NYC Department of Education Building Condition Assessment Survey 2018-2019 X876 Architectural Inspection Inspection Type Last Edited Time In InspectionId BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457 School: 4946 2019-05-21 12:39PM 2019-05-21 11:14PM ARCHITECTURAL - ASSOCIATE 4991 2019-05-21 08:19AM 2019-06-27 05:08PM ARCHITECTURAL - SENIOR Asset Data Question Answer Was the Building Fully Accessible for Inspection? Yes Principal(s) Information Principal Name G. Valcing Principal Organization Bronx Leadership Academy - Bronx Meeting with Principal? Yes Principal Feedback The Principal had no comments regarding the Physical building condition at this time. Custodian Rich Leonard Fireman Doodnauth Mangroo Building Square Footage 48,000 Comments on the Area (Square Feet) None Comments on the Stories (Floors) plus Basements 2 (No Basement) Comments on the Year Built 1930 Comments on the Student Population 595 Comments on the Staff Population 96 Comments on the Number of Classrooms 26 Weather Fair Facade Photo Easter Avenue - West View Main Entrance Photo Facade A - Webster Avenue Page 1 of 27 Print Date: 7/3/2019 Mobile Validity Version 2.0 (P)

Upload: others

Post on 24-May-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Inspection Type Last EditedTime InInspectionId

BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457School:

4946 2019-05-21 12:39PM 2019-05-21 11:14PMARCHITECTURAL - ASSOCIATE

4991 2019-05-21 08:19AM 2019-06-27 05:08PMARCHITECTURAL - SENIOR

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? Yes

Principal(s) Information

Principal Name G. Valcing

Principal Organization Bronx Leadership Academy - Bronx

Meeting with Principal? Yes

Principal Feedback The Principal had no comments regarding the Physical building

condition at this time.

Custodian Rich Leonard

Fireman Doodnauth Mangroo

Building Square Footage 48,000

Comments on the Area (Square Feet) None

Comments on the Stories (Floors) plus Basements 2 (No Basement)

Comments on the Year Built 1930

Comments on the Student Population 595

Comments on the Staff Population 96

Comments on the Number of Classrooms 26

Weather Fair

Facade Photo

Easter Avenue - West View

Main Entrance Photo

Facade A - Webster Avenue

Page 1 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 2: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural InspectionRoof Photo

Roof 1 - North view

Have any Systems/Major Building Components been upgraded? Systems: Complete building renovation for conversion to school

use

Years: 1997

Systems: Limited Roofing repairs

Years: 2006

Systems: Limited Interior Flooring and sub- Flooring

replacement (1st Floor Corridor at Room 102 through

109)

Years: 2015

Systems: Partial interior Door replacement.

Years: 2016

Have there been any New Building Additions? No New Construction

Tandem No Tandem

Leased Space? Yes

Year Leased 1997

Inspection Type Full Inspection

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Accessibility

Accessibility Status Question Response

Physical Breakdown Structure Exists Complies Required Deficiency

FUNCTIONAL ACCESSIBILITY

Exterior Routes

YesExterior Entrances & Exits

NoNoExterior H/C Lifts

NoNoExterior Ramps and Railings

Interior Routes

NoNoCorridor and Lobby H/C Lifts

NoNoInterior Corridor Doors And Hardware

YesInterior Corridors & Lobbies

YesYesInterior Elevators

YesInterior Lobby Doors And Hardware

Page 2 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 3: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Physical Breakdown Structure Exists Complies Required Deficiency

NoInterior Ramps

Rooms & Spaces

NoArt Rooms

NoAuditorium

Cafeteria

Yes Yes1st Floor

Classrooms

Yes Yes1st - 2nd Floors

NoComputer Rooms

Gymnasium

Yes Yes1st Floor

Library

Yes YesRoom 212

Main Office

Yes YesRoom 128

NoMulti-purpose Room

Nurse's Office

Yes YesRoom 115

NoPool

Science Lab

Yes YesRooms 222, 225

Toilet Rooms (boys)

Yes Yes1st - 2nd Floors

Toilet Rooms (girls)

Yes Yes1st - 2nd Floors

Toilet Rooms (staff)

Yes Yes1st - 2nd Floors

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

Page 3 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 4: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

EXTERIOR Inspected

Does not existAREAWAY

Does not existAWNINGS AND CANOPIES

Does not existCHIMNEY

InspectedCOPING

Condition 2- Between Good and Fair

METAL:DETERIORATEDDeficiency

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE-IN-KIND

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1- Facade E

Violations No violations recorded

Does not existCORNICE

InspectedDOORS

InspectedDOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Condition 3- Fair

ROLL-UP DOOR:DETERIORATED DOOR - MINOR

DETERIORATION

Deficiency

Deficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 4 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 5: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Deficiency Photo 1

Exit 1

Violations No violations recorded

InspectedLINTELS

Condition 2- Between Good and Fair

STEEL:MINOR RUSTINGDeficiency

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Exit 4

Violations No violations recorded

Does not existTRANSOM/SIDE LIGHT

InspectedEXTERIOR SOFFITS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedEXTERIOR WALLS

Masonry, OtherMaterial Type(s)

21,000Replacement Quantity

Replacement Uom S.F.

