BOC FS125The Fire Extinguishing Solution
Background - Montreal Protocol
• With the introduction of the Montreal Protocol in 1987, Halon is no longer available in most countries and alternatives must be found.
• Halon will be phased out by 2010 and suitable replacements are required for both existing installations and new projects.
• The replacement agents are required to be more environmentally friendly
• Current alternatives for Halon 1301 include both HFC‟s and Inert gas systems such as FM200, Argonite, Inergen, etc.
HFC‟sZERO ozone
depletion
HCFC‟s(NAF SIII)Some ozone
depletion
Halon 1301CFC‟s
Fire Suppression – Types of Products
FIRE SUPPRESSION
AGENTS
Local Application Total Flooding
CO2
Dry Powder
Inert Gases Halocarbons
Foam
Inergen
Argonite
Nitrogen
Argon
Water
HFC227ea *(NAF S227, FM200, FE227)
HFC 23 *(NAF S23, FE13)
HFC 125 *(BOC FS125, FE25, NAF S125)
HCFC Blend A *(NAF SIII)
NOVEC 1230
C6-PerfluoroketoneCO2
Small spaces need big solutions
BOC Introduces…BOC FS125
A patented Product manufactured by Safety Hi – Tech, Italy• A mixture of Pure HFC 125 & Additive
• Chemical name : Pentaflouroethane (99.85%) & „d‟ Limonine (0.15%)
• Extinguishes the Fire by Chemical reaction & Cooling effect.
• Additive increases the Extinguishing performance compared to Pure HFC 125 due to additive.
• Additive reduces the production of decomposition – by – products.
•Can operate from a temperature of - 18 0C to +54 0C
NAF S125 works by absorbing the heat combined with chemical reaction
HEAT
OXYGEN
FUEL
CHEMICAL REACTION
HEAT
OXYGEN
FUEL
CHEMICAL REACTION
BOC FS125 is safe for the environment
Environmental Properties
Source: Scientific Assessment of Ozone Depletion: 1998
370
FM 200®
290BOC FS 125®
6512Halon 1301
Atmospheric life (years)
ODPExtinguishing Agents
Safe For HumansHence Safe To Use in Manned & Unmanned Areas
The PBPK model introduces a new scientific approach to determine safe exposure limits to halocarbons
The PBPK model is specified in the NFPA 2001 Standard, Edition 2004
At the concentration of use NAF S 125® allows a safe exposure time limit of 5 minute
NAF S 125®
Concentration
(% vol.)
Safe Exposure Time
(minutes)
7.5 5.00
8.0 5.00
8.5 5.00
9.0 5.00
9.5 5.00
10.0 5.00
10.5 5.00
11.0 5.00
11.5 5.00
12.0 1.67
12.5 0.59
Safe For Electrical / Electronic Equipments
As it is Clear & Electrically Non Conductive.
It does not leave any residue after Extinguishing the fire.
NAF S 125® Extinguishing and Design Concentrations in accordance with NFPA 2001 (2004 Edition)
Extinguishing concentrations:
Class A fires* (wood crib, sheets of ABS, PMMA and Polypropylene plastic): 6,7 % v/v - 364 g/m³ @ 20 °C
Class B fires (0,25 m² heptane pan): 8.7 % v/v - 483 g/m³ @ 20°C
Design concentrations:
Class A fires*: 8,0% v/v - 441 g/m³ @ 20 °C
Class B fires : 11,3% v/v - 645 g/m³ @ 20 °C
*Class A fuels represent most common applications protected by halocarbons, such as computer rooms, control rooms, electrical rooms, archives and museums
NAF S 125® is similar to Halon 1301
It distributes quickly and homogeneously inside the protected enclosure, reducing extinguishing times, decomposition by-products and damage
Being “Lighter” than Halon 1301, it maintains the concentration even in the upper part of the protected enclosure, avoiding stratification and possible re-ignition
Extinguishing Agent
Molecular Weight Boiling Point ( C) Vapor Pressure
(bar, @ 20 C)
Halon 1301 148.93 -58 13.72
NAF S 125® 120.02 -48.5 13.71
NAF S 23® 70.0 -82.0 47.29
NAF S 227® 170.04 -16.4 4.57
BOC Introduces…BOC FS125 Fire Extinguishing system
• The BOC FS125 system is a 42 bar system in which BOC FS125 is stored in container & superpressurised upto 42 bar by Nitrogen, providing greater flexibility for design.
