![Page 1: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/1.jpg)
Boiler Condensate Return Basics
Presented by Steve ConnorFebruary 24, 2016
![Page 2: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/2.jpg)
What We Are Covering Today?
• Brief review of the total steam system• Why a proper condensate return system is so important• Condensate return and affect on the property’s operation• What compromises the optimum condensate return system• The corrective actions• Delivering condensate back to the boiler room• The choices for holding and treating this condensate.• Summary• Q/A
2
![Page 3: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/3.jpg)
3
T
T
T
T
T
SteamCondensate
H P Cond ReturnVent
D A TankD A Tank
Feed PumpBoiler
Strainer
Trap Trap
Trap TrapTT
TT
DA Tank
TT
TT
TTT
HP SteamPRV 15 psig
250 F
LP Steam150 psig
366 F
Trap
LP Condensate Return
Cond Recovery& Pump
MotiveForce
Supply and Return System(s)
3
Legend
![Page 4: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/4.jpg)
Water inletTo drainTo drain
Total Boiler Room
4
Chemical feedWater softener
Feed system
![Page 5: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/5.jpg)
5
T
T
T
T
T
SteamCondensate
H P Cond ReturnVent
D A TankD A Tank
Feed PumpBoiler
Strainer
Trap Trap
Trap TrapTT
TT
DA Tank
TT
TT
TTT
HP SteamPRV 15 psig
250 F
LP Steam150 psig
366 F
Trap
LP Condensate Return
Cond Recovery& Pump
MotiveForce
Supply and Return System(s)
5
Legend
![Page 6: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/6.jpg)
Reasons why condensate system is important
• Operating cost reduction• Reliability• Safety
![Page 7: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/7.jpg)
Let’s first look at Efficiency & Cost of Operation
OK…
![Page 8: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/8.jpg)
What is the cost of steam?
2011 Steam Rate ($15.00/1,000 lb)
![Page 9: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/9.jpg)
Steam - Basic Concepts
2120 F.
2000 F.
1000 F.
320 F.
00 F.138 880
Latent Heatof Vaporization(or Latent Heat
of Condensation)
LatentHeat ofFusion
Btu per pound of water
SensibleHeat
SensibleHeat
3380 F.
Boiler operating at 100 psig and 200 OF feed water
1 lb water at 338O F
1 lb steam at 338O F
1 lb water at 200O F
9
![Page 10: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/10.jpg)
Saturated Steam Table
Pressure (psig) 0 10 80 100
Saturation Temp 212 239.5 323.9 337.9
Volume (ft3/lb) 26.4 16.46 4.66 3.89
Sensible Heat (btu/lb) 180 207.9 294.4 308.9
Latent Heat (btu/lb) 970 952.5 891.9 880.7
Total Heat (btu/lb) 1150 1160.4 1186.3 1189.4
Start @ 32 deg. F
10
![Page 11: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/11.jpg)
FWT
30
Gauge Pressure - psig
40
70
80
60
140
100
150
110
50
130
90
160
170
180
120
190
200
212
220
227
230
29.0
29.3
30.1
30.4
29.8
32.1
30.9
32.4
31.2
29.6
31.8
30.6
32.7
33.0
33.4
31.5
33.8
34.1
34.5
34.8
35.0
35.2
29.0
29.2
30.0
30.3
29.8
32.0
30.8
32.4
31.2
29.5
31.7
30.6
32.7
33.0
33.3
31.4
33.7
34.0
34.4
34.7
34.9
35.0
28.8
29.1
29.9
30.1
29.6
31.8
30.6
32.1
30.9
29.3
31.5
30.4
32.4
32.7
33.0
31.2
33.4
33.7
34.2
34.4
34.7
34.8
28.7
29.0
29.8
30.0
29.5
31.7
30.6
32.0
30.8
29.2
31.4
30.3
32.4
32.6
33.0
32.2
33.3
33.6
34.1
34.3
34.5
34.7
28.6
29.4
29.7
29.1
31.4
30.2
31.6
30.5
28.9
31.1
30.0
31.9
32.3
32.6
