bmx art 0414/0814 analog input modules · bmx art 0414/814 120 35011978 07/2012 analog input values...
TRANSCRIPT
35011978 07/2012 113
6
Modicon M340 with Unity Pro
BMX ART 0414/814
35011978 07/2012
BMX ART 0414/0814 Analog Input
Modules
Subject of this Chapter
This chapter presents the BMX ART 0414/0814 modules, their characteristics and
explains how they are connected to the various sensors.
What Is in This Chapter?
This chapter contains the following topics:
Topic Page
Presentation 114
Characteristics 115
Analog Input Values 120
Functional Description 123
Wiring Precautions 128
Wiring Diagram 132
Use of the TELEFAST ABE-7CPA412 Accessory 135
BMX ART 0414/814
114 35011978 07/2012
Presentation
Function
The BMX ART 0414/0814 modules are multi-range acquisition devices with four
inputs for the 0414 and eight inputs for the 0814. The inputs are isolated from each
other. These modules offer the following ranges for each input, according to the
selection made at configuration:
RTD IEC Pt100/Pt1000, US/JIS Pt100/Pt1000, Cu10, Ni100/Ni1000 in 2, 3 or 4
wires
thermocouple B, E, J, K, L, N, R, S, T, U
voltage +/- 40 mV to 1.28 V.
Presentation
These modules offer the following ranges for each input, according to the selection
made at configuration:
Cu50 6651-94, Cu100 6651-94 in 2, 3 or 4 wires
Illustration
The BMX ART 0414/0814 analog input modules looks like this:
BMX ART 0414/814
35011978 07/2012 115
Characteristics
General Characteristics
The general characteristics for the BMX ART 0414/BMX ART 0414H (see page 45)and BMX ART 0814/BMX ART 0814H (see page 45) modules are as follows:
Modules ART 0414 ART 0814
Type of inputs Isolated, RTD, thermocouple and voltage inputs
Nature of inputs +/- 40 mV; +/- 80 mV; +/- 160 mV; +/- 320 mV; +/- 640 mV; 1.28 V
Number of channels 4 8
Acquisition cycle time 400 ms / 4 channels 400 ms / 8 channels
Conversion method Σ∆
Resolution 15-bit + sign
Isolation:
Between channels
Between channels and bus
Between channels and ground
750 Vdc
1400 Vdc
750 Vdc
Maximum authorized over voltage for
inputs
+/- 7.5 Vdc
Cold junction compensation Internal compensation using the dedicated TELEFAST ABE-
7CPA412 wiring accessory, including a sensor.
External compensation dedicating channel 0 to a 2/3-wires Pt100
for CJC.
External compensation using the CJC values of channels 4/7 for
channels 0/3. In this case, only one sensor is needed.
Input filter Low pass filter (1st order numerical)
Rejection in differential mode (50/60 Hz) Typically 60 dB
Common mode rejection (50/60 Hz) Typically 120 dB
Power consumption (3.3 V) Typical 0.32 W 0.32 W
Maximum 0.48 W 0.48 W
Power consumption (24 V) Typical 0.47 W 1.00 W
Maximum 1.20 W 1.65 W
BMX ART 0414/814
116 35011978 07/2012
Voltage Input Characteristics
The characteristics of the voltage inputs of the BMX ART 0414/BMX ART 0414H
(see page 45) and BMX ART 0814/BMX ART 0814H (see page 45) modules are as
follows:
RTD Input Characteristics
The characteristics of the RTD inputs of the BMX ART 0414/BMX ART 0414H
(see page 45) and BMX ART 0814/BMX ART 0814H (see page 45) modules are as
follows:
Voltage range +/- 40 mV; +/- 80 mV; +/- 160 mV; +/- 320 mV; +/- 640 mV;
1.28 V
Input impedance Typically 10 MOhms
Maximum converted value +/- 102.4%
Maximum resolution 2.4 µV in the range +/- 40 mV
Measurement error for standard module
At 25° C (77° F) 0.05% of FS (1)
Maximum in the
temperature range
0...60° C (32...140° F)
0.15% of FS (1)
Measurement error for Hardened module
At 25° C (77° F) 0.05% of FS (1)
Maximum in the
temperature range -
25° C..70° C (-13...140° F)
0.20% of FS (1)
Temperature drift 30 ppm/° C
Legend:
(1) FS: Full Scale
RTD Pt100 Pt1000 Cu10 Ni100 Ni1000
Measurement range In accordance with IEC: -175... +825° C
(-347...+1517° F)
In accordance with US/JIS: -87 +437° C
(-125...+819° F)
-91... +251° C (-132
...+484° F)
-54 +174° C (-
65...+345° F)
Resolution 0.1° C (0.2° F)
Detection type Open circuit (detection on each channel)
Legend
(1) Excluding errors caused by the wiring, +/- 1° C (0.2° F) on the range -100...+200° C (-148...+392° F) for Pt100
(2) See detailed errors at the temperature point (see page 332).