• Is designed by UL Listed software to ensure accuracy & max. Efficiency.
• Has better extinguishing performance compared to low pressue systems.
• Can travel more distance compared to low pressue systems.
• System Dischrge Time – 10 sec
Components of BOC FS125 SystemCentralised system
1
2
3
4
86
11
12
13
10 9 75
ITEM DESCRIPTION
1
MASTER CYLINDER SUPPLIED
WITH: DEEP TUBE, FLANGE
PROTECTOR CAP, LPG VALVE
AND PRESSURE GAUGE.
2
SLAVE CYLINDER SUPPLIED
WITH: DEEP TUBE, FLANGE
PROTECTOR CAP, LPG VALVE
AND PRESSURE GAUGE.
3 SOLENOID VALVE
4 MANUAL PNEUMATIC RELEASE
5PRESSURE SWITCH WITH
LOCKING DEVICE
6 2 WAYS PNEUMATIC CONE
7 Ø 1/4" FLEXIBLE HOSE
81 WAYS PNEUMATIC CONE +
DECOMPRESSION SCREW
9 U BRACKET
10 MANIFOLD
11 NON RETURN VALVE
12 DISCHARGE HOSE
13 BRACKET
BOC FS125 Approvals and Testing
• The BOC FS125 System is UL Listed. Thoroughly tested to the strictest standard
• BOC FS125 is designed to the NFPA 2001 Standard for Clean Agents
• BOC FS125 has been tested according to ISO 14520, Part 1 Annex C (Class A fire tests)
• BOC FS125 has been tested to International Maritime Organization (IMO) MSC/Circ. 848
NAF S 125® UL System Listing
UL website
Other NAF S 125® Recognitions
United Sates Environmental Protection Agency: acceptance of NAF S 125® and its inclusion in the “Significant New Alternative Policy - SNAP”
(ref.: US EPA letter 22/05/2003)
VDS: Class A and B fire testing in accordance with ISO 14520 Standard(ref.: VDS report # CHL 03016 07/11/2002)
Hughes Associates Europe: Class A and B fire testing in accordance with ISO 14520 Standard
(ref.: HAE report 01/05/2002)
Typical Total Flooding System Applications
Shipping Industry
Libraries, Archives
Servers, Data Storage Rooms
Hospitals
Computer Rooms
TYPICAL APPLICATIONS
BOC FS125
Petrochemical, Offshore
Laboratories
Transportation
(Airports, Train Stations)
The Difference with BOC FS125
BOC FS125 has better extinguishing performance
- 20% Less agent required than FM200 (HFC227ea)
- 32% Less agent required than FE13 (HFC 23)
•BOC FS125 has been approved to operate from a temperature of -18 0C to +54 0C
•The addition of d-Limonene increases the extinguishing performance compared to pure HFC 125
• d-Limonene reduces the production of any decomposition by-products
The NAF S125 blend is patented because it contains an innovative detoxifying additive
Advantages of NAF S125 versus Inert Gases
• Fewer cylinders are needed to extinguish the same fire compared to inert gas systems
• Less cylinders means:• Lower system cost • Less storage space required• Low maintenance costs
• Fast extinguishment (Discharge in 10 seconds compared to 60 seconds for Inert gases)
• Faster discharge = Less damages caused by the fire
Comparison of Clean Agent Systems for Protection of1000 m3 Class A Risk (Paper, Cloth, Plastic, etc)
* Halon 1301 is no longer available in non-essential applications with the exception of Korea and China
Extinguishing
Agent
Quantity of
Agent
Number of
Cylinders
Occupied Floor
Space (m3)
Halon 1301* 331 kg 3 of 120L 0.51
BOC FS125 441 kg 4 of 120L 0.68
HFC 227ea
(FM200)
548 kg 5 of 120L 0.85
HFC 23 (FE 13) 644 kg 6 of 120L 1.20
FK 5-1-12 (Novec
1230)
723 kg 7 of 120L 1.20
IG-55 Argonite 547.0 m3 32 of 80L 5.77
IG-100 Nitrogen 485.8 m3 34 of 80L 7.01
IG-541 Inergen 510.00 m3 31 of 80L 6.40
BOC FS125 Summary
• Superior performance to any other system
• Less cylinders = Less cost
• Safe for people
• Safe for the environment