Brazed Plate Heat ExchangerOperations Manual

Page 2: Brazed Plate Heat Exchanger Operations Manualliterature.puertoricosupplier.com/001/EA949.pdfas necessary to make sure vibration cannot be transmitted to the heat exchanger. For larger

TABLE OF CONTENTS

Brazed Heat Exchangers from Polaris

deliver exceptional strength and

performance in a compact package.

These versatile units are widely used in

refrigeration, industrial and hydronics

applications. The highly skilled Polaris

engineering staff employs exclusive

design software to be sure of providing

you with exactly the brazed exchanger

to fit your application. Equally helpful

are Polaris’ experienced field

representatives, many of whom can

provide the brazed exchanger you need

from stock.

Brazed ExchangerOperations Manual

A. How the Polaris Brazed Heat Exchanger operates

B Applications

C Exchanger Specifications

D Advantages of Polaris Brazed Heat Exchangers

E Installation Guide

F Additional Information onRefrigeration Applications

G Start-up Procedures

H Shut-down Procedures

I Cleaning

Page 3: Brazed Plate Heat Exchanger Operations Manualliterature.puertoricosupplier.com/001/EA949.pdfas necessary to make sure vibration cannot be transmitted to the heat exchanger. For larger

How the Polaris BrazedHeat Exchanger operates

Each Polaris Brazed Heat Exchangeris assembled from embossed platesof high-quality stainless steel – up to200 herringbone-patterned plates ina single exchanger. Adjoining platesare reversed so as to form a lattice ofcontact points from the ridges of theplates. With the plates vacuum-brazedtogether, a compact, pressure-resistantand very efficient heat exchanger iscreated. (See Fig. 1)

In the finished unit, the ridges andindentations in the plates form twocompletely distinct channel systems,allowing maximum heat transferwhile keeping the transfer mediarigorously separated. With the media

flowing in true countercurrent anda complex plate pattern that createsvigorous turbulence, heat transfer ishighly efficient. Our standardexchanger meets 390°F, 435 psistandards; maximum flow capacityin our largest unit is 250 gpm.

Applications

Polaris Brazed Heat Exchangers arecost-effective, easy to install orreplace, providing a highly efficientmeans of heat transfer. Specify themfor any of the following applications:(See Fig. 2)

Hydronics• Snow melting –

sidewalk or driveway• Radiant heating• Domestic hot water

Industrial• Boiler blowdown• Hydraulic oil cooling• Heat recovery from hot

waste streams• Packaged systems

Refrigeration• Condensers• Evaporators• Economizers• De-superheaters• Subcoolers• Heat pumps

Fig. 1

A

B

Fig. 2

Oilseparator

Compressor

Storage tank

1. Condensor2. Subcooler3. Economizer

4. Evaporator5. Oil cooler6. Desuperheater

Typical Application for Brazed Heat Exchangers

refrigerante.g. wateroil

A

B

Page 4: Brazed Plate Heat Exchanger Operations Manualliterature.puertoricosupplier.com/001/EA949.pdfas necessary to make sure vibration cannot be transmitted to the heat exchanger. For larger

D

C

A

B

E F

STANDARD DATA• Min. working temperature -300˚F• Max. working temperature +390˚F• Max. working pressure 435 psi• Test pressure 652 psi

MATERIALS

(N = number of plates) (Solder connection available.)Higher working temperatures/pressures available.

TYPE

SL34TL

SL70TL

SL70TK

SL140TL

A

11 1/2"

19 5/8"

19 5/8"

23 7/8"

B

9 1/2"

17 1/2"

17 1/2"

20 1/2"

C

4 5/8"

4 5/8"

4 5/8"

9 3/8"

D

2 1/2"

2 1/2"

2 1/2"

5 7/8"

E

(N x .08)+0.3

(N x .09)+0.3

(N x .09)+0.4

(N x .10)+0.4

WEIGHT

LBS.

(N x .26)+ 1.3

(N x .48)+ 3.0

(N x .48)+ 3.0

(N x .95)+10.0

F

3/4"

3/4"

3/4"

3/4"

CONN. SIZE

NPT

1"

1 1/2"

1 1/2"

2 1/2"

AREA/PLATE

SQ.FT.

