bhaskar

73
Transformer-less Inverter topologies for grid connected solar PV Applications M.Tech. Dissertation Submitted in partial fulfillment of the requirements of the degree of Master of Technology in Energy Systems and Engineering By Annepu Vivek (Roll No : 133170015) Under the guidance of Prof. B. G. Fernandes Dept. of Electrical Engineering Department of Energy Science and Engineering Indian Institute of Technology Bombay June 2015

Upload: vivek-annepu

Post on 24-Jan-2016

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Bhaskar

Transformer-less Inverter topologies for grid

connected solar PV Applications

M.Tech. Dissertation

Submitted in partial fulfillment of the requirements

of the degree of

Master of Technology

in

Energy Systems and Engineering

By

Annepu Vivek

(Roll No : 133170015)

Under the guidance of

Prof. B. G. Fernandes

Dept. of Electrical Engineering

Department of Energy Science and Engineering

Indian Institute of Technology Bombay

June 2015

Page 2: Bhaskar

Dedicated to

My Mother, Father and my Sister

Page 3: Bhaskar

Acknowledgment

I wish to thank the Department of Energy Science and Engineering at Indian In-

stitute of Technology Bombay for providing with this opportunity to pursue my M.Tech.

I express my sincere gratitude towards my guide Prof. B. G. Fernandes for the con-

tinuous guidance and encouragement he provided during my project work.

I would like to thank Mr. Ch. Anand Babu who shared his knowledge for the com-

pletion of this project. I thank Chakridhar, Om Sekhar, Ashok for being such wonderful

batchmates. I, also thank my seniors B. H. Varun, P. Manikanta, S. Rohit whose influence

on me would remain for long. I thank Lab Assistant Mr. A. Khandekar for his sugges-

tions while setting up the hardware. I thank Muni, Vijay, Nanditha, Pratik, DC and all

others who made my stay at IIT Bombay a memorable one. Fianlly, I thank Mr. V. V.

S. Pradeep Kumar whose encouragement and support i never forget and Mr. H. S. V. S

Kumar Nunna for mentoring me during the initial phases of my campus life.

Vivek Annepu

i

Page 4: Bhaskar

M. Tech. Dissertation Approval Sheet

This is to certify that the dissertation titled “Transformer-less Inverter Topolo-

gies for Grid Connected Solar PV Applications” submitted by Mr. Annepu

Vivek(Roll No. 133170015) is approved for the award of degree of Master of Technol-

ogy in Energy Systems Engineering.

Supervisor:

Internal Examiner:

External Examiner:

Chairman:

Date: 29 - June - 2015

Place: IIT Bombay, Mumbai.

ii

Page 5: Bhaskar

Declaration

I declare that this written submission represents my ideas in my own words and where

other’s ideas or words have been included, I have adequately cited and referenced the orig-

inal sources. I also declare that I have adhered to all principles of academic honesty and

integrity and have not misinterpreted or fabricated or falsified any idea/data/fact/source

in my submission. I understand that any violation of the above will be cause for disci-

plinary action by the institute and can also evoke penal action from the sources which

have thus not been properly cited or from whom proper permission has not been taken

when needed.

Vijay Bhaskar

Date: 29 - June - 2015

IIT Bombay, Mumbai

Maharashtra - 400076

iii

Page 6: Bhaskar

Abstract

Distributed energy resources make the grid sustainable. Unlike the conventional grid-

tied inverters, transformer-less inverter do not have any provision for energy storage. This

makes a Transformer-less system less costly with high efficiency and energy density. But,

eliminating a transformer results in high ground leakage currents due to the effect of PV

stray capacitance between the panel and ground. Leakage current results in very high

EMI, causes safety issues to the operating personnel. Hence, transformer-less inverters

are designed to eliminate leakage current and its effect. In this report, an extensive liter-

ature survey of single stage transformer-less voltage source inverters is covered. Various

topologies are classified on the basis of their circuit configuration. A simplified model for

a H-Bridge inverter system is developed to identify the source for leakage current and thus

generalized for all the topologies. Also, basic transformer-less system is analyzed taking

the non-ideal factors like junction capacitance of the switching devices and circuit dead

time into account and their effect on the leakage current. In this point of view, some of

the popular inverter topologies are analyzed and the root cause (and a solution) is iden-

tified. Finally, an improved neutral point clamped transformer-less topology (Improved

NPCTLI) is developed to address these issues on leakage current. Firstly, the presented

theory is demonstrated by thorough simulations. Secondly, A 1 kW generalized hardware

prototype is designed and developed to validate the topologies - H5, oH5, HERIC and

Improved NPCTLI. Finally, a comparative analysis is carried out on the basis of their

common mode characteristics and efficiency.

Page 7: Bhaskar

Contents

1 Introduction 1

1.1 Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

1.1.1 Annual PV capacity additions . . . . . . . . . . . . . . . . . . . . . 1

1.1.2 Grid Integration through the power electronic interface . . . . . . . 1

1.2 Motivation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.3 Objective . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.4 Organization of the Report . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2 Overview of Grid Connected Transformer-less System 4

2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2.2 A Transformer-less grid connected PV system . . . . . . . . . . . . . . . . 4

2.2.1 PV stray capacitance, Cpv1, Cpv2 . . . . . . . . . . . . . . . . . . . . 5

2.2.2 EMI filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.2.3 Ground leakage current . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.3 Leakage current analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

