Produced by the Employees of © Cleaver-Brooks Division, Aqua-Chem, Inc. 2002 The Boiler Book is protected by copyright and is to be used solely by consulting and specifying engineers for the purpose of selecting and specifying Cleaver-Brooks equipment. Any other use of The Boiler Book is strictly prohibited without written permission from Cleaver-Brooks. Cleaver-Brooks P.O. Box 421 Milwaukee, WI 53201 (414) 359-0600 email: [email protected] www.cleaver-brooks.com Printed in the U.S.A. The Boiler Book iii Performance Proven Worldwide

Upload: sally-courtney

Post on 20-Oct-2015

37 views

Category:

Documents


0 download

DESCRIPTION

Boiler operation

TRANSCRIPT

  • Produced by the Employees of

    Cleaver-Brooks Division, Aqua-Chem, Inc. 2002

    The Boiler Book is protected by copyright and is to be used solely by consulting and specifying engineers for the purpose of selecting and specifying Cleaver-Brooks equipment. Any other use of The Boiler Book is strictly prohibited without written permission from Cleaver-Brooks.

    Cleaver-BrooksP.O. Box 421

    Milwaukee, WI 53201

    (414) 359-0600email: [email protected]

    www.cleaver-brooks.com

    Printed in the U.S.A.

    The Boiler Book

    iii

    Performance Proven Worldwide

  • The Boiler Book is intended for use by qualified engineering professionals. All information contained herein is subject to change without notice. Cleaver-Brooks is only responsible for the accuracy of the information and data presented at time of publication. Cleaver-Brooks shall not be responsible for the use of this data or information nor for any systems, designs, or engineering in which the data or information is utilized.

    iv

  • TABLE OF CONTENTS

    Firetube Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section A

    A1 GeneralA2 Model CB BoilersA3 Model CB (LE) BoilersA4 Model CBW Boilers

    A6 Model CB Ohio Special BoilersA7 Model CBE BoilersA8 Model CEW BoilersA9 Model CEW-LN BoilersA10 Model CEW Ohio Special BoilersA11 Model CBL BoilersA12 Model ICB BoilersA13 Model ICB-LN Boilers

    Commercial Boilers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section B

    B1 Model FLX BoilersB2 Model 4 BoilersB3 Model 5 BoilersB4 Electric Boilers

    Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section D

    Emissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section E

    Stacks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section F

    Economizers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section G

    Feedwater Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section H

    H1 Spraymaster Deaerators (Single Tank)H2 Spraymaster Deaerators (Duo Tank)H3 Boilermate DeaeratorsH4 Surge TanksH5 Boiler Feed SystemsH6 Chemical Feed Systems and Metering PumpsH7 FiltersH8 SoftenersH9 DealkalizersH10 Blowdown SeparatorsH11 Blowdown Heat Recovery SystemsH12 Flash Tank Heat ExchangersH13 Sample Coolers

    System Fundamentals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section I

    I1 Boiler Selection ConsiderationsI2 Hot Water SystemsI3 Steam SystemsI4 General Engineering Data

    Glossary/Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section J

    A5 Discontinued

    Industrial Watertube Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Section C

    B5 - TrueFire BoilersB6 - ClearFire Boilers

    http://www.speci-fire.com/SPECI-FIRE_PDF/J-Glossary-Index.pdf
  • A1-1

    12-02

    Model CB Boilers

    Section A1

    GENERAL

    Model CBE Boilers

    Model CB-LE Boilers

    Model CB Ohio Special Boilers

    A2

    A3

    A4

    A5

    A6

    A7

    Model CEW Boilers

    Model CEW-LN Boilers

    A8

    A9

    Model CEW Ohio Special Boilers A10

    Model CBL Boilers A11

    A12

    A13

    Model ICB Boilers

    Model ICB-LN Boilers

    A1_TEXT.fm Page 1 Tuesday, December 10, 2002 2:35 PM

    Model CBH Boiler (discontinued)

    Model CBW Boilers

  • A1-2

    GGGGeeeennnneeeerrrraaaallll FFFFiiiirrrreeeettttuuuubbbbeeee BBBBooooiiii lllleeeerrrrssss

    12-02

    FEATURES AND BENEFITS

    The following Cleaver-Brooks firetube boiler models (CB, CB-LE, CBW, CB Ohio Special) include the following fea-tures and benefits.

    Packaged Design with Integral Front Head:

    Integral front head provides proper burner/boiler compatibility for maximum efficiency and ease of maintenance.

    Packaged boiler is factory assembled, wired, and tested for guaranteed performance and reliability.

    Packaged design allows for easy connection of utilities, minimum start-up requirements, and lower long-term maintenance requirements.

    Built and tested to ASME standards.

    Single Point Positioning Combustion Control Package:

    Accurate, repeatable combustion control for responsiveness to load swings.

    Single point linkage assembly for air and fuel simplifies adjustments and reduces start-up and maintenance costs.

    Unique variable contour.cam assembly allows accurate adjustment and enhances safe operation of the boiler.

    Computerized burner control provides accurate sequencing and continuous monitoring for optimum safety, efficiency, and reliability.

    Low Stack Temperatures:

    Guaranteed efficiency verified by low stack temperatures.

    Reduced fuel and operating costs.

    Low Excess Air:

    Operates at 3% O

    2

    with less than 200 ppm CO for maximum combustion efficiency.

    High efficiency and low maintenance requirements.

    High Steam Quality:

    Large steam space and liberal surface area ensure high steam quality, free from entrained particles of moisture.

    Provides reliable, high quality (98.5% dry) source of steam.

    Quiet Operation:

    Integral front head with vibration free combustion air fan provides quiet operation.

    Ideal for sound critical applications, like hospitals and schools.

    Heavy duty motor with direct drive, maintenance free, case-less fan.

    Integral forced draft fan eliminates the need for:

    Large diameter breeching.

    High chimneys.

    Induced draft fans.

    Barometric dampers.

    Sequencing draft controls.

    Thick Fiberglass Insulation:

    2" insulation covered with sturdy sheet metal lagging provides maximum efficiency and durable construction.

    All units finished with hard enamel paint coating.

    Customer Service and Support:

    Boiler start-up, final adjustment, and operator training provided with all firetube boilers.

    Emergency service response 24 hours a day, 7 days a week, from the industrys most advanced worldwide computerized parts/service distribution network.

    Largest network of factory trained technicians provide:

    System trouble shooting.

    Operator training.

    Customized factory-backed planned maintenance programs.

    Emergency boiler rental.

    Total after-sale support.

  • A1-3

    FFFFiiiirrrreeeettttuuuubbbbeeee BBBBooooiiii lllleeeerrrrssss GGGGeeeennnneeeerrrraaaallll

    12-02

    PRODUCT OFFERING

    Cleaver-Brooks firetube boilers are available in low pressure steam, high pressure steam, and hot water designs. Burners are available to fire natural gas, light oil, heavy oil, or a combina-tion of oil and gas. Optional alternate fuel (propane, mixed gas, digester gas, etc.) burners are also available.

    The firetube product offering is available in the following models.

    The Model CB Boiler (standard offering) is the premium fire-tube product offering providing maximum boiler efficiency, the widest range of size and pressures, and premium control packages.

    Four-pass dryback design.

    15 hp through 800 hp.

    150-350 psig high pressure steam.

    15 psig low pressure steam.

    30 or 125 psig hot water.

    Natural gas, light oil, or heavy oil firing.

    The Model CB (LE) Boiler is the premium firetube product offering with a low emission package.

    Four-pass dryback design.

    125-800 hp.

    20-60 ppm packages (natural gas).

    15 psig low pressure steam.

    150-300 psig high pressure steam.

    30 and 125 psig hot water.

    Natural gas or light oil.

    The Model CBW Boiler (standard offering) provides the advantages of the Cleaver-Brooks integral front head in a three-pass wetback design.

    Three-pass wetback design.

    100 hp through 800 hp.

    150-250 psig high pressure steam.

    15 psig low pressure steam.

    30 or 125 psig hot water.

    Natural gas, light oil, or heavy oil firing.

    The Model CB Ohio Special Boiler (standard offering) design is based on operator requirements of the state of Ohio, under the rules and regulations for unattended units.

    100 hp through 225 hp.

    Four-pass dryback design (100 hp).

    Two-pass dryback design (125-225 hp).

    150, 200 and 250 psig high pressure steam.

    15 psig low pressure steam.

    Natural gas or light oil firing.

    The Model CBE Boiler (standard offering) provides high qual-ity steam or hot water, utilizing a baseline boiler/burner design.

    Three-pass dryback design.

    60-350 hp.

    15 psig low pressure steam.

    150-300 psig high pressure steam.

    30 and 125 psig hot water.

    Natural gas or light oil.

    The Model CEW Boiler (standard offering) provides high quality steam or hot water, utilizing a baseline boiler/burner design.

    Three-pass wetback design.

    125-800 hp.

    15 psig low pressure steam.

    150-250 psig high pressure steam.

    30 and 125 psig hot water.

    Natural gas or light oil.

    The Model CEW-LN Boiler is the baseline firetube product offering with a low emission package.

    Three-pass wetback design.

    125-800 hp.

    30 ppm package (natural gas).

    15 psig low pressure steam.

    150-250 psig high pressure steam.

    30 and 125 psig hot water.

    Natural gas or light oil.

  • A1-4

    GGGGeeeennnneeeerrrraaaallll FFFFiiiirrrreeeettttuuuubbbbeeee BBBBooooiiii lllleeeerrrrssss

    12-02

    The Model CEW Ohio Special Boiler (standard offering) baseline design is based on operator requirements of the state of Ohio, under the rules and regulations of unattended units.

    Three-pass wetback design.

    100-225 hp.

    15 psig low pressure steam.

    150-200 psig high pressure steam.

    Natural gas or light oil.

    The Model CBL Boiler (standard offering) line provides high quality steam utilizing a boiler/burner package.

    Three or four-pass wetback design.

    800-1500 hp.

    150-250 psig high pressure steam.

    Natural gas, light oil, or heavy oil firing.

    The Model ICB Boiler is a baseline firetube product, designed to provide high quality steam or hot water. Its revolutionary design incorporates the key features and benefits of both the wetback and dry back firetube boilers.

    Three or four-pass Intercooled design.

    100 800 hp.

    15 psig low pressure steam.

    150 300 psig high pressure steam.

    30 and 125 psig hot water.

    Natural gas or light oil firing.

    The Model ICB-LN Boiler is a baseline firetube product, designed to provide high quality steam or hot water with a low emission package. Its revolutionary design incorporates the key features and benefits of both the wetback and dry back firetube boilers.

    Three or four-pass Intercooled design.

    100 800 hp.

    30 ppm package (natural gas).

    15 psig low pressure steam.

    150 300 psig high pressure steam.

    30 and 125 psig hot water.

    Natural gas or light oil firing.

    MODEL NUMBER, FUEL SERIES NUMBER, HORSEPOWER, AND DESIGN PRESSURE

    The model designation for Cleaver-Brooks firetube boilers includes the following:

    Light Oil: Series 100

    Natural Gas: Series 700

    Heavy Oil: Series 600

    Light Oil and Natural Gas: Series 200

    Heavy Oil and Natural Gas: Series 400

    For example, a model CB700-350-150ST would represent a model CB boiler, natural gas fired, 350 hp, 150 psig steam design pressure.

    All Cleaver-Brooks firetube boilers are built in accordance with ASME Codes and, with the exception of the Ohio Special Boilers and CBL Boilers, UL/ULC standards.

    Insurance requirements (e.g., Industrial Risk Insurance IRI, Factory Mutual FM, etc.) or special local code requirements may dictate additional controls or equipment to be included. Please contact your local Cleaver-Brooks authorized represen-tative for assistance in completing your specification or for additional information and optional equipment.

    Refer to Table A1-1 for information on the standard product offering for each firetube boiler model.

  • Table A1-1. Quick Comparison of Standard Features for Cleaver-Brooks FIretube Boilers

    A

    Consult your local Cleaver-Brooks authorized representative for higher design pressures.

    B

    Consult your local Cleaver-Brooks authorized representative for No. 4 & No. 5 oil applications.

    C

    Ohio Special-Model CB 100 hp 4-pass dryback, 125-225 hp 2-pass dryback.