0.366

0.753

0.753

1.506

VOLUME/CHANNEL

GALLON

0.014

0.023

0.023

0.084

(inch)

• Close Temperature Approach –A small difference in thetemperatures of the exchangemedia (for instance, betweencondensing and cooling water)can result in substantially higherefficiency to the overall system.It’s often possible with brazedexchangers to use smaller systemcomponents, such as compressors.

• High Working Pressures – PolarisBrazed Heat Exchangers are ratedto pressures of 40 bar, making themwell suited to high-pressureapplications including thecondensing side of refrigerationsystems.

• Freeze Resistance – Because of thehigh turbulence in the channels,any tendency toward freezing ofcooling water is minimized. Assuch, temperatures at the waterside can be lower than in any otherkind of heat exchanger. Should asystem failure cause freezing in theunit, Polaris Brazed HeatExchangers will recover betterthan other types of heatexchangers.

• Compactness – Polaris Brazed HeatExchangers occupy as little as one-sixth the area of other types ofexchangers – a tremendousadvantage in many applications,especially prefabricated systems.

• Modularity – When systems arebuilt in modules, Polaris BrazedHeat Exchangers can easily bearranged in parallel.

• Economy – Considering theadvantages of brazed heatexchangers – low purchase price,fast and easy installation, lowshipping cost, simple tubinginstallation, smaller cabinets andso on – Polaris Brazed HeatExchangers are often considerablymore economical than alternatives.

Advantages of Polaris Brazed Heat Exchangers

D

C

Exchanger Specifications

Page 5: Brazed Plate Heat Exchanger Operations Manualliterature.puertoricosupplier.com/001/EA949.pdfas necessary to make sure vibration cannot be transmitted to the heat exchanger. For larger

Installation guide

1. General

Where possible, Polaris Brazed HeatExchangers should be mounted inthe vertical position. (See Fig. 3)Install mufflers or vibration absorbersas necessary to make sure vibrationcannot be transmitted to the heatexchanger. For larger connectiondiameters, use an expansion devicein the pipeline. A rubber mountingstrip can serve as a buffer betweenthe unit and the mounting clamp.(See Fig. 4)

2. Connecting to the system

• Use flexible connectors. It’s criticalthat vibrations from pipework andcontrol valves not be transferredto the heat exchanger.

• Don’t overtighten female unionsonto the threaded connections;

excessive force will shear theconnection braze. The threads areparallel. Polaris advises use of aconnection with the female partsealing against the top of the heatexchanger connection. (Check thechart below for maximumallowable torque.) Seal unions withO-rings or round gaskets at the endof the connection. Tape may alsobe used to seal the threads.

• Be sure that adequateexpansion/safety valves areinstalled into the adjacentpipework. Polaris recommendsthe use of expansion tanks.

• If pipework is to be soldered intothe nozzles on the exchanger:

– Fill the outer circuit with water;the circuit must be open to the air.

– Wrap a wet towel around the baseof the connection to be soldered.

– Use solder containing at least 45percent silver.

– Never weld connections onto ornear the exchanger. (See Fig. 5)

3. Avoiding water hammer.

Sudden changes in the velocity of anoncompressible fluid (such aswater) can result in “water hammer,”a condition that damages pipes,valves, heat exchangers and otherequipment. The quick closing of asolenoid valve in liquid lines is atypical cause. Sudden interruptionsof the fluid flow increase pressurefar above normal levels. High-intensity pressure waves then moveback and forth in the pipe betweenclosure and relief points. At a reliefpoint such as a large-diameter header,these waves can strike at extremelyhigh speed.

