  • 8/10/2019 [BTP-502-02-D15A]

    1/2

    VALUE UNIT

    50 KA1 sec

    50 cm

    = I X sqrt (t) / k 625 sqmm50 KA1 sec

    80

    1.1 x 625 687.5 sqmm

    400 m

    2 l w x t

    20 -m

    40000 cm7.5 cm50 cm

    Ra = 0.13

    2 dWhere,

    300 cm6.5 cm

    Rb = 5.54

    6 0.92

    1/ R ab 1/R a + 1/R bb

    Rab Ra x R b / (R a + R bb)

    Rab 0.11169388

    VALUE UNIT

    50 KA1 sec

    50 cm

    = I X sqrt (t) / k 625 sqmm50 KA1 sec

    80t = Operating time in (secs) =k = 80 for steel as per IS-3043

    I = Faulth Current (KA) =

    TECHNICAL DATAa) Resistivity (avg.) of soil ( ) - m =

    20 -m= (27.11+20.11+14.79+14.32+15.62)/5=18.39 say, 20(Reference Geotechnical report)b) Maximum fault current (I) - KA (rms) =c) Duration of shock (t) considered as sec.d) Depth of Burial of conductor (h) - cm

    RESISTANCE OF EARTHING MAT:

    Required Size of Earthing Grid (S)

    Ground Resistance is less than 1.0 , hence the calculation is OK

    Therefore 6 nos. of Earth Pits Provided are OK.

    PRIMARY REQUIREMENTa) The impedence to ground (Over all resistance of the earthing system)should not exceed 1.0 as per IS:3043

    EARTHING CALCULATION FOR PLANT AREA FOR BTP

    Rab = Total earth resistance

    Resistance of one electrode in isolation:(Refer IS-3043-1987)

    Rb = 100 Ln 4l

    L = Length of electrode in cmD = Diameter of electrode in cm

    Since Over all resistance for 1 Electrode should be

  • 8/10/2019 [BTP-502-02-D15A]

    2/2