bhuvi report work detail

74
Week 1 1.1 RESISTOR The resistor is a two terminal electrical component that opposes the flow of either direct or alternating current, employed to protect, operate, or control the circuit. A resistor is a passive two-terminal electrical component that implements electrical resistance as a circuit element. Resistors act to reduce current flow, and, at the same time, act to lower voltage levels within circuits, it is used in electrical circuits to maintain a constant relation between current flow and voltage. When current flows through a resistance, electrical energy is converted into heat .The power P dissipated by a resistor (or the equivalent resistance of a resistor network) is calculated as: P=VI Fig.1.1 Symbol of resistor (A) RESISTORS CONNECTED IN SERIES Components connected in series are connected along a single path, so the same current flows through all of the components. Series circuits are sometimes called current-coupled or daisy chain-coupled. The current in a series circuit goes through every component in the circuit. Therefore, all of the components in a series connection carry the same current. 1

Upload: bhuwnesh-gupta

Post on 12-Apr-2017

313 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: BHUVI REPORT WORK DETAIL

Week 1

1.1 RESISTOR

The resistor is a two terminal electrical component that opposes the flow of either direct or

alternating current, employed to protect, operate, or control the circuit. A resistor is

a passive two-terminal electrical component that implements electrical resistance as a circuit

element. Resistors act to reduce current flow, and, at the same time, act to lower voltage

levels within circuits, it is used in electrical circuits to maintain a constant relation between

current flow and voltage.

When current flows through a resistance, electrical energy is converted into heat .The power

P dissipated by a resistor (or the equivalent resistance of a resistor network) is calculated as:

P=VI

Fig.1.1 Symbol of resistor

(A) RESISTORS CONNECTED IN SERIES

Components connected in series are connected along a single path, so the same current flows

through all of the components. Series circuits are sometimes called current-coupled or daisy

chain-coupled. The current in a series circuit goes through every component in the circuit.

Therefore, all of the components in a series connection carry the same current. There is only

one path in a series circuit in which the current can flow.

Fig.1.2 Resistors connected in series

I1 = I2= I3 = In

Req . =R1 + R2 +...........+Rn

(B) RESISTORS CONNECTED IN PARALLEL

The potential differences across the components are the same in magnitude, and they also

have identical polarities. To find the total resistance of all components, add the reciprocals of

1

Page 2: BHUVI REPORT WORK DETAIL

the resistances of each component and take the reciprocal of the sum. Total resistance will

always be less than the value of the smallest resistance:

Fig.1.3 Resistor connected on parallel

Req .=1R1+

1R2 +........+

1Rn

1.2 INDUCTOR

An inductor or a reactor is a passive electrical component that can store energy in a magnetic

field created by the electric current passing through it. An inductor's ability to store magnetic

energy is measured by its inductance, in units of henries. Typically an inductor is a

conducting wire shaped as a coil; the loops help to create a strong magnetic field inside the

coil due to Ampere's Law. Due to the time-varying magnetic field inside the coil, a voltage is

induced, according to Faraday's law of electromagnetic induction, which by Lenz's Law

opposes the change in current that created it. Inductors are one of the basic components used

in electronics where current and voltage change with time, due to the ability of inductors to

delay and reshape alternating currents. Inductors called chokes are used as parts of filters in

power supplies or to block AC signals from passing through a circuit.

Fig.1.4 Symbol of inductor

(A) APPLICATION OF INDUCTOR

1. Inductors are used extensively in analogy circuits and signal processing. Inductors in

conjunction with capacitors and other components form tuned circuits which can

emphasize or filter out specific signal frequencies.

2

Page 3: BHUVI REPORT WORK DETAIL

2. An inductor is used as the energy storage device in some switched-mode power

supplies.

3. Inductors are also employed in electrical transmission systems, where they are used to

depress voltages from lightning strikes and to limit switching currents and fault

current.

4. Larger value inductors may be simulated by use of gyrator circuit.

1.3 CAPACITOR

A capacitor (formerly known as condenser) is a passive electronic component consisting of a

pair of conductors separated by a dielectric (insulator). When there is a potential difference

(voltage) across the conductors, a static electric field develops in the dielectric that stores

energy and produces a mechanical force between the conductors. An ideal capacitor is

characterized by a single constant value, capacitance, measured in farads. This is the ratio of

the electric charge on each conductor to the potential difference between them. It may be

polar or non polar type capacitor. In non polar terminal

Fig. 1.5 Symbol of capacitor

(A) APPLICATION

1. Capacitive touch switches are now used on many consumer electronic products.

2. To start the motor, a secondary winding is used in series with a non-polarized starting

capacitor to introduce a lag in the sinusoidal current through the starting winding.

3. For improving power factor.

1.4 BASIC ELECTRICAL DEFINITION

(A) VOLTAGE

Voltage is the electric energy charge difference of electric potential energy transported

between two points. Voltage is equal to the work done per unit of charge against a

static electric field to move the charge between two points. A voltage may represent either a

source of energy (electromotive force), or lost, used, or stored energy (potential drop).

3

Page 4: BHUVI REPORT WORK DETAIL

A voltmeter can be used to measure the voltage (or potential difference) between two points

in a system.

(B) CURRENT

An electric current is a flow of electric charge. In electric circuits this charge is often carried

by moving electrons in a wire. It can also be carried by ions in an electrolyte, or by both ions

and electrons such as in a plasma. The SI unit for measuring an electric current is the ampere,

which is the flow of electric charge across a surface at the rate of one coulomb per second.

Electric current is measured using a device called an ammeter.

(C) MAGNETIC INDUCTION

A generator is a machine that converts mechanical energy into electrical energy by using the

principle of magnetic induction. Magnetic induction is used to produce a voltage by rotating

coils of wire through a stationary magnetic field, or by rotating a magnetic field through

stationary coils of wire. This is one of the most useful and widely employed applications of

producing vast quantities of electric power.

(D) FLUX

Magnetic flux (often denoted Φ or ΦB) through a surface is the surface integral of the normal

component of the magnetic field B passing through that surface. The SI unit of magnetic flux

is the Weber (wb), and the CGS unit is the max well. Magnetic flux is usually measured with

a flux meter, which contains measuring coils and electronics that evaluates the change

of voltage in the measuring coils to calculate the magnetic flux.

1.5 ELECTRICITY

Electricity gives a wide variety of well-known effects, such as lightning, static

electricity, electromagnetic induction and current. Electricity is set of physical phenomena

associated with the presence and flow of electric charger addition, electricity permits the

creation and reception of electromagnetic radiation such as radio waves. Electricity is the

flow of electrons through a conductor. The amount of current (amps) is related to the voltage

(volts) pushing the electrons and the degree of resistance to flow (ohms). During their flow

around a circuit, electrons can be used to create a number of useful by products such as heat

and light. As electrons flow, they alter the charge of the matter they flow through, which may

also generate electromagnetic effects.

