bonheiden, 24 march 2016 mechelsesteenweg 247 ampli · pdf file2.3. - measurement of the total...

13
klant: 3816 ; verslag: XE3/00/016-00 (24/03/2016) ; p 1 / 4 Mechelsesteenweg 247 2820 BONHEIDEN telefoon: 015 55 51 51 telefax: 015 55 06 30 e-mail: [email protected] Bonheiden, 24 march 2016 AMPLI B.V.B.A. Leuvensesteenweg 128 3191 BOORTMEERBEEK Report number XE3/00/016-00 Date of inspection: 23 march 2016 Place of inspection: Belgium, Boortmeerbeek, Leuvensesteenweg 128. code - KB Data of inspection : 23.03.2016 Division : ELECTRICITY. Periodical examination according to art.271 of the A.R.E.I. Naam v/d verantwoordelijke die de controle bijwoonde:Mr Beghin Didier & Mr Carl Vandenbosch Inspection carried out by Mr. Boban in the presence of Mr. Beghin Didier & Mr Carl Vandenbosch 1. Description : Dimmer unit ART2000-1 (serial A2F586), containing: 5x residual current circuit breaker 63A / 30mA 4P 4x circuit breaker 63A 3P 1x circuit breaker 32A 3P 3x circuit breaker 16A 1P 4x ART tray (interchangeable) Dimmer unit ART2000-2 (serial A2F718), containing: 5x residual current circuit breaker 63A / 30mA 4P 4x circuit breaker 63A 3P 1x circuit breaker 32A 3P 3x circuit breaker 16A 1P 4x ART tray (interchangeable) Dimmer unit ART2000-3 (serial A2F889), containing: 5x residual current circuit breaker 63A / 30mA 4P 4x circuit breaker 63A 3P 1x circuit breaker 32A 3P 3x circuit breaker 16A 1P 4x ART tray (interchangeable) Dimmer unit ART2000-4 (serial A2F1040), containing: 5x residual current circuit breaker 63A / 30mA 4P 4x circuit breaker 63A 3P 1x circuit breaker 32A 3P 3x circuit breaker 16A 1P 4x ART tray (interchangeable) Dimmer unit ART2000-5 (serial A2F1039), containing: 5x residual current circuit breaker 63A / 30mA 4P 4x circuit breaker 63A 3P 1x circuit breaker 32A 3P 3x circuit breaker 16A 1P 4x ART tray (interchangeable) Dimmer unit ART2000-6 (serial A2F1819), containing: 5x residual current circuit breaker 63A / 30mA 4P 4x circuit breaker 63A 3P 1x circuit breaker 32A 3P 3x circuit breaker 16A 1P 4x ART tray (interchangeable)

Upload: dodung

Post on 22-Mar-2018

219 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Bonheiden, 24 march 2016 Mechelsesteenweg 247 AMPLI · PDF file2.3. - Measurement of the total insulation resistance at 500 VDC. 3. Remarks : - None. 4. Conclusion : ... Power distribution

klant: 3816 ; verslag: XE3/00/016-00 (24/03/2016) ; p 1 / 4

Mechelsesteenweg 2472820 BONHEIDENtelefoon: 015 55 51 51telefax: 015 55 06 30e-mail: [email protected]

Bonheiden, 24 march 2016

AMPLI B.V.B.A.

Leuvensesteenweg 128

3191 BOORTMEERBEEK

Report number XE3/00/016-00Date of inspection: 23 march 2016Place of inspection: Belgium, Boortmeerbeek, Leuvensesteenweg 128.

code - KB

Data of inspection : 23.03.2016

Division : ELECTRICITY.Periodical examination according to art.271 of the A.R.E.I.