30.8
32.9
33.2
33.5
33.0
34.2
34.4
34.5
28.4
29.2
29.5
28.9
31.1
30.0
31.4
30.3
28.7
30.8
29.8
31.7
32.0
32.3
30.6
32.6
32.9
33.2
33.6
33.9
34.1
34.2
28.3
29.1
29.4
28.8
31.0
29.9
31.3
30.2
28.6
30.7
29.6
31.6
31.9
32.2
30.4
32.5
32.8
33.1
33.5
33.8
34.0
34.1
28.2
29.0
29.3
28.8
30.9
29.8
31.2
30.1
28.5
30.6
29.6
31.5
31.8
32.1
30.3
32.4
32.7
33.0
33.4
33.7
33.9
34.0
28.2
28.9
29.2
28.7
30.8
29.7
31.1
30.0
28.4
30.5
29.5
31.4
31.7
32.0
30.2
32.3
32.6
32.9
33.3
33.5
33.8
33.9
28.1
28.8
29.1
28.6
30.7
29.6
31.0
29.8
28.3
30.4
29.3
31.2
31.5
31.8
30.0
32.2
32.5
32.8
33.2
33.4
33.7
33.8
28.0
28.8
29.0
28.5
30.6
29.5
30.9
29.8
28.2
30.3
29.2
31.2
31.4
31.7
30.0
32.1
32.4
32.7
33.1
33.3
33.6
33.7
28.0
28.7
29.0
28.5
30.6
29.5
30.8
29.8
28.2
30.3
29.2
31.2
31.4
31.7
30.0
32.0
32.4
32.6
33.0
33.3
33.5
33.6
27.9
28.7
28.9
28.4
30.5
29.4
30.8
29.7
28.2
30.2
29.2
31.1
31.4
31.7
30.0
32.0
32.3
32.6
33.0
33.2
33.5
33.6
27.9
28.6
28.9
28.4
30.5
29.4
30.8
29.7
28.2
30.2
29.2
31.1
31.4
31.6
30.0
32.0
32.3
32.6
33.0
33.2
33.4
33.5
27.9
28.6
28.9
28.4
30.4
29.4
30.8
29.7
28.2
30.2
29.1
31.0
31.3
31.6
29.9
31.9
32.2
32.6
32.9
33.1
33.4
33.5
27.9
28.6
28.8
28.3
30.4
29.3
30.7
29.6
28.1
30.1
29.1
31.0
31.3
31.6
29.9
31.9
32.2
32.5
32.9
33.1
33.3
33.4
27.9
28.6
28.8
28.3
30.4
29.3
30.7
29.6
28.1
30.1
29.1
30.9
31.2
31.5
29.8
31.8
32.1
32.4
32.8
33.1
33.3
33.4
0 2 10 15 20 40 50 60 80 100 120 140 150 160 180 200 22027.8
28.5
28.8
28.3
30.4
29.3
30.6
29.6
28.1
30.1
29.0
30.9
31.2
31.5
29.8
31.8
32.1
32.4
32.8
33.0
33.3
33.4
240
Capacity At Operating Pressures vs. FWT
.
![Page 12: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/12.jpg)
Energy Dollars at Risk
$DOWNTHE
DRAIN
12
Every 10 degree drop in feed watertemperature equals a 1% drop in efficiency!
![Page 13: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/13.jpg)
13
Blowdown Heat Recovery Types
Blowdown Heat Recovery Unit• Proportional blowdown heat recovery system • Atmospheric feed or deaerator• Automatically controls TDS• Single or Multiple Boilers • Blowdown is cooled before discharge (Code compliance)
![Page 14: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/14.jpg)
Condensate Recovery
Savings Derived from:
• Fuel savings• Chemicals• Water • Sewer costs
Bringing back condensate at higher pressures will result in even greater savings!
![Page 15: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/15.jpg)
Reliability Issues
![Page 16: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/16.jpg)
Shell & Tube
Plate & FramePressure Regulating Valve
16
Jacketed Kettle
Split System
![Page 17: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/17.jpg)
Condensate Back-up or “Stall”
17
![Page 18: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/18.jpg)
Constant Orifice Purge
![Page 19: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/19.jpg)
Steam Pump Trap
Steam power pump
![Page 20: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/20.jpg)
Vacuum breaker
Water leg
Vacuum breaker
Trap
NOTE: 2.3 feet of static head = 1 pound pressure
![Page 21: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/21.jpg)
Air vent
![Page 22: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/22.jpg)
Non Condensable Gas Corrosion
Courtesy:http://www.engineeringtoolbox.com/oxygen-steel-pipe-...
