bms automation wiring

14
Wiring Control Wiring Multi strand , Annealed tin copper ,with sheath and PVC insulation Power Wiring Multistrand Copper conductor with PVC insulation Communication wiring Multistrand , sheathed , stranded PVC insulated CAT 5 or 6 Cable

Upload: gautam-koppala-jorge

Post on 23-Jan-2018

3.830 views

Category:

Engineering


4 download

TRANSCRIPT

Page 1: BMS Automation wiring

Wiring

• Control Wiring – Multi strand , Annealed tin copper ,with sheath and

PVC insulation

• Power Wiring – Multistrand Copper conductor with PVC insulation

• Communication wiring – Multistrand , sheathed , stranded PVC insulated

– CAT 5 or 6 Cable

Page 2: BMS Automation wiring

DDC CONTROL LOOP

Page 3: BMS Automation wiring

BACNet Router

SCHEMATIC DIAGRAM FOR BUILDING MANAGEMENT SYSTEM

Alarm / Report

Printer

Modem

Operator Work station

Remote Web browser client

BACnet / LON

DDC

DRAWING: AHU Control

T Two way valve actuator

Room Temperature sensor

www SMS

Soft Room Temperature Set point

from Operator Workstation

CAT 6 Cable

Shielded Twist Pair

Page 4: BMS Automation wiring

Typical BMS System Architecture

Page 5: BMS Automation wiring

Four-conductor shielded cable with

metal foil shield and drain wire.

Page 6: BMS Automation wiring

Application & Use Type of Wire

1. Communication Cabling between

DDC to DDC

2 core Twisted & Shielded Pair of

Wire 0.8 sq mm to 1.5 sq mm

2. Signal Cabling between Thermistor

Temp. Sensors & DDC

2 core Twisted & Shielded Pair of

Wire 0.8 sq mm to 1.5 sq mm

3. Signal Cabling between Active

Sensors & DDC

2 or 3 or 4 core Twisted & Shielded

Pair of Wire 1 sq mm or 1.5 sq mm

4. Cabling between VAV Zone Sensor

& VAV

2/3/4 core depending upon the type

of Zone Sensor 0.8 sq mm to 1.5 sq

mm

5. Cabling between Valve Actuator &

DDC

2/4 core 1 or 1.5 sq mm

6. System Level Cabling CAT 6 cabling

Typical I-O DEVICES IN HVAC SYSTEM

Page 7: BMS Automation wiring

Typical BMS Wiring Interlock with the Starter Panel

Page 8: BMS Automation wiring

Differential Pressure Sensor Wiring Details

Page 9: BMS Automation wiring

Building Room Pressure Transducer Wiring Details

Page 10: BMS Automation wiring

VFD Wiring Details

Page 11: BMS Automation wiring

Typical Chiller Motorized Isolation Valve Wiring

Page 12: BMS Automation wiring

Typical DDC Wiring Details

Page 13: BMS Automation wiring

BACNet Router

SCHEMATIC DIAGRAM FOR BUILDING MANAGEMENT SYSTEM

Alarm / Report

Printer

Modem

Operator Work station

Remote Web browser client

BACnet / LON

DDC

DRAWING : Networked VAVs

THROUGH GATEWAY

www SMS

VAV Controller ..n

VAV Controller-01

Gateway

Room Temperature &

Set point

Damper

Actuator

CAT 5 Cable

Shielded Twist Pair

Shie

lded

Tw

ist P

air

Page 14: BMS Automation wiring

BACNet Router

SCHEMATIC DIAGRAM FOR BUILDING MANAGEMENT SYSTEM

Alarm / Report

Printer

Modem

Operator Work station

Remote Web browser client

BACnet / LON

DDC

DRAWING : Networked PACs

THROUGH GATEWAY

www SMS

Gateway

PAC PAC PAC

PAC= Precision Air Conditioning

CAT 5 Cable

Shielded Twist Pair

Shielded Twist Pair