Building Environment
and Human ComfortCT10404
Thermal Comfort
By: Pubudu Kudahetti
![Page 2: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/2.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 2/80
Comfort
That condition of mind that expresses satisfaction with
the environment – CIBSE
Environmental Factors Considered for Comfort
Thermal Condition
![Page 3: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/3.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 3/80
Comfort
Environmental Factors Considered for Comfort
Visual Condition
![Page 4: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/4.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 4/80
Comfort
Environmental Factors Considered for Comfort
Acoustic Condition
![Page 5: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/5.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 5/80
Comfort
Environmental Factors Considered for Comfort
Indoor Air Quality (IAQ)
![Page 6: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/6.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 6/80
Comfort
Environmental Factors Considered for Comfort
Electromagnetic Fields
Static Electricity
![Page 7: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/7.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 7/80
Health Aspects
• A state of complete physical, mental and social well-being, not merely the absence of disease and infirmity - World Health Organization
Occupants Experience Symptoms
• mausea
• mucosal dryness or irritation, runny nose, eye problems,
• headaches, skin problems, heavy head and flu-like symptoms,
If a significant proportion of occupants experience these symptoms then, by definition the occupants are suffering from ‘sick building syndrome’
![Page 8: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/8.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 8/80
Thermal comfort
• Factors Affecting Thermal Comfort A person’s sensation of warmth is influenced by the following mainphysical parameters, which constitute the thermal environment
air temperature
mean radiant temperature
relative air speed
humidity.
• Besides these environmental factors there are personal Factors that affect thermal comfort :
Metabolic heat production
Clothing.
![Page 9: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/9.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 9/80
Thermal comfort
It is also required that there be no local discomfort
(either warm or cold) at any part of the human
body due to followings;
Asymmetric thermal radiation
Draughts
Warm or cold floors
Vertical air temperature differences.
![Page 10: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/10.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 10/80
Thermal comfort
Body Temperature
37 C 34 C
Hot Cold
•The normal body core temperature is 37 C.
• We have separate heat and cold sensors.• Heat sensors are located in the skin.
Signals when temperature is higher than 37
oC.
• Cold sensors are located in the skin. They
send signals when skin temperature is below34 oC.
• There are more cold sensors that warm
sensors.
• Heating mechanism:
– Reduced blood flow. – Shivering.
• Cooling mechanism:
– Increased blood flow.
– Sweating (Evaporation)
![Page 11: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/11.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 11/80
11
•Heat sensor sends impulses to
the hypothalamus whentemperature exceeds 37 oC.
•Cold sensors sends impulses tothe hypothalamus when skintemperature below 34 oC.
•The bigger temperaturedifference, the more impulses.
•If impulses are of samemagnitude, you feel thermallyneutral.
•If not, you feel cold or warm.
Warm
impulsesCold
impulses Activity
Perception of Thermal Environment
![Page 12: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/12.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 12/80
12
The Energy Balance
•Thermal Comfort can only be maintained when heat produced by metabolism equals
the heat lost from body.
Heat
Produ-
ced
Heat
Lost
![Page 13: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/13.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 13/80
13
The Energy Balance
•Parameters influencing the heat loss from a person
The dry heat loss (R+C)
represents ~70% at low Clo-
values and ~60% at higher Clo-values.
The evaporative heat loss (E) represents
~25% at moderate activities
Heat Loss by Conduction (K) and
Respiration (RES) are normally insignificant
compared to the total heat exchange.
Man is a poor machine. The efficiency is
less than 20% even for well-trained
athletes. Normally set to zero in thecomfort equation.