4

Page 5: BHUVI REPORT WORK DETAIL

(A) PROPERTY OF ELECTRICITY

1. Heating effect

2. Magnetic effect

3. Chemical effect

(B) APPLICATION OF ELECTRICITY

1. Electricity is a very convenient way to transfer energy, and it has been adapted to a

huge, and growing, number of uses.

2. Electricity is also used to fuel public transportation, including electric buses and trains.

3. Electricity is used within telecommunications

4. The effects of electromagnetism are most visibly employed in the electric motor, which

provides a clean and efficient means of motive power.

5

Page 6: BHUVI REPORT WORK DETAIL

Week 2

2.1 INTERNATIONAL STANDERED TERMINAL MARKING

In any type of electrical machine, terminal marking is important during operating time.

Terminal marking located on terminal box of machine. In every country, different terminal

marking is used. For example, in India phase marking is R, Y, and B. In German country

phase marking is R, S, and T. Similarly, for electric motor and alternator different terminal

marking is used.

(A) STANDARD TERMINAL MARKING FOR PHASE

COUNTRY PHASE

INDIA RED,YELLOW,BLUE

UK RED,YELLOW,BLUE

GERMAN R,S,T

AMERICAN L1,L2,L3

Table 2.1 Standard terminal marking for phase

(B) INTERNATIONAL STANDARD TERMINAL MARKING FOR ELECTRIC

MOTOR

COUNTRY TERMINAL MARKING

INDIA

A1,A2

B1,B2

C1,C2

UK

A,A1

B,B1

C,C1

GERMANU,V,W

X,Y,Z

AMERICANT1,T2,T3

T4,T5,T6

Table 2.2 Standard terminal marking for electric motor

6

Page 7: BHUVI REPORT WORK DETAIL

(C) INTERNATIONAL STANDARD TERMINAL MARKING FOR ALTERNATOR

COUNTRY TERMINAL MARKING

INDIA

A1,A2

B1,B2

C1,C2

UK

A,A1

B,B1

C,C1

GERMANU,V,W

X,Y,Z

AMERICANT1,T2,T3

T4,T5,T6

Table 2.3 Standard terminal marking for alternator

2.2 CELL

An electrochemical cell is a device capable of either generating electrical energy

from chemical reactions or facilitating chemical reactions through the introduction of

electrical energy. A common example of an electrochemical cell is a standard 1.5-volt battery

meant for consumer use. Some electrical cells, once their potential (chemical) energy has all

been changed to electricity and used up, must be thrown away. They are no good anymore.

These are called primary cells. Primary cells include the ones you usually put in a flashlight,

in a transistor radio, and in various other consumer devices.

Fig. 2.1 Symbol of cell

(A) OPERATION OF BATTERY

When the circuit is completed, a deflection is observed in the (G) towards the zinc electrode

indicating that the e- is flowing from the Zn electrode to Cu electrode.

At the Zn electrode, oxidation takes place.

7

Page 8: BHUVI REPORT WORK DETAIL

Zn → Zn+2 + 2e- (oxidation) (1)

The electron 'e' is removed, lost or retained by the metal move through the material contained

in the electrode, and reach the Copper electrode at which they are accepted by Copper ions of

the solution to form the neutral Copper atoms.

Cu+2 + 2e- → Cu (2)

In an electrochemical cell, each electrode constitutes one half of the cell and the reaction

taking place at the electrode is called half-cell reaction. The overall cell reaction is obtained

by adding the two half-cell reactions (1) and (2).

Zn + Cu+2 → Zn+2 + Cu (Overall Reaction)

From this, it is found that, when Zn is added to CuSO4 solution, Zn displaces Cu from

CuSO4 with the liberation of heat. But, in the electrochemical cell, there is no direct contact

between Zn and CuSO4. The heat energy that would have been liberated appears in the form

of electrical energy. Hence, the electrochemical cell acts as a source of current, although for a

short interval.

(B) APPLICATION OF CELL

1. Wrist and wall watch

2. Electronics items

3. Light sources like torch

(C) IDENTIFICATION OF BATTERY TERMINAL

1. Red one goes to the positive terminal and the black goes to negative

2. Marking of negative (-) and positive (+) terminal.

3. Usually the positive post is slightly larger than the negative.

When battery terminal pass in a potato via wire, then if

Potato colour red Positive terminal

Potato colour blue Negative terminal

Table 2.4 Identification of battery terminal

8

Page 9: BHUVI REPORT WORK DETAIL

2.3 BATTERY

An electric battery is a device consisting of two or more electrochemical cell that converts

stored chemical energy into electrical energy. Each cell contains a positive terminal, or

cathode, and a negative terminal, or anode .Cell allows ions to move between the electrodes

and terminals, which allows current to flow out of the battery to perform work.

.

Fig. 2.2 Symbol of cell

(A) OPERATION OF BATTERY

Batteries convert chemical energy directly to electrical energy. A battery consists of some

number of voltaic cells. Each cell consists of two half-cells connected in series by a

conductive electrolyte containing anions and cations. One half-cell includes electrolyte and

the negative electrode, the electrode to which anions (negatively charged ions) migrate; the

other half-cell includes electrolyte and the positive electrode to which cat ions (positively

charged ions) migrate. Redox reactions power the battery. Cat ions are reduced (electrons are

added) at the cathode during charging, while anions are oxidized (electrons are removed) at

the anode during discharge. The electrodes do not touch each other, but are electrically

connected by the electrolyte. Some cells use different electrolytes for each half-cell. A

separator allows ions to flow between half-cells, but prevents mixing of the electrolytes.

(B) APPLICATION

1. Ship, Plain

2. Inverter

3. Railway

4. Power system

5. Domestic purpose

9

Page 10: BHUVI REPORT WORK DETAIL

2.4 GENERATOR

A machine is a tool containing one or more parts that uses energy to perform an intended

action. Machines are usually powered by mechanical, chemical, thermal, or electrical means,

and are often motorized.

An electrical machine is the apparatus that converts energy in three categories:

1. Generators which convert mechanical energy to electrical energy

2. Motors which convert electrical energy to mechanical

3. Transformers which change the voltage level of an alternating current

Fig. 2.3 Generator

An electrical machine which capable to convert mechanical energy into electrical energy.  A

generator forces electrons to flow through an external electrical circuit. It is somewhat

analogous to a water pump, which creates a flow of water but does not create the water

inside. The source of mechanical energy, the prime mover, may be a reciprocating or

turbine steam engine, water falling through a turbine or waterwheel, an internal combustion

engine, a wind turbine, a hand crank, compressed air or any other source of mechanical .

(A) TYPE OF GENERATOR

1. AC generator

2. DC generator

Further of these, AC generator and DC generator has also many types. AC generator may be

synchronous or asynchronous generator.