Naam v/d verantwoordelijke die de controle bijwoonde:Mr Beghin Didier & Mr CarlVandenboschInspection carried out by Mr. Boban in the presence of Mr. Beghin Didier & Mr CarlVandenbosch

1. Description :Dimmer unit ART2000-1 (serial A2F586), containing:5x residual current circuit breaker 63A / 30mA 4P4x circuit breaker 63A 3P1x circuit breaker 32A 3P3x circuit breaker 16A 1P4x ART tray (interchangeable)

Dimmer unit ART2000-2 (serial A2F718), containing:5x residual current circuit breaker 63A / 30mA 4P4x circuit breaker 63A 3P1x circuit breaker 32A 3P3x circuit breaker 16A 1P4x ART tray (interchangeable)

Dimmer unit ART2000-3 (serial A2F889), containing:5x residual current circuit breaker 63A / 30mA 4P4x circuit breaker 63A 3P1x circuit breaker 32A 3P3x circuit breaker 16A 1P4x ART tray (interchangeable)

Dimmer unit ART2000-4 (serial A2F1040), containing:5x residual current circuit breaker 63A / 30mA 4P4x circuit breaker 63A 3P1x circuit breaker 32A 3P3x circuit breaker 16A 1P4x ART tray (interchangeable)

Dimmer unit ART2000-5 (serial A2F1039), containing:5x residual current circuit breaker 63A / 30mA 4P4x circuit breaker 63A 3P1x circuit breaker 32A 3P3x circuit breaker 16A 1P4x ART tray (interchangeable)

Dimmer unit ART2000-6 (serial A2F1819), containing:5x residual current circuit breaker 63A / 30mA 4P4x circuit breaker 63A 3P1x circuit breaker 32A 3P3x circuit breaker 16A 1P4x ART tray (interchangeable)

Page 2: Bonheiden, 24 march 2016 Mechelsesteenweg 247 AMPLI · PDF file2.3. - Measurement of the total insulation resistance at 500 VDC. 3. Remarks : - None. 4. Conclusion : ... Power distribution

klant: 3816 ; verslag: XE3/00/016-00 (24/03/2016) ; p 2 / 4

Dimmer unit ART2000-11 (serial A1F307), containing:3x residual current circuit breaker 63A / 30mA 4P3x circuit breaker 63A 3P3x circuit breaker 16A 1P

ART breaker tray 01 (serial 3825), containing:12x circuit breaker 16A 1P

ART breaker tray 02 (serial 3826), containing:12x circuit breaker 16A 1P

ART breaker tray 03 (serial 3876), containing:12x circuit breaker 16A 1P

ART breaker tray 04 (serial 4210), containing:12x circuit breaker 16A 1P

ART breaker tray 05 (serial 4412), containing:12x circuit breaker 16A 1P

ART breaker tray 06 (serial 4413), containing:12x circuit breaker 16A 1P

ART breaker tray 07 (serial 4625), containing:12x circuit breaker 16A 1P

ART breaker tray 08 (serial 4628), containing:12x circuit breaker 16A 1P

ART breaker tray 09 (serial 6630), containing:12x circuit breaker 16A 1P

ART breaker tray 10 (serial 6631), containing:12x circuit breaker 16A 1P

ART breaker tray 11 (serial 6632), containing:12x circuit breaker 16A 1P

ART breaker tray 12 (serial 6633), containing:12x circuit breaker 16A 1P

ART dimmer tray 13 (serial 9684),containing :12x circuit breaker 16A 1P

ART dimmer tray 14 (serial 9685),containing :12x circuit breaker 16A 1P

ART dimmer tray 01 (serial 2505), containing:12x circuit breaker 16A 1P

ART dimmer tray 02 (serial 2506), containing:12x circuit breaker 16A 1P

ART dimmer tray 03 (serial 2507), containing:12x circuit breaker 16A 1P

ART dimmer tray 04 (serial 2659), containing:12x circuit breaker 16A 1P

ART dimmer tray 05 (serial 3078), containing:12x circuit breaker 16A 1P

ART dimmer tray 06 (serial 3079), containing:12x circuit breaker 16A 1P

ART dimmer tray 07 (serial 3080), containing:

