brcp splitter block · install screws and nuts. tighten with properly sized close block elements....

18
BRCP Splitter Block BRCP-SP048IB BRCP-SP064IB BRCP-SP072IB Instructions July 2006 78-8135-7584-8-A

Upload: others

Post on 05-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

BRCP Splitter BlockBRCP-SP048IBBRCP-SP064IBBRCP-SP072IB

Instructions

July 2006 78-8135-7584-8-A

Page 2: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

� 78-8135-7584-8

Page 3: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

378-8135-7584-8

1.0 KitContentsNote: Examine kit contents. Ensure that all

components are present and that they are in a usable and defect free condition.

A. 3M™ BRCP Block (1) B. Diamond nut (2) C. Mounting bracket (2) D. Braided cable protector (2) E. Cable ties (2) F. Small screws (4) G. Large screws (2)

2.0 Blockidentification

Terminology:

Management rings Block back mount frame

Jumper ringsWire guidesColor code for wire guides:

Black = POTSWhite = LineOrange = DSLAM

Labelsandlabelholders:

Line identification labels are located at the left side of the block.

Free marking area is located at the right side of the block.

Page 4: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

4 78-8135-7584-8

An additional label holder (option) may be snapped onto the module front.

The blocks can be installed vertically, one above the other, or horizontally, side by side. Accordingly, the labels can be removed and flipped to properly represent horizontal or vertical installation.

3.0MountingtheBlock3.1 Disengage the locking latches and open the block.

Each block element can be secured in the open position.

Locking latches

Page 5: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

578-8135-7584-8

3.2 Verify that the existing holes in the frame mounting bar line up with the holes of the block back mount frame.

m CAUTION If the holes do not line up, drill new holes on the frame mounting bar. Do not drill holes on the block back mount frame as the heads of the screws will not allow the block to fully close with splitters installed.

Alignblockandmarkholes. Drillholeswithproperlysized drillbit.

3.3 Fix the block back mount frame on the frame mounting bar.

Installscrewsandnuts. Tightenwithproperlysized Closeblockelements. screwdriver.

Option1Use the diamond nuts and the large screws.

Option2Use the mounting brackets and the small screws if horizontal bar is thinner than 1.10" (28 mm).

4.0 DSLAMTermination

V0–V7: Termination of pairs 1 to 8 - VOICE (Blue strip, Black wire guide channel)

L0–L7: Termination of pairs 1 to 8 - LINE (Blue strip, White wire guide channel)

D0–D7: Termination of pairs 1 to 8 - DSLAM (Orange strip, Orange wire guide channel)

D8–D15: Termination of pairs 9 to 16 -DSLAM (Orange strip, Orange wire guide channel)

V8–V15: Termination of pairs 9 to 16 - LINE (Blue strip, White wire guide channel)

L8–L15: Termination of pairs 9 to 16 - VOICE (Blue strip, Black wire guide channel)

Termination Plan For 1 Block Element

Page 6: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

� 78-8135-7584-8

DSLAM termination can be achieved in two ways:

1. When running a jumper from another block: the jumper passes through the jumper ring on the top of the block and into the wire guide channel.

2. When running a jacketed cable directly from the DSLAM: the cables pass through the back mount frame first, then through the management rings and finally reach the top of the element passing through the openings in the block element mounting bracket.

4.1 Open the block element.

4.2 Pass the cable through the block back mount frame (leave a minimum of 15 inches (380 mm) of cable extending from the back mount frame).

4.3 Slide the braided cable protector up the cable.

Page 7: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

778-8135-7584-8

4.4 Cut the cable sheath approximately 1 inch (25 mm) outside the rear of the block back mount frame, per company practice.

4.5 Slide the cable sheath down the conductors about 10 inches (250 mm).

4.6 Slide the braided cable protector into the entrance port of the back mount frame and cable tie the braided cable protector on the outside of the back mount frame.

mCAUTION

Prior to completely removing the cable sheath, organize internal binder groups, per company practice.