10

Page 11: BHUVI REPORT WORK DETAIL

Fig. 2.4 Classification of generator

1. AC generator

An AC generator converts mechanical energy into alternating current electricity. Because

power transferred into the field circuit is much less than power transferred into the armature

circuit, AC generators nearly always have the field winding on the rotor and the armature

winding on the stator.

2. DC generator

A DC generator produces direct current electrical energy from mechanical energy. A DC

generator can operate at any speed within mechanical limits and always output a direct

current waveform. Direct current generators known as dynamos work on exactly the same

principles as alternators, but have a commutate on the rotating shaft, which convert the

alternating current produced by the armature to direct current.

(B) APPLICATION

1. Electrolytic process

2. Welding process

3. For supplying excitation

4. To compensate the voltage drop in Feeders.

5. Used as booster

6. Battery charging

11

Page 12: BHUVI REPORT WORK DETAIL

2.5 MOTOR

An electric motor converts electrical energy into mechanical energy. The reverse process of

electrical generators, most electric motors operate through interacting magnetic

fields and current-carrying conductors to generate rotational force. Electric motors are found

in applications as diverse as industrial fans, blowers and pumps, machine tools, household

appliances, power tools, and disk drives.

(A) TYPES OF MOTOR

1. AC motors

2. DC motor

Fig 2.5 Classification of electric motor

1. AC motor

An AC motor converts alternating current into mechanical energy. It commonly consists of

two basic parts, an outside stationary stator having coils supplied with alternating current to

produce a rotating magnetic field, and an inside rotor attached to the output shaft that is given

a torque by the rotating field. The two main types of AC motors are distinguished by the type

of rotor used.

2. DC motor

The brushed DC electric motor generates torque directly from DC power supplied to the

motor by using internal commutation, stationary permanent magnets, and rotating electrical

12

Page 13: BHUVI REPORT WORK DETAIL

magnets. Brushes and springs carry the electric current from the commutate to the spinning

wire windings of the rotor inside the motor. Brushless DC motors use a rotating permanent

magnet in the rotor, and stationary electrical magnets on the motor housing. A motor

controller converts DC to AC. This design is simpler than that of brushed motors because it

eliminates the complication of transferring power from outside the motor to the spinning

rotor. An example of a brushless, synchronous DC motor is a stepper motor which can divide

a full rotation into a large number of steps. The motor's position can be

controlled precisely without any feedback mechanism as long as the motor is carefully sized

to the application.

(B) TYPES OF AC MOTOR

1. Permanently star connected motor

2. Permanently delta connected motor

3. Permanently star and delta connected motor

1. Permanently star connected motor

In this motor terminals are connected in star connection only permanently. These motor have

power rating from 0.25 HP to 5 HP

Fig. 2.7 Star connected motor

. These motor are available in several pole. As no. of poles increases speed will decreases.

POLE SPEED (rpm)

2 2900

4 1440

6 950

8 725

Table 2.5 Speed v/s pole relation of permanent star connected motor

13

Page 14: BHUVI REPORT WORK DETAIL

Permanently delta connected motor

These motor are terminals connected in delta connection. These are also available in 2-5 HP.

Fig 2.8 Delta connected motor

As no of poles increases, speed will decreases of motor.

POLE SPEED (rpm)

2 2900

4 1440

6 950

8 725

Table 2.6 Speed v/s pole relation of permanent delta connected motor

Permanently star and delta connected motor

Fig.2.9 Star and delta connected motor

14

Page 15: BHUVI REPORT WORK DETAIL

These are motor terminal connected in star as well as delta connection. In it 6 terminals are

available. These motor are available up to 2000 HP power.

Power rating of squirrel cage induction motor

5-7.5-10-15-20-30 HP 300HP-500HP

30-40-50 HP 500HP-1000HP

50-75-100 HP 1000HP-3000HP

100HP-200HP 1000HP-1500HP

200HP-300HP

300HP-500HP

POLE SPEED(rpm)

2 2900

4 1440

6 950

8 725

Table 2.7 Speed v/s pole relation of star and delta motor

2.6 OHM’S LAW

Ohm's law states that the current through a conductor between two points is

directly proportional to the potential difference across the two points.

Where I is the current through the conductor in units of amperes, V is the potential difference

measured across the conductor in units of volts, and R is the resistance of the conductor in

units of ohms. More specifically, Ohm's law states that the R in this relation is

I=VR

The interdependence between current, voltage, and resistance is one of the most fundamental

rules, or laws, in electrical circuits. It is called Ohm’s Law, named after the scientist who

supposedly first expressed it.

15

Page 16: BHUVI REPORT WORK DETAIL

Fig. 2.10 Ohm’s law

Three formulas denote this law

V=IR

2.7 STAR AND DELTA CONNECTION

There are two types of system available in electric circuit, single phase and three phase

system. In single phase circuit, there will be only one phase. The current will flow through

only one wire and there will be one return path called neutral line to complete the circuit. So

in single phase minimum amount of power can be transported. Three phase circuit is the poly

phase system where three phases are sending together from the generator to the load. Each

phase are having a phase difference of 120°, ie. 120° angle electrically. So from the total of

360°, three phases are equally divided into 120° each. The power in three phase system is

continuous as all the three phases are involved in generating the total power.

(A) STAR CONNECTION

Fig. 2.11 Star connection

In star connection, there is four wire, three wires are phase wire and fourth is neutral which is

taken from the star point. Star connection is preferred for long distance power transmission

because it is having the neutral point. In this we need to come to the concept of balanced and

unbalanced current in power system.

16

Page 17: BHUVI REPORT WORK DETAIL

When equal current will flow through all the three phases, then it is called as balanced

current. And when the current will not be equal in any of the phase, then it is unbalanced

current. In this case, during balanced condition there will be no current flowing through the

neutral line and hence there is no use of the neutral terminal. But when there will be

unbalanced current flowing in the three phase circuit, neutral is having a vital role. It will take

the unbalanced current through to the ground and protect the transformer. Unbalanced current

affects transformer and it may also cause damage to the transformer and for this star

connection is preferred for long distance transmission.

Line voltage = √3 phase voltage

Line current = phase current

(B) DELTA CONNECTION

Fig. 2.12 Delta connection

In delta connection, there is three wires alone and no neutral terminal is taken. Normally delta

connection is preferred for short distance due to the problem of unbalanced current in the

circuit. The figure is shown below for delta connection. In the load station, ground can be

used as neutral path if required.

In delta connection, the line voltage is same with that of phase voltage. And the line current is

√3 times of phase current. It is shown as expression below:

Line voltage = phase voltage

Line current = √3 phase current

(C) TYPES OF DELTA CONNECTION

1. Forward delta

17

Page 18: BHUVI REPORT WORK DETAIL

2. Reverse delta

1. Forward delta

Fig. 2.13 Forward delta connection

In this type of delta A1 connected to B2, B1 connected to C2 and C1 connected to A2.

In 1966, ISO declares forward delta as standard delta.