![Page 14: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/14.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 14/80
14
Mapping Physical & Psychological Comfort
Territories
temperature
h u m i d i t y
![Page 15: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/15.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 15/80
15
Mapping Physical & Psychological Comfort
Territories
-- dishealth
-- dishealth
conditions the body’s response
![Page 16: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/16.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 16/80
Heat Flow to/from Human Body
Conduction (sensible)
Convection (sensible)
Radiation (sensible)
Evaporation/Condensation
(latent)
![Page 17: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/17.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 17/80
Conduction
The flow of heat between two adjacentand touching solids (or from one part toanother part within an object) by direct
interaction between moleculesexample: walking on a beach in your barefeet
for comfort, the key environmental variableis: SURFACE TEMPERATURE
![Page 18: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/18.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 18/80
![Page 19: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/19.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 19/80
Radiation
The flow of heat between objects that are notin direct contact—but that can “see” eachother via electromagnetic radiation; theobjects may be a few inches or a million miles
apartexample: warming yourself in front of afireplace
for comfort, the key environmental variable is:SURFACE TEMPERATURE
![Page 20: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/20.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 20/80
Evaporation
The flow of heat that must be provided as amaterial changes state (from a liquid to a gas);this heat represents the energy required tobreak molecular bonds (called the latent heat
of vaporization)example: feeling cool coming out of aswimming pool on a breezy day
for comfort, the key environmental variables
are: RELATIVE HUMIDITY | AIR SPEED
![Page 21: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/21.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 21/80
Physical Basis of Thermal Comfort
Fundamentally, comfort involves a heat balance (athermal equilibrium) … where:
heat in ≈ heat out
where “heat in” is provided by metabolism, radiation,conduction, convection
where “heat out” is via radiation, conduction,convection, evaporation
![Page 22: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/22.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 22/80
Heat Flow to/from Human Body
Sensible Heat
– Flows via conduction, radiation, and convection
– Flow rate is generally related to space temperatures
Latent Heat
– Flows via evaporation
– Flow rate is generally related to space humidity
Total Heat Flow = sensible + latent flows
![Page 23: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/23.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 23/80
Heat Flow Mechanisms
three external “to” mechanisms; four “from”
mechanisms
![Page 24: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/24.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 24/80
The Mechanisms Adapt
the body automatically adapts to surrounding environmental conditions in its quest for thermalequilibrium; under high temperatures, evaporation becomes critically important
![Page 25: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/25.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 25/80
Measuring Environmental Factors
data logging
air temperature,
RH, wind speed
air speed
surface
temperature
wet and dry bulbtemperatures
![Page 26: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/26.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 26/80
MRT
MRT stands for mean radiant temperature
MRT is the (hypothetical) uniformtemperature of surrounding surfaces with
which the human body would exchange the
same heat by radiation as occurs in an
actual (non-uniform) environment
![Page 27: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/27.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 27/80
MRT
Surface temperatures in a typical room areoften not all the same (for example, cold
window glass, warm radiators); the human
body will radiate to/from these differentsurfaces. MRT is the temperature (if all
surfaces were at this one temperature) at
which the body would exchange the sameheat by radiation as occurs in the messy,
many-temperature real space.
![Page 28: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/28.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 28/80
Personal Factors Affecting Comfort
• Physical
– Clothing (specifically its insulation value in “clo”)
– Activity level (specifically metabolic heat production in“met”)
• Mental
– State of mind (experiences, expectations, influences ofother conditions, …)
These factors are not controlled through design, butmust be understood by a designer as they will affectoccupant thermal comfort responses
![Page 29: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/29.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 29/80
Physical Basis of Thermal Comfort
The potential for thermal equilibrium is:
– Influenced by environmental factors
• Often common to all occupants in a space
• Designer must control these conditions
– Influenced by personal physical factors
• Individual to each occupant in a space
• Designer must be aware of and consider theseconditions
![Page 30: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/30.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 30/80
The Designer’s Job
• Understand the physical basis of thermal
comfort and related variables
• Appreciate the influence of the psychologicalaspects of thermal comfort
• Use this understanding and appreciation to designspaces that building users will decide are thermallycomfortable
![Page 31: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/31.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 31/80
ASHRAE Thermal Comfort Chart
comfort
zone(s)
addressing operative temperature, relative humidity, and occupant clothing
For 80% occupant acceptability
![Page 32: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/32.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 32/80
Combined Heath Effect: Temperature + Humidity
http://www.nws.noaa.gov/om/heat/index.shtml
![Page 33: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/33.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 33/80
Humidity indoors
• Indoor humidity is a function of
– Outdoor humidity
– Indoor sources:
– Unvented cooking,
– Unvented bathrooms – Showering
– Number of Occupants
– Humidifier use
– Air conditioner use
– Clothes drying--mechanical or air drying
![Page 34: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/34.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 34/80
Humidity - Health Effects
(from Arundel et al., 1986)
Optimum
ZoneBacteria
Viruses
Fungi
Mites
Respiratory Infections*
Allergic Rhini tis and Asthma
Chemical Interactions
Ozone Production
10 20 30 40 50 60 70 80 90
Percent Relative Hu midity
![Page 35: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/35.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 35/80
35
Conditions for Thermal Comfort
•Two conditions must be fulfilled to
maintain Thermal Comfort: – Heat produced must equal heat lost. – Signals from Heat and Cold sensors
must neutralise each other.