Instance on Concrete Stucco Cement on Masonry - All Facades Inspected

2- Between Good and FairInstance Condition

Instance Quantity 21,000

Instance Quantity Uom S.F.

BRICK:DETERIORATED MASONRY SILLSDeficiency

Page 5 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 6: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan Reference

Elevation

Elevation Reference Facade A

40Deficiency Quantity

Quantity Uom L.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

STUCCO CEMENT SURFACE:CRACKS, SPALLINGDeficiency

Roof Plan Reference

Elevation

Elevation Reference Facades A, D, F, H

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 6 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 7: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo 1

Above Exit 1

Violations No violations recorded

Does not existLOADING DOCK

InspectedLOUVER

Condition 2- Between Good and Fair

BROKEN/ DENTED BLADESDeficiency

Roof Plan Reference

Elevation

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade F

Violations No violations recorded

InspectedPARAPETS

OtherMaterial Type(s)

4,500Replacement Quantity

Replacement Uom C.F.

Instance on Stucco over CMU Inspected

2- Between Good and FairInstance Condition

Instance Quantity 4,500

Instance Quantity Uom CF

No deficiencies recordedDeficiency

Does not existPLAZA DECK

InspectedROOF

Page 7 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 8: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

EXTERIOR

ROOF

InspectedROOFING

Replacement Quantity 28,000

Replacement Uom S.F.

InspectedLEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedROOF BARRIER

4- Between Fair and PoorCondition

CHAIN LINK:DETERIORATED, MAJOR RUSTINGDeficiency

Deficiency Location/Instance

120Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1 perimeter

Violations No violations recorded

Does not existROOF CAGE

Does not existROOF FENCE

Does not existROOF HATCH/SMOKE HATCH

InspectedROOFING

Instance on Modified Bitumen:All Roofs Inspected

3- FairInstance Condition

Instance Quantity 28,000

Instance Quantity Uom S.F.

“Does the roof have major mechanical equipment sitting on Dunnage

Steel less than 18" above the Roofing?"

No

Installation Year 2008

Source of Installation Year Documented

MODIFIED BITUMEN:ROOFING:DELAMINATIONDeficiency

Deficiency Location/Instance

200Deficiency Quantity

Quantity Uom S.F.

Page 8 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 9: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

EXTERIOR

ROOF

ROOFING

ROOFING

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENT

REMOVAL

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1( all over the roof)

Violations No violations recorded

MODIFIED BITUMEN:FLASHING:BASE FLASHING

DETERIORATED

Deficiency

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1

Violations No violations recorded

InspectedROOFING DRAINS

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedSPECIALTIES

InspectedBULKHEAD/PENTHOUSE

4- Between Fair and PoorCondition

BULKHEAD/PENTHOUSE

WALLS/EXTERIOR:CRACKS/SPALLING - MINOR

Deficiency

Page 9 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 10: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

EXTERIOR

ROOF

SPECIALTIES

BULKHEAD/PENTHOUSE

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Bulkhead

Violations No violations recorded

BULKHEAD/PENTHOUSE WALLS/INTERIOR:CMU OPEN

JOINTS

Deficiency

Deficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Bulkhead

Violations No violations recorded

BULKHEAD/PENTHOUSE DOORS:DETERIORATED DOOR

AND FRAME

Deficiency

Page 10 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 11: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

EXTERIOR

ROOF

SPECIALTIES

BULKHEAD/PENTHOUSE

Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE DOOR AND FRAME

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

BH

Violations No violations recorded

Does not existCUPOLA/ SPIRES/ TOWERS

Does not existDORMER

InspectedDUNNAGE STEEL

4- Between Fair and PoorCondition

MINOR RUSTINGDeficiency

Deficiency Location/Instance

200Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Roof 1 Dunnage

Violations No violations recorded

Does not existROOF/GRAVITY TANK

Does not existSKYLIGHT/ROOF VENT

Does not existSTAIRS/RAMPS: EXTERIOR

Page 11 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 12: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

EXTERIOR

InspectedWINDOWS

4,000Replacement Quantity

Replacement Uom S.F.

InspectedEXTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWINDOWS

Material Type(s) Aluminum

Instance on Aluminum - Double Hung:All Facades Inspected

3- FairInstance Condition

Instance Quantity 4,000

Instance Quantity Uom S.F.