2. Reverse delta

Fig. 2.14 Reverse delta connection

18

Page 19: BHUVI REPORT WORK DETAIL

Week 3

3.1 CLASS OF INSULATION

The type of insulation is used in a motor depends upon the operating temperature that the

motor will experience. Average insulation life decreases rapidly with increase in motor

internal operating temperature.

(A) TYPES OF INSULATION

Table 3.1 Insulation of motor

3.2 DEGREE OF PROTECTION

1. The degree of protection is classified in IS 4691.

2. It is denoted by two digits.

3. The first digit denotes protection against solid bodies.

4. The second digit denotes protection against liquid.

5. It is represented by IP.

6. It provides knowledge about sensitivity of motor.

19

CLASS OF INSULATIONTEMPERATURE

(in Degree centigrade)

Y 70-90

A 90-105

B 120

E 130

F 155

H 180-200

C 200-240

Page 20: BHUVI REPORT WORK DETAIL

DEGREE OF PROTECTION

Parameter

No

Protection

Water

falling

vertical

Water

falling

to 150

from

vertical

Water

falling

up to

600

vertical

Water

splashes

Water

projected

by nozzle

Water

from

heavy

seas

0 1 2 3 4 5 6

0No

protection

1

Special

protection

against

50mm

diameter

2

DP

protection

against 12

mm

diameter

IP 21 IP 22 IP23

4

TEFC

protection

against 1

mm

diameter

IP 44

5

TEFC

protection

against

powder

IP 54 IP 55 IP56

Table 3.2 Degree of protection

20

Page 21: BHUVI REPORT WORK DETAIL

3.3 NAME PLATE AND ITS IMPORTANT TERMS AND LEGEND

NAME OF MANUFATURER

NEW MAN ELECTRIC MOTOR LIMITED (ENGLAND)

FRAME SIZE 200-L

MODEL DR-9002

STANDARD BS

KW/HP 75/100

PHASE 3 PHASE

HZ 50 HZ

S.NO C-4865

RPM 2900

AMB 40 DEGREE

CONNECTION STAR, DELTA, STAR-DELTA

TERMINAL STANDARD MARKING JIS

D.E. BEARING 6210-C3

N.D.E. BEARING 6210-C3

IP 44

POWER FACTOR 0.8

TYPE SQUIRREL CAGE T.E.F.C

CLASS OF INSULATION B

VOLT 415+-2% 400-415,380,400,440

TAP CHANGING

NAME OF THE STANDARD BS,IS,NEMA,CSA

Table 3.3 Name plate of motor

21

Page 22: BHUVI REPORT WORK DETAIL

3.4 SINGLE PHASE MOTOR Single-

phase motors do not have the rotating magnetic field of a three phase motor  and require a

secondary magnetic field that causes the rotor to move in the proper direction.

(A) SINGLE PHASE TWO POLE

1. Symbolic diagram

Fig. 3.1 Symbolic diagram

2. Location diagram

Fig. 3.2 Location diagram

22

Page 23: BHUVI REPORT WORK DETAIL

3. Schematic diagram

Fig. 3.3 Schematic diagram

(B) SINGLE PHASE FOUR POLE

In this type of four pole motor, four running winding and four starting winding are connected.

From view of symbolic diagram, four pole and two pole motor are same.

1. Symbolic diagram

Fig. 3.4 Symbolic diagram

23

Page 24: BHUVI REPORT WORK DETAIL

2. Location diagram

Fig. 3.5 location diagram

3. Schematic diagram

Fig. 3.6 Schematic diagram

3.5 TWO PHASES WITH THREE VARIABLE SPEEDS MOTOR

In this type of motor, there are different tapping for different speed. As our requirement, we

can connect one phase to different tapping terminals. There is a selector switch, which is used

to connect the tapping. A capacitor is connected in series with starting winding to start the

motor.

24

Page 25: BHUVI REPORT WORK DETAIL

(A) BENIFITS OF MOTOR

1. Soft starting of the motor & load reducing mechanical stresses & reduced water hammer

with pumps.

2. Energy Savings

3. Ability to control the speed of the motor.

(B) DIFFERENT REPRESENTATION

1. Symbolic diagram

Fig. 3.7 Symbolic diagram

2. Schematic diagram

Fig. 3.8 Schematic diagram

25

Page 26: BHUVI REPORT WORK DETAIL

3.6 TRANSFORMER

A transformer is a static device that converts alternating current from one voltage level to

another level (higher or lower), or to the same level, without changing the frequency. A

transformer transfers electrical energy from one circuit to another through inductively

coupled conductors the transformer's coils. A varying electric current in the first

or primary winding creates a varying magnetic flux in the transformer's core and thus a

varying magnetic field through the secondary winding.

Fig. 3.9 Symbol of transformer

Two parallel lines represent magnetic coupling.

(A) OPERATION OF TRANSFORMER

Fig. 3.10 Operation of transformer

A varying current in the transformer's primary winding creates a varying magnetic flux in the

core and a varying magnetic field impinging on the secondary winding. This varying

magnetic field at the secondary induces a varying electromotive force (EMF) or voltage in the

secondary winding. The primary and secondary windings are wrapped around a core of

infinitely high magnetic permeability so that all of the magnetic flux passes through both the

primary and secondary windings. With a voltage source connected to the primary winding

26

Page 27: BHUVI REPORT WORK DETAIL

and load impedance connected to the secondary winding, the transformer currents flow in the

indicated directions.

According to Faraday's law of induction, since the same magnetic flux passes through both

the primary and secondary windings in an ideal transformer, a voltage is induced in each

winding in the secondary winding case, in the primary winding case. The primary EMF is

sometimes termed counter EMF. This is in accordance with Lenz's law, which states that

induction of EMF always opposes development of any such change in magnetic field.

(B) TYPES OF TRANSFORMER

1. Single phase transformer

2. Three phase’s transformer

(C) CONSTRUCTION PART OF TRANSFORMER

11.4.1 Cores

11.4.2 Windings

11.4.3 Cooling

11.4.4 Insulation drying

11.4.5 Bushings

(D) APPLICATION OF TRANSFORMER

1. Isolate two circuits.

2. Change the voltage level.

3. A measuring of voltage and current of transmission line.

3.7 AUTO TRANSFORMER

An autotransformer is an electrical transformer with only one winding. In an autotransformer,

portions of the same winding act as both the primary and secondary sides of the transformer.

In contrast, an ordinary transformer has separate primary and secondary windings which are

not connected.