BMX ART 0414/814
35011978 07/2012 117
Error at 25° C (77° F) (1) +/- 2.1 ° C (+/- 3.8° F) +/- 2.1 ° C (+/- 3.8° F) +/- 4 ° C (+/- 7.2° F) +/- 2.1 ° C
(+/- 3.8° F)
+/- 0.7 ° C
(+/- 1.3° F)
Maximum error for
standard modules in
the temperature range
0...60° C (32...140° F) (2)
+/- 3 ° C (+/- 5.4° F) +/- 3 ° C (+/- 5.4° F) +/- 4 ° C (+/- 7.2° F) +/- 3 ° C
(+/- 5.4° F)
+/- 1.3 ° C
(+/- 2.3° F)
Maximum error for
Harened modules in
the temperature range
-25° C..70° C (-
13...140° F) (2)
+/- 3.5 ° C (+/- 6.3° F) +/- 3.5 ° C (+/- 6.3° F) +/- 4.5 ° C (+/- 8.1° F) +/- 3.5 ° C
(+/- 6.3° F)
+/- 1.5 ° C
(+/- 2.7° F)
Maximum wiring resistance
4-wire 50 Ohms 500 Ohms 50 Ohms 50 Ohms 500 Ohms
2/3-wire 20 Ohms 200 Ohms 20 Ohms 20 Ohms 200 Ohms
Temperature drift 30 ppm/° C
RTD Pt100 Pt1000 Cu10 Ni100 Ni1000
Legend
(1) Excluding errors caused by the wiring, +/- 1° C (0.2° F) on the range -100...+200° C (-148...+392° F) for Pt100
(2) See detailed errors at the temperature point (see page 332).
RTD CU50 CU100
Measurement range -200...+200° C
Resolution 0.1° C (0.2° F)
Detection type Open circuit (detection on each channel)
Error at 25° C (77° F) (1) +/- 2.1° C (+/- 3.8° F)
Maximum error for standard modules in the
temperature range 0...60° C (32...140° F) (2)
+/- 3° C (+/- 5.4° F)
Maximum error for Hardened modules in
the temperature range -25° C..70° C (-
13...140° F) (2)
+/- 3.5° C (+/- 6.3° F)
Maximum wiring resistance:
4-wire
2/3-wire
50 Ohms
20 Ohms
Temperature drift 30 ppm/° C
Legend
(1) Excluding errors caused by the wiring, +/- 1° C (0.2° F) on the range -100...+200° C
(-148...+392° F) for Pt100
(2) See detailed errors at the temperature point (see page 332).
BMX ART 0414/814
118 35011978 07/2012
Thermocouple Input Characteristics
This table presents the general characteristics of the thermocouple inputs of the
BMX ART 0414/BMX ART 0414H (see page 45) and
BMX ART 0814/BMX ART 0814H (see page 45) modules.
Thermocouples B E J K L
Measurement range +171 +1,779° C
(340...3234° F)
-240 +970° C
(-400...1778° F)
-177 +737° C
(-287...1359° F)
-231 +1,331° C
(-384...2428° F)
-174 +874° C
(-281...1605° F)
Thermocouples N R S T U
Measurement range -232 +1,262° C
(-386...2304° F)
-9 +1,727° C
(340...3234° F)
-9 +1,727° C
(-15...3141° F)
-254 +384° C
(-425...723° F)
-181 +581° C
(-294...1078° F)
Resolution 0.1° C (0.2° F)
Detection type Open circuit (detection on each channel)
Error at 25° C +/- 3.2° C for J, L, R, S and U types (see Characteristics of the BMX ART 0414/814
Thermocouple Ranges in Degrees Celsius, page 334 for detailed errors at temperature
point for each type); +/- 3.7° C for B, E, K, N and T types
Maximum error for
standard modules in the
temperature range -
25° C..70° C (-13...140° F) (2)
+/- 4.5° C (+/-8.1° F) for types: J, L, R, S and U; +/- 5° C (+/-9° F) for types: B, E, K, N and
T (using the TELEFAST accessory with its internal cold junction compensation).