    E

    Shell varies by square foot of pressure vessel and boiler horsepower.

    F

    ICB Three-Pass Boiler utilizes multiblade 100-350 and Rotary 400-800.

    MODEL

    CB15-800 HP

    (SECTION A2)

    CBLE125-800 HP

    (SECTION A3)

    CBW 100-800 HP

    (SECTION A4)

    CB OHIO SPECIAL100-225 HP

    (SECTION A6)

    CBE60-350 HP

    (SECTION A7)

    CEW125-800 HP

    (SECTION A8)

    CEW-LN125-800 HP

    (SECTION A9)

    CEW OHIO SPECIAL

    100-225 HP(SECTION A10)

    CBL800-1500 HP

    (SECTION A11)

    ICB100-800 HP

    (SECTION A12)

    ICB-LN100-800 HP

    (SECTION A13)

    Rated Capacity 15-800 hp 125-800 hp 100-800 hp 100-225 hp 60-350 hp 125-800 hp 125-800 hp 100-225 hp 800-1500 hp 100-800 hp 100-800 hp

    DesignPressure

    A

    Steam15-300 psig

    Steam15-300 psig

    Steam15-250 psig

    Steam Only15-250 psig

    Steam15-300 psig

    Steam15-250 psig

    Steam15-250 psig

    Steam15-250 psig

    Steam150-250 psig

    Steam15-300 psig

    Steam15-300 psig

    Hot Water30 & 125 psig

    Hot Water30 & 125 psig

    Hot Water30 & 125 psig

    Hot Water30 & 125 psig

    Hot Water30 & 125 psig

    Hot Water30 & 125 psig

    Hot Water30 & 125 psig

    Hot Water30 & 125 psig

    Boiler Type 4-Pass Dry Back 4-Pass Dry Back 3-Pass Wet Back Passes Vary C

    3-Pass Dry Back 3-Pass Wet Back 3-Pass Wet Back 3 Pass Wet Back 3 or 4-Pass Wet Back

    4-Pass Intercooled3-Pass Option

    4-Pass Intercooled3-Pass Option

    Shell Size 36" 15-40 hp48" 50-100 hp

    60" 125-200 hp78" 250-350 hp96" 400-800 hp

    60" 125-200 hp78" 250-350 hp96" 400-800 hp

    60" 100-200 hp78" 250-400 hp96" 500-800 hp

    48" 100 hp60"125-225 hp

    48" 60-100 hp60" 125-200 hp78" 250-350 hp

    60" 125-200 hp78" 250-400 hp96" 500-800 hp

    60" 125-200 hp78" 250-400 hp96" 500-800 hp

    60" 100-225 hp 114" or 126"

    E

    55" 100-125 hp60" 150-200 hp72" 250-300 hp78" 350-400 hp92" 500-600 hp

    106" 700-800 hp

    55" 100-125 hp60" 150-200 hp72" 250-300 hp78" 350-400 hp92" 500-600 hp

    106" 700-800 hp

    Fuel 15-800 hpNo. 2 Oil, Gas,Combination

    Oil/Gas

    No. 2 Oil,Gas,

    Combination Oil/Gas

    No. 2 Oil,Gas,

    CombinationOil/Gas

    100-225 hpNo. 2 Oil,

    Gas,Combination

    Oil/Gas

    No. 2 Oil,Gas,

    Combination Oil/Gas

    No. 2 Oil,Gas,

    CombinationOil/Gas

    No. 2 Oil,Gas,

    Combination Oil/Gas

    No. 2 Oil,Gas,

    Combination Oil/Gas

    800-1300 hpNo. 2 Oil, Gas, Combination

    Oil/Gas

    No. 2 Oil,Natural Gas

    Combination Oil/Gas

    No. 2 Oil,Natural Gas

    Combination Oil/Gas

    50-800 hpNo. 6 Oil

    B

    ,Gas,

    CombinationOil/Gas

    No. 6 Oil

    B

    ,Gas,

    Combination Oil/Gas

    100 hpNo. 6 Oil,

    Gas,Combination

    Oil/Gas

    800-1500 hpGas

    800-1000 hpNo. 6 Oil, Gas, Combination

    Oil/Gas

    Firing Method 15-20 hpOn-off

    Full Modulation Full Modulation Full Modulation Full Modulation Full Modulation Full Modulation Full Modulation Full Modulation Full Modulation Full Modulation

    30-40 hpLow-High-Low-Off

    50-800 hpFull Modulation

    Air Damper Type Single Blade15-40 hp

    Rotary 50-800 hp

    Rotary Rotary Rotary Multi-Blade Multi-Blade125-350 hp,

    Rotary 400-800 hp

    Rotary Multi-Blade Rotary & Louvers Multiblade100-250 hp

    Rotary 300-800 hp

    F

    Rotary

    Paint Color Blue Blue Blue Blue Blue Blue Blue Blue Blue Blue Blue

    Approvals UL & ULCBoiler/Burner

    UL & ULCBoiler/Burner

    UL & ULCBoiler/Burner

    N/A UL & cULBoiler/Burner

    UL & cUL Boiler/Burner

    UL & cULBoiler/Burner

    N/A 800-1000 hp UL & CSA

    (Burner Only)

    UL & cUL Boiler/Burner

    UL & cUL Boiler/Burner

    Steam Trim-Low Water Control

    McD&M 157 McD&M 157 McD&M 157 McD&M 157 McD&M 157 McD&M 157 McD&M 157 McD&M 157 McD&M 193-7 McD&M 157, McD&M 193

    McD&M 157, McD&M 193

    Steam Trim AuxLow Water Control

    Warrick 3C-2 Warrick 3C-2 Warrick 3C-2 Warrick 3C-2 Warrick 3C-2 Warrick 3C-2 Warrick 3C-2 Warrick 3C-2 Warrick 3C-2 Warrick 3C-2 Warrick 3C-2

    Water Trim-LowWater Control

    McD&MPS 750-MT-120

    McD&M PS 750-MT-120

    McD&MPS 750-MT-120

    N/A McD&MPS 750-MT-120

    McD&MPS 750-MT-120

    McD&MPS 750-MT-120

    N/A N/A McD&MPS 750-MT-120

    McD&MPS 750-MT-120

    12-02

  • Table A1-1. Quick Comparison of Standard Features for Cleaver-Brooks FIretube Boilers (Continued)

    MODEL

    CB15-800 HP

    (SECTION A2)

    CBLE125-800 HP

    (SECTION A3)

    CBW 100-800 HP

    (SECTION A4)

    CB OHIO SPECIAL100-225 HP

    (SECTION A6)

    CBE60-350 HP

    (SECTION A7)

    CEW125-800 HP

    (SECTION A8)

    CEW-LN125-800 HP

    (SECTION A9)

    CEW OHIO SPECIAL

    100-225 HP(SECTION A10)

    CBL800-1500 HP

    (SECTION A11)

    ICB100-800 HP

    (SECTION A12)

    ICB-LN100-800 HP

    (SECTION A13)

    ControlsSteam & Hot

    Water Controls

    Hi Limit (MR),Oper. Limit,Firing Rate30-800 hp

    Hi Limit (MR),Oper. Limit,Firing Rate

    Hi Limit (MR),Oper. Limit,Firing Rate

    Hi Limit (MR),Oper. Limit,Firing Rate

    Hi Limit (MR),Oper.Limit,Firing Rate

    Hi Limit (MR),Oper. Limit,Firing Rate

    Hi Limit (MR),Oper. Limit,Firing Rate

    Hi Limit (MR),Oper. Limit,Firing Rate

    Hi Limit (MR),Oper. Limit,Firing Rate

    Hi Limit (MR),Oper. Limit,Firing Rate

    Hi Limit (MR),Oper. Limit,Firing Rate

    Surface BlowoffConn. & Dip

    Tube on top C/L

    HPS-StdLPS-Conn. Only

    HPS-StdLPS-Conn. Only

    HPS-StdLPS-Conn. Only

    HPS-StdLPS-Conn. Only

    HPS-StdLPS-Conn. Only

    HPS-StdLPS-Conn. Only

    HPS-StdLPS-Conn. Only

    HPS-StdLPS-Conn. Only

    HPS-Std HPS-StdLPS-Conn. Only

    HPS-StdLPS-Conn. Only

    Air Vent Connection

    HW-Std. HW-Std. HW-Std. N/A HW-Std. HW-Std. HW-Std. N/A N/A HW-Std HW-Std

    Stack Thermometer

    Yes Yes Yes Yes No No No No Yes No No

    Drain Valve-HW & 15 psig-Steam

    No No No No No No No No N/A No No

    Front Door Hinge 15-200 hpDavit/Hinge250-800 hp

    Hinge 125-200 hpDavit /Hinge250-800 hp

    Hinge 100-200 hpDavit/Hinge250-800 hp

    Hinge Davit Davit Davit Davit Davit Davit Davit

    Rear Door Hinge 15-100 hpDavit 125-800 hp

    Davit Davit Hinge 100 hpDavit 125-225 hp

    Davit Davit Davit Davit Davit Davit Davit

    Insulation 2 inch 2 inch 2 inch 2 inch 2 inch 2 Inch 2 Inch 2 Inch 2 Inch 2 inch 2 inch

    StandardVoltage

    Requirements

    3 Phase 3 Phase 3 Phase 3 Phase 60-80 hp-1 Phase

    100-350 hp-3 Phase

    3 Phase 3 Phase 3 Phase 3 Phase 3 Phase 3 Phase

    Fuse Protection Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control Circuit &All 3 Phase Loads

    Except RemoteOil Pump

    Control CircuitTransformer

    Yes Yes Yes Yes Yes-3 Phase Only Yes Yes Yes Yes Yes Yes

    Flame SafeguardControl

    Cleaver-BrooksCB780

    Cleaver-BrooksCB780

    Cleaver-BrooksCB780

    Cleaver-BrooksCB780

    Cleaver-BrooksCB110

    Cleaver-BrooksCB110

    Cleaver-BrooksCB110

    Cleaver-BrooksCB110

    Cleaver-BrooksCB110

    Cleaver-BrooksCB110

    Cleaver-BrooksCB110

    Scanner Type Infrared Infrared Infrared Infrared Ultraviolet Ultraviolet Ultraviolet Ultraviolet Ultraviolet (Gas & No. 2 Oil)

    Infrared (No. 6 Oil)

    Ultraviolet Ultraviolet

    Control PanelLocation

    Front Head withKey Lock

    Front Head withKey Lock

    Front Head withKey Lock

    Front Head withKey Lock

    Burner withoutKey Lock

    Burner withoutKey Lock

    Burner withoutKey Lock

    Burner withoutKey Lock

    Burner withoutKey Lock

    On Burnerwithout Key Lock

    Remote-Right Side without

    Key Lock

    Indicating Lights 50-800 hpLD, FV, LW, FF

    LD, FV, LW, FF LD, FV, LW, FF LD, FV, LW, FF LD, FV, LW, FF LD, FV, LW, FF LD, FV, LW, FF LD, FV, LW, FF LD, FV, LW, FF LD, FV, LW, FF LD, FV, LW, FF

    Type of Pilot Interrupted Gas Pilot-Gas,

    No. 6 Oil & All Combination15-800 hp

    Interrupted Gas Pilot-Gas & All Combination

    Interrupted Gas Pilot-Gas,

    No. 6 Oil & All Combination

    Interrupted Gas Pilot-Gas, No. 6 Oil

    & All Combination

    Interrupted Gas Pilot-Gas & All Combination

    Interrupted Gas Pilot-Gas, No. 2 Oil & All Combination

    Interrupted Gas Pilot-Gas, No. 2 Oil

    &All Combination

    Interrupted Gas Pilot-Gas, No. 2 Oil

    &All Combination

    Interrupted Gas Pilot-Gas, No. 2 Oil,

    No. 6 Oil&

    All Combination

    Interrupted Gas Pilot-Gas, No. 2 Oil

    All Combination

    Interrupted Gas Pilot-Gas, No. 2 Oil

    All Combination

    Direct SparkIgnition-No. 2 Oil

    15-40 hp

    Spark Ignited Oil Pilot No. 2 Oil

    Spark Ignited Oil Pilot No. 2 Oil

    Spark Ignited Oil Pilot No. 2 Oil

    No. 2 OilDirect Spark

    Ignition60-100 hpGas Pilot

    125-350 hp

    Spark Ignited Oil Pilot-No. 2 Oil

    50-800 hp

    12-02

  • D

    Altitude, size, and fuel series limitations may apply.