•Mean Skin Temp. and Sweat Loss arethe only physiological parameterswhich influence the heat balance at a
given Metabolic Rate•The sweat production is used insteadof body core temperature, as measureof the amount of warm impulses.
•Relation between the parametersfound empirically in experiments.
•No difference between sex, age, race
or geographic origin.
Metabolic Rate
Metabolic Rate
80
100
31
0 1 2 3 4
0 1 2 3 4
20
40
60
W/m2
S w
e a t p r o d .
29
30
32
3334
![Page 36: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/36.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 36/80
Comfort Equation
![Page 37: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/37.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 37/80
Comfort Equation
![Page 38: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/38.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 38/80
Comfort Equation
![Page 39: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/39.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 39/80
Comfort Equation
H (Dry Heat Loss)
Ec Evaporative heat exchange at the skin
Cres Respiratory convective heat exchange
Eres Respiratory evaporative heat exchange
![Page 40: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/40.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 40/80
Thermal comfort predictive model
Most widely used :
•Comfort equation method (heat balance method)
(Links environmental conditions to body thermal load)
•Predicted Mean Vote method (PMV model).
(links body thermal load to a Thermal sensation scale)•Predicted percentage of dissatisfied (PPD).
(Empirically PMV is related to PPD)
Standards:
• ASHRAE Standard 55-2004: “Thermal Environmental conditions for Human
Occupancy.”
•ISO Standard 7730: “Moderate thermal environments- Determination of thePMV and PPD Indices and specification of the conditions for thermal comfort”.
![Page 41: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/41.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 41/80
Predicted Mean Vote Scale
- +3 Hot
- +2 Warm
- +1 Slightly warm
- +0 Neutral
- - 1 Slightly cool
- -2 Cool
- -3 Cold
The PMV index is used to quantify the degree of
discomfort
![Page 42: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/42.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 42/80
Predicted Mean Vote (PMV) Index
• The PMV index is mathematically complex to
compute, so Fanger (1970) provided look-up
tables to help practitioners determine
appropriate thermal conditions.
• Information from these tables, and graphical
representations of comfort conditions, is also
provided in modern thermal comfortstandards (e.g. ASHRAE, 2004: ISO, 1994).
![Page 43: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/43.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 43/80
Predicted Mean Vote (PMV) Index
The PMV index predicts the mean response
of a large group of people according to the
ASHRAE thermal sensation scale
![Page 44: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/44.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 44/80
Predicted Percentage Dissatisfied (PPD) Index
-0.5 < PMV <0.5 when PPD < 10%
PPD = 100-95 exp[-(0.03353PMV4+0.2179PMV2]
![Page 45: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/45.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 45/80
Predicted Percentage Dissatisfied (PPD) Index
PPD = 100-95 exp[-(0.03353PMV4+0.2179PMV2]
-< PMV <0.5 when PPD < 100.5 %
![Page 46: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/46.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 46/80
PMV/PPD Method
PMV = [0.303 exp ( -0.036 M ) + 0.028 ] L
L - Thermal load on the body
L = Internal heat production - heat loss to the actual
environmentL = M - W - [( Csk + Rsk + Esk ) + ( Cres + Eres )]
Predicted Percentage Dissatisfied (PPD)
PPD = 100 - 95 exp [ - (0.03353 PMV4 + 0.2179
PMV2)]
![Page 47: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/47.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 47/80
PMV PPD
0 5%
+- 0.5 20%
+-1.0 50%
![Page 48: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/48.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 48/80
Graphical representation Thermal comfort zones?
