bsic aircon and sprinkler computation

7
BASIC SIZING ( air conditioning ) a . calculate the area to be cooled. b. Using tables determine the coding capacity in BTU / h . c. 1 BTU / hr = 0.00039 ( Hp ) A . PRINCIPAL AND ADMIN OFFICE ( 10 person maximum ) ( 7x 9 ) = 63 m 2 52-63 m 2 In the table ; 52-63 m 2 is equivalent to 12500 BTU/ h Condition ; open in day time + 10 % Room ; more than two ( 2 person ) , # person ( 600 BTU/ h ) computation for space area of 52-63 m 2 Basic BTU = 12500 + 0.10 ( 12500 ) + 10 ( 600 BTU/ h ) Ans. 19, 750 BTU / h 7. 70 hp MODEL SYSTEM S24NKUA

Upload: glem-castro

Post on 21-Nov-2015

215 views

Category:

Documents


2 download

DESCRIPTION

for building

TRANSCRIPT

BASIC SIZING ( air conditioning ) a . calculate the area to be cooled. b. Using tables determine the coding capacity in BTU / h . c. 1 BTU / hr = 0.00039 ( Hp )

A . PRINCIPAL AND ADMIN OFFICE ( 10 person maximum )

( 7x 9 ) = 63 m2 52-63 m2

In the table ; 52-63 m2 is equivalent to 12500 BTU/ h Condition ; open in day time + 10 % Room ; more than two ( 2 person ) , # person ( 600 BTU/ h )

computation for space area of 52-63 m2

Basic BTU = 12500 + 0.10 ( 12500 ) + 10 ( 600 BTU/ h ) Ans. 19, 750 BTU / h 7. 70 hp

MODEL SYSTEM S24NKUAWall mounted model in Panasonic 19,750 24,000 Btu / h

CS-S24NKUA CU-S24NKUA

B. faculty 1 @ SECOND FLOOR ( 20 person maximum )

(7 x 9 ) = 63 m2 52-63 m2

In the table ; 52-63 m2 is equivalent to 12500 BTU/ h Condition ; Too sunny place + 10 % Room ; more than two ( 2 person ) , # person ( 600 BTU/ h )

Computation for space area of 52-63 m2

Basic BTU = 12500 + 0.10 ( 12500) + 20 ( 600 BTU/ h ) Ans. 25,750 BTU / h 10.04 hp

MODEL SYSTEM KS30NKUA

Wall mounted model in Panasonic 25,750 9,000 Btu / h CS-KS30NKU ( INDOOR UNIT )

C. faculty 2 @ THIRD FLOOR ( 20 person maximum )

(7 x 9 ) = 63 m2 52-63 m2

In the table ; 52-63 m2 is equivalent to 12500 BTU/ h Condition ; Too sunny place + 10 % Room ; more than two ( 2 person ) , # person ( 600 BTU/ h )

Computation for space area of 52-63 m2

Basic BTU = 12500 + 0.10 ( 12500) + 20 ( 600 BTU/ h ) Ans. 25,750 BTU / h 10.04 hp

MODEL SYSTEM KS30NKUA

Wall mounted model in Panasonic 25,750 30, 000 Btu / h CS-KS30NKU ( INDOOR UNIT )

D. faculty 3 @ FOURTH FLOOR ( 15 person maximum )

(7 x 9 ) = 63 m2 52-63 m2

In the table ; 52-63 m2 is equivalent to 12500 BTU/ h Condition ; Too sunny place + 10 % Room ; more than two ( 2 person ) , # person ( 600 BTU/ h )

Computation for space area of 52-63 m2

Basic BTU = 12500 + 0.10 ( 12500) + 15 ( 600 BTU/ h ) Ans. 22, 750 BTU / h 8.87 hp

MODEL SYSTEM 26PSK1U6

Wall mounted model in Panasonic 22, 750 25,000 Btu / h S-26PK1U6 ( INDOOR UNIT )

Computation( SPRINKLER & CISTERN )

Automated Sprinkler

Area per floor= 775. 03 sq. m. The building has an non-combustible construction

; C=0.8 ;

fire demand per floorTotal Fire Demand= 1314.91 gal/min. x 4 =5259.63 gallon Horizontal pipes = 25 mm in diameter Vertical pipes= 102mm in diameter because the building is less than Size of Cistern Tank1314.91 gallon per minute x 30 minutes= 39,447.3 gallons

Fire Escape SystemThe number of occupants per floor:1st floor- 1502nd floor- 2003rd floor-1804th floor- 120

Use: Ordinary use -7.6mm/person

Number of Occupants on 2nd floor ,since it has the most number of occupants.

7.6mm/person x 200 persons = 1520mm or 1.52 m width of the stairwell BRITISH THERMINAL UNIT ( BTU )

AREA ( m2 )

BTU / h

9-14 5000

15-23

6000

24-28

6500

29-33

7250

34-38

8000

39-41

8750

42-46

9650

47-51

10500

52-65

12500

66-93

15000

94-112

17700

113-149

24000

150-160

167-260

27000

33000