2.4 Overview of grid connected transformer-less system . . . . . . . . . . . . . 11

2.4.1 Topologies derived from full-bridge inverter . . . . . . . . . . . . . . 11

2.4.2 Topologies derived from Full Bridge inverter . . . . . . . . . . . . . 13

2.4.3 Topologies derived the from the Half-bridge inverter . . . . . . . . . 15

2.5 Limitations of the study . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

2.6 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

3 An Improved Neutral-point Clamped Transformer-less Inverter 20

3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

3.2 Analysis of optimized H5 (oH5) Inverter . . . . . . . . . . . . . . . . . . . 20

3.2.1 Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 21

3.2.2 Operation of Clamping branch . . . . . . . . . . . . . . . . . . . . . 23

i

Page 8: Bhaskar

3.2.3 Effect of dead time on Common Mode Voltage . . . . . . . . . . . . 24

3.2.4 Improved transformer-less Inverter . . . . . . . . . . . . . . . . . . 26

3.2.5 Simulation Results . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

3.3 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

4 Hardware Implementation 32

4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

4.2 Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

4.2.1 Selection of DC link Capacitor . . . . . . . . . . . . . . . . . . . . . 33

4.2.2 Design of output Filter . . . . . . . . . . . . . . . . . . . . . . . . . 34

4.2.3 Sensing Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

4.2.4 Level Shifting Stage/ Buffer Circuit . . . . . . . . . . . . . . . . . . 35

4.2.5 Driver Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

4.2.6 Measurement of leakage current . . . . . . . . . . . . . . . . . . . . 36

4.3 Control Strategy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

4.3.1 Grid Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . 36

4.3.2 Current Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

4.3.3 Block Diagram of the Control Scheme . . . . . . . . . . . . . . . . . 41

4.4 Hardware Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

4.4.1 H5 Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

4.4.2 Highly Efficient and Reliable Inverter concept (HERIC) . . . . . . . 43

4.4.3 Optimized H5 Inverter . . . . . . . . . . . . . . . . . . . . . . . . . 45

4.4.4 Improved NPC Transformer-less Inverter . . . . . . . . . . . . . . . 47

4.5 Efficiency Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

4.6 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

5 Conclusion 55

Appendix 56

References 56

6 Appendix 56

ii

Page 9: Bhaskar

List of Figures

1.1 A Single phase grid connected system . . . . . . . . . . . . . . . . . . . . . 2

1.2 A Single phase transformer-less grid connected system . . . . . . . . . . . . 2

2.1 A Full bridge transformer-less inverter system . . . . . . . . . . . . . . . . 5

2.2 Schematic of a roof top installation along with parasitic capacitance [6] . . 6

2.3 EMI filter configuration (a) L filter (b) LC (c) LCL filter 1 (d) LCL Filter 2 7

2.4 A simple Full-bridge transformer-less system . . . . . . . . . . . . . . . . 8

2.5 Equivalent model using voltage sources step 1 & 2 . . . . . . . . . . . . . . 9

2.6 Equivalent model using voltage sources in Step 3 . . . . . . . . . . . . . . . 9

2.7 Equivalent model using voltage sources (a) Step I (b) Step II . . . . . . . . 10

2.8 Leakage current characteristic for a Bipolar PWM operation . . . . . . . . 11

2.9 Voltage across the PV stray capacitance in UPWM inverter . . . . . . . . 12

2.10 FFT analysis for (a) Bipolar PWM (b) Unipolar PWM . . . . . . . . . . . 13

2.11 HUPWM: Voltages across PV stray capacitance to ground . . . . . . . . 13

2.12 H5 Topology by SMA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

2.13 HERIC Topology by Sunways . . . . . . . . . . . . . . . . . . . . . . . . . 14

2.14 Common mode and differential characteristics of a HERIC inverter . . . . 15

2.15 A Full bridge Zero Voltage rectifier based transformer-less inverter . . . . . 16

2.16 FB-ZVR: common mode and differential mode characteristics . . . . . . . 16

2.17 Classification of transformer-less voltage source inverters . . . . . . . . . . 18

2.18 H6 inverter with DC bypass and Neutral point clamping . . . . . . . . . . 19

2.19 H6-DCBP: common mode and differential mode characteristics . . . . . . 19

3.1 An optimized H5 Inverter topology . . . . . . . . . . . . . . . . . . . . . . 20

3.2 Switching strategy for oH5 topology . . . . . . . . . . . . . . . . . . . . . . 21

3.3 Mode I : vg, ig > 0;S1, S4, S5 −ON . . . . . . . . . . . . . . . . . . . . . . 22

3.4 Mode II : vg > 0, ig > 0;S2, S6−ON . . . . . . . . . . . . . . . . . . . . . 23

iii

Page 10: Bhaskar

3.5 Operation Modes of oH5 Inverter (a) Mode III (b) Mode IV (c) Clamping

through S6 (d) through D6 . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

3.6 Resonant circuit for (a) Differential mode for vAN > vBN (b) Common

mode for vAN = vBN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

3.7 Circuit for Improved oH5 Inverter topology . . . . . . . . . . . . . . . . . . 26

3.8 Impedance(Z) vs Frequency (f) plot for H5, oH5, HERIC Inverters . . . . 28

3.9 Simulated waveforms for H5 topology: Zoomed view of vAN and vBN . . . 29

3.10 Simulated waveforms for improved H5 topology: Zoomed view of vAN and

vBN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

3.11 Simulated waveforms for oH5 topology (a) Variations in CMV along with

vAN , vBN and (b) Waveforms for vAB, vg, 20× ig and iCM . . . . . . . . . 30

3.12 Simulated waveforms for Improved oH5 topology (a) Variations in CMV

along with vAN , vBN and (b) Waveforms for vAB, vg, 20× ig and iCM . . . 31

4.1 Circuit layout for experimentation . . . . . . . . . . . . . . . . . . . . . . . 32

4.2 1 KW Hardware Setup for a transformer-less system 1) Programmable

DC supply, 2) DC link capacitors, 3) Generalized Power PCB, 4) Sens-

ing board, 5) Driver circuit, 6) Regulated DC power supplies, 7) Filter

inductors, 8) Auto-transformer (grid), 9) Controller : TMS320F28335, 10)

Level shifter(Buffer circuit with pull-up resistor) . . . . . . . . . . . . . . . 33

4.3 Simple Block diagram of phase locked loop (PLL) . . . . . . . . . . . . . . 37

4.4 Phase detector of enhanced phase locked loop (EPLL) . . . . . . . . . . . . 38

4.5 Frequency response of an Ideal P+R controller with compensation . . . . . 41

4.6 Closed loop current control scheme for a single phase PV based grid-tied

inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

4.7 Differential and Common-mode characteristics of H5 topology, vAN(200V/div),

vBN(200V/div), vCM , vg (200V/div), ig (5A/div) . . . . . . . . . . . . . . 43

4.8 H5: Zoomed view of vAN(200V/div), vBN(200V/div) showing the oscilla-

tions during the free-wheeling period . . . . . . . . . . . . . . . . . . . . . 44

4.9 H5: Inverter output voltage, vAB (200V/div), and the leakage current iCM

(100 mA/div) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

4.10 H5: FFT analysis of the leakage current, FFT(iCM), 1mA/div . . . . . . 45

4.11 HERIC: Inverter pole voltages, vAN & vBN (200 V/div) CMV, vg(200V/div),

ig(5A/div) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

iv

Page 11: Bhaskar

4.12 HERIC Inverter: Oscillations performed by the pole voltages during the

transitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

4.13 HERIC Inverter: Differential voltagevAB(200V/div),leakage current, iCM(50mA/div),

Grid voltage, vg(200V/div), grid current, ig(5A/div) . . . . . . . . . . . . . 46

4.14 HERIC: FFT Analysis for the leakage current of (iCM = 1mA/div) . . . . 47

4.15 oH5 Inverter: Pole voltages, vAN & vBN (200 V/div) CMV, vg(200V/div),

ig(5A/div) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

4.16 oH5 Inverter: Zoomed waveforms of Variations in CMV along with vAN ,

vBN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

4.17 oH5 Inverter: Differential voltagevAB(200V/div),leakage current, iCM(50mA/div),

Grid voltage, vg(200V/div), grid current, ig(5A/div) . . . . . . . . . . . . . 48

4.18 oH5 InverterFFT analysis of the leakage current iCM , 1 mA/div . . . . . 49

4.19 Improved NPCTLI: Pole voltages, vAN & vBN (200 V/div) CMV,

vg(200V/div), ig(5A/div) . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

4.20 Improved NPCTLI: Voltage distribution across the DC link capacitors,

CDC1, CDC2, VON (200v/div) . . . . . . . . . . . . . . . . . . . . . . . . . 50

4.21 Improved NPCTLI: FFT analysis of the leakage current iCM , 1 mA/div 50

4.22 Improved NPCTLI: FFT analysis of the leakage current iCM , 1 mA/div 51

4.23 Efficiency comparison for H5, HERIC, oH5 and Improved NPCTLI . . . . 54

v

Page 12: Bhaskar

List of Tables

2.1 Standards based on VDE 0126-1-1 . . . . . . . . . . . . . . . . . . . . . . . 7

3.1 The Equivalent Resonant circuits with their resonant frequency . . . . . . 28

3.2 Simulation Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

4.1 Hardware Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

4.2 Device specifications and losses at rated power . . . . . . . . . . . . . . . . 53

vi

Page 13: Bhaskar

Chapter 1

Introduction

1.1 Background

The Renewable Industry (especially PV) experienced a very large growth compared to the

fossil fuels in the last fifteen years [1]. Due to the increasing demand, there is a huge deficit

in power which led to the exploration of new and renewable forms of energy. Wind, Solar,

biomass are some of the cleanest energy resources available in the earth’s atmosphere. The

renewable forms of energy are less reliable and the extraction methods are not efficient.

