Briefing on using renewables to integrate renewables Clyde Loutan, Sr. Advisor, Renewable Energy Integration Board of Governors Meeting General Session December 14-15, 2016

Upload: others

Post on 03-Oct-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Briefing on using renewables to integrate renewables

Clyde Loutan, Sr. Advisor, Renewable Energy Integration

Board of Governors MeetingGeneral SessionDecember 14-15, 2016

Page 2: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Can variable energy resources provide essential reliability services to reliably operate the grid?

• NERC identified three essential reliability services to reliably integrate higher levels of renewable resources– Frequency control

– Voltage control

– Ramping capability or flexible capacity

• Test results demonstrated the plant has the capability to provide these essential reliability services

• Advancement in smart inverter technology allows VERs to provide services similar to conventional resources

• VERs with the right operating characteristics are necessary to decarbonize the grid

Page 2

Page 3: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

The ISO, First Solar and NREL demonstrated how a 300 MW solar PV plant can provide essential reliability services

Page 3

Test Performance

Ram

ping

• Ramp its real-power output at a specified ramp-rate

• Provide regulation up/down service

Voltage

• Provide reactive power support in various modes- Control a specified voltage schedule- Operate at a constant power factor- Produce a constant level of MVAR- Provide controllable reactive support (droop setting)- Capability to provide reactive support at night

Frequency

• Provide frequency response for low frequency and high frequency events- Control the speed of frequency response- Provide fast frequency response to arrest frequency

decline

Page 4: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Demonstrated how a solar plant ramping capability can be controlled to a specified ramp rate

Page 4

Page 5: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Demonstrated that the solar plant was able to accurately follow the 4-second regulation signals

Page 5

Page 6: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Regulation accuracy of the solar plant demonstration exceeded accuracy of conventional resources

Page 6

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

SteamTurbine

PumpTurbine

Hydro CombinedCycle

LimitedEnergyStorage

GasTurbine

Solar PV(Middle ofthe Day)

Solar PV(Sunset)

Solar PV(Sunrise)

Regulation Up Accuracy

Blue bars taken from the ISO’s informational submittal to FERC on the performance of resources providing regulation services between January 1, 2015 and March 31, 2016

Page 7: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Voltage Control: Test demonstrated the plant’s capability to control system voltage at night

Page 7

By changing the reactive output of the plant from +100 MVAR to -100 MVAR, the voltage at the POI changed from 242 kV to 227 kV (Green curve)

Page 8: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Solar plant frequency responsiveness was similar to or better than conventional resources

Page 8

Events ConventionalResource Performance

Solar PV response to high frequency

Compared to a combined cycle plant

Solar PV response to high frequency

Compared to a hydro plant

Solar PV response to low frequencyCompared to a hydro plant

Solar PV ability to arrest frequency decline within the inertia response timeframe (Fast frequency response)

Compared to a hydro plant

Page 9: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Solar response similar to a combined cycle plant using 3% governor-like droop setting for high frequency event

Page 9

192

194

196

198

200

202

204

10:2

9:29

10:2

9:31

10:2

9:33

10:2

9:35

10:2

9:37

10:2

9:39

10:2

9:41

10:2

9:43

10:2

9:45

10:2

9:47

10:2

9:49

10:2

9:51

10:2

9:53

10:2

9:55

10:2

9:57

10:2

9:59

10:3

0:01

10:3

0:03

10:3

0:05

10:3

0:07

10:3

0:09

10:3

0:11

10:3

0:13

10:3

0:15

10:3

0:17

10:3

0:19

10:3

0:21

10:3

0:23

10:3

0:25

10:3

0:27

10:3

0:29

10:3

0:31

10:3

0:33

10:3

0:35

10:3

0:37

10:3

0:39

MW

Actual Solar Response Expected Response (Combined Cycle Plant)

Page 10: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Solar response similar to a hydro plant using 5% governor-like droop setting for high frequency event

Page 10

Page 11: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Ability of solar plant to respond and arrest frequency decline similar to a hydro plant for a low frequency event

Page 11

Page 12: Briefing on using renewables to integrate renewables...resources providing regulation services between January 1, 2015 and March 31, 2016 Voltage Control: Test demonstrated the plant’s

Next steps• Continue to share test results:

– NERC’s Essential Reliability Services Task Force– NREL & GE Technical Review Committee for the West Wide study

on frequency response– FERC staff

• Evaluate the existing solar fleet to determine the amount of capacity able to provide essential reliability services

• Further explore additional opportunities for renewable resources to participate in the various markets for energy and ancillary services

• Issue final report in 4th quarter of 2016Page 12