Industrial and Commercial Power Systems Topic 5 FAULT CALCULATIONS The University of New South Wales School of Electrical Engineering and Telecommunications

Upload: others

Post on 10-Mar-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Industrial and Commercial Power SystemsTopic 5

FAULT CALCULATIONS

The University of New South Wales

School of Electrical Engineeringand Telecommunications

Page 2: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

short-circuit faults in supply system.

very high fault current causing equipment damage, fire, injury, etc.

require protection systems to detect fault currents and to take remedial action.

need to establish methods of calculating fault current in any particular location of the electrical installation.

Page 3: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

many types of fault in three phase systems

must know impedances of all system components

fault impedance itself may be non-zero, value =?

difficult to estimate accurately earth impedance

fault current contribution from machines etc.

DC offset in initial cycles of fault current

DC system faults also include inductance effects

Difficulties:

Page 4: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

three phase (symmetrical) faults

three phase to earth fault

single phase to earth fault

phase to phase fault

phase to phase to earth fault

Possible fault types:

We consider only symmetrical 3-phase faults. Often, this type gives maximum fault current level at any location and represents worst case situations.

Page 5: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 6: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

important parameter that designer of an electrical installation needs to know. Can be obtained from electricity distributor

prospective short-circuit current = current which would flow as a result of a bolted 3-phase fault.

"Bolted" refers to the phases being connected via a zero impedance connection.

In reality this is not physically possible, since there will always be a resistive component with a fault occurs.

Prospective s/c current and fault level (power):

Page 7: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Typical value at point of supply for 230/400V NSW distribution systems

Suburban residential areas: 10 kA Commercial and industrial areas: 25 kA

Knowing fault level: impedance of upstream circuit and devices (e.g.

transformers, conductors) can be derived.

Page 8: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

The prospective fault current varies at different points in the supply

Page 9: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 10: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 11: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 12: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

1

PER UNIT SYSTEM

Page 13: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

normalize electrical quantities

express voltage, current, kVA and impedance as percentages (per unit values) of their base values

simplify calculations substantially.

transformer treated as a simple impedance (no need for ratio).

Page 14: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Per unit values:

Page 15: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

need to specify two base values, and the other two base values can be derived.

usually, specify VB and SB

and thus:

Page 16: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

normally, VB is taken as rated system voltage.

SB is arbitrarily specified (say 10 or 1 MVA), or use rating of a major system component, e.g. supply transformer.

Page 17: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Three-phase systems

calculations done on a single-phase basis using per unit phase impedances in the one-line diagram.

VB is line voltage and SB is three-phase kVA

and note:

Page 18: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Example:

Page 19: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 20: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Example:

Page 21: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 22: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 23: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 24: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

2

EFFECTS AND REQUIREMENTS

Page 25: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

over-current protection requirements

peak electromagnetic forces

thermal heating effects

maximum fault current (and minimum fault current)

time discrimination requirements of protection operation

touch voltage on earthed object (personnel safety)

Knowing fault levels enables determination of:

Page 26: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Sources of fault currents:

electrical utility supply grid system

any in-house generation systems operating at time of the fault

any motors operating within the system at time of the fault

any electrical storage elements in the system (e.g capacitors)

Page 27: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Fault impedance variation:

for the utility supply, source impedance is constant (a stiff source)

for in-house generators or motors, impedance is time-varying, depending on the time after the short circuit:sub-transient reactance (Xd”) (First cycle)transient reactance (Xd’) (1.5 to 4 cycles)synchronous reactance (Xs) (30 cycles)

Synchronous motors sustain fault current longer than induction motors

Page 28: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 29: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

DC offset:

offset can increase initial current levels substantially

magnitude of DC offset level governed primarily by X/R ratio of faulted circuit

also dependent on angle on voltage waveform at which fault occurs

The physics behind is not easy!

Page 30: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

The system X/R determines how rapidly the DC decays.

Faults that occur at a current zero crossing don't produce a DC offset

Those that occur at a current max or min produce the largest DC offset that circuit will produce.

The actual DC offset will range between those values and will be different in each phase.

Page 31: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 32: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

3

FAULT CALCULATION METHODS

Page 33: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Assumptions:

Page 34: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Procedure: convert all impedances to per unit values

draw single line diagram of fault circuit,

all possible sources are modeled as ideal voltage source with their source impedance

simplify circuit and reduce it to

Page 35: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 36: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

4

FAULTS IN DC SYSTEMS

Page 37: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Sources: DC generators, synchronous converters, DC motors, rectifiers, battery banks, UPS

only resistance elements determine steady-state fault current.

L/R time constants usually long enough that steady state fault current will not be reached before protection operates.

arc interruption is much more difficult for DC than for AC

Page 38: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 39: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 40: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

5

FAULT CALCULATION DATAAND EXAMPLE

Page 41: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 42: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 43: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 44: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 45: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Example:

Required to find fault current at location A.

Use 20 MVA base.

Page 46: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 47: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 48: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 49: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 50: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 51: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 52: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 53: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection
Page 54: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Example (Students try in groups)

An 11kV, 10MVA, 50Hz, three-phase generator of 0.08 per unit reactance and negligible resistance, is connected to an 11/33kV, 12MVA transformer of 0.02+j0.05 per unit impedance. A line having a series impedance of 2+j4 ohms/phase is connected to the 33kV side of the transformer.

A symmetrical fault of zero impedance develops at the far end of the line. Calculate the fault current. How much energy would be dissipated in the system if the current remained at this value for 8 cycles?

Page 55: Bow Bowing Substation - University of New South …...short-circuit faults in supply system. very high fault current causing equipment damage, fire, injury, etc. require protection

Solution

11 kV10 MVAX = 8%

11/33 kV12 MVA

Z=0.02+j0.05 pu

(2+j4) Ω11 kV10 MVAX = 8%

11/33 kV12 MVA

Z=0.02+j0.05 pu

(2+j4) Ω

AV

SISVZkVV

AV

SISVZkVV

MVAS

base

base

base

base

base

basebase

base

base

base

base

base

basebase

base

1753

; 9.108 :33For

5253

; 1.12 :11For

:Thus ,10 Choose

2

2

=Ω===

=Ω===

=