    MODEL

    CB15-800 HP

    (SECTION A2)

    CBLE125-800 HP

    (SECTION A3)

    CBW 100-800 HP

    (SECTION A4)

    CB OHIO SPECIAL100-225 HP

    (SECTION A6)

    CBE60-350 HP

    (SECTION A7)

    CEW125-800 HP

    (SECTION A8)

    CEW-LN125-800 HP

    (SECTION A9)

    CEW OHIO SPECIAL

    100-225 HP(SECTION A10)

    CBL800-1500 HP

    (SECTION A11)

    ICB100-800 HP

    (SECTION A12)

    ICB-LN100-800 HP

    (SECTION A13)

    Gas Burner Type High Radiant Multi-Port-All Except

    125-200 hp-Annular Entry

    High Radiant Multi-Port-All Except

    125-200 hp-Annular Entry

    High Radiant Multi-Port-All Except

    125-200 hp-Annular Entry

    High RadiantMulti-Port 100 hp

    Annular 125-225 hp

    High RadiantMulti-Port

    High RadiantMulti-Port

    High RadiantMulti-Port

    High RadiantMulti-Port

    High RadiantMulti-Port

    High RadiantMulti-Port

    High RadiantMulti-Port

    Main Gas Valve Motorized Motorized Motorized Motorized Solenoid, Motorized Solenoid, Motorized Solenoid, Motorized Solenoid, Motorized Motorized Solenoid, Motorized Solenoid, Motorized

    Main Gas Control System

    Butterfly Valve Butterfly Valve Butterfly Valve Butterfly Valve Butterfly Valve Butterfly Valve Butterfly Valve Butterfly Valve Butterfly Valve Butterfly Valve Butterfly Valve

    Gas Pressure Regulator

    Required, Not Included

    Required, Not Included

    Required, Not Included

    Required, Not Included

    Included Included Included Included Included Included Included

    Gas PilotRegulator

    Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

    High & Low Gas Pressure Switches

    No-15-50 hpYes-60-800 hp

    Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

    Oil Burner Type Air Atomizing Air Atomizing Air Atomizing Air Atomizing Pressure Atomizing60-200 hp

    Air Atomizing250-350 hp

    Air Compressor-Shipped Loose

    Pressure Atomizing125-200 hp

    Air Atomizing250-800 hp

    Air Compressor -Shipped loose

    Air AtomizingAir Compressor

    125-300 hp-Mounted

    350-800 hp-Shipped Loose

    Air Atomizing Air Atomizing Pressure Atomizing

    100-150 hp Air Atomizing 200-800 hp

    Air Atomizing

    Main Oil Valves Solenoid Solenoid Solenoid Solenoid Solenoid Solenoid Solenoid Solenoid Motorized Solenoid Solenoid

    Oil ControlSystem

    Metering Valve Metering Valve Metering Valve Metering Valve Metering System Metering System Metering System Metering System Metering System Metering System Metering System

    Oil Pump Included Included Included Included Included Included Included Included Included Included Included

    Location of Oil Pump

    No. 2 Oil 15-40 hp on Front Head;

    50-800 hp Remote

    No. 2 Oil125-800 hp

    Remote

    No. 2 Oil 100-800 hp Remote

    No. 2 Oil100-225 hp

    Remote

    No. 2 Oil 60-200 hp Burner Mounted

    No. 2 Oil 250-350 hp

    Remote

    No. 2 Oil125-200 hp

    Burner MountedNo. 2 Oil

    250-800 hpRemote

    No. 2 Oil125-800 hp

    Remote

    No. 2 Oil100-225 hp

    Remote

    No. 2 Oil Remote

    No. 2 Oil100-150 hp

    Burner Mounted No. 2 Oil

    200-800 hp Remote

    No. 2 Oil100-800 hp

    Remote

    No. 6 Oil 50-800 hp, Remote

    No. 6 Oil100-800 hp Remote

    No. 6 Oil100-225 hp

    Remote

    No. 6 Oil Mounted on Oil Pump/Oil

    Heater Skid

    NOx Control No-Use CBLE Induced FGR

    D

    (LE Option)125-800 hp20-60 ppm

    (Natural Gas)

    No-Use CEW-LN N/A N/A No-Use CEW-LN Induced FGR30 ppm(Natural

    Gas)

    N/A Optional-Induced FGR 30 ppm

    (Natural Gas) up to 1300 hp.

    No-Use ICB-LN Induced FGR 30 ppm

    (Natural Gas)

    Maximum StackPressureVariation

    15-40 hp+ or-0.25" W.C.

    + or-0.25" W.C. + or-0.50" W.C. + or-0.25" W.C. + or-0.25" W.C. + or-0.25" W.C. + or-0.25" W.C. + or-0.25" W.C. + or-0.50" W.C. + or-0.25" W.C. + or-0.25" W.C.

    50-800 hp+ or-0.50" W.C.

    + or-0.25" W.C.With FGR

    Start-Up Included Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes

    Table A1-1. Quick Comparison of Standard Features for Cleaver-Brooks FIretube Boilers (Continued)

    12-02

  • A1-8

    GGGGeeeennnneeeerrrraaaallll FFFFiiiirrrreeeettttuuuubbbbeeee BBBBooooiiii lllleeeerrrrssss

    12-02

    Notes

  • A2-1

    07-02

    CONTENTS

    FEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-3 PRODUCT OFFERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-3DIMENSIONS AND RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-4PERFORMANCE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-21

    Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-21Emissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-21

    ENGINEERING DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-24Blowdown Water Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-24Sound Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-27Gas-Fired Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-30Gas Pressure Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-31Oil-Fired Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-36No. 6 Oil Piping, Storage Tank Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-36Boiler Room Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-44Stack Support Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-44Stack/Breeching Size Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-44Boiler Room Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-44

    SAMPLE SPECIFICATION (MODEL CB BOILER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-47

    ILLUSTRATIONS

    Figure A2-1. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure - 15 to 100 hp) Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-10

    Figure A2-2. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure - 125 to 800 hp) Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-12

    Figure A2-3. Model CB Hot Water Boiler Dimensions (30 psig and 125 psig Design Pressure - 15 to 100 hp) - Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-14

    Figure A2-4. Model CB Hot Water Boiler Dimensions (30 psig and 125 psig Design Pressure - 15 to 100 hp) - Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-16

    Figure A2-5. Space Required to Open Rear Head on Model CB Boilers Equipped with Davits . . . . . . . . . . . . . . . . . . . A2-18Figure A2-6. Lifting Lug Location, Model CB Boilers - Sheet 1 of 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-18Figure A2-7. Model CB Boiler Mounting Piers 20Figure A2-8. Predicted Stack Temperature Increase for Pressure Greater Than 125 psig . . . . . . . . . . . . . . . . . . . . . . . . A2-23Figure A2-9. Standard Gas Train Connection Size and Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-34

    Section A2

    MODEL CB BOILERS

  • A2-2

    Model CB Boilers Firetube Boilers

    07-02

    Figure A2-10. Typical Gas Piping Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-35Figure A2-11. Model CB Gas Train Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-36Figure A2-12. No. 2 Oil Connection Size, Location and Recommended Line Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-37Figure A2-13. No. 6 Oil Connection Size, Location and Recommended Line Sizes, Model CB Boiler . . . . . . . . . . . . . . A2-37Figure A2-14. No. 2 Oil Piping, Single Boiler Installation, Remote Oil Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-38Figure A2-15. No.2 Oil Piping, Single Boiler Installation Oil Pump Integral with Boiler . . . . . . . . . . . . . . . . . . . . . . . . A2-38Figure A2-16. No. 2 Oil Piping, Multiple Boiler Installation, Remote Oil Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-39Figure A2-17. No. 2 Oil Piping, Multiple Boiler Installation, Oil Pump Integral with Boiler . . . . . . . . . . . . . . . . . . . . . A2-39Figure A2-18. No. 2 Oil Piping, Multiple Boiler Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-40Figure A2-19. No. 6 Oil Piping, Single Boiler Installation, Remote Oil Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-40Figure A2-20. No. 6 Oil Piping, Multiple Boiler Installation, Remote Oil Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-41Figure A2-21. No. 6 Oil Piping, Multiple Boiler Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-41Figure A2-22. No. 2 Oil Transfer Tank Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-42Figure A2-23. Typical Fuel Storage Tank Arrangement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-42Figure A2-24. Typical Cross Section of Bundled Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-43Figure A2-25. Schematic of Standard Alstrom Hot Water Safety-Type Preheating System . . . . . . . . . . . . . . . . . . . . . . . A2-43Figure A2-26. Boiler Room Length (Typical Layout) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-45Figure A2-27. Boiler Room Width (Typical Layout) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-45Figure A2-28. Breeching Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-46

    TABLES

    Table A2-1. Model CB Steam Boiler Ratings (15 - 100 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-5Table A2-2. Model CB Steam Boiler Ratings (125 - 800 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-5Table A2-3. Model CB Hot Water Boiler Ratings (15 - 100 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-6Table A2-4. Model CB Hot Water Boiler Ratings (125 - 800 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-6Table A2-5. Steam Boiler Safety Valve Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-7Table A2-6. Hot Water Boiler Relief Valve Openings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-8Table A2-7. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 10 psig, Natural Gas . . . . . . . . . . . . . . . . . A2-22Table A2-8. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 125 psig, Natural Gas . . . . . . . . . . . . . . . . A2-22Table A2-9. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 10 psig, No. 6 Oil . . . . . . . . . . . . . . . . . . . A2-22Table A2-10. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 125 psig, No 6 Oil . . . . . . . . . . . . . . . . . . A2-22Table A2-11. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 10 psig, No. 2 Oil . . . . . . . . . . . . . . . . . . A2-23Table A2-12. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 125 psig, No. 2 Oil . . . . . . . . . . . . . . . . . A2-23Table A2-13. Model CB Boiler Emission Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-24Table A2-14. Heating Surface, Model CB Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-24Table A2-15. Steam Volume and Disengaging Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-25Table A2-16. Water Circulation Rate and Temperature Drop for Hot Water Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-25Table A2-17. Recommended Steam Nozzle Size (To Maintain 4000 to 5000 fpm Nozzle Velocity) . . . . . . . . . . . . . . . A2-26Table A2-18. Recommended Non-Return Valve Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-26Table A2-19. Model CB Blowdown Tank Sizing Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-27Table A2-20. Sound Pressure Level Summary (50 - 800 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-27Table A2-21. Model CB Boiler Sound Pressure Level Details (40 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-27Table A2-22. Model CB Boiler Sound Pressure Level Details (50 - 125 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-28Table A2-23. Model CB Boiler Sound Pressure Level Details (125 - 200 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-29Table A2-24. Model CB Boiler Sound Pressure Level Details (250 - 350 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-29Table A2-25. Model CB Boiler Sound Pressure Level Details (400 - 800 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-30Table A2-26. Minimum Required Gas Pressure at Entrance to Standard and FM Gas Trains

    (Downstream of Gas Pressure Regulator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-31Table A2-27. Minimum Gas Pressure at Entrance to Gas Trains Equipped with Industrial Risk Insurers

    (IRI) Requirements (Downstream of Gas Pressure Regulator) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-31Table A2-28. Under and Oversized Standard and FM Gas Trains, Model CB Boilers (50 - 800 hp) . . . . . . . . . . . . . . . . A2-32Table A2-29. Under and Oversized IRI Gas Trains, Model CB Boilers (50 - 800 hp) . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-33Table A2-30. Minimum Required Gas Pressure Altitude Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2-33Table A2-31. Maximum Gas Consumption (CFH) for Natural Gas and Propane Vapor & Gas Pilot Data. . . . . . . . . . . . A2-34

  • A2-3

    Firetube Boilers Model CB Boilers

    07-02

    FEATURES AND BENEFITS

    In addition to the features provided on all Cleaver-Brooks Firetube Boilers, the following features apply specifically to Model CB Firetube Boilers. The CB four-pass dryback boiler is the premium firetube boiler design available.

    Four-Pass Dryback Design:

    Four-pass design provides high flue gas velocities and low stack temperature for guaranteed maximum efficiency.