Page 3: Bonheiden, 24 march 2016 Mechelsesteenweg 247 AMPLI · PDF file2.3. - Measurement of the total insulation resistance at 500 VDC. 3. Remarks : - None. 4. Conclusion : ... Power distribution

klant: 3816 ; verslag: XE3/00/016-00 (24/03/2016) ; p 3 / 4

12x circuit breaker 16A 1P

ART dimmer tray 08 (serial 3081), containing:12x circuit breaker 16A 1P

ART dimmer tray 09 (serial 3823), containing:12x circuit breaker 16A 1P

ART dimmer tray 10 (serial 3824), containing:12x circuit breaker 16A 1P

ART dimmer tray 11 (serial 4622), containing:12x circuit breaker 16A 1P

ART dimmer tray 12 (serial 4623), containing:12x circuit breaker 16A 1P

ART dimmer tray 13 (serial 4624), containing:12x circuit breaker 16A 1P

ART dimmer tray 14 (serial 4626), containing:12x circuit breaker 16A 1P

ART dimmer tray 15 (serial 4627), containing:12x circuit breaker 16A 1P

ART dimmer tray 16 (serial 4628), containing:12x circuit breaker 16A 1PHoist controller V8/01, containing:1x residual current circuit breaker 40A / 300mA 4P1x circuit breaker 32A 4P1x circuit breaker 20A 4P3x circuit breaker 20A 2P8x motor protective circuit breaker 1,6-2,5A 4P

Hoist controller V8/02, containing:1x residual current circuit breaker 40A / 300mA 4P2x fuse-carrier 2P with 1x fuse cartridge (1P)2A8x motor protective circuit breaker 4-6.3A,3P

Hoist controller V16/01, containing:1x residual current circuit breaker 32A / 300mA 4P1x circuit breaker 32A 4P6x circuit breaker 20A 2P16x motor protective circuit breaker 0,4-8,3A 4P

Hoist controller V4/02, containing:1x circuit breaker 32A 4P

2. Control content :2.1. - Visual inspection of all the parts with regards to conformity with the BelgianRegulations.2.2. - Measurement of the continuity of the earth protecting conductors.2.3. - Measurement of the total insulation resistance at 500 VDC.

3. Remarks :- None.

4. Conclusion :The examinated electrical equipment is conform with A.R.E.I. regulations.The equipment may be put into service as far as it is correctly installed and maintainedin according to the directions of use.

The director,

Ir. K. CAERS

The inspector,

Billy Boban

Page 4: Bonheiden, 24 march 2016 Mechelsesteenweg 247 AMPLI · PDF file2.3. - Measurement of the total insulation resistance at 500 VDC. 3. Remarks : - None. 4. Conclusion : ... Power distribution

klant: 3816 ; verslag: XE3/00/016-00 (24/03/2016) ; p 4 / 4

Notes:1. Unless permitted otherwise by ATK and the client, this report may only be reproduced in its entirity.2. A report without signature or not printed on ATK watermarked paper, is only valid as initial notification, pending the final and detailed report.

© ATK 1999..2016 - XE3/00/016-00 - 24/03/2016 - 3816 - Type : [C-ENG]algemeenP:3816AMPLI-20160422.659 - I:ATK-BB-20160324.276 - M:ATK-BB-20160324.277 - VslID:43392665 - VslHash:5kws3yrazm6btu7c - https://eva.atk.be/verslag

Page 5: Bonheiden, 24 march 2016 Mechelsesteenweg 247 AMPLI · PDF file2.3. - Measurement of the total insulation resistance at 500 VDC. 3. Remarks : - None. 4. Conclusion : ... Power distribution

klant: 3816 ; verslag: XE3/00/016-01 (24/03/2016) ; p 1 / 2

Mechelsesteenweg 2472820 BONHEIDENtelefoon: 015 55 51 51telefax: 015 55 06 30e-mail: [email protected]

Bonheiden, 24 march 2016

AMPLI B.V.B.A.

Leuvensesteenweg 128

3191 BOORTMEERBEEK

Report number XE3/00/016-01Date of inspection: 23 march 2016Place of inspection: Belgium, Boortmeerbeek, Leuvensesteenweg 128.

code - KB

Data of inspection : 23.03.2016

Division : ELECTRICITY.Periodical examination according to art.271 of the A.R.E.I.