The highest conversion efficiency achieved for a solar cell is approximately 40%. One

should ensure that this energy generated has been utilized to the fullest. Maximum power

point tracking (MPPT) is done to extract maximum power available at a particular time

in a day. Also, the solar power available through PV is not suitable for direct use. Power

electronic converter helps convert the power according to the requirements.

1.1.1 Annual PV capacity additions

Most of the installations are from Germany and Italy. But only 0.2% of electricity gen-

eration is from PV. Around 80% of the global demand is from the European market [2].

Apart from these two countries, the major emerging markets are China, the Middle East,

South Korea, India and other Southeast-Asian countries.

1.1.2 Grid Integration through the power electronic interface

:

In the early 90’s, most of the applications (telecommunications, rural electric supply)

used to get the power from the stand-alone PV systems. And there are a lot of grid

1

Page 14: Bhaskar

connections available. The reduction in the overall cost of the system has led to such

a change. The grid connection is possible only through a DC to AC converter which

supports the interconnection of the distributed generation systems, storage elements, and

renewable energy systems to the electric power system.

Grid converter is mainly a semiconductor based circuit technology which inverts the

incoming signal (i.e., AC-DC and DC-AC). The rise in power demand has led to the

creation of new control methods to achieve more voltage levels leading to much more

complex topologies [4]. For example, a normal H-Bridge converter modified to multilevel

converters or interleaved structures etc.

1.2 Motivation

The power electronics convert the available power to the desired stage and it involves

various stages (Fig. 1.1):

1. Source conversion stage (Solar to Electric energy through PV modules)

2. Maximum power point tracking and DC-DC conversion stage

3. DC-AC conversion stage (Standalone/ Grid-tied mode)

Figure 1.1: A Single phase grid connected system

As the no. of stages increase, the size and cost of the system goes up. Also, the overall

efficiency of the system gets degraded. If the available PV string voltage is in the range of

(340−700)V , A single stage conversion is sufficient. Transformer-less inverter connections

(Fig. 1.2) offer high energy density with reduced cost and improved efficiency as the cost

of transformer costs around(14

)thof the total system cost [3].

Figure 1.2: A Single phase transformer-less grid connected system

2

Page 15: Bhaskar

1.3 Objective

Although the transformer-less grid connection has many benefits, they are limited by

inherent leakage current causing electric shocks to the operating personnel, DC current

injection into the grid frequent tripping of residual current monitoring units (RCMUs)

blocking the PV source from feeding the grid [5]. The objectives of my project are:

1. To study the effects of the circuit parasitics which influence the common mode

voltage(CMV) and hence the leakage current.

2. To develop a transformer-less topology which addresses the leakage current issue by

maintaining constant CMV.

1.4 Organization of the Report

The organization of the report is as follows:

Chapter 2 discusses various transformer-less inverter topologies presented in the literature.

A simplified leakage current model is developed based on a H-Bridge transformer-less

system where, mathematical expressions are derived for the common mode voltage (CMV)

and its effect on the leakage current is discussed.

In Chapter 3, The dead time and the switch capacitance effects are discussed in detail

and a new method to suppress them is identified. Simulation studies are done to validate

the effectiveness of the method

Chapter 4 deals with the hardware implementation to validate the simulations and

the results

Finally, Chapter 5, concludes the report by summarizing the observations and results

along with the future scope of study.

3

Page 16: Bhaskar

Chapter 2

Overview of Grid Connected

Transformer-less System

2.1 Introduction

In this chapter, a single-stage grid connected voltage source based transformer-less system

for PV applications is introduced. Based on the model developed, expressions for the

common-mode voltage and leakage current are derived and few popular topologies to

address this leakage current issue are discussed.

2.2 A Transformer-less grid connected PV system

AC-DC converters are classified based on their power rating:

1. Micro-inverters (< 200 W )

2. String inverters (0.5− 6.5 kW )

3. Mini-central/ Multi-string inverters (< 15 kW )

4. Central inverters (> 15 kW )

Single phase transformer-less inverter falls into the category of String inverters. A

Single phase full bridge based transformer-less topology is shown in the Fig. 2.1 where

L1 and L2 are filter inductors placed on both the output phases of inverter. The choice

of filter made is elaborated in the next section. Assumptions are made in a way that

there is enough PV string voltage available at input side. The PV stray capacitance is

4

Page 17: Bhaskar

denoted by CPV 1 and CPV 2 and the leakage current which is produced by a very fast

varying voltage(∼ kHz) across the stray capacitors is denoted by iCM .

Figure 2.1: A Full bridge transformer-less inverter system

Fig. 2.1 shows a PV based grid connected transformer-less inverter system. The various

components of this system are listed below:

1. Large PV string with the operating voltage range (300− 700)V hence no dedicated

boosting stage on the input stage

2. Inverter which converts available DC input to AC output

3. EMI Filter

4. PV stray capacitance Cpv1 and Cpv2

2.2.1 PV stray capacitance, Cpv1, Cpv2

The PV panel comes with a metallic frame which when charged by an external voltage

signal, the metallic frame forms a capacitance with ground as the other surface and air as

dielectric. So, the stray capacitance which when energized with a high frequency signal

allows a significant current to pass through it. The capacitance CPV is calculated using

the following relation:

Cpv1, Cpv2 = εoεrAcd

(2.1)

From the above equation, this value of capacitance depends on various factors like the

total surface area of the PV panel and its frame, distance between the layers, dust and

humidity :

5

Page 18: Bhaskar

Figure 2.2: Schematic of a roof top installation along with parasitic capacitance [6]

• C1 is the capacitance due to a layer of water (Fig. 2.2)

• C2 is the capacitance through the grounded frame

• C3 is through the roof surface area

The typical values of the capacitance varies from 60 nF/kW on a normal dry day to

110nF/kW on a rainy day. These values are applicable for Crystalline silicon PV panels.

2.2.2 EMI filter

EMI filters are used to block the high frequency component to avoid interference either

conductive or radiative. These filters ensure the current and voltage after the filter to be

sinusoidal. A variety of filter configurations are used for grid connected applications [7].

Traditional L filter is replaced by LC and LCL filters (Fig. 2.3) which are independent of

grid distortions [11]. Also, they provide high stability due to the addition of a pole on the

left hand side of S-plane and harmonic rejection capability. But according to the circuit

topology and modulation scheme, the filter configuration is chosen carefully.