4.7 Remove remaining section of cable sheath from the conductors.

Page 8: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

8 78-8135-7584-8

4.8 Route the first 16 cable pairs into the management ring (use the ring closest to the DSLAM module, as shown).

4.9 Route the first 16 cable pairs through the opening in the block element mounting bracket of the orange DSLAM module.

4.10 Close the block element.

4.11 Pull conductor bundle through mounting bracket.

4.12 Route the conductors into the orange wire guide per company practice and color code.

Page 9: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

�78-8135-7584-8

4.13 Pull each pair of conductors over the corresponding IDC slots, and split the pair between the slots, per company color code. Do this for all 8 pairs.

Terminate using the approved 3M™ SOR-OC Standard Tool.

4.14 Straddle the tool on the IDC contact with the screw head facing toward the middle of the module.

4.15 Push the tool into the module until “click” is felt, signifying the IDC contact.

Note: The strength applied on the tool does not have any influence on the quality of the termination.

4.16 Remove the wire scrap.

4.17 Repeat steps 4.14 through 4.16 until DSLAM termination is complete.

5.0 POTSJumperTermination

Note: Jumpers are terminated one pair at a time. The following steps will be repeated until all jumper pairs are connected.

5.1 Route POTS jumper from POTS block into the BRCP jumper ring.

5.2 Route the jumper pair into the black wire guide per company practice and color code.

Page 10: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

10 78-8135-7584-8

5.3 Pull each pair of conductors over the corresponding IDC slots and split the pair between the slots, per company color code.

Use the approved 3M™ SOR-OC Standard Tool, to achieve termination.

5.4 Straddle the tool on the IDC contact with the screw head facing toward the middle of the module.

5.5 Push the tool into the module until “click” is felt, signifying the IDC contact.

Note: The strength applied on the tool does not have any influence on the quality of the termination.

5.6 Remove the wire scrap.

5.7 Repeat steps 5.3 through 5.6 until POTS jumper termination is complete.

6.0 LINEJumperTermination

Note: Jumpers are terminated one pair at a time. The following steps will be repeated until all jumper pairs are connected.

6.1 Route LINE jumper from subscriber block into the 3M™ BRCP Jumper Ring.

Page 11: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

1178-8135-7584-8

6.2 Route the jumper pair into the white wire guide per company practice and color code.

6.3 Pull each pair of conductors over the corresponding IDC slots, and split the pair between the slots per company color code.

Terminate using the approved 3M™ SOR-OC Standard Tool.

6.4 Straddle the tool on the IDC contact with the screw head facing toward the middle of the module.

6.5 Push the tool into the module until “click” is felt, signifying the IDC contact.

Note: The strength applied on the tool does not have any influence on the quality of the termination.

6.6 Remove the wire scrap.

6.7 Repeat steps 6.4 through 6.6 until LINE jumper termination is complete.

7.0 ADSLSplitterModuleInsertion7.1 Open the block element.

Page 12: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

1� 78-8135-7584-8

7.2 Place the splitter module by inserting the 2 leading module guides into the light blue module.

Note: The directional arrow on the back of the splitter module should be pointing towards the center of the block element.

m CAUTIONEnsure the splitter module does not straddle both sides of the DSLAM (orange) module as possible damage could occur. When properly inserted, the splitter module will fully cover the blue mod-ule and straddle half of the DSLAM (orange) module as shown

.

7.3 Ensure the module is fully seated to provide proper connectivity.

Note: When two splitter modules are installed next to each other, the directional arrows must be pointing towards each other.

7.4 Close the block element.

Note: Removing the module: The subscriber can be disconnected from the data line simply by removing the splitter. After splitter removal, voice service is still active.

Page 13: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

1378-8135-7584-8

8.0 BridgingModuleInsertion

8.1 Open the block element.

8.2 Place the bridging module by inserting the 2 leading module guides into the light blue module.

Note: The directional arrow on the back of the bridging module should be pointing towards the center of the block element.

m CAUTIONEnsure the bridging module does not straddle both sides of the DSLAM module (orange) as possible damage could occur.

When properly inserted, the module will fully cover the blue module and straddle half of the DSLAM (orange) module as shown.