27

Page 28: BHUVI REPORT WORK DETAIL

Fig. 3.11 Arrangement of auto transformer

(A) OPERATION

An autotransformer has a single winding with two end terminals, and one or more terminals

at intermediate tap points, or it is a transformer in which the primary and secondary coils

have part or all of their turns in common. The primary voltage is applied across two of the

terminals, and the secondary voltage taken from two terminals, almost always having one

terminal in common with the primary voltage. The primary and secondary circuits therefore

have a number of windings turns in common. Since the volts-per-turn is the same in both

windings, each develops a voltage in proportion to its number of turns. In an autotransformer

part of the current flows directly from the input to the output, and only part is transferred

inductively, allowing a smaller, lighter, cheaper core to be used as well as requiring only a

single winding. However the voltage and current ratio of autotransformers can be formulated

the same as other two-winding transformers:

V 1V 2

= N 1N 2

= I 2I 1

(B) APPLICATION

1. Power transmission and distribution

2. Railways

3. Audio system

(C) ADVANTAGES OF AUTO TRANSFORMER

1. Its efficiency is more when compared with the conventional one.

2. Its size is relatively very smaller.

3. Voltage regulation of autotransformer is much better.

28

Page 29: BHUVI REPORT WORK DETAIL

4. Lower cost

5. Low requirements of excitation current.

6. Less copper is used in its design and construction

29

Page 30: BHUVI REPORT WORK DETAIL

Week 4

4.1 DEPARTMENT OF POWER SYSTEM

An electric power system is a network of electrical components used to supply, transmit and

use electric power. An example of an electric power system is the network that supplies a

region's homes and industry with power for sizable regions, this power system is known

as the grid and can be broadly divided into the generators that supply the power,

the transmission system that carries the power from the generating centres to the load centres

and the distribution system that feeds the power to nearby homes and industries. Smaller

power systems are also found in industry, hospitals, commercial buildings and homes. The

majority of these systems rely upon three-phase AC power the standard for large-scale power

transmission and distribution across the modern world. 

Fig 4.1 Power system structure

(A) DEPARTMENT OF POWER SYSTEM

1. Generation

2. Transmission

3. Distribution

1. Generation

Electricity generation is the process of generating electric power from other sources

of primary energy.. His basic method is still used today: electricity is generated by the

movement of a loop of wire, or disc of copper between the poles of a magnet. For electric

utilities, it is the first process in the delivery of electricity to consumers.

30

Page 31: BHUVI REPORT WORK DETAIL

Electricity is most often generated at a power station by electromechanical generators,

primarily driven by heat engines fuel by chemical combustion or nuclear fission but also by

other means such as the kinetic energy of flowing water and wind. Other energy sources

include solar photo voltaic and geothermal power.

Fig. 4.2 Different sources of generate power supply

2. Transmission

Electric-power transmission is the bulk transfer of electrical energy, from generating power

plants to electrical substations located near demand centre. This is distinct from the local

wiring between high-voltage substations and customers, which is typically referred to

as electric power distribution.

Most transmission lines are high-voltage three-phase alternating current (AC),

although single phase AC is sometimes used in railway electrification systems. High-voltage

direct-current (HVDC) technology is used for greater efficiency at very long distances

(typically hundreds of miles (kilo meters), or in submarine power cables (typically longer

than 30 miles (50 km)). HVDC links are also used to stabilize and control problems in large

power distribution networks where sudden new loads or blackouts in one part of a network

can otherwise result in synchronization problems and cascading failures.

Electricity is transmitted at high voltages (120 kV or above) to reduce the energy losses in

long-distance transmission. Power is usually transmitted through overhead power

lines. Underground power transmission has a significantly higher cost and greater operational

limitations but is sometimes used in urban areas or sensitive locations.

31

Page 32: BHUVI REPORT WORK DETAIL

3. Distribution

An electric power distribution system is the final stage in the delivery of electric power; it

carries electricity from the transmission system to individual consumers. Distribution

substations connect to the transmission system and lower the transmission voltage to medium

voltage ranging between 2 kV and 35 kV with the use of transformers. Primary distribution

lines carry this medium voltage power to distribution transformers located near the

customer's premises. Distribution transformers again lower the voltage to the utilization

voltage of household appliances and typically feed several customers

through secondary distribution lines at this voltage. Commercial and residential customers are

connected to the secondary distribution lines through service drops. Customers demanding a

much larger amount of power may be connected directly to the primary distribution level or

the sub transmission level.

4.2 LOW VOLTAGE CONTROL PANEL

There are held two types of circuit, control circuit and power circuit. In control circuit,

control components of panel like start, stop push button, auxiliary contact, tripping contacts

and no volt coil are present.

(A) CONTROL PANEL DIAGRAM

Fig. 4.4 low voltage control panel

32

Page 33: BHUVI REPORT WORK DETAIL

(B) DIFFERENT COMPONENTS OF CONTROL PANEL

1. Air break contactors

A contactor is an electrically controlled switch used for switching an electrical power circuit,

similar to a relay except with higher current ratings. A contactor is controlled by a circuit

which has a much lower power level than the switched circuit.

Characteristic of contactor

1. Rated current up to 10,000 A.

2. Trip characteristics often fully adjustable including configurable trip thresholds and delays.

3. Usually electronically controlled—some models are microprocessor controlled.

2. No volt coil

Mostly no volt coil energise through two phases. But in preset scenario single phase no volt

coil is also available, that operating voltage is 230v. No volt coil is connected through

auxiliary contact and air circuit breakers.

3. Stop button

Red button indicates red push button. It is used to cut off the supply from machine. If in any

panel more than one stop wants to connect then all stop button must be in series. Stop button

become normally close.

Fig. 4.5 Stop button

4. Start button

Green button indicates start push button. It is used to ON the power supply in control circuit.

More than one start button must be in parallel manner. Start button become normally open.

Fig. 4.6 Start button

33

Page 34: BHUVI REPORT WORK DETAIL

5. Auxiliary contact

Auxiliary contact is connected in parallel to start button.

6. Tripping contact

In overloading condition of machine, it become trip and power supply off. Tripping contact is

connected to stop button in series.

(C) Application

1. Starting of motor

2. Interlocking of motors

3. Automation of motor

4.3 METHOD OF STARTING OF THREE-PHASE INDUCTION

MOTOR

The need for using starters in IM to reduce the starting current, first two (Star-Delta and

Auto-transformer) types of starters used for Squirrel cage IM and then, the starter using

additional resistance in rotor circuit, for Wound rotor (Slip-ring) IM, are presented along with

the starting current drawn from the input (supply) voltage, and also the starting torque

developed using the above starters.

(A) NEED OF DIFFERENT STARTING METHODS

In starting of motor, starting current is very large. From these, winding may be damage. For

protection from large starting current, we can use different methods of starting. With the help

of these starting methods, we can limit starting voltage and starting current.

(B) TYPES OF STARTING METHODS

1. Star delta starter

This type is used for the induction motor, the stator winding of which is nominally delta-

connected. This is a simple starter, which can be easily reconfigured. The motor must be delta

connected during a normal run, in order to be able to use this starting method. The received

starting current is about 30 % of the starting current during direct on line start and the starting

torque is reduced to about 25 % of the torque available at a D.O.L start. This starting method

only works when the application is light loaded during the start. If the motor is too heavily

34

Page 35: BHUVI REPORT WORK DETAIL

loaded, there will not be enough torque to accelerate the motor up to speed before switching

over to the delta position.