2.2.3 Ground leakage current

In the above system discussed, there is no galvanic isolation due to the absence of a

transformer. As a result, the grid neutral is directly connected to the PV panel grounding.

The voltage near the PV terminals to ground vary at a very high frequency. This frequency

is determined by the resonant circuit formed by the PV parasitic capacitance to ground

and the cables. Due to this large variation in voltage, a very high current flows through

6

Page 19: Bhaskar

Figure 2.3: EMI filter configuration (a) L filter (b) LC (c) LCL filter 1 (d) LCL Filter 2

the system. This may cause electric shocks to the operator [8], [9]. The presence of high

leakage currents cause EMI, frequent tripping of inverters, additional system losses, grid

current distortion etc.

Limits of leakage current for safer operation

According to the German standards, V DE0126−1−1, the leakage current limits for nor-

mal operation of the inverter are given in Table. 2.1 [10]. It also suggests the installation

of residual current monitoring units (RCMUs) and the system should be disconnected

from the grid within 0.3 s after the rise

Table 2.1: Standards based on VDE 0126-1-1

Value of current Break time4icm > 30mA 0.3s4icm > 60mA 0.15s4icm > 100mA 0.04s

2.3 Leakage current analysis

A transformer-less inverter topology is derived to limit the leakage current. The leakage

current is estimated using an equivalent model of the system. From Fig. 2.1, i1 and i2

7

Page 20: Bhaskar

are the currents flowing through L1 and L2. The inductance of the grid is neglected.

vCM , vDM represents the common mode voltage (CMV) and the differential mode voltage

(DMV) of the inverter and are given by:

Figure 2.4: A simple Full-bridge transformer-less system

vDM = vAN − vBN

vCM =vAN + vBN

2

(2.2)

Similarly, the currents are

iCM = i1 + i2

iDM =i1 − i2

2

(2.3)

Where, vAN and vBN are the inverter pole voltages varying with switching frequency.

From Eq. 2.2 and 2.3,

vAN = vCM +vDM

2; vBN = vCM −

vDM2

i1 =iCM

2+ iDM ; i2 =

iCM2− iDM

(2.4)

The inverter pole voltages vAN and vBN are pulsating in nature. As a result currents

i1 and i2 are forced through L1 and L2 respectively. The equivalent circuit is shown in

Fig. 2.5 shows the most important components of the system considered in this analysis.

• L1 and L2 are filter inductors in which the current is controlled

• Lg is the inductance of the grid and is neglected as Lg << L1(L2)

8

Page 21: Bhaskar

Figure 2.5: Equivalent model using voltage sources step 1 & 2

• CAG and CBG are the parasitic capacitances between inverter output and the ground

All other parasitic effects are neglected for this analysis. For safety reasons, the grid

neutral is directly connected to the grounded aluminum frame.

The voltage vK at the node ‘K’ is expressed by,

vK = vAG −1

2vDM

= vBG +1

2vDM

(2.5)

The voltage difference of the parasitic capacitors of the heat sink (CAG, CBG) is zero

and do not attribute to leakage current. Hence, the loop is removed. The circuit is

Figure 2.6: Equivalent model using voltage sources in Step 3

reconfigured (Fig. 2.6) and the common mode leakage current model is derived. The

9

Page 22: Bhaskar

equivalent inductance is given by

Leq =L1L2

L1 + L2

+ Lg (2.6)

The total common mode voltage is derived as,

vtCM = vCM + evDM (2.7)

where, evDM is the effective DMV and is given by,

evDM =vDM

2

(L2 − L1

L2 + L1

)(2.8)

Figure 2.7: Equivalent model using voltage sources (a) Step I (b) Step II

The Leakage current model is shown in the (Fig. 2.7) forms a resonant circuit with

L and C elements. For the leakage current to be ideally zero, the total CMV according

to Eq. 2.7 has to be maintained constant. If the network has a symmetric inductor

configuration, then L1 = L2, this relation does not hold good otherwise [19], [32].

vtCM =

vAN+vBN

2+ vDM

2

(L2−L1

L2+L1

)if L1 6= L2

vAN+vBN

2if L1 = L2

This model is applicable to all types of transformer-less topologies. Every time a

new factor is considered, the equivalent circuit is modeled accordingly by making minor

changes. For half-bridge topologies, asymmetric inductor configuration is used. For full-

bridge networks, filter inductors are placed on both the phases. This will ensure a constant

CMV. The effect of grid voltage is not considered but it has a contribution of 7.2 mA/kW

at 50 Hz.

10

Page 23: Bhaskar

2.4 Overview of grid connected transformer-less sys-

tem

A simple full bridge transformer-less grid connected inverter with conventional pulse width

modulation (PWM) techniques is studied in order to explain the need for deriving new

transformer-less topologies.

2.4.1 Topologies derived from full-bridge inverter

Bipolar pulse width modulation :

As simple H-Bridge inverter is shown in Fig 2.4. In bipolar modulation technique, the

switches S1, S2 are complementary to S3, S4. The inverter output voltage varies from

+VPV to VPV , hence bipolar pulse width modulation. The output voltage and current of

the inverter has dominant switching frequency( fs) component. This technique is suitable

for transformer-less connection as the leakage current is well within the specified limits

(iCM < 30mA) as shown in (Fig 2.8).

Figure 2.8: Leakage current characteristic for a Bipolar PWM operation

Unipolar PWM

In unipolar PWM technique, both the legs are operated independently using comple-

mentary modulating signals. Here, the inverter output voltage is unipolar in nature (

VAB = +VPV - 0 - −VPV ). The output voltage consists of dominant 2 × fs component

having less ((12

)) filtering requirement compared to BPWM. The current ripple is half that

11

Page 24: Bhaskar

of the BPWM technique, thus having reduced core losses and switching losses. Unlike the

BPWM, this technique produces a very high leakage current as the VPG, VNG varies at

switching frequency (Fig 2.9).

Figure 2.9: Voltage across the PV stray capacitance in UPWM inverter

Fig 2.10 shows the FFT analysis for both the unipolar and bipolar modulation tech-

niques.

Hybrid Unipolar PWM (HUPWM)

Considering the above two techniques, a hybrid technique where one leg of the inverter(S1, S3)

is operated at fundamental frequency(50 Hz) and the other leg (S2, S4) at switching fre-

quency, fs. A unipolar output voltage is achieved having the advantages of BPWM and

UPWM techniques [24]. When there is no filter inductor on phase B, the voltage VPG, VNG

vary at fundamental frequency. Though the variation is very slow (50 Hz), large spikes

in the leakage current near the zero crossings and large/complex filtering requirements

makes it unfit for transformer-less connection Fig. 2.11.

In order to address these limitations, several transformer-less topologies are suggested

in the literature [12]- [27]. These inverters are classified based on the type of network

configuration proposed in the literature as shown in the Fig.2.17. The transformer-less

inverter topologies are classified on the basis of:

1. Depending on the filter inductor configuration and position Symmetric/Asy-

mmetric Inductor type

2. Depending on the side (DC/AC) of decoupling, inverters are classified into DC/AC

decoupling circuits

3. Other classification of circuits with and without Neutral point clamping(NPC)

12

Page 25: Bhaskar

(a)

(b)

Figure 2.10: FFT analysis for (a) Bipolar PWM (b) Unipolar PWM

Figure 2.11: HUPWM: Voltages across PV stray capacitance to ground

which are further classified into Active NPC (ANPC) where a controlled switch

is used in the clamping branch whereas diodes are used in a simple NPC circuits.