1. Description :

Dimmer unit DX626/1, containing:1x residual current circuit breaker 40A / 30mA 4P1x circuit breaker 32A 4P3x circuit breaker 20A 2P6x circuit breaker 25A 2P

Dimmer unit DX626/2, containing:1x residual current circuit breaker 40A / 30mA 4P1x circuit breaker 32A 4P3x circuit breaker 20A 2P6x circuit breaker 25A 2P

Dimmer unit MP-6/1 (serial E99 0001), containing:6x circuit breaker 25A 2P

Dimmer unit MP-6/2 (serial 627609), containing:6x circuit breaker 25A 2P

Dimmer unit MP-12/1 (serial 035/99), containing: 12x circuit breaker 20A 2P

Dimmer unit MP-24/1, containing:1x residual current circuit breaker 125A / 300mA 4P24x circuit breaker 12A 2P6x circuit breaker 20A 2P

Dimmer unit MP-24/2, containing:1x residual current circuit breaker 125A / 300mA 4P24x circuit breaker 12A 2P6x circuit breaker 20A 2P

Dimmer unit POWERCUBE-01 (serial A2K-PC-00131), containing: 3x residual current circuitbreaker 63A / 30mA 2P1x circuit breaker 63A 4P18x circuit breaker 10A 1P8x circuit breaker 16A 1P

Dimmer unit SR12/1 (serial 13146), containing:1x residual current circuit breaker 40A / 30mA 4P12x circuit breaker 13A 2P

Dimmer unit SR12/2 (serial 212824), containing:1x residual current circuit breaker 40A / 30mA 4P

Page 6: Bonheiden, 24 march 2016 Mechelsesteenweg 247 AMPLI · PDF file2.3. - Measurement of the total insulation resistance at 500 VDC. 3. Remarks : - None. 4. Conclusion : ... Power distribution

klant: 3816 ; verslag: XE3/00/016-01 (24/03/2016) ; p 2 / 2

12x circuit breaker 13A 2P

Dimmer unit SR12/3 (serial 992242), containing:1x residual current circuit breaker 40A / 30mA 4P12x circuit breaker 13A 2P

Dimmer unit SR12/4 (serial 231958), containing:1x residual current circuit breaker 40A / 30mA 4P12x circuit breaker 13A 2P

Dimmer unit SR12/5 (serial 242552), containing:1x residual current circuit breaker 40A / 30mA 4P12x circuit breaker 13A 2P

Dimmer unit SR12/6 (serial 271404), containing:1x residual current circuit breaker 40A / 30mA 4P12x circuit breaker 13A 2P

Dimmer unit WORK D-40K2, containing:12x circuit breaker 15A 1P---------------------------------------------------All Materials are inspected by BB on the 23.03.2016 Inspector: BB = Billy Boban

2. Control content :2.1. - Visual inspection of all the parts with regards to conformity with the BelgianRegulations.2.2. - Measurement of the continuity of the earth protecting conductors.2.3. - Measurement of the total insulation resistance at 500 VDC.

3. Remarks :- None.

4. Conclusion :The examinated electrical equipment is conform with A.R.E.I. regulations.The equipment may be put into service as far as it is correctly installed and maintainedin according to the directions of use.

The director,

Ir. K. CAERS

The inspector,

Billy Boban

Notes:1. Unless permitted otherwise by ATK and the client, this report may only be reproduced in its entirity.2. A report without signature or not printed on ATK watermarked paper, is only valid as initial notification, pending the final and detailed report.

© ATK 1999..2016 - XE3/00/016-01 - 24/03/2016 - 3816 - Type : [C-ENG]algemeenP:3816AMPLI-20160422.660 - I:ATK-BB-20160324.273 - M:ATK-BB-20160324.274 - VslID:43392626 - VslHash:6gabdh8r4zduancs - https://eva.atk.be/verslag

Page 7: Bonheiden, 24 march 2016 Mechelsesteenweg 247 AMPLI · PDF file2.3. - Measurement of the total insulation resistance at 500 VDC. 3. Remarks : - None. 4. Conclusion : ... Power distribution

klant: 3816 ; verslag: XE3/00/016-02 (24/03/2016) ; p 1 / 4

Mechelsesteenweg 2472820 BONHEIDENtelefoon: 015 55 51 51telefax: 015 55 06 30e-mail: [email protected]

Bonheiden, 24 march 2016

AMPLI B.V.B.A.