Maximum error for
Hardened modules in the
temperature range -
25° C..70° C (-13...140° F) (2)
+/- 5.5° C (+/-9° F) for types: J, L, R, S and U; +/- 6° C (+/-10.8° F) for types: B, E, K, N
and T (using the TELEFAST accessory with its internal cold junction compensation).
Temperature drift 30 ppm/° C
BMX ART 0414/814
35011978 07/2012 119
Resistive Input Characteristics
The characteristics of the resistive inputs of the BMX ART 0414/BMX ART 0414H
(see page 45) and BMX ART 0814/BMX ART 0814H (see page 45) are as follows.
Range 400 Ω; 4000 Ω
Type measurement 2, 3, 4 wires
Maximum resolution 2.5 mΩ in the range 400 Ω
25 mΩ in the range 4000 Ω
Measurement error for
standard module
At 25° C (77° F) 0.12% of FS (1)
Maximum in the
temperature range 0...60° C
(32...140° F)
0.2% of FS (1)
Measurement error for
ruggedized module
At 25° C 0.12% of FS (1)
Maximum in the
temperature range -
25° C..70° C (-13...140° F)
0.3% of FS (1)
Temperature drift 25 ppm/° C
Legend:
(1) FS: Full Scale
BMX ART 0414/814
120 35011978 07/2012
Analog Input Values
Description
For RTD and TC sensors, the data is a multiple of 10 of the real temperature in ° C
or ° F. The last digit represents 0.1° C or 0.1° F.
For millivoltmeter, the data ranges from 40 mV, 320 mV to 1280 mV and is also a
multiple of 10 of the real measurement. The last digit represents 10 nV.
For millivoltmeter, the data range of 640 mV is a multiple of 100 of the real
measurement. The last digit represents 100 nV.
RTD Ranges
The table below presents the ranges for the RTD sensors (values in brackets are in
1/10° F).
Range Under flow Lower scale Upper scale Over flow
Pt100 IEC 751-1995, JIS C1604-1997 (2/4 wires) -1990
(-3260)
-1750
(-2830)
8250
(15170)
8490
(15600)
Pt1000 IEC 751-1995, JIS C1604-1997 (2/4 wires) -1990
(-3260)
-1750
(-2830)
8250
(15170)
8490
(15600)
Ni100 DIN43760-1987 (2/4 wires) -590
(-750)
-540
(-660)
1740
(3460)
1790
(3550)
Ni1000 DIN43760-1987 (2/4 wires) -590
(-750)
-540
(-660)
1740
(3460)
1790
(3550)
Pt100 IEC 751-1995, JIS C1604-1997 (3 wires) -1990
(-3260)
-1750
(-2830)
8250
(15170)
8490
(15600)
Pt1000 IEC 751-1995, JIS C1604-1997 (3 wires) -1990
(-3260)
-1750
(-2830)
8250
(15170)
8490
(15600)
Ni100 DIN43760-1987 (3 wires) -590
(-750)
-540
(-660)
1740
(3460)
1790
(3550)
Ni1000 DIN43760-1987 (3 wires) -590
(-750)
-540
(-660)
1740
(3460)
1790
(3550)
JPt100 JIS C1604-1981, JIS C1606-1989 (2/4 wires) -990
(-1460)
-870
(-1240)
4370
(8180)
4490
(8400)
JPt1000 JIS C1604-1981, JIS C1606-1989 (2/4
wires)
-990
(-1460)
-870
(-1240)
4370
(8180)
4490
(8400)
JPt100 JIS C1604-1981, JIS C1606-1989 (3 wires) -990
(-1460)
-870
(-1240)
4370
(8180)
4490
(8400)
BMX ART 0414/814
35011978 07/2012 121
TC Ranges
The table below presents the ranges for the TC sensors (values in brackets are in
(1/10° F).