50 F
86 F
122 F
• Almost 2 times more corrosive at 122o F than at 86o F
• Dissolved oxygen is 10 times more corrosive than CO2
CO2O2
![Page 23: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/23.jpg)
23
Air and Corrosion
The Piping is Subject to Corrosion
Subcooled Condensate + CO2 Forms Carbonic Acid
( CO2 + H2O H2CO3 )
40% more corrosive when combined with dissolved O2!!
23
![Page 24: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/24.jpg)
Carbonic Acid Corrosion
Cause and EffectCO2 + H2O = H2CO3
• Created where condensate is not fully drained.
• Attacks pipe and coil material.
![Page 25: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/25.jpg)
25
Carbonic Acid attack
Cause and EffectCO2 + H2O = H2CO3
25
![Page 26: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/26.jpg)
Mechanical Chemical
26
Most Economical Long-Term Approach
![Page 27: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/27.jpg)
27
Steam/Water Separator
Separation Mechanism
Cyclonic Type
• Cyclonic (centrifugal force)• Baffle (directional flow change)• Coalescence (trapping media) pad)
![Page 28: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/28.jpg)
Secondary Steam Branch Line
In-line separator
28To condensate return line
![Page 29: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/29.jpg)
Drip pockets & Steam Trap Set
Isolation valves
Check valve
strainertrap
![Page 30: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/30.jpg)
Drip Pockets
Steam Trap
Drip Leg6-10”
BD and Venting
Locations:• Low Spots• End of Main Ahead of
Expansion Joints• Ahead of Valves,
Bends & Regulators
30
Locate every 150 – 300 feet in a linear length of steam pipe
![Page 31: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/31.jpg)
31
Steam Main Size Drip Leg Diameter Drip leg Length4” 4” 12”6” 4” 12”8” 4” 12”10” 6” 18”12” 6” 18”14” 8” 24”16” 8” 24”18” 10” 30”20” 10” 30”24” 12” 36”
Suggested Sizing
31
![Page 32: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/32.jpg)
Moving condensate from source to boiler room
Motive force of steam pressure differential
![Page 33: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/33.jpg)
Condensate Transfer Tanks
• Standard models 200°F or less
• 210°F floor mounted units w/ low NPSH pumps
• 212°F elevated units available, thereby increasing NPSH
![Page 34: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/34.jpg)
Steam & Condensate Velocity
Typical Velocities in steam systems:Process Piping 6000 – 8000 fpm(70 – 90 MPH)LP Heating Systems
4000 – 6000 fpm
(45 – 70 MPH)Typical Velocities in Condensate return systemsLiquid 180 – 420 fpmBi-phase Approx. 3000-
7000 fpm
• Boiler operating pressure• Pounds of condensate• Pressure at trap inlet• Pressure in line• Condensate pipe diameter• Allowable pressure drop
Note: Pressure drop should not exceed 20% of boiler’s maximum operating pressure
![Page 35: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/35.jpg)
35
T
T
T
T
T
SteamCondensate
Common Condensate Return
D A TankD A Tank
Feed PumpBoiler
Strainer
Trap Trap
Trap TrapTT
TT
DA Tank
TT
TT
TTT
HP Steam LP Steam150 psig
366 F
MotiveForce
Supply and Return System(s)
35
Legend
Trap
![Page 36: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/36.jpg)
Saturated Steam Table
Pressure (psig) 0 10 80 100
Saturation Temp 212 239.5 323.9 337.9
Volume (ft3/lb) 26.4 16.46 4.66 3.89
Sensible Heat (btu/lb) 180 207.9 294.4 308.9
Latent Heat (btu/lb) 970 952.5 891.9 880.7
Total Heat (btu/lb) 1150 1160.4 1186.3 1189.4
Start @ 32 deg. F
36
.017
![Page 37: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/37.jpg)
Steam & Condensate Velocity
Typical Velocities in steam systems:
Process Piping 6000 – 8000 fpm
(70 – 90 MPH)
LP Heating Systems 4000 – 6000 fpm
(45 – 70 MPH)
Preferred Velocities in Condensate return systems
Liquid 180 – 420 fpm
Bi-phase Approx. 3000 - 7000 fpm
![Page 38: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/38.jpg)
Condensate Pipe sizing
• Boiler operating pressure• Pounds of condensate• Pressure at trap inlet• Pressure in line• Condensate pipe diameter• Allowable pressure drop
Condensate pipe sizing criteria
Example:• 2000#/HR• 7000 ft/min• ¼# drop• 150# inlet• Zero & 15# outlet
![Page 39: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/39.jpg)
And what’s the Safety Issue with condensate?