Installation Year 1996

Source of Installation Year Documented

ALUMINUM - DOUBLE HUNG:DETERIORATEDDeficiency

Roof Plan Reference

Elevation

Elevation Reference All Facades

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE WINDOW

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

INTERIOR Inspected

Does not existAUDITORIUM

CAFETERIA

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

5- PoorInstance Condition

WOOD:DETERIORATED DOORDeficiency

EntrancesDeficiency Location/Instance

3Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

Page 12 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 13: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

CAFETERIA

Door(s)

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Entrance

Violations No violations recorded

Fixed Equipment

Instance on 1st Floor Does not exist

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Sliding-folding Partition

Instance on 1st Floor Does not exist

Stage

Instance on 1st Floor Does not exist

Walls

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 1st Floor Does not exist

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 2- Between Good and Fair

TECTUM:DAMAGED/MISSINGDeficiency

Corridor near Room 126, Rooms 102, 128, 208, 222 and other

Locations

Deficiency Location/Instance

60Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 222

Violations No violations recorded

InspectedDoor(s)

Condition 5- Poor

WOOD:DETERIORATED DOORDeficiency

Page 13 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 14: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

Rooms 105, 203, 213, 215Deficiency Location/Instance

5Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 203

Violations No violations recorded

METAL:DETERIORATED DOORDeficiency

Room 217Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 217

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Rooms 222, 237, Corridor near Rooms 119, 123, 225, and other

Locations

Deficiency Location/Instance

400Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor near Room 123

Violations No violations recorded

Page 14 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 15: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedSpecialties

InspectedClassroom Locker(s)

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existFixed Seating

InspectedWalls

Condition 2- Between Good and Fair

GYPSUM BOARD:DETERIORATEDDeficiency

Corridor near Rooms 107, 108, 202, 212 and other LocationsDeficiency Location/Instance

85Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor near Room 212

Violations No violations recorded

GYMNASIUM

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor Inspected

4- Between Fair and PoorInstance Condition

METAL:DAMAGED LOUVERDeficiency

Rooms 111B, 111 CDeficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 111B

Violations No violations recorded

Fixed Equipment

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

Page 15 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 16: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

GYMNASIUM

Fixed Equipment

No deficiencies recordedDeficiency

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Seating

Instance on 1st Floor Does not exist

Sliding-folding Partition

Instance on 1st Floor Does not exist

Stage

Instance on 1st Floor Does not exist

Walls

Instance on 1st Floor Inspected

3- FairInstance Condition

WALL PADDING:DETERIORATEDDeficiency

North, South, East, West Sides of RoomDeficiency Location/Instance

140Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

West Side of Room

Violations No violations recorded

PLASTER:CRACKS/SPALLINGDeficiency

West Side of RoomDeficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

West Side of Room

Violations No violations recorded

GYPSUM BOARD:DETERIORATEDDeficiency

Near Drinking FountainDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Page 16 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 17: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

GYMNASIUM

Walls

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Drinking Fountain

Violations No violations recorded

MASONRY:CRACKS/SPALLINGDeficiency

North, East Sides of RoomDeficiency Location/Instance

260Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

East Side of Room

Violations No violations recorded

Window Curtains/Shades/Blinds

Instance on 1st Floor Does not exist

InspectedINTERIOR DOOR HARDWARE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedINTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

KITCHEN

Instance on 1st Floor Inspected

Ceiling

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

METAL PAN:DAMAGED/MISSINGDeficiency

Near Room 137D, OfficeDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 17 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 18: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

KITCHEN

Ceiling

Deficiency Photo 1

Near Room 137D

Violations No violations recorded

ACOUSTIC TILES:DAMAGED/MISSINGDeficiency

Room 137DDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 137D

Violations No violations recorded

Door(s)

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

CONCRETE:CRACKSDeficiency

Room 137DDeficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 137D

Violations No violations recorded

Walls

Page 18 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 19: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

KITCHEN

Walls

Instance on 1st Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

LIBRARY

Instance on Room 212 Inspected

Built-in Furnishing

Instance on Room 212 Does not exist

Ceiling

Instance on Room 212 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Room 212 Inspected

4- Between Fair and PoorInstance Condition

WOOD:DETERIORATED DOORDeficiency

EntranceDeficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Entrance

Violations No violations recorded

Floor Finish

Instance on Room 212 Inspected

2- Between Good and FairInstance Condition

VINYL TILES:DETERIORATED SUBSTRATEDeficiency

Center of RoomDeficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Center of Room

Violations No violations recorded

Walls

Page 19 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 20: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

LIBRARY

Walls

Instance on Room 212 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

LOCKER ROOM

Instance on 1st Floor - Boys (75 Lockers) Inspected

NoAlternative Use

Instance on 1st Floor - Girls (72 Lockers) Inspected

NoAlternative Use

Ceiling

Instance on 1st Floor - Boys (75 Lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st Floor - Girls (72 Lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor - Boys (75 Lockers) Inspected