• ASHRAE 55-2004
– Based on
satisfaction (20%PPD)
– Season dependent
– For Officebuildings- nothomes
• Environmental
Factors:
– Metabolic rate-activity
– Clothing- insulation
– Air temperature
– Radiant temperature
– Air- speed
– HumidityOperative temperature
![Page 49: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/49.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 49/80
Operative Temperature
Operative temperature (To):
To = 0.45 Tair + 0.55 Tmrt
Tmrt - Mean radiant temperature
Tmrt = S AiTi / S Ai
Ti - Surface temperature of enclosure i
Ai - Area of surface i
NOTE: Operative temperature is the same as
dry bulb temperature if there is no radiant
heat!!! ( cos Tair =Tmrt)
![Page 50: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/50.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 50/80
Graphical representation Thermal comfort zones?
• ASHRAE 55-2004 – Based on
satisfaction (20%PPD)
– Season dependent
– For Officebuildings- not
homes (specificactivity level,clothing level)
– Adjusted comfort
zones for other
Summer
Winter
![Page 51: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/51.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 51/80
PMV and PPD
•PMV-index (Predicted Mean Vote) predicts the subjective ratings of the environment in agroup of people.
•PPD-index predicts the number of dissatisfied people.
![Page 52: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/52.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 52/80
What should be Estimated?
Parameters to estimate and calculate are:
Met - Estimation of Metabolic Rate
Clo - Calculation of Clo value
![Page 53: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/53.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 53/80
![Page 54: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/54.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 54/80
Met Value Table
Activity Metabolic Rates [M]
Reclining 46 W/m2 0.8 Met
Seated relaxed 58 W/m2 1.0 Met
Clock and watch repairer 65 W/m2 1.1 Met
Standing relaxed 70 W/m2 1.2 Met
Car driving 80 W/m2
1.4 MetStanding, light activity (shopping) 93 W/m2 1.6 Met
Walking on the level, 2 km/h 110 W/m2 1.9 Met
Standing, medium activity (domestic work) 116 W/m2 2.0 Met
Washing dishes standing 145 W/m2 2.5 Met
Walking on the level, 5 km/h 200 W/m2 3.4 Met
Building industry 275 W/m2 4.7 Met
Sports - running at 15 km/h 550 W/m2 9.5 Met
![Page 55: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/55.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 55/80
Met Value Examples
![Page 56: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/56.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 56/80
Calculation of Insulation in Clothing
• 1 Clo = Insulation value of 0,155 m2 oC/W
![Page 57: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/57.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 57/80
Cl l bl
![Page 58: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/58.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 58/80
Clo Values Table
Garment description Iclu Clo Iclu m2 C/W
Jackets VestJacket
0.130.35
0.0200.054
Coats over-trousers
CoatParkaOveralls
0.600.700.52
0.0930.1090.081
Sundries SocksShoes (thin soled)BootsGloves
0.020.020.100.05
0.0030.0030.0160.008
Skirt,dresses
Light skirt, 15cm above kneeHeavy skirt, knee-lengthWinter dress, long sleeves
0.100.250.40
0.0160.0390.062
Sleepwear ShortsLong pyjamasBody sleep with feet
0.100.500.72
0.0160.0780.112
Chairs Wooden or metalFabric-covered, cushioned
Armchair
0.000.100.20
0.0000.0160.032
![Page 59: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/59.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 59/80
Adj f Cl V l
![Page 60: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/60.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 60/80
Adjustment of Clo Value
1.0 Clo 0.5 Clo
1.2 met
Operative Temperature
P
P D ( P
r e d i c t e d P
e r c e n t a g e D i s s a t i s f i e
d )
![Page 61: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/61.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 61/80
M R di t T t
![Page 62: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/62.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 62/80
Mean Radiant Temperature
•The Mean Radiant Temperature is that uniform temperature of an imaginary
black enclosure resulting in same heat loss by radiation from the person, as theactual enclosure.