When starting up, the load torque is low at the beginning of the start and increases with the

square of the speed. When reaching approximately 80-85% of the motor rated speed the load

torque is equal to the motor torque and the acceleration ceases. To reach the rated speed, a

switch over to delta position is necessary, and this will very often result in high transmission

and current peaks.

In some cases the current peak can reach a value that is even bigger than for a D.O.L start.

Applications with a load torque higher than 50% of the motor rated torque will not be able to

start using the star-delta starter. When starting up, the load torque is low at the beginning of

the start and increases with the square of the speed. When reaching the motor rated speed the

load torque is equal to the motor torque and the acceleration ceases. To reach the rated speed,

a switch over to delta position is necessary, and this will very often result in high

transmission and current peaks.

It may be manual star delta starter or automatic star delta starter. In automatic star delta

starter timer is used.

Fig. 4.7 Manual star delta starter

2. Direct on-line starter

Induction motors can be started Direct-on-Line (DOL), which means that the rated voltage is

supplied to the stator, with the rotor terminals short-circuited in a wound rotor (slip-ring)

35

Page 36: BHUVI REPORT WORK DETAIL

motor. For the cage rotor, the rotor bars are short circuited via two end rings. The main

problem in starting induction motors having large or medium size lies mainly in the

requirement of high starting current, when started direct-on-line (DOL). Assume that the

distribution line is starting from a substation, where the supply voltage is constant.

The line feeds a no. of consumers, of which one consumer has an induction motor with a

DOL starter, drawing a high current from the line, which is higher than the current for which

this line is designed. This will cause a drop in the voltage, all along the line, both for the

consumers between the substation and this consumer, and those, who are in the line after this

consumer.

This drop in the voltage is more than the drop permitted, i.e. higher than the limit as per ISS,

because the current drawn is more than the current for which the line is designed. Only for

the current lower the current for which the line is designed, the drop in voltage is lower the

limit. So, the supply authorities set a limit on the rating or size of IM, which can be started

DOL. Any motor exceeding the specified rating, is not permitted to be started DOL, for

which a starter is to be used to reduce the current drawn at starting.

Fig. 4.8 DOL starter

3. Auto transformer starter

This is another starting method that reduces the starting current and starting torque but

contrary to Star-Delta starting where this starting method needs three wires and three

terminals on the motor. Autotransformers are generally equipped with taps at each phase in

36

Page 37: BHUVI REPORT WORK DETAIL

order to adapt the starting parameters to the application starting requirement. During starting,

the motor is connected to the autotransformer taps. With the star and autotransformer

contactors closed, the motor is under reduced voltage. Consequently the torque is reduced as

the square of the applied voltage. When the motor reaches the 80 to 95% of the nominal

speed, the star contactor opens.

Fig. 4.9 Auto transformer

4. Resistance starter

In a slip-ring (wound rotor) induction motor, resistance can be inserted in the rotor circuit via

slip rings, so as to increase the starting torque. The input (stator) current is proportional to the

rotor current. The starting current (input) reduces, as resistance is inserted in the rotor circuit.

But the starting torque, [Tst=3.(Ist)2.(r2+Rext)] increases, as the total resistance in the rotor

37

Page 38: BHUVI REPORT WORK DETAIL

circuit is increased. Though the starting current decreases, the total resistance increases, thus

resulting in increase of starting torque and also obtained by using the expression given

earlier, for increasing values of the resistance in the rotor circuit. If the additional resistance

is used only for starting, being rated for intermittent duty, the resistance is to be decreased in

steps, as the motor speed increases.

Fig. 4.10 Resistance starter

38

Page 39: BHUVI REPORT WORK DETAIL

Week 5

5.1 FORWARD AND REVERSE OPERATION OF INDUCTION

MOTOR

To change the direction a three phase induction machine rotation, two of its phases needs to

be exchanged, thus changing the phase sequence form, say RYB to RBY. This can be

accomplished by using two contactors, one for the forward or CW rotation and one for the

reverse or CCW rotation. The forward and reverse contactors are mechanically interlocked

i.e., if one of them is closed the other cannot close. This is done to avoid dead short circuit in

case both the contactors closing simultaneously. Also electrical interlocking could be

provided using the contactors control contacts.

(A) CIRCUIT DIAGRAM

Fig. 5.1 Forward and reverse operation of motor

39

Page 40: BHUVI REPORT WORK DETAIL

(B) CIRCUIT DESCRIPTION

In this circuit, there are control circuit and power circuit as usual. In control circuit, forward

and reverse no volt coil is present.

5.2 LADDER PROGRAMMING

A hardwired control circuit can be represented by conventional hardwired relay ladder

diagram. In any hardwired circuit, there should be electrical continuity in order for the load to

energize. Electrical sequence of operation in hardwired relay circuits can be represented by

electrical ladder diagram. Ladder diagram shows the interconnection of field devices. In the

ladder diagram, each rung shows how a field device is turned on and also shows how it

interacts with next field devices. Ladder diagrams are specialized schematics commonly used

to document industrial control logic systems. They are called “ladder” diagrams because they

resemble a ladder, with two vertical rails (supply power) and as many “rungs” (horizontal

lines) as there are control circuits to represent.

(A) LOGICAL OPERATION

Logical operations performed by PLC are nothing but fundamental logic operation, using

fundamental logic operators like: AND, OR, and NOT. These operators are used to combine

the instructions on a PLC rung so as to make the outcome of each rung either true or false.

1. AND logic operation

Fig. 5.2 AND logic

The series circuit of 2 switches can be looked as an AND logic function. In fig. both switch1

and switch2, must be closed to have electrical continuity. When there is electrical continuity,

output (light1) will energize. Hence the keyword here is AND.

2. OR logic operation

In an OR - LOGIC function, the output is true if any input is true. The OR logic also states

that if all inputs are true, the output will be true.

40

Page 41: BHUVI REPORT WORK DETAIL

Fig. 5.3 OR logic

In the above figure, if switch1 OR switch2 is energized then light1 will energize. Also, if

both SW1 and SW2 are true, the output will also be true.

3. NOT logic operation

A normally closed relay contact passes power any time when the relay coil is not energized.

In the same manner, the normally closed PLC ladder logic instruction will pass power any

time when the input status file bit associated is not a 1. In this condition, the physical

hardware input is not sending an input signal into the PLC's input module. The opposite of

normally open PLC instruction or contact is the NOT logic. NOT logic can be used in

conjunction with AND or OR logic, when a logical 0 in the status file is expected to activate

some output device. In other words, NOT logic is used when an input is not energized i.e., 0

in the associated status bit, the output should be energized. Also, when the input is energized

i.e., 1 in the associated status bit, the output should not be energized.