2.4.2 Topologies derived from Full Bridge inverter

H5 Inverter by SMA

An additional series switch S5 is used on the PV side to eliminate the path for leakage

current [28]. From Fig. 2.12 S1, S3 are operated at grid frequency and are complementary.

S4, S3 are operated at switching frequency during negative and positive cycles of grid

13

Page 26: Bhaskar

voltage [15]. S5 is operated in sync with S3 and S4 at switching frequency. During the

free-wheeling mode of the inverter, S5 is turned off, hence breaking the leakage current

path.

Figure 2.12: H5 Topology by SMA

But, this operation is valid only if all the switches are ideal, i.e., if all the switches are

perfectly open. But there exists some junction capacitance which provides path for the

current during the freewheeling period. As, the circuit is asymmetric, there is an unequal

thermal stress and the CMV during the freewheeling is floating.

Highly Efficient and Reliable concept Inverter (HERIC)

In 2006, a new transformer-less topology where two anti-parallel switches are connected

the AC side of the H-bridge inverter was patented by the Sunways, Fig 2.13 [29].

Figure 2.13: HERIC Topology by Sunways

The system is isolated during the free-wheeling period with the help of two AC bypass

switches S+ and S−. Only two devices conduct in the powering mode unlike H5 topology,

14

Page 27: Bhaskar

thus having very high efficiency.Hence, the name Highly Efficient and Reliable Inverter

Concept (HERIC).

Figure 2.14: Common mode and differential characteristics of a HERIC inverter

Fig. 2.14 shows the common mode and differential modes characteristics. From the

simulation results, it is clearly understood, the common mode voltage in H5 topology is

oscillating (not constant) and it gives rise to a very high leakage current. This is due to the

capacitive coupling between the grid and PV array. Though, the HERIC topology show

very less oscillations, as the grid is decoupled from the PV array using AC bypass network,

the CMV is still floating due to its inability to clamp the voltage. Also, this topology

with the above mentioned switching scheme do not support reactive power exchange.

2.4.3 Topologies derived the from the Half-bridge inverter

A simple half-bridge voltage sourced converter uses two switches ans the neutral is always

connected to the mid point of DC link. But the output voltage is bipolar and maintains

a constant CMV. This requires two seperate dc sources whereas the H-Bridge topology

require only one source. Although this inverter is suitable for transformer-less connection,

VDC> 1000 V or more is practically not viable. Some of the few popular topologies based

on full-bridge derived from the NPC action of half-bridge inverter are discussed as follows:

1. Optimized topology (oH5)

2. H-Bridge Zero Voltage Rectifier (HB-ZVR)

3. Full Bridge DC bypass topology (FB-DCBP)/ H6DCBP

15

Page 28: Bhaskar

Full-Bridge Zero Voltage Rectifier (FB-ZVR)

This topology is derived from HERIC topology. Instead of connecting two bypass switches

on the AC side, a ZVR- Zero voltage rectifier operating with a controlled switch is used [1]

as shown in the Fig. 2.15 to develop this. An extra clamping diode is added to maintain

constant CMV. The bi-directional diode bridge is clamped to the mid-point of DC link

capacitor using a diode and this is done during the free-wheeling period.

Figure 2.15: A Full bridge Zero Voltage rectifier based transformer-less inverter

Figure 2.16: FB-ZVR: common mode and differential mode characteristics

The positive vector is achieved by switching S1−S4 and negative vector by S2−S3. The

zero-vector is achieved by switching on the S5 by providing a small dead time (0.8−1.5µs)

to avoid short-circuit of the input capacitor. The current during the zero voltage free cycles

across the bridge rectifier. During the dead time, the grid current finds a way through

16

Page 29: Bhaskar

the diodes which incurring more losses. Hence, this topology has lesser efficiency than the

HERIC topology. Also 6 extra diodes are incorporated for implementing this topology

which makes it less reliable and more costly.

Full Bridge DC bypass Transformer-less inverter (FB-DCBP)

Fig. 2.18 [14] is a NPC based full bridge topology. Switches S1, S4, S5 conduct

during the positive half-cycle of grid voltage and S2, S3, S6 during the negative half-

cycle. This topology is symmetrical unlike the H5 inverter having uniform thermal distri-

bution. During the freewheeling period, the diodes D+ and D− clamp the CMV to +VPV

2.

The speed of clamping is solely dependent on the diodes D+, D−.

This inverter has excellent common-mode characteristics. Due to the conduction of

four devices during the active period, this converter is lossy. The diodes (D1, D2) forms

a capacitor divider, hence, the PIV of the switches S1 and S2 are halved. The leakage

current characteristics are excellent in comparison with the other topologies, but the effi-

ciency is very low due the conduction of 2 extra switches in the powering mode (Fig. 2.19).

Finally, the classification of various transformer-less inverters is shown in the next page

(Fig. 2.17)

2.5 Limitations of the study

The transformer-less topologies are analyzed by making the following assumptions

• All the devices are assumed to be ideal

• Effects of grid voltage [30] is not considered

• Dead time issues are not discussed [31]

But, in all practical situations, the junction capacitance of the inverter switches

and other parasitics influence the CMV depending upon the topology used. Thorough

study has to be carried out to analyze their effects.Hence, following needs to be done on

transformer-less inverters,

• Find a method to analyze the topologies when switch capacitance and dead time

are considered

• Study some of the sensitive topologies towards these effects

17

Page 30: Bhaskar

Fig

ure

2.17

:C

lass

ifica

tion

oftr

ansf

orm

er-l

ess

volt

age

sourc

ein

vert

ers

18

Page 31: Bhaskar

Figure 2.18: H6 inverter with DC bypass and Neutral point clamping

Figure 2.19: H6-DCBP: common mode and differential mode characteristics

• Devise a solution to overcome these effects and verify through simulations

• Validate the solution using hardware experimentation

2.6 Summary

An overview of the transformer-less topologies is presented in this chapter. A simplified

leakage current model is discussed and necessary conditions are formulated to maintain

low leakage current. An overall classification of the inverter topologies is presented by

virtue of their nature. Limitations for the study performed in the literature are pointed

out and a clear objective of this project is mentioned.

19

Page 32: Bhaskar

Chapter 3

An Improved Neutral-point

Clamped Transformer-less Inverter

3.1 Introduction

This chapter deals with the effects of junction capacitance of the inverter switches. Leak-

age current analysis is carried out during the freewheeling period and dead time as well.

Based on the analysis, a simple solution if suggested to reduce the leakage current

3.2 Analysis of optimized H5 (oH5) Inverter

An optimized H5 (oH5) transformer-less inverter is shown in Fig. 3.1 [25]. This topology is

derived from H5 by SMA ltd. where the pole voltages are floating during the freewheeling

period.

Figure 3.1: An optimized H5 Inverter topology

Under ideal operation, the CMV is maintained constant through a clamping branch.

