by- embuilt technologies [email protected] (thd measurement with examples and figures)...

35
THDPM-1 By- EMBUILT TECHNOLOGIES www.embuilt.com www.energylogger.blogspot.com [email protected] (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date- 03/09/2014

Upload: james-cabbage

Post on 15-Jan-2016

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

THDPM-1

By-EMBUILT TECHNOLOGIES

www.embuilt.comwww.energylogger.blogspot.com

[email protected]

(THD MEASUREMENT WITH EXAMPLES AND FIGURES)

Date-03/09/2014

Page 2: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

THDPM-1

Auxiliary Supply : 180 – 240 VoltsInput Voltage : 3V – 300 VoltsCurrent : 10mA – 2.0 A*(200mA,500mA,10A,20A range are also available)

Frequency 45-55 Hz (45-65 Hz is also available)Measures upto 55th HarmonicAccuracy Class : 0.2%Voltage HarmonicsCurrent Harmonics

Page 3: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

INTRODUCTION

THDPM-1 is THD analyzer which measures upto 55th harmonic.

It provides Voltage and Current THD. It shows the net effect on THD due to load. It also shows following parameters-

VoltageCurrentWattFrequencyPower Factor

It is useful for testing of LED Drivers, SMPS, CFL, CHOKES, Charger, AC to DC Converter, UPS etc.

Page 4: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

MAIN PAGE

VOLTAGE

CURRENTWATT

PF

VOLTAGE THD

CURRENT THD

NET THD

(Frequency and PF shows alternately )

Press to see Voltage Harmonics

Page 5: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

VOLTAGE THD PAGE

3rdHarmonicVoltage

5th Harmonic7th Harmonic

Voltage rms Value

1st Harmonic

THD %

Press to see more Harmonics (upto 55th harmonic can be seen)

Press to see Current Harmonics

Press to see Previous Harmonic

Page 6: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

CURRENT THD PAGE

3rd Harmonic

Current

5th Harmonic7th Harmonic

Current rms Value

1st Harmonic

Current THD %

Press

to see more Harmonics (upto 55th harmonic can be seen)

Press to see previous Harmonic

Press to see to go to main page

Page 7: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

TEST BENCH SETUP

Page 8: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

THD ANALYSIS

Page 9: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

Experiment 1

Lets start testing with only Bulb load.

We take a 100 Watt Bulb load and connect it to load side.

Voltage THD is 2.90% and Current THD is 4.85%.

So Bulb causes a small distortion in current.

WITH BULB LOAD

Page 10: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 1 PART AVOLTAGE THD

Page 11: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 1 PART BCURRENT THD

Page 12: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

WITH CFL LOAD

Experiment with only CFL load.

We take a normal 14 Watt CFL and connect it to load side.

Voltage THD is 3.56% and Current THD is 26.99%.

A CFL distorts the current more.

Experiment 2

Page 13: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 2 PART AVOLTAGE THD

Page 14: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 2 PART BCURRENT THD

Page 15: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

WITH BULB AND CFL LOAD

Experiment with Bulb and CFL load.

Bulb specification is 100 Watt . CFL specification is 14W. Voltage THD is 3.23% and Current THD is

5.99% . Bulb has more power than CFL and also

linear in nature so it tends to decrease the current distortion.

Experiment 3

Page 16: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 3 PART AVOLTAGE THD

Page 17: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 3 PART BCURRENT THD

Page 18: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

WITH BULB AND CAPACITOR LOAD

Experiment with Bulb and Capacitor.

We take a capacitor of 3.15µF and connect to load side with a normal Bulb load.

Voltage THD is 3.12% and Current THD is 15.34%.

A Capacitor also distorts the current.

Experiment 4

Page 19: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 4 PART AVOLTAGE THD

Page 20: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 4 PART BCURRENT THD

Page 21: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

WITH LAPTOP LOAD

Experiment with Laptop load.

We take a laptop and connect it to supply with charger of 65watt.

Voltage THD is 7.92% and Current THD is 113.1%.

AC to DC Converters provides high distortion in current.

Experiment 5

Page 22: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 5 PART AVOLTAGE THD

Page 23: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 5 PART BCURRENT THD

Page 24: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

WITH BULB AND LAPTOP LOAD

Experiment with Laptop and Bulb load.

We Connect Bulb and Laptop at load side. Voltage THD is 8.83% and Current THD is

69.59% . A linear load reduces the current distortion. BULB has more power than Laptop Charger and

also linear in nature so it tends to decrease the current distortion.

Experiment 6

Page 25: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 6 PART AVOLTAGE THD

Page 26: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 6 PART BCURRENT THD

Page 27: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

WITH LED DRIVER LOAD

Experiment with LED and LED Driver Load.

We Connect 60 LEDs of 1Watt each at load side through LED Driver.

Voltage THD is 1.68% and Current THD is 133.9% .

LED Driver produces high distortion in current.

Experiment 7

Page 28: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 7 PART AVOLTAGE THD

Page 29: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 7 PART BCURRENT THD

Page 30: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

WITH LED BULB LOAD

Experiment with LED Bulb.

We Connect LED Bulb at at load side. Voltage THD is 2.55% and Current THD is

63.40% . LED Driver produces distortion in current.

Experiment 8

Page 31: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 8 PART AVOLTAGE THD

Page 32: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 8 PART BCURRENT THD

Page 33: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

WITH LED BULB AND NORMAL BULB LOAD

Experiment with LED Bulb and normal Bulb load.

We Connect LED Bulb and normal Bulb at load side.

Voltage THD is 1.78% and Current THD is 7.02%.

Bulb is linear device and has power more than LED Bulb so it reduces the Current distortion.

Experiment 9

Page 34: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 9 PART AVOLTAGE THD

Page 35: By- EMBUILT TECHNOLOGIES   Embuilt.tech@gmail.com (THD MEASUREMENT WITH EXAMPLES AND FIGURES) Date-03/09/2014

EXPERIMENT 9 PART BCURRENT THD