    Dryback design provides full access to boiler tubes, tube sheet, and furnace for ease of maintenance.

    Dryback design includes single rear tube sheet construction, providing reduced tube sheet stresses.

    Five Square Feet of Heating Surface per Boiler hp:

    Maximum heat transfer with minimum thermal stresses provide guaranteed efficiency and long boiler life.

    Highest guaranteed fuel-to-steam efficiencies.

    Low Furnace Location

    Furnace located well below water level with generous clearance from bottom of boiler, allowing proper circulation.

    Low furnace provides additional safety margin between furnace and water level.

    Reduces water carryover, producing drier steam.

    Hinged or Davited Front and Rear Doors:

    Provides full access to front and rear tube sheet and furnace.

    Reduces maintenance costs.

    High Turndown Burner:

    4:1 turndown (gas and oil) is standard on boilers up to 250 hp.

    Guaranteed 10:1 turndown (gas fired) 8:1 (No. 2 oil fired) standard on 250 hp through 800 hp.

    Advanced burner design provides maximum combustion efficiencies and high turndown.

    Reduced boiler cycling and maintenance.

    Boiler stays on line during low load conditions for optimum efficiency and performance.

    Gas, No. 2 Oil, No. 6 Oil, and Combination Gas and Oil Burners Available:

    High radiant multi-port gas burner designed for high gas velocities and complete fuel/air mixing, providing maximum combustion efficiencies.

    Air atomizing oil burner available for proper oil atomization, maximum combustion efficiency, and low maintenance requirements.

    Air atomizing compressor provided with the boiler package for clean oil burning and ease of maintenance.

    Combination gas/oil burners provide quick fuel changeover without re-adjustment of the burner.

    Fuel oil controller eliminates the need for over 40 connections, combining gauges, valves, and regulators into a single casting.

    Retractable oil nozzle provides easy access and cleaning and eliminates coking of oil and nozzle tip when firing gas.

    Low NOx Capability Available:

    20 ppm NOx guarantee available on Model CB (LE) Boilers.

    PRODUCT OFFERING

    Model CB Firetube Boilers are available in low pressure steam, high pressure steam, and hot water designs. Burners are available to fire natural gas, light oil, heavy oil, or a combina-tion of oil and gas. Optional alternate fuel burners are also available.

    Model CB Boilers include:

    Four-pass dryback design.

    15 hp through 800 hp.

    150 psig - 350 psig high pressure steam.

    15 psig low pressure steam.

    30 psig or 125 psig hot water.

    Natural gas, light oil, or heavy oil firing.

    The Model CBBoiler is the premium firetube product offering providing maximum boiler efficiency, the widest range of size and pressures, and premium control packages.

    Available options: For option details, contact your Cleaver-Brooks authorized representative. Options include the following:

    Boiler Options

    Auxiliary low water cut-off (standard on steam boilers).

    Drain valves.

    Additional screwed or flanged tappings.

    Special design pressures.

    Surge load baffles.

    Seismic design.

  • A2-4

    Model CB Boilers Firetube Boilers

    07-02

    Internal hot water coils.

    Blowdown valves.

    Non-return valves.

    Feedwater valves and regulators.

    Special doors, davited, hinged, left swing.

    Special base rails.

    Surface blowdown systems.

    Combustion relief door.

    Weather-proofing.

    Blend pump.

    Burner/Control Options

    Special modulation controls.

    Low NOx equipment.

    Optional flame safeguard controller.

    Lead/lag system.

    High altitude design, up to 12,000 ft.

    Special insurance and code requirements (e.g., IRI, FM, ASME CSD-1).

    Alarm bell/silence switch.

    Special motor requirements (TEFC, high efficiency).

    Remote contacts.

    Special purpose indicator lights.

    Main disconnect.

    Elapsed time meter.

    Voltmeter/micro-ammeter.

    NEMA enclosures.

    Low fire hold controls.

    Remote emergency shut-off (115V).

    Circuit breaker.

    Day/night controls.

    Special power requirements.

    Fuel Options

    Automatic fuel changeover.

    Special gas pressure regulator.

    Oversized/undersized gas trains.

    Gas strainer.

    Special fuel shut-off valves.

    Special pilot.

    Alternate fuel firing (propane, digester gas, etc.).

    Special oil pumps.

    DIMENSIONS AND RATINGS

    Dimensions and ratings for the Model CB boilers are shown in the following tables and illustrations:

    Table A2-1. Model CB Steam Boiler Ratings (15 thru 100 hp)

    Table A2-2. Model CB Steam Boiler Ratings (125 thru 800 hp)

    Table A2-3. Model CB Hot Water Boiler Ratings (15 thru 100 hp)

    Table A2-4. Model CB Hot Water Boiler Ratings (125 thru 800 hp)

    Table A2-5. Safety Valve Openings

    Table A2-6. Relief Valve Openings

    Figure A2-1. Model CB Steam Boiler Dimensions (15 and 150 lb design pressure) (15 thru 100 hp)

    Figure A2-2. Model CB Steam Boiler Dimensions (15 and 150 lb design pressure) (125 thru 800 hp)

    Figure A2-3. Model CB Hot Water Boiler Dimensions (30 lb design pressure) (15 thru 100 hp)

    Figure A2-4. Model CB Hot Water Boiler Dimensions (20 lb design pressure) (125-800 hp)

    Figure A2-5. Space Required to Open Rear Head on Model CB Boilers Equipped with Davits

    Figure A2-6. Lifting Lug Locations, Model CB Boilers

    Figure A2-7. Model CB Boiler Mounting Piers

  • A2-5

    Firetube Boilers Model CB Boilers

    07-02

    BOILER HP 15

    C

    20

    C

    30

    C

    40

    C

    50 60 70 80 100

    RATINGS - SEA LEVEL TO 3000 FT

    Rated Cap. (lbs steam/hr @212F)Btu Output (1000 Btu/hr)

    518502

    690670

    10351004

    13801339

    17251674

    20702009

    24152343

    27602678

    34503348

    APPROXIMATE FUEL CONSUMPTION AT RATED CAPACITY

    Light Oil (gph)

    A

    4.5 6.0 9.0 12.0 15.0 18.0 21.0 24.0 30.0

    Heavy Oil (gph)

    B

    - - - - 14.0 16.5 19.5 22.5 28.0

    Gas (cfh) 1000 Btu-NatGas (Therm/hr)

    6256.3

    8358.4

    125512.6

    167516.8

    209521.0

    251025.1

    293029.3

    335033.5

    418541.9

    POWER REQUIREMENTS - SEA LEVEL TO 3000 FT, 60 HZ

    Blower Motor hp (except gas) 1 1 1-1/2 2 2 2 2 2

    D

    3

    Gas Models (only) 1 1 1-1/2 2 2 2 2 2

    D

    3

    Oil Pump Motor, hp No. 2 Oil Belt-Driven From Blower 1/3 1/3 1/3 1/3 1/3

    Oil Pump Motor, hp No. 6 Oil - - - - 1/3 1/3 1/3 1/3 1/3

    Oil Heater kW No. 6 Oil - - - - 5 5 5 5 5

    Air Compressor Motor hp (Oil firing Only)

    Air Compressor Belt-Driven from Blower Motor 2 2 2 2 2

    NOTES:1. For altitudes above 3000 ft, contact your local Cleaver-Brooks authorized representative for verification of blower motor hp.A. Based on 140,000 Btu/gal.B. Based on 150,000 Btu/gal.C. No. 6 Oil not available in 15-40 hp range.D. 3 hp above 2000 ft.

    Table A2-1. Model CB Steam Boiler Ratings (15 - 100 hp)

    Table A2-2. Model CB Steam Boiler Ratings (125 - 800 hp)

    BOILER HP 125 150 200 250 300 350 400 500 600 700 750 800

    RATINGS SEA LEVEL TO 3000 FT

    J

    Rated Cap. (lbs steam/hr @ 212F)Btu Output (1000 Btu/hr)

    43134184

    51755021

    69006695

    86258369

    1035010043

    1207511716

    1380013390

    1725016738

    2070020085

    2415023432

    2587525106

    2760026779

    APPROXIMATE FUEL CONSUMPTION AT RATED CAPACITY

    Light Oil (gph)

    A

    37.5 45.0 60.0 74.5 89.5 104.5 119.5 149.5 179.5 209.0 224.2 239.3

    Heavy Oil (gph)

    B

    35.0 42.0 56.0 69.5 83.5 97.5 111.5 139.5 167.5 195.5 209.2 223.4

    Gas (cfh)MBTU-natGas(Therm/hr)

    5230

    52.3

    6280

    62.8

    8370

    83.7

    10460

    104.6

    12555

    125.5

    14650

    146.5

    16750

    167.5

    20925

    209.3

    25100

    251.0

    29300

    293.0

    31385

    313.8

    33480

    334.8

    POWER REQUIREMENTS - SEA LEVEL TO 3000 FT, 60 HZ

    Blower Motor hp (except gas) 5 7-1/2 15 7-1/2 10

    C

    15

    D

    10

    C

    15

    E

    20

    F

    30

    G

    40

    L

    50

    H

    Gas Models (only) 5 5 10 7-1/2 7-1/2

    I

    15 10

    C

    15

    E

    20

    F

    30

    G

    40

    L

    50

    H

    Oil Pump Motor, hp No. 2 Oil 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 1 1 1

    Oil Pump Motor, hp No. 6 Oil 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 3/4 3/4

    Oil Heater kW No. 6 Oil 5 5 5 7-1/2 7-1/2 7-1/2 7-1/2 7-1/2

    K

    7-1/2

    K

    7-1/2

    K

    7-1/2

    K

    7-1/2

    K

    Air Compressor Motor hp (Oil firing Only)

    Air Compressor Belt-Driven From Blower Motor 7-1/2 7-1/2 7-1/2 7-1/2 7-1/2 7-1/2

    NOTES:1. For altitudes above 3000 ft, contact your local Cleaver-Brooks autho-rized representative for verification of blower motor hp.A. Based on 140,000 Btu/gal.B. Based on 150,000 Btu/gal.C.15 hp above 2500 ft.D. 20 hp above 2500 ft.E. 20 hp above 2000 ft.

    F. 30 hp above 2500 ft.G. 40 hp above 2000 ft.H. 60 hp above 3000 ft.I. 10 hp above 2500 ft.J. Sea level to 2,500 ft for 300 and 350 Hp sizes.K. 10 kW on low pressure.L. 50 hp above 2500 ft.

  • A2-6

    Model CB Boilers Firetube Boilers

    07-02

    BOILER HP 15

    c

    20

    c

    30

    c

    40

    c

    50 60 70 80 100A 100 125A

    RATINGS - SEA LEVEL TO 3000 FT

    Rated Cap Btu Output (1000 Btu/hr) 502 670 1004 1339 1674 2009 2343 2678 3348 3348 4184

    APPROXIMATE FUEL CONSUMPTION AT RATED CAPCITY

    Light Oil (gph)

    A

    4.5 6.0 9.0 12.0 15.0 18.0 21.0 24.0 30.0 30.0 37.5

    Heavy Oil (gph)

    B

    - - - - 14.0 16.5 19.5 22.5 28.0 28.0 35.0

    Gas (cfh)MBtu- natGas (Therm/hr)

    6256.3

    8358.4

    125512.6

    167516.8

    209521.0

    251025.1

    293029.3

    335033.5

    418541.9

    418541.9

    523052.3

    POWER REQUIREMENTS - SEA LEVEL TO 3000 FT, 60 HZ

    Blower Motor hp (except gas) 1 1 1-1/2 2 2 2 2 2

    D

    3 3 3

    Gas Models (only) 1 1 1-1/2 2 2 2 2 2

    D

    3 3 3

    Oil Pump Motor, hp No. 2 Oil Belt-Driven From Blower 1/3 1/3 1/3 1/3 1/3 1/3 1/2

    Oil Pump Motor, hp No. 6 Oil - - - - 1/3 1/3 1/3 1/3 1/3 1/3 1/2

    Oil Heater kW No. 6 Oil - - - - 5 5 5 5 5 5 5

    Air Compressor Motor hp (Oil firing Only)

    Air Compressor Belt-Driven from Blower Motor

    2 2 2 2 2 2 2

    NOTES:1. For altitudes above 3000 ft, contact your local Cleaver-Brooks authorized representative for verification of blower motor hp.A. Based on 140,000 Btu/gal.B. Based on 150,000 Btu/gal.C. No. 6 Oil not available in 15-40 hp range.D. 3 hp above 2000 ft.