8.3 Ensure the bridging module is fully seated to provide proper connectivity.

Note: When two bridging modules are installed next to each other, the directional arrows must be pointing towards each other.

8.4 Close the block element.

9.0 DisconnectionPlug Subscriber may be disconnected from the

POTS line by inserting the disconnection plug into the front of the blue module.

m CAUTIONThe splitter module must be removed otherwise the plug used for the POTS disconnection is not effective.

Page 14: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

14 78-8135-7584-8

9.1 Open the block element.

9.2 Remove the splitter module at the rear of the block.

9.3 Close the block element.

9.4 Insert the disconnection plug into the front side of the blue module.

Note: The arrow on the top of the plug has no significance.

Page 15: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

1578-8135-7584-8

10.0 Testingthe3M™BRCPBlock10.1 TestPlug – To test the BRCP block the

C242739A test plug should be used. This test plug has four banana plugs on one side and a 3M™ BRCP Interface plug on the other. A pair of banana plugs is separately wired to each side of the BRCP interface plug. The BRCP interface plug shell color and corresponding banana plugs are shown below:

BRCPinterfaceplug Bananaplugs

Blue Blue/Yellow

White White/Red

The BRCP interface plug may be inserted into the block in two directions, allowing the technician to test any module in any direction by simply attaching two of the banana plugs to their tester.

Note: The splitter module for the pair being tested should be removed from the BRCP block prior to attempting any of these tests. The following tests will be done wherever the block is installed, ie. central office, remote, etc.

10.2 VoiceTesting - To test the V (Voice) side of a module, attach the blue and yellow banana plugs to the test unit. Insert the BRCP interface plug into the light blue module to be tested with the blue side of the BRCP interface plug facing the V side of the module.

10.3 LineTesting - To test the L (Line) side of a module, attach the blue and yellow banana plugs to the test unit. Insert the BRCP interface plug into the light blue module to be tested with the blue side of the BRCP interface plug facing the L side of the module.

Page 16: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

1� 78-8135-7584-8

10.4 DSLAMTesting - To test the D (DSLAM) side of a module, attach the blue and yellow banana plugs to the test unit. Insert the BRCP interface plug into the orange module to be tested with the blue side of the BRCP interface plug facing the appropriate D side of the module.

11.0 Alternatetestingthroughthe3M™BRCPBlock

Note: The splitter module for the pair being tested should be installed in the BRCP block prior to attempting the following tests. The following tests will be done from the customer premise back to the central office or remote.

11.1 POTSTesting - From the customer NID (Network Interface Device), a test unit may be plugged into the voice pair on the NID. Select the POTS test on the test unit and begin the test. The device will communicate through the BRCP block and splitter with the voice switch in the central office or remote location. A proper test unit will allow the technician to measure POTS loss, noise, longitudinal balance, etc.

11.2 xDSLTesting-The following test may only be performed if the test unit being used is capable of xDSL testing with a modem function. From the customer NID (Network Interface Device), a test unit may be plugged into the xDSL pair on the NID. A connection can then be made through the modem of the test unit, through the BRCP block and splitter and connect to the DSLAM in the central office or remote location. A proper test unit will allow the technician to measure maximum data rates, attenuation, line power, etc.

11.0 Accessories

Item 3M Part Number

Additional Label Holder P44505AA

Termination Tool 3M SOR OC C�34030A

Bridging Module C�4�738A

Disconnection Plug C����0�A

Test Plugs C�4�73�A

Page 17: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

1778-8135-7584-8

Page 18: BRCP Splitter Block · Install screws and nuts. Tighten with properly sized Close block elements. screw driver. Option 1 Use the diamond nuts and the large screws. Option 2 Use the

3M is a trademark of 3M Company.

Important NoticeAll statements, technical information, and recommendations related to 3M’s products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M’s current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M.

Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture for a period of one (1) year from the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted.

CommunicationMarketsDivision3MTelecommunications6801 River Place Blvd. Austin, TX 78726-9000 800.426.8688Fax 800.626.0329www.3MTelecommunications.com Please Recycle.

Litho in USA© 3M �00� 78-8135-7584-8-A