This branch employs an IGBT-Diode based switch to do the necessary. Hence, this

20

Page 33: Bhaskar

topology falls into the category of Active NPC inverters. The shoot-through issue is dealt

by adding a small dead time between the complementary switches (S5, S6).

3.2.1 Modes of Operation

The modes of operation for this inverter are detailed below. The control is done such that

power is fed into the grid at unity power factor. Fig. 3.2 refers to the switching scheme for

the converter switches. S1 & S2 are complementary, operated at grid frequency(50Hz). S3

& S4 are operated at switching frequency and are turned off when S1 and S2 respectively

are turned on. And, S5, S6 are operated at switching frequency (fs) during both the half

cycles of grid period.

Figure 3.2: Switching strategy for oH5 topology

21

Page 34: Bhaskar

The inverter is operated in the following modes:

• Mode I: vg, ig > 0;S1, S4, S5 −ON

• Mode II : vg > 0, ig > 0;S2, S6−ON

• Mode III : vg < 0, ig < 0;S2, S3, S5 −ON

• Mode IV : vg < 0, ig < 0;S2, S6 −ON

Mode I

For vg, ig > 0, switches S1, S4 and S5 are conducting where S1 is continuously ON for half

the grid period. The current flows through P − S5− S1−L1−L2− S4−N . The voltage

across the inverter output terminals, vAB = +VDC and the pole voltages

Figure 3.3: Mode I : vg, ig > 0;S1, S4, S5 −ON

vAN = +VDC ; vBN = 0V (3.1)

Hence, the common mode voltage when L1 = L2 is given by

vtCM =vAN + vBN

2+ evDM

= +VDC

2(3.2)

Mode II

In this mode, both switches S4&S5 are turned OFF so that the current in L1&L2 free-

wheels through S1&D2 (Fig. 3.4). Hence the pole voltages vAN = vBN = +VDC

2and hence

22

Page 35: Bhaskar

the common mode voltage is,

vtCM = +VDC

2(3.3)

Any deviation in the inverter pole voltages, clamping branch bearing switches S6 − D6

Figure 3.4: Mode II : vg > 0, ig > 0;S2, S6−ON

clamps the voltage to +VDC

2, hence maintaining the CMV constant in both the powering

and free-wheeling mode.

Mode III & Mode IV

Operation of the inverter in Modes III & IV are similar to Modes I & II except for the

output voltage (either 0V or −VDC). Switch S2 and S3 conducts, where S2 operates at

50Hz and the latter at fs (Fig. 3.5(a),(b)). The common mode voltage remains +VDC

2.

3.2.2 Operation of Clamping branch

The DC side of the inverter is provided with two capacitors offering almost similar char-

acteristics. Hence, this mid point (‘O’) is accessed to clamp the pole voltages vAN &

vBN through S6. S6 is operated complementary to S5 when either S1 or S2 are turned

ON. The path for the current flow depends on the magnitude and polarity of the voltages

vAN(= vBN). When vAN < +VDC

2, then current flows through the diode D6 Fig. 3.5(c),(d)

otherwise the current will flow though the already turned S6 clamping the voltages to

+VPV

2. The effectiveness of the clamping circuit depends on how fast the switch S6 and

D6 can be turned ON [32].

Due to the unidirectional nature of the current through D6, the lower capacitor CDC2

discharges as soon as the inverter is started. To avoid this, a very large resistance can be

placed across the two capacitors or an active balancing circuit be employed to maintain

23

Page 36: Bhaskar

Figure 3.5: Operation Modes of oH5 Inverter (a) Mode III (b) Mode IV (c) Clampingthrough S6 (d) through D6

the mid point voltage. Here, a resistive divider circuit is used to maintain the mid point

voltage. The value of the resistor is too high (> 27kΩ) which influences the efficiency

very less(0.1%). Under non-ideal conditions, a small dead time, (0.5− 1.5)µs is provided

between S5 and S6 to avoid the short circuit of capacitor CDC1. As a result, large spikes

appear in the pole voltages and CMV which gives rise to spikes in leakage current.

3.2.3 Effect of dead time on Common Mode Voltage

Dead time is provided to avoid shoot through problems in a converter. In oH5 inverter, a

small dead time is provided between S6 and S5 to avoid short circuit of CDC1. Effective

clamping is not achieved during the dead time as the switch S6 is turned OFF. Realistic

assumptions are made to analyze the behavior of the converter during this period. All the

switches are realized by their junction capacitances [31], [14], [33] “Cce” when they are

switched OFF. During the transition between Mode I&II or Mode III&IV, the resultant

circuit is shown in the Fig. 3.6(a).

During the transition from Mode I to II, immediately after S5 is turned OFF and S6

is ON, the voltage vAN = +VPV and vBN = 0V . So, the diode D2 is reverse biased. The

inductor current free-wheels through the junction capacitance of the switches S2, S3, S4,

S5, S6. During this time, the capacitors C3, C2 discharges and C4 charges through C5 and

24

Page 37: Bhaskar

C6. When the voltages vAN = vBN , the diode D2 starts conducting

Figure 3.6: Resonant circuit for (a) Differential mode for vAN > vBN (b) Common modefor vAN = vBN

as in Fig. 3.6(b). By applying Kirchoff’s current law at nodes A and B,

ig = i2 + i3 + i5 + i6

ig = i2 + i4

i1 = i2 + i5 + i6

i4 = i3 + i5 + i6

(3.4)

From the equations, C5, C6, C3 are parallel to each other and by using charge conser-

vation theorem, the voltages vAN and vBN are found out to be by

vAN = vBN =C3 + C5 + C6

C3 + C4 + C5 + C6

VPV (3.5)

in mode I-II and,

vAN = vBN =C4 + C5 + C6

C3 + C4 + C5 + C6

VPV (3.6)

25

Page 38: Bhaskar

In mode III-IV

If all the capacitances assumed to be same, the common mode voltage(CMV) is given by,

vAN = vBN = vCM = +3VDC

4(3.7)

3.2.4 Improved transformer-less Inverter

From the Eq. 3.5, 3.6, the pole voltages are a relation of the junction capacitances of the

converter switches. To maintain the pole voltages and hence the common mode voltage

to +VPV

2,

vAN = vBN =C3 + C5 + C6

C3 + C4 + C5 + C6

VPV == +VPV

2(3.8)

and,

vAN = vBN =C4 + C5 + C6

C3 + C4 + C5 + C6

VPV = +VPV

2(3.9)

Figure 3.7: Circuit for Improved oH5 Inverter topology

The necessary and sufficient conditions to be met are given by

C3 = C4 + C5 + C6

C4 = C3 + C5 + C6

(3.10)

From Eq. 3.10, it is noted that, S3, S4 requires additional capacitors across collector-

emitter to satisfy the below equations:

C3 >> C5 + C6

C4 >> C5 + C6

(3.11)

26

Page 39: Bhaskar

The typical value of the capacitance C3 and C4 are ten times that of the C5 and C6. The

same analysis is applied for H5 inverter [15], [26], the common mode voltage is +23VDC if

all the switches are dissimilar (C6 = 0F ), then

vAN = vBN = vCM =C3 + C5

C3 + C4 + C5

VPV (3.12)

also,

vAN = vBN = vCM =C4 + C5

C3 + C4 + C5

VPV (3.13)

To maintain the CMV at +VPV

2,

C3, C4 >> C5 (3.14)

Selection of Transformer-less Inverter

One of the most important factor considered for validating the effectiveness is the circuit

symmetry. For example, all the derived full-bridge topologies have symmetrical inductor

configuration. Similarly, the symmetry of the circuit is evaluated on the basis of their

resonant circuit. As soon as the converter is forced to free-wheeling mode, the inverter

pole voltages vAN and vBN are a measure of CMV. These voltages are estimated using the

theory discussed in the previous section. Considering the topologies - H5, oH5, HERIC,

the resonant circuits along with their resonant frequency are shown in the Table. 3.1.