Fig. 5.4 NOT logic

(C) ADVANTAGE OF LADDER PROGRAMMING

1. They are also easy to troubleshoot.

2. Allowing for less mechanical downtime.

5.3 TIMER

A timer is specialized type of clock for measuring time intervals. A timer which counts

upwards from zero for measuring elapsed time is often called a stopwatch; a device which

counts down from a specified time interval is more usually called a timer or a countdown

41

Page 42: BHUVI REPORT WORK DETAIL

timer. A simple example for this type is an hourglass. Time switches, timing mechanisms

which activate a switch, are sometimes also called "timers".

(A) TYPES OF TIMER

Different types of timer are available

1. Mechanical timer

Mechanical timers use clockwork to measure time. Manual timers are typically set by turning

a dial to the time interval desired; turning the dial stores energy in a mainspring to run the

mechanism. They function similarly to a mechanical alarm clock; the energy in the

mainspring causes a balance wheel to rotate back and forth.

2. Electromechanical timer

Short-period bimetallic electromechanical timers use a thermal mechanism, with a metal

finger made of strips of two metals with different rates of thermal expansion sandwiched

together; steel and bronze are common. An electric current flowing through this finger causes

heating of the metals, one side expands less than the other, and an electrical contact on the

end of the finger moves away from or towards an electrical switch contact

3. Electronic timer

Electronic timers are essentially quartz clocks with special electronics, and can achieve

higher precision than mechanical timers. Electronic timers have digital electronics, but may

have an analog or digital display. Integrated circuits have made digital logic so inexpensive

that an electronic timer is now less expensive than many mechanical and electromechanical

timers. Individual timers are implemented as a simple single-chip computer system, similar to

a watch and usually using the same, mass-produced, technology.

(B) APPLICATION OF TIMER

1. Auto star delta starter of motor

2. Toaster, washing machine

3. Clocks, stopwatch etc.

42

Page 43: BHUVI REPORT WORK DETAIL

(C) AUTOMATIC STAR DELTA STARTER USING TIMER

Fig. 5.5 Automatic star delta starter

1. Power circuit

The main circuit breaker serves as the main power supply switch that supplies electricity to

the power circuit. The main contactor connects the reference source voltage R, Y, B to the

primary terminal of the motor U1, V1, W1.In operation, the Main Contactor and the Star

Contactor are closed initially, and then after a period of time, the star contactor is opened, and

then the delta contactor is closed. The control of the contactors is by the timer built into the

starter. The Star and Delta are electrically interlocked and preferably mechanically

interlocked as well.

2. Control circuit

In control circuit, auxiliary contactor, start button, stop button, no volt coils are connected as

usual. There is interlocking also possible. From L1 The phase current flows to thermal

overload contact through Fuse, then OFF Push button, On Push button Interlocking Contact

2, and then C3. This way, the circuit is completed.

43

Page 44: BHUVI REPORT WORK DETAIL

3. Advantages

1. Simple Design and Operation

2. Comparatively cheaper than other voltage controlling methods

3. Torque and Current performance of the Star delta starter is well.

4. It draws two times starting current of the FLA (Full Load Ampere) of the connected motor

5. It reduced the starting current to one-third (approximately) as compared to DOL

4. Disadvantage

1. Starting Torque is also reduce to one-third because starter reduce the starting current to

one-third of the rated current [as Line voltage also reduced to 57% (1/√3)]

2. It required Six leads or terminals Motor (Delta Connected)

3. For Delta connection, the supply voltage must be same as the rated motor voltage.

4. At switching time (From Star to Delta), if the motor does not reach at least 90% of its rated

speed, then the current peak may be equally high as in Direct ON Line starter( D.O.L), thus it

may cause harmful effects on the contactors contacts, so it would not be reliable.

44

Page 45: BHUVI REPORT WORK DETAIL

Week 6

6.1 EARTH LEAKAGE CIRCUIT BREAKER

An Earth Leakage Circuit Breaker (ELCB) is a safety device used in electrical installations

with high earth impedance to prevent shock. It detects small stray voltages on the metal

enclosures of electrical equipment, and interrupts the circuit if a dangerous voltage is

detected. Once widely used, more recent installations instead use residual current circuit

breakers which instead detect leakage current directly.

(A) OPERATION

An ELCB is a specialised type of latching relay that has a building's incoming mains power

connected through its switching contacts so that the ELCB disconnects the power in an earth

leakage (unsafe) condition.

The ELCB detects fault currents from live to the earth (ground) wire within the installation it

protects. If sufficient voltage appears across the ELCB's sense coil, it will switch off the

power, and remain off until manually reset. A voltage-sensing ELCB does not sense fault

currents from live to any other earthed body.

(B) PURPOSE

The main purpose of earth leakage protectors is to prevent injury to humans and animals due

to electric shock.

(C) Types of ELCB

1. Voltage ELCB

 A single phase voltage-ELCB will have six terminals. These are line in, line out, neutral in,

earth, fault, and neutral out. The working principle of voltage ELCB is quite simple. One

terminal of the relay coil is connected to the metal body of the equipment to be protected

against earth leakage and other terminal is connected to the earth directly. If any insulation

failure occurs or live phase wire touches the metal body, of the equipment, there must be a

voltage difference appears across the terminal of the coil connected to the equipment body

and earth. This voltage difference produces a current to flow the relay coil.

45

Page 46: BHUVI REPORT WORK DETAIL

2. Current ELCB

The working principle of current earth leakage circuit breaker or RCCB is also very simple as

voltage operated ELCB but the theory is entirely different and residual current circuit breaker

is more sensitive than ELCB. Actually, ELCBs are of two kinds, but it is general practice to

refer voltage based ELCB as simple ELCB. And current based ELCB is referred as RCD or

RCCB. Here one CT core is energized from both phase wise and neutral wire.

A residual-current circuit breaker (RCCB) is the commonly used ELCB. A RCCB consists of

a 3 winding transformer, which has 2 primary windings and one secondary winding. Neutral

and live wires act as the two primary windings. A wire wound coil is the secondary winding.

The current through the secondary winding is zero at the balanced condition.

3. Single phase ELCB

Fig. 6.1 Single phase ELCB

46

Page 47: BHUVI REPORT WORK DETAIL

4. Three Phases ELCB

Fig. 6.2 Three phase ELCB

(D) ADVANTAGES

1. They are less sensitive to fault conditions.

2. ELCB has fewer nuisance trips.

3. ELCB can be arranged to protect against cable damage only, and not trip on faults in down

line installations.

6.2 CIRCUIT BREAKER

A circuit breaker is an automatically operated electrical switch designed to protect

an electrical circuit from damage caused by overload or short circuit. Its basic function is to

detect a fault condition and interrupt current flow. Unlike a fuse, which operates once and

then must be replaced, a circuit breaker can be reset (either manually or automatically) to

resume normal operation. Circuit breakers are made in varying sizes, from small devices that

47

Page 48: BHUVI REPORT WORK DETAIL

protect an individual household appliance up to large switchgear designed to protect high

voltage circuits feeding an entire city.