JPt1000 JIS C1604-1981, JIS C1606-1989 (3 wires) -990
(-1460)
-870
(-1240)
4370
(8180)
4490
(8400)
Cu10 (2/4 wires) -990
(-1460)
-910
(-1320)
2510
(4840)
2590
(4980)
Cu10 (3 wires) -990
(-1460)
-910
(-1320)
2510
(4840)
2590
(4980)
Range Under flow Lower scale Upper scale Over flow
Range Under flow Lower scale Upper scale Over flow
Type J -1980
(-3260)
-1770
(-2870)
7370
(13590)
7580
(13980)
Type K -2680
(-4500)
-2310
(-3830)
13310
(24270)
13680
(24940)
Type E -2690
(-4510)
-2400
(-3990)
9700
(17770)
9990
(18290)
Type T -2690
(-4520)
-2540
(-4250)
3840
(7230)
3990
(7500)
Type S -500
(-540)
-90
(160)
17270
(29550)
17680
(30250)
Type R -500
(-540)
-90
(160)
17270
(29550)
17680
(30250)
Type B 1320
(2700)
1710
(3390)
17790
(32000)
18170
(32000)
Type N -2670
(-4500)
-2320
(-3860)
12620
(23040)
12970
(23680)
Type U -1990
(-3250)
-1810
(-2930)
5810
(10770)
5990
(11090)
Type L -1990
(-3250)
-1740
(-2800)
8740
(16040)
8990
(16490)
BMX ART 0414/814
122 35011978 07/2012
Voltage Ranges
The table below presents the voltage ranges.
Resistance Ranges
The table below presents the resistance ranges.
Range Under flow Lower scale Upper scale Over flow
+/- 40 mV -4192 -4000 4000 4192
+/- 80 mV -8384 -8000 8000 8384
+/- 160 mV -16768 -16000 16000 16768
+/- 320 mV -32000 -32000 32000 32000
+/- 640 mV -6707 -6400 6400 6707
+/- 1280 mV -13414 -12800 12800 13414
Range Under flow Lower scale Upper scale Over flow
0-400 Ohms 2/4 wires 0 0 4000 4096
0-4000 Ohms 2/4 wires 0 0 4000 4096
0-400 Ohms 3 wires 0 0 4000 4096
0-4000 Ohms 3 wires 0 0 4000 4096
BMX ART 0414/814
35011978 07/2012 123
Functional Description
Function
The BMX ART 0414/814 modules are multi-range acquisition devices with four
inputs for the BMX ART 0414 and eight inputs for the BMX ART 0814.
Both Modules offer the following ranges for each input, according to the selection
made during configuration:
RTD: IEC Pt100, IEC Pt1000, US/JIS Pt100, US/JIS Pt1000, Copper CU10,
Ni100 or Ni1000
thermocouple: B, E, J, K, L, N, R, S, T or U,
voltage: +/- 80 mV, +/- 80 mV, +/- 160 mV, +/- 320 mV, +/- 640 mV, +/- 1.28 V,
ohms: 0..400 Ω, 0..4000 Ω.
NOTE: The TELEFAST2 accessory referenced ABE-7CPA412 facilitates
connection and provides a cold junction compensation device.
Illustration
The BMX ART 0414/0814 input modules perform the following functions.
BMX ART 0414/814
124 35011978 07/2012
Details of the functions are as follows.
Display of Electrical Range Measurements
Measurements may be displayed using standardized display (in %, to two decimal
places).
It is also possible to define the range of values within which measurements are
expressed, by selecting:
the lower threshold corresponding to the minimum value for the range -100.00 %
the upper threshold corresponding to the maximum value for the range +100.00
%
These lower and upper thresholds are integers between -32,768 and 32,768.
Address Element Function
1 Adapting the Inputs Adaptation consists in a common mode and ifferential mode filter. Protection
resistors on the inputs allowt to withstand voltage spikes of up to +/- 7.5 V.
A layer of multiplexing allows self-calibration of the acquisition device offset, as
close as possible to the input terminal, as well as selecting the cold junction
compensation sensor included in the TELEFAST housing.
2 Amplifying Input
Signals
Built around a weak-offset amplifier internal to the A/N converter.
A current generator ensures the RTD resistance measurement.
3 Conversion The converter receives the signal issued from an input channel or from the cold
junction compensation. Conversion is based on a Σ ∆ 16 -bit converter. There is a
converter for each input.