3- FairInstance Condition

METAL:DAMAGED LOUVERDeficiency

EntranceDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Entrance

Violations No violations recorded

Instance on 1st Floor - Girls (72 Lockers) Inspected

3- FairInstance Condition

METAL:DAMAGED LOUVERDeficiency

EntranceDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Page 20 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 21: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

LOCKER ROOM

Door(s)

Entrance

Violations No violations recorded

Floor Finish

Instance on 1st Floor - Boys (75 Lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st Floor - Girls (72 Lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Locker Room Lockers

Instance on 1st Floor - Boys (75 Lockers) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on 1st Floor - Girls (72 Lockers) Inspected

2- Between Good and FairInstance Condition

DAMAGED UNITSDeficiency

Locker 15Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Locker 15

Violations No violations recorded

Walls

Instance on 1st Floor - Boys (75 Lockers) Inspected

2- Between Good and FairInstance Condition

GYPSUM BOARD:DETERIORATEDDeficiency

Near EntranceDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Entrance

Violations No violations recorded

Page 21 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 22: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

LOCKER ROOM

Walls

Instance on 1st Floor - Girls (72 Lockers) Inspected

2- Between Good and FairInstance Condition

GYPSUM BOARD:DETERIORATEDDeficiency

Near EntranceDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Entrance

Violations No violations recorded

Does not existMULTI-PURPOSE ROOM

Does not existPOOLS

SCIENCE DEMO ROOM

Instance on Room 223 Inspected

NoAlternative Use

Instance on Room 224 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 223 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 224 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

SCIENCE LAB

Instance on Room 222 Inspected

NoAlternative Use

Instance on Room 225 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 222 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Instance on Room 225 Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

SCIENCE PREP ROOM

Instance on Room 227 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 227 Inspected

2- Between Good and FairInstance Condition

Page 22 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 23: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

SCIENCE PREP ROOM

Fixed Equipment

No deficiencies recordedDeficiency

Does not existSHOWER ROOM

InspectedSTAIRS/RAMPS: INTERIOR

Do Letter Stair Signs Exist? 1

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

METAL:DAMAGED LOUVERDeficiency

Stair A/1Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair A/1

Violations No violations recorded

Does not existPartition

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs and Landings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

MASONRY:CRACKS/SPALLINGDeficiency

Stair C/1Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair C/1

Violations No violations recorded

Page 23 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 24: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

InspectedSTRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFLOOR STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFOUNDATION WALLS

Material Type(s) Masonry

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedROOF STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existVAULTS-BUNKERS

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTOILET ROOMS - STUDENTS

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 5- Poor

WOOD:DAMAGED LOUVERDeficiency

Rooms 117, 118, 210, 211, 112ADeficiency Location/Instance

5Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 210

Page 24 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 25: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Door(s)

Violations No violations recorded

METAL:MISSING DOORDeficiency

Boys Locker RoomDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Boys Locker Room

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 3- Fair

BROKEN/MISSINGDeficiency

Boys Locker RoomDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Boys Locker Room

Violations No violations recorded

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

LIFE SAFETY Inspected

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Inspected

Does not existCONTAINERIZATION

Does not existDRAINAGE SYSTEM FOR ASPHALT

Does not existDRAINAGE SYSTEM FOR CONCRETE

Does not existDRAINAGE SYSTEM FOR SOIL

Does not existDRINKING FOUNTAINS

Page 25 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 26: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

SITE

Does not existFENCES

Does not existIRRIGATION SYSTEM

InspectedPAVING

InspectedDOT Sidewalk

Does not existAsphalt

InspectedConcrete

3- FairCondition

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

Along Webster Avenue, East 172nd StreetDeficiency Location/Instance

425Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Webster Avenue

Violations No violations recorded

Does not existPavers

InspectedSite Sidewalks & Walkways

Does not existAsphalt

InspectedConcrete

2- Between Good and FairCondition

CRACKS - MAJORDeficiency

Main EntranceDeficiency Location/Instance

15Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Main Entrance

Violations No violations recorded

Does not existPavers

Does not existStudent Non-Use

Does not existStudent Use

Does not existPLAYGROUNDS

Does not existPLAYING SURFACE

Does not existRETAINING WALLS

Does not existSEATING

Does not existSITE WALLS (NOT RETAINING WALLS)

Page 26 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 27: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, … · InspectionId Inspection Type Time In Last Edited School: BRONX LEADERSHIP ACADEMY - X, 1710 WEBSTER AVENUE, BRONX, NY, 10457

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X876Architectural Inspection

Question Response

SITE

Does not existSTAIRS/RAMPS: EXTERIOR

Page 27 of 27 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)