The symmetry of the circuit is decided by the charging and discharging process of

all the junction capacitance os switches. For a circuit to be symmetric, it requires equal

charging and discharging of both the switches C3 and C4. Also, once the circuit reaches

steady state (in a PWM half-cycle), the inverter pole-voltages settles to +VDC

2.

By evaluating the resonant frequencies for all the topologies and from the Fig. 3.8,

HERIC topology offers has the highest resonant frequency at fs, rest follows as

fs << fHERIC > fH5 > foH5 (3.15)

ZHERIC > ZH5 > ZoH5 (3.16)

From the above relations, the voltage oscillations are more in the HERIC topology

which is a symmetric circuit. Hence, leakage current is still present in the system. To

avoid this, a clamping branch is suggested in the literature.

27

Page 40: Bhaskar

Table 3.1: The Equivalent Resonant circuits with their resonant frequency

Topology Resonant Circuit vAN = vBN = vCM Ceq fr

H5 23Vdc 3C//eCPV ≈ 3C 1

π

√1

6LC

HERIC 12Vdc

12C//eCPV ≈ C 1

π

√1

2LC

oH5 34Vdc 4C//eCPV ≈ 4C 1

π

√1

8LC

Figure 3.8: Impedance(Z) vs Frequency (f) plot for H5, oH5, HERIC Inverters

3.2.5 Simulation Results

While simulating the inverter, all the switches are assumed to be same with junction

capacitance of 29 pF, device part no.IKW15N120H3. Additional capacitors (Ce = 330pF )

are used to validate the improved topology. Table. 3.2 gives the data used while performing

the simulation study.

Fig. 3.9 shows the simulated waveforms for H5 topology. Here, the voltages vAN and

vBN have switching oscillations while transitioning from powering to free-wheeling mode.

28

Page 41: Bhaskar

Table 3.2: Simulation Parameters

Rated Power 1kW

Input Voltage 380V

Grid voltage/ frequency 230V/50Hz

Switching Frequency 20kHz

Filter Inductor L1 & L2 3mH

Filter Capacitor Cf 2µF

PV Stray Capacitance, CPV 0.1µF

Extra Capacitor, Ce 330pF

IGBT, Cj 29pF (IKW15N120H3)

Figure 3.9: Simulated waveforms for H5 topology: Zoomed view of vAN and vBN

Figure 3.10: Simulated waveforms for improved H5 topology: Zoomed view of vAN andvBN

For every transition, there appears a spike followed by oscillations. Since this topology is

not a NPC based configuration, the oscillations die out at a very slow rate. Hence very

29

Page 42: Bhaskar

(a)

(b)

Figure 3.11: Simulated waveforms for oH5 topology (a) Variations in CMV along withvAN , vBN and (b) Waveforms for vAB, vg, 20× ig and iCM

high oscillations (∼ 220V ) appear in the CMV (Fig. 3.9) inducing very high leakage

current (>50 mA). When additional capacitors are connected across the switches S3 and

S4 are connected, the voltage oscillations are damped out (< 20V ).

As the free-wheeling period reduces, the voltage spikes increases, thus increasing the

leakage current at the zero-crossings of the grid reference.NPC based topologies are best

suited for this purpose. They clamp-out the pole-voltages to VPV

2by absorbing peaky

currents. If the dead time is to be provided, circuit parasitics forces a variable CMV

characteristics (oH5 Inverter) as shown in Fig. 3.11

3.3 Summary

In this chapter, some of the popular transformer-less topologies are investigated. The

effect of switch parasitics is analyzed during dead time. Based on the analysis, a simple

30

Page 43: Bhaskar

(a)

(b)

Figure 3.12: Simulated waveforms for Improved oH5 topology (a) Variations in CMValong with vAN , vBN and (b) Waveforms for vAB, vg, 20× ig and iCM

modification is suggested. Size and the efficiency are least effected. Various simulation

studies are performed to validate the theory discussed. Certain assumptions are made

studying the system. Fluctuations in input power is neglected whose variation contributes

to the leakage current.

31

Page 44: Bhaskar

Chapter 4

Hardware Implementation

4.1 Introduction

The hardware results implying the effects in all the presented topologies are shown and

the results for the improved NPC inverter are produced. Also, efficiency calculations are

done for all the four topologies and compared with the improved inverter.

4.2 Hardware Setup

A 1 kW hardware setup is designed and developed for a transformer-less grid connected

PV system. Fig. 4.1 shows a generalized layout [9] to validate four topologies namely:

Figure 4.1: Circuit layout for experimentation

32

Page 45: Bhaskar

• H5 Topology

• HERIC Topology

• oH5(Optimized H5) Topology

• Improved oH5 topology

Figure 4.2: 1 KW Hardware Setup for a transformer-less system 1) Programmable DCsupply, 2) DC link capacitors, 3) Generalized Power PCB, 4) Sensing board, 5) Drivercircuit, 6) Regulated DC power supplies, 7) Filter inductors, 8) Auto-transformer (grid),9) Controller : TMS320F28335, 10) Level shifter(Buffer circuit with pull-up resistor)

4.2.1 Selection of DC link Capacitor

The sizing of the DC link capacitor is estimated by neglecting the switching and conduc-

tion losses initially. Later, it is extended for non ideal case. In such case, using energy

balance balance equations for a grid connected system,

pac = vg.ig

= 2VgIg sin2(ωt+ ψ)

= Po + Po cos(2ωt) (4.1)

The ripple power varying at 2ω is provided by the DC side capacitor. Considering the

DC link voltage to be constant with some ripple (∼ 2%), the ripple power handled by the

33

Page 46: Bhaskar

DC link capacitor is

Pdc(t) = vc(t).ic(t) (4.2)

vc(t) = Vdc + vr (4.3)

Assuming unity power factor operation on the grid side, i.e., both vg and ig are in

phase,

vgig =VgIg

2− VgIg

2cos(2ωt)

= Po − Po cos(2ωt) (4.4)

If the DC link voltage is ripple free,

ic(t) =PoVdc

cos(2ωt)

= Cdcdvrdt

(4.5)

vr(t) = Vr sin(2ωt) (4.6)

From Eq. 4.3,4.4 and 4.5, Cdc is expressed as

Cdc =Po

2ωVdc∆vr(4.7)

The parameters considered are Po = 1kW , Vdc = 380V , ω = 100π radians, vr = 76V ,

the value of DC link capacitor is found out to be Cdc = 551µF .