    Table A2-3. Model CB Hot Water Boiler Ratings (15 - 100 hp)

    Table A2-4. Model CB Hot Water Boiler Ratings (125 - 800 hp)

    BOILER HP 150 175A 200 250 300 350 400 500 600 700 750 800

    RATINGS - SEA LEVEL TO 3000 FT

    J

    Rated Cap. Btu Output (1000 Btu/hr) 5021 5858 6695 8369 10043 11716 13390 16738 20085 23432 25106 26779

    APPROXIMATE FUEL CONSUMPTON AT RATED CAPCITY

    Light Oil (gph)

    A

    45.0 52.5 60.0 74.5 89.5 104.5 119.5 149.5 179.5 209.0 224.2 239.3

    Heavy Oil (gph)

    B

    42.0 49.0 56.0 69.5 83.5 97.5 111.5 139.5 167.5 195.5 209.3 223.4

    Gas (cfh)MBtu-Natural Gas (Therm/hr)

    628062.8

    732073.2

    837083.7

    10460104.6

    12555125.5

    14650146.5

    16750167.5

    20925209.3

    25100251.0

    29300293.0

    31385313.8

    33480334.8

    POWER REQUIREMENTS - SEA LEVEL TO 3000 FT, 60 HZ

    Blower Motor hp (except gas) 7-1/2 7-1/2 15 7-1/2 10

    C

    15

    D

    10

    C

    15

    E

    20

    F

    30

    G

    40

    K

    50

    H

    Gas Models (only) 5 5 10 7-1/2 7-1/2

    I

    15 10

    C

    15

    E

    20

    F

    30

    G

    40

    K

    50

    H

    Oil Pump Motor, hp No. 2 Oil 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 1 1 1

    Oil Pump Motor, hp No. 6 Oil 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 3/4 3/4

    Oil Heater kW No. 6 Oil 5 5 5 7-1/2 7-1/2 7-1/2 10 10 10 10 10 10

    Air Compressor Motor hp (Oil firing Only) 7-1/2 7-1/2 7-1/2 7-1/2 7-1/2 7-1/2

    NOTES:1. For altitudes above 3000 ft, contact your local Cleaver-Brooks au-thorized representative for verification of blower motor hp.A. Based on 140,000 Btu/gal.B. Based on 150,000 Btu/gal.C. 15 hp above 2500 ft.D. 20 hp above 2500 ft.E. 20 hp above 2000 ft.

    F. 30 hp above 2500 ft.G. 40 hp above 2000 ft.H. 60 hp above 3000 ft.I. 10 hp above 2500 ft.J. Sea level to 2,500 ft for 300 and 350 hp sizes.K. 50 hp above 2500 ft.

  • A2-7

    Firetube Boilers Model CB Boilers

    07-02

    VALVE SETTING 15 PSIG STEAM 100 PSIG STEAM 125 PSIG STEAM 150 PSIG STEAM 200 PSIG STEAM 250 PSIG STEAM

    BOILERHP

    NO. OF VALVESREQ'D

    OUTLET SIZE(IN.)

    NO. OF VALVESREQ'D

    OUTLET SIZE(IN.)

    NO. OF VALVES REQ'D

    OUTLET SIZE(IN.)

    NO. OF VALVESREQ'D

    OUTLET SIZE(IN.)

    NO. OF VALVESREQ'D

    OUTLET SIZE(IN.)

    NO. OF VALVES REQ'D

    OUTLET SIZE(IN.)

    15 1 1-1/2 1 1 1 3/4 1 3/4 1 3/4 1 3/4

    20 1 1-1/2 1 1 1 1 1 3/4 1 3/4 1 3/4

    25 1 2 1 1 1 1 1 1 1 3/4 1 3/4

    30 1 2 1 1-1/4 1 1 1 1 1 3/4 1 3/4

    40 1 2-1/2 1 1-1/4 1 1-1/4 1 1 1 1 1 1

    50 1 2-1/2 1 1-1/2 1 1-1/2 1 1-1/4 1 1 1 1

    60 1 2 1 1-1/2 1 1-1/2 1 1-1/4 1 1-1/4 1 1

    70 1 2 1 2 1 1-1/2 1 1-1/4 1 1-1/4 1 1-1/4

    80 1 2-1/2 1 2 1 1-1/2 1 1-1/2 1 1-1/4 1 1-1/4

    100 1 2-1/2 1 2 1 2 1 1-1/2 1 1-1/2 1 1-1/4

    125 1 3 2 1-1/2 2 (1) 1-1/2(1) 1-1/4 2(1) 1-1/2(1) 1-1/4 2

    (1) 1-1/4(1) 1 2 1

    150 1 3 2 (1) 2(1) 1-1/2 2 1-1/2 2(1) 1-1/2(1) 1-1/4 2 1-1/4 2

    (1) 1(1) 1-1/4

    200 2 2-1/2 2 2 2 (2) 1-1/2 2 2) 1-1/2 2 (1) 1-1/2(1) 1-1/4 2 (2) 1-1/4

    250 2 (1) 2-1/2(1) 3 2(1) 2-1/2

    (1) 2 2 2 2(1) 2

    (1) 1-1/2 2 1-1/2 2(1) 1-1/2(1) 1-1/4

    300 2 3 2 2-1/2 2 (1) 2-1/2 (1) 2 2 2 2 (1) 2

    (1) 1-1/2 2 1-1/2

    350 3 (1) 2 (2) 3 3(1) 2-1/2

    (2) 2 2 2-1/2 2(1) 2-1/2

    (1) 2 2 2 2(1) 1-1/2

    (1)2

    400 3 (2) 3(1) 2-1/2 3(1) 2

    (2) 2-1/2 2 2-1/2 2(1) 2-1/2

    (1) 2 2 2 2(1) 2

    (1) 1-1/2

    500 3 3 3 2-1/2 3 (2) 2-1/2 (1) 2 2 2-1/2 2(1) 2-1/2

    (1) 2 2 2

    600 4 (1) 2-1/2(3) 3 4(3) 2-1/2

    (1) 2 3 2-1/2 32-1/2 (1) 2 2 2-1/2 2

    (1) 2(1) 2-1/2

    700 5 (3) 3 (2)2-1/2 5(3) 2-1/2

    (2) 2 4(3) 2-1/2

    (1) 2 3(2) 2-1/2

    (1) 2 2 2-1/2 2 2-1/2

    750 5 (3) 3 (2)2-1/2 5(3) 2-1/2

    (2) 2 4(3) 2-1/2

    (1) 2 3(2) 2-1/2

    (1) 2 2 2-1/2 2 2-1/2

    800 5 (3) 3 (2)2-1/2 5(3) 2-1/2

    (2) 2 4(3) 2-1/2

    (1) 2 3(2) 2-1/2

    (1)2 2 2-1/2 2 2-1/2

    NOTE: Valve manufacturers are Kunkle, Consolidated or Conbraco, depending on availability.

    Table A2-5. Steam Boiler Safety Valve Openings

  • A2-8

    Model CB Boilers Firetube Boilers

    07-02

    VALVE SETTING 30 PSIG HW 60 PSIG HW 100 PSIG HW 125 PSIG HW

    BOILERHP

    NO. OF VALVES REQ'D

    OUTLETSIZE (IN.)

    NO. OF VALVES REQ'D

    OUTLET SIZE(IN.)

    NO. OF VALVES REQ'D

    OUTLET SIZE(IN.)

    NO. OF VALVES REQ'D

    OUTLET SIZE(IN.)

    15 1 1 1 1 1 1 1 1

    20 1 1 1 1 1 1 1 1

    25 1 1-1/4 1 1 1 1 1 1

    30 1 1-1/4 1 1 1 1 1 1

    40 1 1-1/4 1 1 1 1 1 1

    50 & 50A 1 2 1 1-1/4 1 1 1 1

    60 1 2 1 1-1/4 1 1 1 1

    70 1 2 1 2 1 1-1/4 1 1

    80 1 2 1 2 1 1-1/4 1 1-1/4

    100 1 2-1/2 1 2 1 1-1/4 1 1-1/4

    100A 1 2-1/2 1 2 1 1-1/4 1 1-1/4

    125 1 2-1/2 1 2 1 2 1 1-1/4

    125A 1 2-1/2 1 2 1 2 1 1-1/4

    150 1 2-1/2 1 2-1/2 1 2 1 2

    175A 2 (1) 1(1) 2-1/2 1 2-1/2 1 2 1 2

    200 2 (1) 2-1/2(1) 1-1/4 1 2-1/2 1 2 1 2

    250 2 (1) 2(1) 2-1/2 1 2-1/2 1 2-1/2 1 2

    300 2 2-1/2 2 (1) 1(1) 2-1/2 1 2-1/2 1 2-1/2

    350 3 (2) 2-1/2(1) 1 2(1) 2-1/2

    (1) 2 1 2-1/2 1 2-1/2

    400 3 (1) 2(2) 2-1/2 2 (1) 2

    (1) 2-1/2 2 (1) 1

    (1) 2-1/2 1 2-1/2

    500 4 (1) 1(3) 2-1/2 2 (2) 2-1/2 2(1) 2-1/2(1) 1-1/4 2

    (1) 1 (1) 2-1/2

    600 4 (3) 2-1/2(1) 2 3 (1) 1-1/4(2) 2-1/2 2

    (1) 2(1) 2-1/2 2

    (1) 2-1/2(1) 1-1/4

    700 5 (1) 1(4) 2-1/2 3(1) 2

    (2) 2-1/2 2 (2) 2-1/2 2(1) 2-1/2

    (1) 2

    750 5 (1) 1(4) 2-1/2 3 (1) 2

    (2) 2-1/2 2 (2) 2-1/2 2(1) 2-1/2

    (1) 2

    800 5 (1) 1(4) 2-1/2 3 (1) 2

    (2) 2-1/2 2 (2) 2-1/2 2(1) 2-1/2

    (1) 2

    NOTES: 1.Hot water relief valves are Kunkle #537.2. BHP followed by A designates hot water boilers furnished in a smaller vessel size with additional tubes in theupper portion of the vessel.

    Table A2-6. Hot Water Boiler Relief Valve Openings

  • A2-9

    Firetube Boilers Model CB Boilers

    07-02

    NOTES

  • A2-10

    Model CB Boilers Firetube Boilers

    07-02

    BOILER HP DIM 15 20 30 40 50 60 70 80 100

    LENGTHS

    Overall A 96-5/8 96-5/8 114-5/8 140-5/8 129 129 168 168 187

    Shell B 62-5/8 62-5/8 80-5/8 106-5/8 92 92 131 131 150

    Base Frame C 59 59 77 103 91 91 130 130 148

    Front Head Extension D 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2

    Rear Head Extension E 15-1/2 15-1/2 15-1/2 15-1/2 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2

    Front Ring Flange to Nozzle - 15 psig F 36 36 45 57 46 46 65-1/2 65-1/2 75

    Front Ring Flange to Nozzle - 150 psig F 36 36 45 57 46 46 72-1/2 72-1/2 82

    Ring Flange to Base G 1-13/16 1-13/16 1-13/16 1-13/16 5/8 1/2 1/2 1/2 1/2

    WIDTHS

    Overall I 61 61 61 61 73 73 73 73 73

    ID, Boiler J 36 36 36 36 48 48 48 48 48

    Center to Water Column K 33 33 33 33 39 39 39 39 39

    Center to Outside Hinge KK 22 22 22 22 29 29 29 29 29

    Center to Lagging L 20 20 20 20 27 27 27 27 27

    Center to Auxiliary LWCO LL 28 28 28 28 34 34 34 34 34

    Base, Outside M 28 28 28 28 37-5/8 37-3/8 37-3/8 37-3/8 37-3/8

    Base, Inside N 22 22 22 22 29-5/8 29-5/8 29-5/8 29-5/8 29-5/8

    Figure A2-1. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure - 15 to 100 hp) Sheet 1 of 2