SL 34 30 50 20 30SL 70 60 150 40 90SL 140 160 350 100 200

Standard Connectionsfor Brazed Heat Exchangers

Assembly conditions*Twisting Bending TwistingBending

Operating conditions**

Maximum connection loads on brazed heat exchangers

Allowable Torque, Nm

* Single assembly loading in cold condition

** Load due to piping forces during normal operation, not considering high cycle fatigue

Fig. 4Fig. 3 Fig. 5

CorrectMountingPosition

Bottom Support Crossbar & bolts Studbolts

E

Mounting Options

Page 6: Brazed Plate Heat Exchanger Operations Manualliterature.puertoricosupplier.com/001/EA949.pdfas necessary to make sure vibration cannot be transmitted to the heat exchanger. For larger

Gas in Water out

Water inCondensate out

Refrigerant side Water side

The shock wave produced in thisway can cause substantial damageas it alternately expands andcontracts the pipe lines. In brazedheat exchangers, water hammer candeform the front or back plate intoa bulb shape, with resulting internalor external leakage.

An air chamber or water hammerarrestor can avoid or eliminate theseproblems. Valves with controlledclosing times or characteristics canalso control the problem.(See Fig. 6)

4. Refrigeration details

CondensersRefrigerant gas flows in at the topleft. Condensate liquid flows out atbottom left. Water inlet is at thebottom right and water outlet at thetop right. Connect water andrefrigerant for countercurrent flow.

Regulate and control the system viathe service medium circuit. Solderconnections to the refrigerant sidewhen using Polaris Brazed HeatExchangers as condensers.(See Fig. 7)

EvaporatorsThe mixture of liquid and refrigerantgas flows in at bottom left. Gas flowsout at top left. Water inlet is at thetop right and water outlet at bottomright. Connect water and refrigerantfor countercurrent flow in mostcases.

Place the expansion valve near theinlet connection. The valve shouldbe of slightly higher capacity thanthe unit, and should have an externalpressure equalizing connection toavoid unnecessary heating.

The sensor bulb located on thesuction side should be insulated fromambient air. It must be sensitiveenough to respond quickly to

changes in gas temperature. Allow atleast 500 mm between bulb and therefrigerant outlet connection.

Pipe diameter between theexpansion valve and the brazedexchanger should be the same asthat of the liquid line. Solderconnections to the refrigerant sidewhen using Polaris Brazed HeatExchangers as evaporators.(See Fig. 8)

Additional Informationon RefrigerationApplications

a. When operating temperatures arelow, insulate the unit to keepcondensation from freezing on theouter surface of the plate pack.

b. Use quick-acting controls for mostrefrigeration applications.

Fig. 7Fig. 6

F

Water hammer

Normal workingconditions, open valve

Quick closing of solenoidvalve, producing sudden

pressure rise

High-intensity pressurewaves travel back and

forth in the pipes

Flow Pattern for Condensor

Page 7: Brazed Plate Heat Exchanger Operations Manualliterature.puertoricosupplier.com/001/EA949.pdfas necessary to make sure vibration cannot be transmitted to the heat exchanger. For larger

Fig. 8

Gas out Water in

Water outGas/liquid in

Refrigerant side Water side

Start-up Procedures

1. Close all isolation valves.2. Fill and vent the coldest circuit

first.3. Start circulation of the cold circuit,

opening isolation valves gradually.4. Repeat the process with the hot

circuit.5. Start automatic control regulation.6. In steam systems, drain the steam

circuit before opening steamvalves. This precaution helpsreduce the chance of waterhammer and damage to theexchanger.

Shut-down Procedures

1. Close down the hot circuit byslowly adjusting the control valve.Maintain full flow on the coldcircuit.

2. When the control valve is fullyclosed, switch off the pump.

3. Slowly close down the cold circuit,then switch off the pump.

4. Close all isolation valves.5. When the unit is cool, drain it

completely.

Cleaning

When the likelihood of fouling ishigh (for instance, when hard wateris used), clean the exchanger bycirculating a cleaning liquid throughit. Use a tank with a weak acid forthis clean-in-place (CIP) process.A five-percent solution of phosphoricacid is a safe and effective choice formost units. If the exchanger iscleaned frequently, use a five-percentsolution of oxalic acid.

For best results, the cleaning solutionflow rate should be at least 1.5 timesthe normal flow rate, preferably inbackflush mode. Before restarting,flush the unit with plenty of freshwater to purge any remaining acid.Clean at regular intervals.(See Fig. 9)

Heat exchanger

Weak Acid

Fig. 9

H I

Evaporator Flow Arrangement Cleaning in place

G