4 Transforming
incoming values
into workable
measurements for
the user
recalibration and alignment coefficients to be applied to measurements, as well
as the module’s self-calibration coefficients
(numeric) filtering of measurements, based on configuration parameters
scaling of measurements, based on configuration parameters
5 Communicating
with the Application
manages exchanges with CPU.
topological addressing
receiving configuration parameters from module and channels
sending measured values, as well as module status, to the application
6 Module monitoring
and sending error
notification back to
application
conversion string test
range under/overflow on channels and cold junction compensation process test
watchdog test
7 Cold Junction
Compensation
internal compensation using the TELEFAST ABE-7CPA412
external compensation by Pt100
external compensation using the CJC values of channels 4/7 for channels 0/3.
In this case, only one sensor is needed
Type of Range Display
Bipolar range from -10,000 to +10,000 (-100.00 % to +100.00 %)
BMX ART 0414/814
35011978 07/2012 125
Display of Temperature Range Measurements
Measurements provided to the application are directly usable. It is possible to
choose either "In Temperature" Display or Standardized Display:
for "In Temperature" display mode, values are provided in tenths of a degree
(Celsius or Fahrenheit, depending on the unit you have selected).
for the user-specified display, you may choose a Standardized Display 0...10,000
(meaning from 0 to 100.00 %), by specifying the minimum and maximum
temperatures as expressed in the 0 to 10,000 range.
Measurement Filtering
The type of filtering performed by the system is called "first order filtering". The
filtering coefficient can be modified from a programming console or via the program.
The mathematical formula used is as follows:
where:
α = efficiency of the filter
Mesf(n) = measurement filtered at moment n
Mesf(n-1) = measurement filtered at moment n-1
Valg(n) = gross value at moment n
You may configure the filtering value from 7 possibilities (from 0 to 6). This value
may be changed even when the application is in RUN mode.
NOTE: Filtering may be accessed in Normal or Fast Cycle.
The filtering values are as follows. They depend on the sensor type. T is a cycle time
of 200 ms for TC and mV. T is also a cycle time of 400 ms for RTD and Ohms.
Desired Efficiency Required
Value
Corresponding α Filter
Response
Time at 63%
Cut-off Frequency
(in Hz)
No filtering 0 0 0 0
Low filtering 1
2
0.750
0.875
4 x T
8 x T
0.040 / T
0.020 / T
Medium filtering 3
4
0.937
0.969
16 x T
32 x T
0.010 / T
0.005 / T
High filtering 5
6
0.984
0.992
64 x T
128 x T
0.025 / T
0.012 / T
BMX ART 0414/814
126 35011978 07/2012
The values may be displayed using standardized display (in %, to two decimal
places).
The user may also define the range of values within which measurements are
expressed, by selecting:
the lower threshold corresponding to the minimum value for the range -100.00 %
the upper threshold corresponding to the maximum value for the range +100.00
%.
These lower and upper thresholds are integers between -32,768 and +32,767.
Main frequency 50/60 Hz Rejection
Depending on the country, the user can configure the frequency rejection of main
power harmonics by adapting the speed of sigma delta converter.
Sensor Alignment
The process of "alignment" consists in eliminating a systematic offset observed with
a given sensor, around a specific operating point. This operation compensates for
an error linked to the process. Therefore, replacing a module does not require a new
alignment. However, replacing the sensor or changing the sensor’s operating point
does require a new alignment.
Conversion lines are as follows:
Type of Range Display
Unipolar range from 0 to 10,000 (0 % at +100.00 %)
Bipolar range from -10,000 to 10,000 (-100.00 % to +100.00 %)
BMX ART 0414/814
35011978 07/2012 127
The alignment value is editable from a programming console, even if the program is
in RUN Mode. For each input channel, you can:
view and modify the desired measurement value.
save the alignment value.
determine whether the channel already has an alignment.
The alignment offset may also be modified through programming.
Channel alignment is performed on the channel in standard operating mode, without
any effect on the channel’s operating modes.
The maximum offset between measured value and desired (aligned) value may not
exceed +/-1,500.
NOTE: To align several analog channels on the BMX ART/AMO/AMI/AMM
modules, we recommand proceeding channel by channel. Test each channel after
alignment before moving to the next channel in order to apply the parameters
correctly.
BMX ART 0414/814
128 35011978 07/2012
Wiring Precautions
Introduction
In order to protect the signal from outside interference induced in series mode and
interference in common mode, we recommend that you take the following
precautions.