    NOTE: ALLOW 3 FEET

    FOR DOOR SWING PER NEC

  • A2-11

    Firetube Boilers Model CB Boilers

    07-02

    BOILER HP DIM 15 20 30 40 50 60 70 80 100

    HEIGHTS

    Base to Steam Outlet (15 psig only) PL 50-1/4 50-1/4 50-1/4 50-1/4 64-3/4 64-3/4 64-3/4 64-3/4 64-3/4

    Overall OO 66 66 66 66 78-3/4 78-3/4 78-3/4 78-3/4 78-3/4

    Base to Vent Outlet O 53-1/2 53-1/2 53-1/2 53-1/2 70 70 70 70 70

    Base to Steam Outlet (150 psig only) PH 50-1/4 50-1/4 50-1/4 50-1/4 66-31/2 66-1/2 66-1/2 66-1/2 64-3/4

    Height of Base Q 8 8 8 8 12 12 12 12 12

    Base to Bottom of Boiler R 12 12 12 12 16 16 16 16 16

    BOILER CONNECTIONS

    Chemical Feed H 1 1 1 1 1 1 1 1 1

    Feedwater, Right and Left S 1 1 1 1 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4

    Low Pressure (15 psig only)Steam NozzleDrain, Front and Rear

    UW

    41

    41

    41

    6

    A

    1-1/46

    A

    1-1/46

    A

    1-1/46

    A

    1-1/26

    A

    1-1/28

    A

    1-1/2

    High Pressure (150 psig only)Surface Blowoff, Top CLSteam Nozzle Blowdown, Front and Rear

    TYW

    11-1/2

    1

    11-1/2

    1

    121

    121

    13

    1-1/4

    13

    1-1/4

    13

    1-1/4

    13

    1-1/4

    14

    B

    1-1/4

    VENT STACK

    Diameter (flgd connection) BB 6 6 8 8 10 10 12 12 12

    Front Ring Flange to Vent CL CC 4 4 5 5 6 6 7 7 7

    MINIMUM CLEARANCES

    Rear Door Swing

    C

    DD 44 44 44 44 55 55 55 55 55

    Front Door Swing

    C

    EE 44 44 44 44 55 55 55 55 55

    Tube Removal, Rear FF 56 56 74 100 84 84 123 123 142

    Tube Removal, Front GG 46 46 64 90 74 74 113 113 132

    MINIMUM BOILER ROOM LENGTH ALLOWING FOR DOOR SWING AND TUBE REMOVAL FROM:

    Rear of Boiler RR 163 163 199 251 231 231 309 309 347

    Front of Boiler RF 153 153 189 241 221 221 299 299 337

    Thru Window or Doorway RD 151 151 169 195 202 202 241 241 260

    WEIGHT IN LBS

    Normal Water Capacity 1340 1300 1710 2290 3130 2920 4620 4460 5088

    Approx. Ship Wgt - 15 psig 3000 3100 3650 4350 6900 7000 8100 8200 9000

    Approx. Ship Wgt - 150 psig 3100 3200 3800 4500 7000 7200 8800 9000 9500

    Approx. Ship Wgt - 200 psig 3300 3400 4100 4700 7400 7600 9300 9500 10000

    NOTES:1. Air compressor belt driven from blower motor on sizes 15 thru 402. Air compressor module on sizes 50 thru 100 hp.3. Accompanying dimensions, while sufficiently accurate for layout purposes, must be confirmed for construction by certified dimension prints.A. ANSI 150 psig flange.B. ANSI 300 psig flange. C. 15 thru 100 hp standard hinged door.

    Figure A2-1. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure - 15 to 100 hp) Sheet 2 of 2

  • A2-12

    Model CB Boilers Firetube Boilers

    07-02

    Figure A2-2. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure - 125 to 800 hp) Sheet 1 of 2

    BOILER HP DIM 125 150 200 250 300 350 400 500 600 700 750 800

    LENGTHS

    Overall A 174-1/2 199-/12 232-1/2 197 227 257 210 244 284 317 319 319

    Shell B 125 149 180 144 171 201 152 186 222 255 255 255

    Base Frame C 124 148 179 143 170 200 151 185 221 254 254 254

    Front Head Extension D 30 31 33 29 32 32 26 26 30 30 32 32

    Rear Head Extension E 19-1/2 19-1/2 19-1/2 24 24 24 32 32 32 32 32 32

    Front Ring Flange to Nozzle - 15 psig

    F 62-1/2 74-1/2 90 72 85-1/2 100-1/2 76 93 111 127-1/2 127-1/2 127-1/2

    Front Ring Flange to Nozzle - 150 psig

    F 55 66 78 59-1/2 73 88 62 79 97 127-1/2 127-1/2 127-1/2

    Ring Flange to Base G 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

    WIDTHS

    Overall I 85 85 85 103 103 103 123 123 123 123 123 123

    ID, Boiler J 60 60 60 78 78 78 96 96 96 96 96 96

    Center to Water Column K 45 45 45 54 54 54 64 64 64 64 64 64

    Center to Outside Hinge KK 35 35 35 51 51 51 62 62 62 62 62 62

    Center to Lagging L 33 33 33 42 42 42 51 51 51 51 51 51

    Center to Auxiliary LWCO LL 40 40 40 49 49 49 59 59 59 59 59 59

    Base, Outside M 52-1/2 52-1/2 52-1/2 64-3/8 64-3/8 64-3/8 72 72 72 72 72 72

    Base, Inside N 44-1/2 44-1/2 44-1/2 52-3/8 52-3/8 52-3/8 56 56 56 56 56 56

    NOTE: ALLOW 3 FEET

    FOR DOOR SWING PER NEC

  • A2-13

    Firetube Boilers Model CB Boilers

    07-02

    BOILER HP DIM 125 150 200 250 300 350 400 500 600 700 750 800

    HEIGHTS

    Base to Steam Outlet (15 psig only) PL 77 77 77 96 96 96 116 116 116 116 116 116

    Overall OO 88 88 88 106 106 106 126 126 126 126 126 126

    Base to Vent Outlet O 85 85 85 106 106 106 126 126 126 126 126 126

    Base to Steam Outlet (150 psig only)

    PH 77 77 77 96 96 96 116 116 116 116 116 116

    Davit (Front) DF - - - 104 104 104 125 125 125 125 125 125

    Davit (Rear) DR 84-3/4 84-3/4 84-3/4 104 104 104 126 126 126 126 126 126

    Height of Base Q 12 12 12 10 10 10 12 12 12 12 12 12

    Base to Bottom of Boiler R 16 16 16 17 17 17 19 19 19 19 19 19

    BOILER CONNECTIONS

    Chemical Feed H 1 1 1 1 1 1 1 1 1 1 1 1

    Feedwater, Right and Left S 1-1/2 1-1/2 2 2 2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2

    Low Pressure (15 psig only)Steam Nozzle (Note A) Drain, Front and Rear

    UW

    81-1/2

    81-1/2

    102

    102

    122

    122

    122

    122

    122

    122

    122

    122

    High Pressure (150 psig only)Surface Blowoff, Top CLSteam Nozzle (Note B)Blowdown, Front and Rear

    T

    YW

    1

    41-1/2

    1

    41-1/2

    1

    41-1/2

    1

    61-1/2

    1

    61-1/2

    1

    61-1/2

    1

    62

    1

    82

    1

    82

    1

    82

    1

    82

    1

    82

    VENT STACK

    Diameter (flgd. connection) BB 16 16 16 20 20 20 24 24 24 24 24 24

    Front Ring Flange to Vent CL CC 9 9 9 10-1/2 10-1/2 10-1/2 12-1/2 12-1/2 12-1/2 12-1/2 12-1/2 12-1/2

    MINIMUM CLEARANCES

    Rear Door Swing DD 32C 32C 32C 43C 43C 43C 53C 53C 53C 53C 53C 53C

    Front Door Swing EE 67 67 67 89C 89C 89C 108C 108C 108C 108C 108C 108C

    Tube Removal, Rear FF 115 139 170 131 157 187 135 169 205 238 238 238

    Tube Removal, Front GG 103 127 158 116 142 172 116 151 187 220 220 220

    MINIMUM BOILER ROOM LENGTH ALLOWING FOR DOOR SWING AND TUBE REMOVAL FROM:

    Rear of Boiler RR 307 355 417 364 417 477 395 463 535 601 601 601

    Front of Boiler RF 260 308 370 303 356 416 322 390 462 528 528 528

    Thru Window or Doorway RD 224 248 279 275 302 332 313 347 383 416 416 416

    WEIGHT IN LBS

    Normal Water Capacity 5750 7250 8625 10670 13000 15465 15340 19300 23425 27790 27790 27790

    Approx. Ship Wgt - 15 psig 12200 12900 15200 21800 24000 27300 33500 38400 44000 51400 51400 51400

    Approx. Ship Wgt - 150 psig 12800 13800 16300 23400 26000 28500 36500 41400 47000 54100 54100 54100

    Approx. Ship Wgt - 200 psig 13400 14500 17100 25200 28000 30000 38300 44000 50500 57700 57700 57700

    NOTES: 1. Air compressor belt driven from blower motor on sizes 125 thru 350 hp.2. Control Panel relocation on boilers 250 hp and up.3. Air compressor module on sizes 400 thru 800 hp.4. Accompanying dimensions, while sufficiently accurate for layout purposes, must be confirmed for construction by certified dimension prints.A. ANSI 150 psig flange.B. ANSI 300 psig flange.C. Davit equipped, standard, 125 - 800 hp (rear door).D. Davit equipped, standard, 250- 800 hp (front door)

    Figure A2-2. Model CB Steam Boiler Dimensions and Weights (15 and 150 psig Design Pressure - 125 to 800 hp) Sheet 2 of 2

  • A2-14

    Model CB Boilers Firetube Boilers

    07-02

    Figure A2-3. Model CB Hot Water Boiler Dimensions (30 psig and 125 psig Design Pressure - 15 to 100 hp) - Sheet 1 of 2

    BOILER HP DIM 15 20 30 40 50 60 70 80/ 100A100/125A

    LENGTHS

    Overall A 97 97 114-5/8 140-5/8 129 129 168 168 187

    Shell B 62-5/8 62-5/8 80-5/8 106-5/8 92 92 131 131 150

    Base Frame C 59 59 77 103 91 91 130 130 148

    Front Head Ext. D 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2

    Rear Head Ext. E 15-1/2 15-1/2 15-1/2 15-1/2 18-1/2 18-1/2 18-1/2 18-1/2 18-1/2

    Front Ring Flange to Return F 43-5/8 43-5/8 62 81 69 69 108 108 127

    Front Ring Flange to Outlet G 55-1/8 55-1/8 73-1/8 98-1/2 84-5/8 84-5/8 123-5/8 123-5/8 142-5/8

    Ring Flange to Base H 1-13/16 1-13/16 1-13/16 1-13/16 5/8 5/8 5/8 5/8 1

    WIDTHS

    Overall I 48-3/4 48-3/4 48-3/4 48-3/4 63 63 63 63 63

    ID, Boiler J 36 36 36 36 48 48 48 48 48

    Center to Entrance Box K 28-3/4 28-3/4 28-3/4 28-3/4 36 36 36 36 36

    Center to Outside Hinge KK 22 22 22 22 29 29 29 29 29

    Center to Lagging L 20 20 20 20 27 27 27 27 27

    Base, Outside M 28 28 28 28 37-5/8 37-5/8 37-5/8 37-5/8 37-5/8

    Base, Inside N 22 22 22 22 29-5/8 29-5/8 29-5/8 29-5/8 29-5/8

    LWCO

    NOTE: ALLOW 3 FEET

    FOR DOOR SWING PER NEC

  • A2-15

    Firetube Boilers Model CB Boilers

    07-02

    BOILER HP DIM 15 20 30 40 50 60 70 80/ 100A100/ 125A

    HEIGHTS

    Overall OO 66 66 66 66 72-5/8 72-5/8 72-5/8 72-5/8 72-5/8

    Base to Vent Outlet O 53-1/2 53-1/2 53-1/2 53-1/2 70 70 70 70 70

    Base to Return and outlet P 50 50 50 50 67 67 67 67 67

    Davit (Front) DF - - - - - - - - -

    Davit (Rear) DR - - - - - - - - -

    Height of Base Q 8 8 8 8 12 12 12 12 12

    Base to bottom of boiler R 12 12 12 12 16 16 16 16 16

    BOILER CONNECTION

    Waterfill Conn. Right & Left S 1 1 1 1 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4