•Measuring all surface temperatures and calculation of angle factors is timeconsuming. Therefore use of Mean Radiant Temperature is avoided whenpossible.
O ti d E i l t T t
![Page 63: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/63.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 63/80
Operative and Equivalent Temperature
Operative temperature
Equivalent temperature
For given values of humidity, air speed,
metabolic rate, and clothing insulation, a
comfort zone may be determined. The comfort
zone is defined in terms of a range of operative
temperatures that provide acceptable thermal
environmental conditions or in terms of thecombinations of air temperature and mean
radiant temperature that people find thermally
acceptable
O ti d E i l t T t
![Page 64: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/64.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 64/80
Operative and Equivalent Temperature
Operative temperature Equivalent temperature
P j t d A F t
![Page 65: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/65.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 65/80
Projected Area Factor
tr = 20 C tr = 20 C tr = 20 C
O ti T t
![Page 66: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/66.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 66/80
Operative Temperature
• The Operative temperature to integrates the effect of ta and tr.
• An Operative Temperature transducer must have same heat exchange properties as
an unheated mannequin dummy.
D H t L
![Page 67: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/67.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 67/80
Dry Heat Loss
• Dry Heat Loss or equivalent temperature can be measured directly, using a heated
Operative Temperature shaped transducer.
• The Equivalent temperature teq integrates the effect of ta, tr and va .
• The Dry Heat Loss transducer is heated to the same temperature
as the surface temperature of a person’s clothing.
C f t T t
![Page 68: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/68.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 68/80
Comfort Temperature
1,7 CLO
2,5 METRH=50%
tco=6oC.
0,8 CLO
2,2 METRH=50%
tco=18oC.
0,5 CLO
1,2 METRH=50%
tco=24,5oC.
General Thermal Comfort
![Page 69: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/69.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 69/80
General Thermal Comfort
General Thermal Comfort
![Page 70: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/70.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 70/80
General Thermal Comfort
Local Thermal Discomfort
![Page 71: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/71.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 71/80
Local Thermal Discomfort
•Draught Radiation
Asymmetry
Vertical Air
Temperature
Differences
Floor
Temperature
![Page 72: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/72.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 72/80
Draught
![Page 73: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/73.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 73/80
Draught
•The sensation of
Draught dependson the airtemperature.
•At lower airtemperatures ahigher number
will bedissatisfied.
Mean Air Velocity
Evaluating Draught Rate
![Page 74: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/74.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 74/80
Evaluating Draught Rate
•Fluctuations in Air Velocity is describedby Turbulence Intensity (Tu).
•Draught Rate equation is based onstudies of 150 people, and stated in• ISO 7730.
Tu = 100*( SD / va)
SD:Standard Deviation of Air Velocity
va: Local Mean Air Velocity
Radiation Asymmetry
![Page 75: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/75.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 75/80
Radiation Asymmetry
•Radiant Temperature Asymmetry is perceived uncomfortable.•Warm ceilings and cold walls causes greatest discomfort.
Vertical Air Temperature Difference
![Page 76: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/76.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 76/80
Vertical Air Temperature Difference
•Vertical Air Temperature Difference is
the difference between AirTemperature at ankle and neck level.
Vertical Air Temperature Difference
25 oC
19 oC
Radiant asymmetry in the vertical
direction shall be less than 5oC (9oF) under
a warm ceiling and less than 10oC (18oF) in
the horizontal direction from a cool wall.
![Page 77: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/77.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 77/80
Workplace Measurements
![Page 78: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/78.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 78/80
Workplace Measurements
- 1.1 m
- 0.1 m
- 0.6 m
- 0.1 m
- 1.1 m
- 1.7 m
• Measurements of Vertical Temp. difference and Draught at ankle and neck.
• Other measurements should be performed at persons centre of gravity.
![Page 79: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/79.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 79/80
![Page 80: Building Env. & Human Comf](https://reader034.vdocuments.us/reader034/viewer/2022052313/577cc4991a28aba71199dd38/html5/thumbnails/80.jpg)
8/11/2019 Building Env. & Human Comf
http://slidepdf.com/reader/full/building-env-human-comf 80/80
Questions