(A) OPERATION

A circuit breaker works in one of two ways, with an electromagnet (or solenoid) or a bi-metal

strip. In either case, the basic design is the same: when turned on, the breaker allows

electrical current to pass from a bottom to an upper terminal across the solenoid or strip.

When the current reaches unsafe levels, the magnetic force of the solenoid becomes so strong

that a metal lever within the switch mechanism is thrown, and the current is broken.

Alternately, the metal strip bends, throwing the switch and breaking the connection.

To reset the flow of electricity after the problem is resolved, the switch can simply be turned

back on, reconnecting the circuit. Circuit breakers are often found in a cabinet of individual

switches, called a breaker box. The simple switch action of a circuit breaker also makes it

easy to turn off an individual circuit in a house if it's necessary to work on the wiring in that

location.

(B) TYPES OF CIRCUIT BREAKER

Many different classifications of circuit breakers can be made, based on their features such as

voltage class, construction type, interrupting type, and structural features.

1. Low-voltage circuit breakers

2. Magnetic circuit breaker

3. Thermal magnetic circuit breaker

4. Common trip circuit breaker

5. Sulphur hexafluoride (SF6) circuit breaker

6.3 FUSE

In electronics and electrical engineering, a fuse is a type of low resistance resistor that acts as

a sacrificial device to provide over current protection, of either the load or source circuit. Its

essential component is a metal wire or strip that melts when too much current flows through

it, interrupting the circuit that it connects. Short circuits, overloading, mismatched loads, or

device failure are the prime reasons for excessive current. Fuses are an alternative to circuit

breakers.

48

Page 49: BHUVI REPORT WORK DETAIL

A fuse interrupts excessive current ("blows") so that further damage by overheating or fire is

prevented. Wiring regulations often define a maximum fuse current rating for particular

circuits. Over current protection devices are essential in electrical systems to limit threats to

human life and property damage. The time and current operating characteristics of fuses are

chosen to provide adequate protection without needless interruption. Slow blow fuses are

designed to allow harmless short term currents over their rating while still interrupting a

sustained overload. Fuses are manufactured in a wide range of current and voltage ratings to

protect wiring systems and electrical equipment.

Fig. 6.3 Symbol of fuse

(A) CONSTRUCTION

The fuse element is made of zinc, copper, silver, aluminium, or alloys to provide stable and

predictable characteristics. The fuse ideally would carry its rated current indefinitely, and

melt quickly on a small excess. The element must not be damaged by minor harmless surges

of current, and must not oxidize or change its behaviour after possibly years of service.

(B) OPERATION

There are many different types of fuses for residential and commercial use, but the most

common type is made up of a metal wire or filament that is enclosed in a glass or ceramic and

metal casing. In a home, the fuse is typically plugged into a central fuse box where all the

building’s wiring passes through. When the electricity is flowing normally, the fuse permits

the power to pass unobstructed across its filament, between circuits. If an overload occurs,

the filament melts, stopping the flow of electricity.

It generally takes very little time for the filament in the type of fuse used in a home to melt,

so any power surge is quickly stopped. Once a fuse is blown, however, it must be discarded

and replaced with a new one. There are many different voltage and ratings available that

handle different capacities of electricity, and the best fuse for a circuit is typically one that is

rated for slightly higher than the normal operating current.

(C) TYPES OF FUSE

1. High voltage fuse

49

Page 50: BHUVI REPORT WORK DETAIL

2. Resettable fuse

3. Thermal fuse

4. Automotive fuse

(D) FUSES COMPARED WITH CIRCUIT BREAKERS

1. Fuses have the advantages of often being less costly and simpler than a circuit breaker for

similar ratings.

2. Some types of circuit breakers must be maintained on a regular basis to ensure their

mechanical operation during an interruption. This is not the case with fuses, which rely on

melting processes where no mechanical operation is required for the fuse to operate under

fault conditions.

6.4 RECTIFICATION

A rectifier is an electrical device that converts alternating current (AC), which periodically

reverses direction, to direct current (DC), which flows in only one direction. The process is

known as rectification.

(A) NEEDED OF RECTIFICATION

Such as power supplies for radio,television and computer equipment, require a steady

constantDC current (as would be produced by a battery). In these applications the output of

the rectifier issmoothed by an electronic filter (usually a capacitor) to produce a steady

current.

(B) TYPES OF RECTIFICATION

1. Single phase half wave rectification

In half wave rectification of a single-phase supply, either the positive or negative half of the

AC wave is passed, while the other half is blocked. Because only one half of the input

waveform reaches the output, mean voltage is lower. Half-wave rectification requires a single

diode in a single-phase supply.

In this set up, one diode is connected to load. When diode in forward biasing it will be in

conducting mode and provide output voltage across load. When it will be in reverse bias then

no any type of voltage across load.

50

Page 51: BHUVI REPORT WORK DETAIL

17.3.1.2 Single phase full wave rectification

A full-wave rectifier converts the whole of the input waveform to one of constant polarity

(positive or negative) at its output. Full-wave rectification converts both polarities of the

input waveform to pulsating DC (direct current), and yields a higher average output voltage.

Fig. 6.5 Single phase full wave rectifier

3. Three phase rectification

Single-phase rectifiers are commonly used for power supplies for domestic equipment.

However, for most industrial and high-power applications, three-phase rectifier circuits are

the norm. Three phase rectification is very important for HVDC transmission system and

industrial application.

Fig. 6.6 Three phase rectifier

51

Page 52: BHUVI REPORT WORK DETAIL

RESULT

We learn about starting method of three phase induction motor and their various overloads

with high and low voltage control panel. We also study about motor, types of motor,

connection arrangement of windings, transformer, ELCB, timer with interlocking, split phase

motor and alternator.

52

Page 53: BHUVI REPORT WORK DETAIL

CONCLUSION

In this training we get practical or industrial knowledge about some electrical equipment like

motor, transformer, alternator, etc.

We also understand concept of starter in three phase system i.e. starter is not only used for

limiting current but also provide protection of whole system which is connected throw that

starter. Timer is used for automatic control of particular system.

We learn a newly electrical equipment i.e. ELCB (Earth Leakage Circuit Breaker). It is

protects from leakage current throw earth.

53

Page 54: BHUVI REPORT WORK DETAIL

REFRENCE

1. Electrical technology by B.L. theraja, Vol. 2

2. Electrical machine by Ashfaq hussain

3. NPTL Module 8, three phase induction motor

4. NPTL module 2, DC circuit

5. https://en.wikipedia.org/wiki/Ladder_logic

6. http://www.electrical4u.com/starting-methods-for-polyphase-induction-machine/

7. http://www.electricaleasy.com/2014/02/starting-of-three-phase-induction-motors.html

8. https://en.wikipedia.org/wiki/Earth_leakage_circuit_breaker

9. https://en.wikipedia.org/wiki/Rectifier

54