    Water Return - Threaded T 2-1/2 2-1/2 3 3 4 4 4 4 4

    Water Outlet - Threaded

    A

    U 2-1/2 2-1/2 3 3 4 4 4 4 4

    Air Vent v 1 1 1 1 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4

    Drain, Front and Rear W 1 1 1 1-1/4 1-1/4 1-1/4 1-1/2 1-1/2 1-1/2

    Auxiliary Connection X 1 1 1 1 1 1 1 1 1

    VENT STACK

    Diameter (flgd. connection) BB 6 6 8 8 10 10 12 12 12

    Front Ring Flange to vent CL CC 4 4 5 5 6 6 7 7 7

    MINIMUM CLEARANCES

    Rear Door Swing DD 44 44 44 44 55 55 55 55 55

    Front Door Swing EE 44 44 44 44 55 55 55 55 55

    Tube Removal, Rear FF 56 56 74 100 84 84 123 123 142

    Tube, Removal, Front GG 46 46 64 90 74 74 113 113 132

    MINIMUM BOLER ROOM LENGTH ALLOWING FOR DOOR SWING AND TUBE REMOVAL FROM:

    Rear of Boiler RR 163 163 199 251 231 231 309 309 347

    Front of Boiler RF 153 153 189 241 221 221 299 299 337

    Thru Window or Doorway RD 151 151 169 195 202 202 241 241 260

    WEIGHT IN LBS

    Water Capacity Flooded 1500 1460 1915 2585 3665 3500 5420 5250 5960

    Approx. Ship. Wgt. 30 psigApprox. Ship. Wgt. 125 psig

    30003300

    31003400

    36503880

    43504580

    68007100

    70007300

    80008350

    81008450

    88009150

    NOTES:1. Accompanying dimensions and ratings while sufficiently accurate for layout purposes, must be confirmed for construction by certified dimension prints.2. Air compressor belt driven from blower motor on sizes 15 thru 40 hp. 3. Air compressor module on sizes 50 thru 100 hp.4. 15 - 100 hp, hinged door standard.5. Add 370lbs to the 80 hp ship weight for 100A and 485 lbs to the 100 hp ship weight for the 125A.A. Dip Tube included.

    Figure A2-3. Model CB Hot Water Boiler Dimensions (30 psig Design Pressure - 15 to 100 hp) - Sheet 2 of 2

  • A2-16

    Model CB Boilers Firetube Boilers

    07-02

    Figure A2-4. Model CB Hot Water Boiler Dimensions (30 psig Design Pressure - 125 - 800 hp) - Sheet 1 of 2

    A

    BOILER HP DIM 125 150/175A 200 250 300 350 400 500 600 700 750 800

    LENGTHS

    Overall A 174-1/2 199-1/2 232-1/2 197 227 257 210 244 284 317 319 319

    Shell B 125 149 180 144 171 201 152 186 222 255 255 255

    Base Frame C 124 148 179 143 170 200 151 185 221 254 254 254

    Front Head Extension D 30 31 33 29 32 32 26 26 30 30 32 32

    Rear Head Extension E 19-1/2 19-1/2 19-1/2 24 24 24 32 32 32 32 32 32

    Front Ring Flange to Return F 91 102 131 104-1/2 131-1/2 161-1/2 111-1/2 139 175 207 207 207

    Front Ring Flange to Outlet G 114 136 167 131 158 188 146 170 206 239 239 239

    Ring Flange to Base H 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2

    WIDTHS

    Overall I 75-1/2 75-1/2 75-1/2 93 93 93 113 113 113 113 113 113

    ID, Boiler J 60 60 60 78 78 78 96 96 96 96 96 96

    Center to Entrance Box K 42-1/2 42-1/2 42-1/2 51 51 51 62 62 62 62 62 62

    Center to Outside Hinge KK 35 35 35 51 51 51 62 62 62 62 62 62

    Center to Lagging L 33 33 33 42 42 42 51 51 51 51 51 51

    Base, Outside M 52-1/2 52-1/2 52-1/2 64-3/8 64-3/8 64-3/8 72 72 72 72 72 72

    Base, Inside N 44-1/2 44-1/2 44-1/2 52-3/8 52-3/8 52-3/8 56 56 56 56 56 56

    LWCO

    NOTE: ALLOW 3 FEET

    FOR DOOR SWING PER NEC

  • A2-17

    Firetube Boilers Model CB Boilers

    07-02

    Figure A2-4. Model CB Hot Water Boiler Dimensions (30 psig Design Pressure - 125 - 800 hp) - Sheet 2 of 2

    BOILER HP DIM 125 150/175A 200 250 300 350 400 500 600 700 750 800

    HEIGHTS

    Overall OO 88 88 88 106 106 106 126 126 126 126 126 126

    Base to Vent Outlet O 85 85 85 106 106 106 126 126 126 126 126 126

    Base to Return and Outlet P 77 77 77 96 96 96 116 116 116 116 116 116

    Davit (Front) DF - - - 104 104 104 125 125 125 125 125 125

    Davit (Rear) DR 84-3/4 84-3/4 84-3/4 104 104 104 126 126 126 126 126 126

    Height of Base Q 12 12 12 10 10 10 12 12 12 12 12 12

    Base to Bottom of Boiler R 16 16 16 17 17 17 19 19 19 19 19 19

    BOILER CONNECTION

    Waterfill Conn. Right & Left S 1-1/2 1-1/2 2 2 2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2 2-1/2

    Water Return FlangeA T 6 6 6 8 8 8 10 10 12 12 12 12

    Water Outlet Flange U 6 6 6 8 8 8 10 10 12 12 12 12

    Air Vent V 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 1-1/2 2 2 2 2 2 2

    Drain, Front and Rear W 1-1/2 1-1/2 2 2 2 2 2 2 2 2 2 2

    Auxiliary Connection X 1 1 1 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4

    VENT STACK

    Diameter (flgd. connection) BB 16 16 16 20 20 20 24 24 24 24 24 24

    Front Ring Flange to vent CL CC 9 9 9 10-1/2 10-1/2 10-1/2 12-1/2 12-1/2 12-1/2 12-1/2 12-1/2 12-1/2

    MINIMUM CLEARANCES

    Rear Door Swing DD 32B 32B 32B 43B 43B 43B 53B 53B 53B 53B 53B 53B

    Front Door Swing EE 67 67 67 89B 89B 89B 108B 108B 108B 108B 108B 108B

    Tube Removal, Rear FF 115 139 170 131 157 187 135 169 205 238 238 238

    Tube, Removal, Front GG 103 127 158 116 142 172 117 151 187 220 220 220

    MINIMUM BOILER ROOM LENGTH ALLOWING FOR DOOR SWING AND TUBE REMOVAL FROM:

    Rear of Boiler RR 307 355 417 364 417 477 395 463 535 601 601 601

    Front of Boiler RF 260 308 370 303 356 416 322 390 462 528 528 528

    Thru Window or Doorway RD 224 248 279 275 302 332 313 347 383 416 416 416

    WEIGHT IN LBS

    Water Capacity Flooded 7670 9295 11130 13880 16840 20090 20630 25925 31510 36600 36600 36600

    Approx. Ship. Wgt. 30 psig 12100 12800 15100 21700 23900 27200 33400 38300 43900 51300 51300 51300

    Approx. Ship. Wgt. 125 psig 12500 13200 15500 22500 24700 28000 34400 39300 44900 52300 52300 52300

    NOTES:1. Accompanying dimensions and ratings while sufficiently accurate for layout purposes, must be confirmed for construction by certified dimension prints.2. Control panel relocated on boilers 250 hp and up.3. Air compressor belt driven from blower motor on sizes 125 thru 350 hp.4. Air compressor module on sizes 400 thru 800 hp.5. Davited front doors are standard on 250 - 800 hp.6. Add 480 lbs to the 150 hp ship weight for 175A.A. Dip Tube included.B. Davited rear doors are standard on 125 - 800 hp units.

  • A2-18

    Model CB Boilers Firetube Boilers

    07-02

    BOILER HPDIMENSION (INCHES)

    A B C D E

    15 - 40, 50A 20 36 28 45 20

    50 - 100, 100A, 125A 27 48 38 60 26

    125 - 200, 175A 33 55 45 68 32

    250 - 350 42 69 58 86 43

    400 - 800 51 88 71 109 53

    NOTE:1. Dimensions in inches.2. 15 - 100 hp (100A & 125A)boilers are standardly equipped with hinges. Davit available as an option.

    Figure A2-5. Space Required to Open Rear Head on Model CB Boilers Equipped with Davits

    PLAN VIEW

    Figure A2-6. Lifting Lug Location, Model CB Boilers - Sheet 1 of 2

  • A2-19

    Firetube Boilers Model CB Boilers

    07-02

    BOILER HP VIEW

    ALL DIMENSIONS IN INCHES

    A B C D E

    15 Steam A 51-3/4 12 38-3/4 - 2-1/2

    Hot Water B 50-1/2 12 38-3/4 6 2-1/2

    20 Steam A 51-3/4 12 38-3/4 - 2-1/2

    Hot Water B 50-1/2 12 38-3/4 6 2-1/2

    25 Steam A 51-3/4 12 56-3/4 - 2-1/2

    Hot Water B 50-1/2 12 56-3/4 6 2-1/2

    30 Steam A 51-3/4 12 56-3/4 - 2-1/2

    Hot Water B 50-1/2 12 56-3/4 6 2-1/2

    40 Steam A 51-3/4 12 82-3/4 - 2-1/2

    Hot Water B 50-1/2 12 82-3/4 6 2-1/2

    50A

    Water B 50-1/2 12 82-3/4 6 2-1/2

    50 All B 68 18 57 10 2-1/2

    60 All B 68 18 57 10 2-1/2

    70 All B 68 27 67 10 2-1/2

    80 All B 68 27 67 10 2-1/2

    100 All B 68 27 86 10 2-1/2

    100A Hot Water B 68 27 67 10 2-1/2

    125A Hot Water B 68 27 100 10 2-1/2

    125 All B 80-1/4 29-3/4 70-1/2 10 2-1/2

    150 All A 80-1/4 29-3/4 83-1/2 10 2-1/2

    175A Hot Water B 80-1/4 29-3/4 83-1/2 10 2-1/2

    200 All B 80-1/4 29-3/4 114-1/2 10 2-1/2

    250 Steam B 99 36 72 10 3

    Hot Water B 99 36 72 10 3

    300 Steam B 99 36 99 10 3

    Hot Water B 99 36 99 10 3

    350 Steam B 99 36 129 10 3

    Hot Water B 99 36 129 10 3

    400 Steam B 119 34-1/2 83 10 3

    Hot Water B 119 34-1/2 83 11 3

    500 Steam B 119 34-1/2 117 11 3

    Hot Water B 119 34-1/2 117 11 3

    600 Steam B 119 34-1/2 153 11 3

    Hot Water B 119 34-1/2 153 11 3

    700 Steam B 119 34-1/2 186 11 3

    Hot Water B 119 34-1/2 186 11 3

    750 Steam B 119 34-1/2 186 11 3

    Hot Water B 119 34-1/2 186 11 3

    800 Steam B 119 34-1/2 186 11 3

    Hot Water B 119 34-1/2 186 11 3

    NOTE: 1. A, B and C Dimensions may vary by 1/2 inch.2. BHP followed by A designates hot water boilers furnished in a smaller vessel size with additional tubes in upper portion of vessel.