Cable Shielding
Connection at the FCN connectors:
Given that there are a large number of channels, a cable of at least 10 twisted
pairs is used, with general shielding (outside diameter 10 mm maximum), fitted
with one or two male 40-pin FCN connectors for direct connection to the module.
Connect the cable shielding to the grounding bar. Clamp the shielding to the
grounding bar on the module side. Use the BMX XSP 0400/0600/0800/1200
electromagnetic protection kit (see Modicon M340 Using Unity Pro, Processors,
Racks, and Power Supply Modules, Setup Manual) to connect the shielding.
TELEFAST connection:
Connect the sensor cable shielding to the terminals provided and the whole
assembly to the cabinet ground.
DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
While mounting / removing the modules:
make sure that each terminal block is still connected to the shield bar and
disconnect voltage supplying sensors and pre-actuators.
Failure to follow these instructions will result in death or serious injury.
BMX ART 0414/814
35011978 07/2012 129
BMX ART 0414/814
130 35011978 07/2012
Sensors shielding
In order for the acquisition system to operate correctly, we recommend you take the
following precautions:
if sensors are isolated from ground, all the shields of the sensor cables must be
referenced to the Telefast/PLC ground.
if sensors are referenced to the sensor ground which is far from PLC ground, all
the shields of the sensor cables must be referenced to the sensors ground to
eliminate the ground loop path.
Using the Sensors Isolated from the Ground
The sensors are connected according to the following diagram:
BMX ART 0414/814
35011978 07/2012 131
If the sensors are referenced in relation to the ground, this may in some cases return
a remote ground potential to the terminals or the FCN connector. It is therefore
essential to follow the following rules:
the potential must be less than the permitted low voltage: for example, 30 Vrms
or 42.4 VDC.
setting a sensor point to a reference potential generates a leakage current. You
must therefore check that all leakage currents generated do not disturb the
system.
Sensors and other peripherals may be connected to a grounding point some
distance from the module. Such remote ground references may carry considerable
potential differences with respect to local ground. Induced currents do not affect the
measurement or integrity of the system.
Electromagnetic Hazard Instructions
DANGERHAZARD OF ELECTRIC SHOCK
Ensure that sensors and others peripherals are not exposed through grounding
points to voltage potential greater than acceptable limits.
Failure to follow these instructions will result in death or serious injury.
CAUTIONUNEXPECTED BEHAVIOR OF APPLICATION
Follow those instructions to reduce electromagnetic perturbations:
use the BMX XSP 0400/0600/0800/1200 electromagnetic protection kit
(see Modicon M340 Using Unity Pro, Processors, Racks, and Power Supply
Modules, Setup Manual) to connect the shielding.
Electromagnetic perturbations may lead to an unexpected behavior of the
application.
Failure to follow these instructions can result in injury or equipment damage.
BMX ART 0414/814
132 35011978 07/2012
Wiring Diagram
Introduction
The BMX ART 0414 input module consists of a 40-pin FCN connector.
The BMX ART 0814 input module consists of two 40-pin FCN connectors.
Connector Pin Assignment and Sensors Wiring
This example uses a probe configuration with:
Channel 0/4: Thermocouple
Channel 1/5: 2-wires RTD
Channel 2/6: 3-wires RTD
Channel 3/7: 4-wires RTD
WARNINGUNEXPECTED EQUIPMENT OPERATION
Take every precaution at the installation to prevent any subsequent mistake in the
connectors. Plugging the wrong connector would cause an unexpected behavior
of the application.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
BMX ART 0414/814
35011978 07/2012 133
The pin assignment for the 40-pin FCN connector and the sensors wiring is shown
below:
MS+: RTD Measure + input / Thermocouple + input
MS-: RTD Measure - input / Thermocouple - input
EX+: RTD probe current generator + output
EX-: RTD probe current generator - output
NC: Not connected
DtC: The CJC sensor detection input is connected to CJ+ if the sensor type is DS600. It is not
connected (NC) if the sensor type is LM31.
NOTE: The CJC sensor is needed for TC only.
