.
95
Figure A-3. Lateral nail capacity failure results C-S-6d. Photo courtesy of George Fernandez, University of Florida.
96
Figure A-4. Lateral nail capacity failure results SST-SS-6d. Photo courtesy of George Fernandez, University of Florida.
97
Figure A-5. Lateral nail capacity failure results SST-RS-6d. Photo courtesy of George Fernandez, University of Florida.
98
LIST OF REFERENCES
1. Allen, H. G. (1969). Analysis and design of structural sandwich panels. Oxford:
Pergamon Press.
2. ASTM D1761-06 (2006) Standard Test Methods for Mechanical Fasteners in
Wood, West Conshohocken, PA: American Society for Testing and Materials,
100 Barr Harbor Drive, PO-Box C700, 1942
3. Baehre, R., & Ladwein, T. (1994). Diaphragm action of sandwich panels. Journal
of Constructional Steel Research, 31(2), 305-316.
4. Daniel, I. M., & Abot, J. L. (2000). Fabrication, testing and analysis of composite
sandwich beams. Composites Science and Technology, 60(12), 2455-2463.
5. Davies, J. M. (1993). Sandwich Panels. Thin-WalledStructures,16, 179-198.
6. Fam, A., Sharaf, T., & Shawkat, W. (2010). Structural performance of sandwich
wall panels with different foam core densities in one-way bending. Journal of
Composite Materials, 44(19), 2249-2263.
7. Florida Building Commission and International Code Council (2010) Florida
building code 2010 International Code Council, Country Club Hills, IL
8. Florida Building Commission and International Code Council (2009) International
Residential Code 2009 International Code Council, Country Club Hills, IL
9. Girhammar, U. A. (2008). Composite beam–columns with interlayer slip—
Approximate analysis. International Journal of Mechanical Sciences, 50(12),
1636-1649.
10. Girhammar, U. A. (2009). A simplified analysis method for composite beams with
interlayer slip. International Journal of Mechanical Sciences, 51(7), 515-530.
11. Girhammar, U. A. (2008). Composite beam-columns with interlayer slip-
approximate analysis.
12. Hartsock, J. A. (1969). Design of foam-filled structures. Stamford, Conn:
Technomic Pub. Co.
99
13. Heuer, R., Adam, C., & Ziegler, F. (2003). Sandwich panels with interlayer slip
subjected to thermal loads. Journal of Thermal Stresses, 26(11-12), 1185-1192.
14. T.C. E. Ho, D. Surry, and D.P. Morrish (2003). BLWT-SS20-2003 NIST/TTU
Cooperative Agreement - Windstorm Mitigation Initiative: Wind Tunnel
Experiments on Generic Low Buildings.
15. T.C. E. Ho, D. Surry, and M. Nywening (2003). BLWT-SS21-2003 NIST/TTU
Cooperative Agreement - Windstorm Mitigation Initiative: Further Experiments on
Generic Low Buildings.
16. Kermani, A., Hairstans, R. (2006). Racking Performance of Structural Insulated
Panels. Journal of Structural Engineering, 132, 1806-1812.
17. Kopp, G., Morrison, M., Gavanski, E., Henderson, D., and Hong, H. (2010).
―Three Little Pigs‖ Project: Hurricane Risk Mitigation by Integrated Wind Tunnel
and Full-Scale Laboratory Tests. Natural Hazards Review, 11(4), 151–161.
18. Manalo, A. C., Aravinthan, T., & Karunasena, W. (2010). Flexural behaviour of
glue-laminated fibre composite sandwich beams. Composite Structures, 92(11),
2703-2711.
19. Mohammed A. M., Nasim U. (2011) Global buckling of composite structural
insulated wall panels, Materials & Design, 32(2), 766-772.
20. Morrison, M. J., & Kopp, G. A. (2011). Performance of toe-nail connections under
realistic wind loading. Engineering Structures, 33(1), 69-76.
21. Mullens, M., & Arif, M. (2006). Structural insulated panels: Impact on the
residential construction process. Journal of Construction Engineering and
Management-ASCE, 132(7), 786-794.