    Figure A2-6. Lifting Lug Location, Model CB Boilers - Sheet 2 of 2

  • A2-20

    Model CB Boilers Firetube Boilers

    07-02

    BOILER HP A B C D E F G X

    15-20 6 8 59 17 33 3 22 9-3/4

    25-30 6 8 77 17 33 3 22 9-3/4

    40-50A 6 8 103 17 33 3 22 9-3/4

    50-60 6 8 91 26 42 4 29-5/8 8-1/4

    70-80, 100A 6 8 130 26 42 4 29-5/8 8-1/4

    100, 125A 6 8 148 26 42 4 29-5/8 8-1/4

    125 6 9 124 39-1/2 57-1/2 4 44-1/2 10-1/4

    150, 175A 6 9 148 39-1/2 57-1/2 4 44-1/2 10-1/4

    200 6 9 179 39-1/2 57-1/2 4 44-1/2 10-1/4

    250 6 12 143 46 70 6 52-3/8 22-1/2

    300 6 12 170 46 70 6 52-3/8 22-1/2

    350 6 12 200 46 70 6 52-3/8 22-1/2

    400 6 14 151 50 78 8 56 24-1/2

    500 6 14 185 50 78 8 56 24-1/2

    600 6 14 221 50 78 8 56 24-1/2

    700-750-800 6 14 254 50 78 8 56 24-1/2

    NOTE: 1. All numbers in table are in inches.2. 6-inch high mounting piers recommended for use beneath the boiler base frame. The use of these piers provides increased inspection

    accessibility to the piping beneath the boiler and added height for washing down the area beneath the boiler.

    Figure A2-7. Model CB Boiler Mounting Piers

  • A2-21

    Firetube Boilers Model CB Boilers

    07-02

    PERFORMANCE DATA

    Efficiency Tables A2-7, A2-8, A2-9, A2-10, A2-11, and A2-12 show pre-dicted fuel-to-steam efficiencies (including radiation and con-vection losses) for Cleaver-Brooks Model CB Firetube boilers. For specific efficiencies on firetube boiler offerings not listed here, contact your local Cleaver-Brooks authorized representa-tive.

    Cleaver-Brooks offers an industry leading fuel-to-steam boiler efficiency guarantee for Model CB Firetube Boilers. The guar-antee is based on the fuel-to-steam efficiencies shown in the efficiency tables and the following conditions. The efficiency percent number is only meaningful if the specific conditions of the efficiency calculations are clearly stated in the specifica-tion (see Cleaver-Brooks publication CB-7768 for a detailed description of efficiency calculations).

    The boiler manufacturer shall guarantee that, at the time of startup, the boiler will achieve fuel-to-steam efficiency (as shown in the tables listed above) at 100% firing rate (add effi-ciency guarantees at 25%, 50%, and 75% of rating, if required). If the boiler(s) fail to achieve the corresponding guaranteed efficiency as published, the boiler manufacturer will rebate, to the ultimate boiler owner, five thousand dollars ($5,000) for every full efficiency point (1.0%) that the actual efficiency is below the guaranteed level. The specified boiler efficiency is based on the following conditions.

    1. Fuel specification used to determine boiler efficiency:

    Natural Gas

    Carbon, % (wt) = 69.98Hydrogen, % (wt) = 22.31Sulfur, % (wt) = 0.0Heating value, Btu/lb = 21,830

    No. 2 Oil

    Carbon, % (wt) = 85.8Hydrogen, % (wt) = 12.7Sulfur, % (wt) = 0.2Heating value, Btu/lb = 19,420

    No. 6 Oil

    Carbon, % (wt) = 86.6Hydrogen, % (wt) = 10.9Sulfur, % (wt) = 2.09Heating value, Btu/lb = 18,830

    2. Efficiencies are based on ambient air temperature of 80 F, relative humidity of 30%, and 15% excess air in the exhaust flue gas.

    3. Efficiencies are based on manufacturers published radiation and convection losses. (For Cleaver-Brooks radiation and con-vection losses, see Boiler Efficiency Facts Guide, publication

    number CB-7767).

    4. Any efficiency verification testing will be based on the stack loss method.

    When specifying the efficiencies in the tables, be sure to include the specific guarantee conditions to maximize the effectiveness of your efficiency specification. If you have any questions regarding the efficiency specifications, please con-tact your local Cleaver-Brooks authorized representative. For efficiencies and stack temperatures at operating pressures not listed, follow these procedures:

    When the operating steam pressure is between 10 psig and 125 psig, interpolate the values from the efficiency tables.

    When the operating steam pressure is above 125 psig, esti-mated efficiency can be calculated as follows:

    Example:

    Boiler: 350 hp.

    Fuel: natural gas.

    Operating steam pressure: 200 psig.

    Find the fuel-to-steam efficiency at 100% firing rate. From Table A2-8 for a 350 hp boiler operating at 100% firing rate and an operating steam pressure of 125 psig, the efficiency is 82.5%.

    Using Figure A2-8, note that the stack temperature increases 36 F at the higher operating pressure. To estimate boiler effi-ciency, use this rule of thumb: For every 40 F increase in stack temperature, efficiency decreases by 1%. Since the stack tem-perature rise is 36 F, the decrease in the boiler efficiency at 200 psig operating pressure is calculated as follows: 36/40 = .9%. Therefore, the boiler efficiency at 200 psig operating pressure is 82.5 - .9 = 81.6%.

    Emissions The emission data included in this section consists of typical uncontrolled emission levels for Cleaver-Brooks Model CB Firetube Boilers.

    Cleaver-Brooks Firetube boilers are available with the standard burner package for Model CB, or optional internal flue gas recirculation on Model CB (LE) (refer to Section A3).

    The Cleaver-Brooks IFGR packages are integrated boiler/burner/control packages designed specifically for Cleaver-Brooks boilers. For detailed information on Cleaver-Brooks IFGR packages, refer to Model CB (LE) in Section A3.

    NOTICE

    The data in Table A2-13 represents typical emission levels only. Guaranteed emission levels are available from your local Cleaver-Brooks authorized represen-tative.

  • A2-22

    Model CB Boilers Firetube Boilers

    07-02

    BOILER HP

    FIRING RATE (%)

    25 50 75 100

    50 83.0 83.2 82.9 82.4

    60 82.9 83.1 82.7 82.3

    70 84.5 84.7 84.3 83.9

    80 84.6 84.8 84.5 84.0

    100 84.4 85.0 84.8 84.4

    125 83.3 83.6 83.4 83.2

    150 84.4 84.6 84.5 84.3

    200 85.0 85.3 85.1 84.9

    250 85.0 84.7 84.0 83.3

    300 85.3 85.3 84.6 83.9

    350 85.3 85.7 85.2 84.5

    400 84.5 84.7 84.6 84.4

    500 85.5 85.7 85.5 85.2

    600 85.7 86.0 85.8 85.6

    700 85.7 86.2 86.0 85.7

    750 85.8 86.1 85.9 85.6

    800 85.8 86.1 85.9 85.6

    Table A2-7. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 10 psig, Natural Gas

    BOILERHP

    FIRING RATE (%)

    25 50 75 100

    50 80.2 80.5 80.4 80.1

    60 80.1 80.4 80.3 80.1

    70 81.7 82.0 81.9 81.7

    80 81.8 82.1 82.0 81.8

    100 81.5 82.4 82.3 82.2

    125 80.4 80.9 81.0 81.0

    150 81.5 82.0 82.0 82.1

    200 82.2 82.7 82.7 82.7

    250 82.0 82.0 81.6 81.3

    300 82.6 82.7 82.2 81.9

    350 82.6 83.2 82.8 82.5

    400 81.8 82.2 82.4 82.2

    500 82.8 83.2 83.3 83.1

    600 82.9 83.5 83.6 83.5

    700 83.0 83.6 83.6 83.6

    750 83.1 83.6 83.7 83.5

    800 83.1 83.6 83.7 83.5

    Table A2-8. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 125 psig, Natural Gas

    BOILERHP

    FIRING RATE (%)

    25 50 75 100

    50 86.8 87.0 86.6 86.1

    60 86.7 86.9 86.5 86.0

    70 88.4 88.6 88.2 87.7

    80 88.5 88.7 88.3 87.8

    100 88.2 88.5 88.3 88.0

    125 87.2 87.4 87.2 87.0

    150 88.4 88.5 88.3 88.1

    200 88.9 89.2 88.9 88.7

    250 88.8 88.5 87.8 87.1

    300 89.1 89.2 88.4 87.7

    350 89.1 89.5 89.0 88.4

    400 88.4 88.5 88.4 88.1

    500 89.4 89.5 89.3 89.2

    600 89.5 89.9 89.7 88.4

    700 89.6 90.0 89.8 89.6

    750 89.7 90.0 89.8 89.5

    800 89.7 90.0 89.8 89.5

    Table A2-9. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 10 psig, No. 6 Oil

    BOILERHP

    FIRING RATE (%)

    25 50 75 100

    50 83.9 84.2 84.0 83.8

    60 83.8 84.1 83.9 83.8

    70 85.5 85.8 85.6 85.4

    80 85.6 85.9 85.7 85.6

    100 84.6 85.8 85.9 85.8

    125 84.1 84.6 84.7 84.8

    150 85.3 85.8 85.8 85.8

    200 86.0 86.5 86.4 86.5

    250 85.8 85.7 85.3 85.0

    300 86.3 86.4 86.0 85.6

    350 86.4 87.0 86.6 86.2

    400 85.5 85.9 86.0 85.9

    500 86.5 86.9 87.0 86.9

    600 86.7 87.3 87.4 87.2

    700 86.8 87.3 87.4 87.4

    750 86.9 87.4 87.5 87.3

    800 86.9 87.4 87.5 87.3

    Table A2-10. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 125 psig, No 6 Oil

  • A2-23

    Firetube Boilers Model CB Boilers

    07-02

    BOILERHP

    FIRING RATE (%)

    25 50 75 100

    50 86.5 86.7 86.3 85.8

    60 86.3 86.6 86.2 85.7

    70 87.9 88.2 87.8 87.3

    80 88.1 88.3 87.9 87.4

    100 87.8 88.4 88.1 87.7

    125 86.7 86.9 86.7 86.6

    150 87.8 88.0 87.8 87.6

    200 88.4 88.7 88.4 88.2

    250 88.3 88.1 87.4 86.7

    300 88.6 88.7 88.0 87.3

    350 88.6 89.0 88.5 87.8

    400 87.9 88.1 87.9 87.6

    500 88.9 89.0 88.9 88.6

    600 89.0 89.4 89.2 89.0

    700 89.1 89.5 89.3 89.1

    750 89.2 89.5 89.3 89.0

    800 89.2 89.5 89.3 89.0

    Table A2-11. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 10 psig, No. 2 Oil

    BOILER HP

    FIRING RATE (%)

    25 50 75 100

    50 83.6 84.0 83.8 83.5

    60 83.5 83.8 83.7 83.5

    70 85.1 85.4 85.3 85.1

    80 85.2 85.6 85.4 85.3

    100 84.8 85.7 85.6 85.5

    125 83.7 84.2 84.3 84.3

    150 84.8 85.3 85.3 85.4

    200 85.6 86.0 86.0 86.0

    250 85.3 85.3 84.9 84.7

    300 85.9 86.0 85.5 85.2

    350 85.9 86.6 86.1 85.8

    400 85.1 85.5 85.6 85.5

    500 86.1 86.5 86.6 86.4

    600 86.2 86.8 86.9 86.8

    700 86.3 86.9 87.0 86.9

    750 86.4 86.9 87.0 86.8

    800 86.4 86.9 87.0 86.8

    Table A2-12. Predicted Fuel-to-Steam Efficiencies (%), Model CB Boilers - 125 psig, No. 2 Oil

    Figure A2-8. Predicted Stack Temperature Increase for Pressure Greater Than 125 psig

  • A2-24

    Model CB Boilers Firetube Boilers

    07-02

    ENGINEERING DATA The following engineering information is provided for Model CB Firetube Boilers. Additional detail is available from your local Cleaver-Brooks authorized representative. Refer to Tables A2-14 through A2-18.

    Blowdown Water Requirements Some local codes require blowdown tanks to be constructed in accordance with recommendations of the National Board of Boiler and Pressure Vessel Inspectors.

    The National Boards recommendations base the size of the blowdown tank on the removal of at least 4 inches of water from the boiler.

    Table A2-19 lists the approximate quantity of water repre-sented by 4 inches of water at normal operating level for Cleaver-Brooks Model CB Boilers.

    POLLUTANTESTIMATED LEVELS - UNCONTROLLED

    NATURAL GAS NO. 2 OILB NO. 6 OILC

    COppmA 200 90 95

    Lb/MMBtu 0.15 0.07 0.075

    NOxppmA 100 185 502

    Lb/MMBtu 0.12 0.25 0.67

    SOxppmA 1 278 278

    Lb/MMbtu 0.001 0.52 0.52

    HC/VOCsppmA 40 50 70

    Lb/MMBtu 0.016 0.025 0.035

    P