Leuvensesteenweg 128

3191 BOORTMEERBEEK

Report number XE3/00/016-02Date of inspection: 23 march 2016Place of inspection: Belgium, Boortmeerbeek, Leuvensesteenweg 128.

code - KB

Data of inspection : 23.03.2016

Division : ELECTRICITY.Periodical examination according to art.271 of the A.R.E.I.

1. Description :Power distribution unit PSU 32A-SH/01, containing:1x residual current circuit breaker 32A / 30mA 4P1x circuit breaker 32A 4P6x circuit breaker 16A 2P

Power distribution unit PSU 32A-SH/02, containing:1x residual current circuit breaker 32A / 30mA 4P1x circuit breaker 32A 4P6x circuit breaker 16A 2P

Power distribution unit PSU 32A-SH/03, containing:1x residual current circuit breaker 32A / 30mA 4P1x circuit breaker 32A 4P6x circuit breaker 16A 2P

Power distribution unit PSU 32A-SH/04, containing:1x residual current circuit breaker 32A / 30mA 4P1x circuit breaker 32A 4P6x circuit breaker 16A 2P

Power distribution unit PSU 32A-XS/01, containing:1x residual current circuit breaker 32A / 100mA 4P5x circuit breaker 16A 2P1x circuit breaker 20A 2P

Power distribution unit PSU 32A-XM/01, containing:1x residual current circuit breaker 32A / 300mA 4P1x circuit breaker 32A 4P3x circuit breaker 32A 2P1x residual current circuit breaker 25A / 30mA 4P1x circuit breaker 20A 2P

Power distribution unit PSU 32A-W/01, containing:1x residual current circuit breaker 40A / 300mA 4P6x circuit breaker 16A 2P

Power distribution unit PSU 32A-WL/02, containing:1x residual current circuit breaker 40A / 30mA 4P6x circuit breaker 16A 2P1x circuit breaker 32A 4P

Page 8: Bonheiden, 24 march 2016 Mechelsesteenweg 247 AMPLI · PDF file2.3. - Measurement of the total insulation resistance at 500 VDC. 3. Remarks : - None. 4. Conclusion : ... Power distribution

klant: 3816 ; verslag: XE3/00/016-02 (24/03/2016) ; p 2 / 4

Power distribution unit PSU 63A-M/01, containing:1x residual current circuit breaker 63A / 300mA 4P2x circuit breaker 32A 4P3x circuit breaker 32A 2P6x circuit breaker 20A 2P3x residual current circuit breaker 25A / 30mA 2P3x circuit breaker 20A 2P

Power distribution unit PSU 63A-MH#01(14164), containing:4x residual current circuit breaker 40A / 30mA 4P2x circuit breaker 32A 4P12x circuit breaker 16A 2P1x mainswitch 4P63A

Power distribution unit PSU 63A-MH#02(14165), containing:4x residual current circuit breaker 40A / 30mA 4P2x circuit breaker 32A 4P12x circuit breaker 16A 2P1x mainswitch 4P63A

Power distribution unit PSU 63A-MH#03,containing:4x residual current circuit breaker 40A / 30mA 4P2x circuit breaker 32A 4P12x circuit breaker 16A 2P1x mainswitch 4P63A

Power distribution unit PSU 63A-MH#04,containing:4x residual current circuit breaker 40A / 30mA 4P2x circuit breaker 32A 4P12x circuit breaker 16A 2P1x mainswitch 4P63A

Power distribution unit PSU 63A-M/03, containing:1x residual current circuit breaker 63A / 300mA 4P2x circuit breaker 32A 4P3x circuit breaker 32A 2P6x circuit breaker 20A 2P3x residual current circuit breaker 25A / 30mA 2P3x circuit breaker 20A 2P