22. Prevatt, D. O. (1994). Improving the cyclone-resistance of traditional Caribbean
house construction through rational structural design criteria. Journal of Wind
Engineering and Industrial Aerodynamics 52 305-319
23. Roberts, J. C., Boyle, M.P., Wienhold, P. D., Ward, E. E. and White, G. J. (2002).
Strains and deflections of GFRP sandwich panels due to uniform out-of-plane
pressure. Marine Technology and SNAME News, 39(4), 223.
100
24. Schnabl, S., Saje, M., Turk, G., & Planinc, I. (2007). Locking-free two-layer
Timoshenko beam element with interlayer slip. Finite Elements in Analysis &
Design, 43(9), 705-714.
25. Uddin, N. and Mousa, M. A. (2010). Debonding of composites structural insulated
sandwich panels. Journal of Reinforced Plastics and Composites, 29(22), 3380-
3391.
26. Vaidya, A, et al. (2010). Structural Characterization of Composite Structural
Insulated Panels for Exterior Wall Applications. Journal of Composites for
Construction, Vol. 14, No. 4, 464-469.
27. Viswanathan, A. V., Tamekuni, M., Boeing Commercial Airplane Company., &
Langley Research Center. (1973). Elastic buckling analysis for composite
stiffened panels and other structures subjected to biaxial inplane loads.
Washington, D.C: National Aeronautics and Space Administration.
28. Wood, L. W., Forest Products Laboratory (U.S.), & University of Wisconsin.
(1958). Sandwich panels for building construction. Madison, Wis: U.S. Dept. of
Agriculture, Forest Service, Forest Products Laboratory.
29. Yoders, J. (2005). Reinventing Modular Construction. Building Design &
Construction, Aug 2005, 46-50.
101
BIOGRAPHICAL SKETCH
George Fernandez was born in 1986 in Jacksonville, North Carolina. At a young
age he moved to Miami, Florida, where he remained until 2005 when he graduated from
Miami Coral Park Sr. High. Raised by a single mother, his mother‘s hard work and
dedication served to motivate George in pursuing his academic endeavors. Always
intrigued by dismantling and reassembling household items, George was afforded a
unique opportunity to enter an engineering magnet program at his high school. During
his time at Miami Coral Park Sr. High George was actively involved in student
government and the robotics team. He was inducted into his school‘s Hall of Fame for
his contribution and dedication in the field of technology. He later moved to Winston-
Salem, North Carolina where he went on to complete the majority of the requirements
for his Associates of Arts degree. George also had the privilege of becoming the first
Hispanic to join a local volunteer fire department and be a registered firefighter in that
state.
In the fall of 2006 George returned to Florida and enrolled in Santa Fe College.
Upon completion of his Associates degree he was admitted into the University of
Florida‘s Civil and Coastal engineering program. Eager to contribute to the University of
Florida‘s community he began his academic career by teaching incoming freshmen
AutoCAD for the deptartment. His first exposure to research was a position assisting
professors with their individual projects at various labs within the civil engineering
department. It was during this time he found his passion for Hurricane research, to
which he would invest the following seven years of his life. Under the guidance and
tutelage of Dr. Forrest Masters and Dr. Kurt Gurley, George was welcomed into the
Hurricane research group in UF‘s civil engineering department. For the duration of his
102
undergraduate degree George was afforded the opportunity to work with some of the
leading experts and professors in the fields of wind engineering and civil engineering.
He became a part of the Florida Coastal Monitoring Program (FCMP), a unique joint
multi university venture established in 1996 that focuses on experimental methods to
quantify tropical cyclone wind behavior and the resulting loads on residential structures.
He assisted in preparation of field deployable instruments to quantify near-surface
cyclone winds for all named storms from fall 2006 through fall 2012.
After completing his Bachelor of Arts degree in the fall of 2009, George was
extended an offer to continue in his research as a graduate student under the
mentorship of Dr. Forrest J. Masters. His graduate work was focused on wind load
resistance Composite Structural Insulated Panels (CSIP), retrofitting FCMP field
observation towers, and serving as the student lead for the Hurricane Hazard
Immersion Program. The latter is an outreach program focused on providing current
event information and hands on research experience to middle school Science,
Technology, Engineering, and Mathematics (STEM) teachers for the development of a
hurricane mitigation curriculum.
George Fernandez is currently a student member of the American Association for
Wind Engineering and American Society of Civil Engineers. Following his graduation
with his Master of Engineering degree, George will join Florida International University
as a research scientist.