EfficiencyReliabilityCaptureTransportation
![Page 40: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/40.jpg)
Cause & Effect of Water Hammer
Three Types of Water Hammer:
Hydraulic
Thermal
Differential
![Page 41: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/41.jpg)
Thermal water hammer
The steam condensing void is rapidly filled with water
Thermal
![Page 42: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/42.jpg)
Thermal Imaging & diffusion of condensate lines
Diffuser
![Page 43: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/43.jpg)
43
Flash Tank
Flash Tank• Higher temperature drip traps• Vent to atmosphere• Use flash steam for LP use (non-modulating)• Preheat boiler feed water
Drip trap location
Steam User
![Page 44: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/44.jpg)
44
Calculating Flash Steam %
Formula: (hf1 – hf2 )/hfg2 = % Flash
HF1: Sensible Btu’s inHF2: Sensible Btu’s outHFG2: Latent Btu’s out
Example: User operating at 150 psig with discharge @ 15 psig…..
338 – 218 = 120/946 = 13% Flash Captured! . Btu’s SAVED!. Water & Sewer charges SAVED!. Chemicals SAVED!
![Page 45: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/45.jpg)
T
T
T
T
T
H P Condensate Return
Cond. Pump
D A TankD A Tank
Feed PumpBoiler
Strainer
Trap Trap
Trap TrapTT
TT
TT
TT
TTT
HP SteamPRV
15 psig250 F
LP Steam175 psig366 F
TrapMotiveForce
Feed Tank or DA
HP Condensate Recovery
![Page 46: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/46.jpg)
High Pressure Condensate Receiver
• Takes high pressure condensate directly from the user.
• No need to deaerate.• Pump directly into
boiler• Feed the HPR from
the DA
![Page 47: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/47.jpg)
Holding the boiler’s feed water and protecting the system
![Page 48: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/48.jpg)
HOT Condensate returned
DeaeratorBoiler Feed System
A vented receiver, wastes energy.
48
Pressurized receiver, saves energy.
Steam diffusing tube
![Page 49: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/49.jpg)
Chemical Feed Tank
49
• Phosphonates• Chelant (de-scaler)• Polymers• Sulfite• Non-sulfite scavengers• Amines (neutralizing or filming)
Mixing and Dispensing
![Page 50: Boiler Condensate Return Basicscleaverbrooks.com/reference-center/resource-library... · 3 T T. T. T. T. Steam. Condensate. H P Cond Return. Vent. D A Tank. Boiler. Feed Pump. Strainer](https://reader030.vdocuments.us/reader030/viewer/2022040617/5f215e53b4fb90766d63c392/html5/thumbnails/50.jpg)
Final Summary
50
• The boiler is part of a total system including its piping supply and return network, and all the associated accessories supporting the total whole.
• Proper condensate line engineering impacts energy efficiency, production reliability, and safety
• Every 10 degree pickup in feedwater temperature = 1% fuel savings• Condensate is sensible energy which increases with increasing
operating pressures• Reliability is affected by system backup (Stall) and system corrosion• Condensate line water hammer is normally Thermal type• Flash recovery systems can mitigate problem and save energy• Recommended velocities in bi-phase condensate lines is 3000 – 7000
ft/min• As line pressure in bi-phase condensate increases the volume
decreases, reducing line size for same velocity. • Condensate line sizing involves knowing boiler pressure, trap inlet
pressure, pounds of condensate, common line pressure, desired velocity, and desired pressure drop