Module Front View - cabling view
Left connector Right connector (BMX ART 414 only)
Cold Junction
temp. sensor
Thermocouple
2-wire RTD probe
3-wire RTD probe
4-wire RTD probe
Channel 6/2
Channel 7/3
Channel 5/1
Channel 4/0
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1B A
EX+EX-
EX+EX-
MS- MS+
MS- MS+
EX+EX-
EX+EX-
MS- MS+
MS- MS+
CJO CJ-
CJ+DtC
NCNC
NCNC
NC
NC NC
NC
NCNC
NCNC
NCNC
NCNC
NCNC
NCNC
NCNCB A
Cold Junction
temp. sensor
2-wire RTD probe
3-wire RTD probe
4-wire RTD probe
TC
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1B A
EX+EX-
EX+EX-
MS- MS+
MS- MS+
EX+EX-
EX+EX-
MS- MS+
MS- MS+
CJO CJ-
CJ+DtC
NCNC
NCNC
NCNC
NCNC
NCNC
NCNC
NCNC
NCNC
NCNC
NCNCB A
BMX ART 0414/814
134 35011978 07/2012
Cold Junction Compensation
For each block of 4 channels (channels 0 to 3 and channels 4 to 7), the external
compensation of the module is performed in the TELEFAST ABE-7CPA412
accessory. This device provides a voltage in mV corresponding to:
Voltage = (6.45 mV * T) + 509 mV (where T = temperature in ° C).
The overall margin of error when using this device is reduced to 1.2° C in the -5° C to
+60° C temperature range.
It is possible to increase the precision of the compensation by using a 2/3-wires
Pt100 probe directly connected to channels 0 and 4 (only for the BMX ART0814)
on the module or connected to the TELEFAST terminal blocks. Channel 0 is thus
dedicated to the cold junction compensation of channels 1, 2 and 3. channel 4 is
thus dedicated to channels 4 to 7.
It is also possible, by using a 2-wire Pt100 probe, provided the initial length of the
probe is limited, to maintain channel 0 as a thermocouple input.
The wiring would then look like this:
The wiring is only valid if the channel 0 is used. If the channel 0 is not used, select
a cold junction with external Pt100. The range of the channel 0 is changed to a 3-
wires Pt100 probe.
The wiring would then look like this:
NOTE: For the BMX ART 0814 Module, the CJC values of channels 4 to 7 can also
be used for channels 0 to 3. Therefore, only one external CJC (see page 135)sensor is wired on channel 4.
BMX ART 0414/814
35011978 07/2012 135
Use of the TELEFAST ABE-7CPA412 Accessory
At a Glance
The TELEFAST ABE-7CPA412 accessory is a base unit used to connect 4-channel
analog modules to screw terminal blocks.
NOTE: When the cabinet where the TELEFAST ABE-7CPA412 accessory is
located and powered up, wait at least 45mn to achieve full precision of the CJC
compensation. It is not necessary to wait 45 mn if the compensation is performed by
an external Pt100 probe.
When using the TELEFAST ABE-7CPA412’s cold junction compensation, in order
to make sure you achieve the indicated level of precision, the movement of air
around the TELEFAST ABE-7CPA412 must not exceed 0.1 m/s. Temperature
variations must not exceed 10° C/hour and the TELEFAST ABE-7CPA412 must be
placed at least 100mm away from all heat sources.
The TELEFAST ABE-7CPA412 can be operated from -40° C to +80° C external
temperature.
Connecting Sensors
Sensors may be connected to the TELEFAST ABE-7CPA412 accessory as shown
in this illustration (see page 128).
Wirings
Legend: Operating in TC mode with Telefast internal cold junction compensation.
2520
1510
51
1 2 3 4
200
100
201
101
202
102
203
103
204
104
205
105
206
106
207
107
T× Probe
EX0+ EX0- MS0 + MS0 - EX1+ EX1- MS1 + MS1 -
EX2+ EX2- MS2 + MS2 - EX3+ EX3- MS3 + MS3 -
BMX ART 0414/814
136 35011978 07/2012
Legend: Operating in TC mode with cold junction compensation using a 2-wire PT100 probe.
Legend: Operating in TC mode with cold junction compensation using a 3-wire PT100 probe.
Connecting Modules
Modules can be connected to a TELEFAST ABE-7CPA412 as shown in the
illustration below:
The BMX ART 0414/0814 analog modules may be connected to the TELEFAST
ABE-7CPA412 accessory using one of the following cables:
BMX FCA 152: length 1.5 m
BMX FCA 302: length 3 m
BMX FCA 502: length 5 m