Power distribution unit PSU 63A-M/02, containing:1x residual current circuit breaker 63A / 300mA 4P2x circuit breaker 32A 4P3x circuit breaker 32A 2P6x circuit breaker 20A 2P3x residual current circuit breaker 25A / 30mA 2P3x circuit breaker 20A 2P

Power distribution unit PSU 63A-XH/01, containing:1x residual current circuit breaker 63A / 300mA 4P2x circuit breaker 32A 4P12x circuit breaker 20A 2P

Power distribution unit PSU 125A-XS/01, containing:1x residual current circuit breaker 125A / 300mA 4P2x circuit breaker 63A 4P4x circuit breaker 32A 4P12x circuit breaker 20A 2P

Power distribution unit PSU 125A-XH/01, containing:

Page 9: Bonheiden, 24 march 2016 Mechelsesteenweg 247 AMPLI · PDF file2.3. - Measurement of the total insulation resistance at 500 VDC. 3. Remarks : - None. 4. Conclusion : ... Power distribution

klant: 3816 ; verslag: XE3/00/016-02 (24/03/2016) ; p 3 / 4

1x residual current circuit breaker 125A / 300mA 4P2x circuit breaker 63A 4P4x circuit breaker 32A 4P24x circuit breaker 20A 2P

Power distribution unit PSU 400A/01, containing:1x residual current circuit breaker 400A / 300mA 4P1x circuit breaker 160A-400A6x residual current circuit breaker 16A-30mA 2P4x circuit breaker 32A 4P4x circuit breaker 63A 4P3x circuit breaker 125A 4PRCB unit DIF 63A/01, containing:1x residual current circuit breaker 63A / 30mA 4P

RCB unit DIF 63A/02, containing:1x residual current circuit breaker 63A / 30mA 4P

RCB unit DIF 63A/03, containing:1x residual current circuit breaker 63A / 30mA 4P

RCB unit DIF 125A/01, containing:1x residual current circuit breaker 125A / 30mA 4P

RCB unit DIF 125A/02, containing:1x residual current circuit breaker 125A / 30mA 4P

RCB unit DIF 125A/03, containing:1x residual current circuit breaker 125A / 30mA 4P

Splitter unit SP 32A/01 (32216), containing:2x circuit breaker 16A 4P

Splitter unit SP 32A/02 (32232), containing:3x circuit breaker 32A 4P

Splitter unit SP 63A/02 (63232), containing:2x circuit breaker 32A 4P

Splitter unit SP 63A/03 (63232), containing:2x circuit breaker 32A 4P

Splitter unit SP 63A/04 (63263), containing:3x circuit breaker 63A 4P

Splitter unit SP 63A/05 (63263), containing:3x circuit breaker 63A 4P

Splitter unit SP 125A/02 (125263), containing:2x circuit breaker 125A 4P----------------------------------------

2. Control content :2.1. - Visual inspection of all the parts with regards to conformity with the BelgianRegulations.2.2. - Measurement of the continuity of the earth protecting conductors.2.3. - Measurement of the total insulation resistance at 500 VDC.

3. Remarks :4. Conclusion :The examinated electrical equipment is conform with A.R.E.I. regulations.The equipment may be put into service as far as it is correctly installed and maintainedin according to the directions of use.

Page 10: Bonheiden, 24 march 2016 Mechelsesteenweg 247 AMPLI · PDF file2.3. - Measurement of the total insulation resistance at 500 VDC. 3. Remarks : - None. 4. Conclusion : ... Power distribution

klant: 3816 ; verslag: XE3/00/016-02 (24/03/2016) ; p 4 / 4

The director,

Ir. K. CAERS

The inspector,

Billy Boban

Notes:1. Unless permitted otherwise by ATK and the client, this report may only be reproduced in its entirity.2. A report without signature or not printed on ATK watermarked paper, is only valid as initial notification, pending the final and detailed report.

© ATK 1999..2016 - XE3/00/016-02 - 24/03/2016 - 3816 - Type : [C-ENG]algemeenP:3816AMPLI-20160422.660 - I:ATK-BB-20160324.278 - M:ATK-BB-20160324.285 - VslID:43392704 - VslHash:vcchmywr2fq3rmpc - https://eva.atk.be/verslag