4.2.2 Design of output Filter

The cut-off frequency (fc) of the output filter is 110th of switching frequency fsw (20kHz)

i.e., 2kHz. For unipolar output of the inverter, the value of filter inductor is calculated

by the following relation,

Lf = L1 + L2 =VDC

8∆iLfmaxfsw(4.8)

For, the ripple in the inductor current be 10% which is in acceptable range with a rated

power of 1kW , the value of Lf is evaluated to be 5.4 mH and the filter capacitor is found

34

Page 47: Bhaskar

out by the following relation of cut-off frequency.

fcut−off =1

2π√

(L1 + L2)Cf(4.9)

Thus, Lf is selected in order to limit the current ripple and Cf to absorb high frequency

ripple. Therefore, Lf = 6mH, Cf = 2µF .

4.2.3 Sensing Circuit

To perform closed loop operation (grid current control), some parameters are sensed and

fed back to the system control loop. In order to read the parameters, current and voltage

sensors are employed followed by stepping down the variables with in the readable range.

Isolation is provided using IC ISO122P between the high and low power circuits.

Voltage sensing

The voltage (both AC and DC) ranges from (0-400)V. To step-down the signal, a simple

op-amp based resistor divider is used which also provides isolated ground. For AC volt-

ages, since the DSP cannot take negative values, a small offset (1.5V) is provided at the

output of the ISO122P by adjusting the output of LM317 using resistors.

Current sensing

For current sensing, LEM based hall effect sensors (LA 55-P) are used for both AC and

DC quantities. Only AC current sensing is required for the experiment, hence, off-set of

1.5 V is provided.

4.2.4 Level Shifting Stage/ Buffer Circuit

The input voltage necessary to trigger the gate driver is 5V (SKHI 22BR). The con-

troller output varies from (0-3.3V). So, to increase the fan-out capability (to avoid load-

ing the input from output) and avoid having floating potential at the driver input pins,

Hex buffers (DM7417) with high output voltage (3-15V) along with a CMOS OR gate

(HEF4071 BP) is used.

35

Page 48: Bhaskar

4.2.5 Driver Circuit

To drive the power switches at 20kHz (IGBT, MOSFET), sufficient driving current (iGE)

is required. Here comes the application of gate drivers. SEMIKRON gate-drivers

(SKHI 22BR) with maximum operating frequency of 50kHz and a driving current of

8mA (peak) are used in this implementation. No blank time (dead-time) is provided as

a software delay of 0.8µs is provided between the complementary switches of an inverter

leg.

4.2.6 Measurement of leakage current

In Fig. 4.1, two measuring points are identified, represented by m1 and m2. The measuring

point m1 requires one current sensor where as, the point m2 requires two sensors along

with an extra computation. Thus, m1 is preferred over the m2. Also, the measurement

of current requires current sensor with a very high resolution. In this experiment, a

high precision resistor (1Ω/1 W ) is used to measure the voltage drop across it which is

numerically equal to the leakage current.

4.3 Control Strategy

In grid connected PV systems, the grid current is in direct relation with the power avail-

able on the input side of PWM DC/AC converter. The control of power is achieved by

controlling the current. This current reference is generated by the power available at the

input side or by regulating the DC link voltage. Following are the essential components

of the control scheme:

• Grid Synchronization

• Current Controller

4.3.1 Grid Synchronization

Grid synchronization is essential in single-phase photovoltaic systems. If a phase or mag-

nitude jump occurs at the PCC (point of common coupling), the system should respond

towards the disturbance created in a very less time. Hence, there should be a robust

mechanism to generate reference signals to drive the inverter during the disturbances/

faults. There are a number os synchronization methods employing mathematical com-

putation (Frequency locked loop through Fourier analysis) and PLL-based methods [42].

36

Page 49: Bhaskar

Adaptive PLLs are implemented the most and became popular with time. A simple PLL

block diagram is shown in the Fig. 4.3 consisting of a phase multiplier (PD), a low pass

filter (LF) and a voltage controlled oscillator (VCO). The PLL is a second order system

with a first order filter.

Figure 4.3: Simple Block diagram of phase locked loop (PLL)

The transfer function for the system is given by

θo(s)

θi(s)=

K1K2Kps+K1K2Ki

s2 +K1K2Kps+K1K2Ki

(4.10)

where,

Kp +Ki/s is the transfer function of loop filter

K1, K2 are the constants of phase detector (PD) and the voltage controlled oscillator

(VCO)

ζ and ωn is the damping ratio and undamped natural frequency of the system.

ζ =1

2

Kp√Ki

; ωn =√Ki (4.11)

And the settling time (K1 = K2 = 1) is given by,

ts =4.6

ζωn(4.12)

The PLLs are distinguished based on their characteristics of phase detector. Also, some

adaptive PLLs are proposed in the literature out of which only two of them Second

order generalized integrator based phase locked loop (SOGI-PLL) and Enhanced phase

locked-loop (E-PLL) are implemented the most. This project deals with the control of

instantaneous active current/ power, thus EPLL which requires less memory and responds

quickly is chosen to implement the hardware.

37

Page 50: Bhaskar

Enhanced Phase Locked Loop (E-PLL)

Enhanced PLL is an adaptive algorithm based filter which can track both the phase and

amplitude of the input signal. In the Fig. 2.3 shown below, the steepest descent algorithm

is used in F (.) to reduce the error signal [37]- [39]. Hence it is a function of both amplitude

and phase of the signal expressed as,

Bm(Vm, θ) =1

2e2 =

1

2(vi − vi)2 (4.13)

where Vm is the estimated value and is found out by a number of iterations such that,

Vm(k + 1) = Vm(k) + ∆Vm (4.14)

Here, k is the iteration number and ∆Vm is step change in the estimated value. The single

weighted adaptive filter whose objective function from Eq. 4.13 is optimized using LMS

(Least mean square approximation) whose final relations are as follows:

∆Vm = −µ∂Bm

∂Vm

= − ∂

∂Vm

(−1

2µe2)

= µe(k) sin( ˆθ(k)) (4.15)

From Eq. 4.14,4.15, the magnitude of the actual voltage vi is calculated to be

Vm =µe

Tssin(θ) (4.16)

Figure 4.4: Phase detector of enhanced phase locked loop (EPLL)

38

Page 51: Bhaskar

and if all the equations are linearized, the ratio VmVm

is expressed as

VmVm

=1

1 + sτ(4.17)

where, τ = 2ka

is the time constant,

4τ = 8ka

is the settling time, ts

The Fig. 4.4 illustrates the adaptive structure of phase multiplier(PD) of the enhanced

PLL with optimized adaptive filter. Here, ’µ’ decides the stability of the system, speed of

convergence and also the residual error of overall adaptive process [40], [38].

For optimum response in terms of rate of convergence, stability and error reduction

following values are chosen for implementation. ka = 100, Kp = 1.7, ki = 120 [?]

4.3.2 Current Controller

The control of power is achieved through an inner current loop controlling and an outer

voltage loop. The reference current i∗ref is generated through the voltage control. Various

current control techniques are used to inject the power such as

• Hysteresis control where in the generated current is directly compared to the ref-

erence and the switches are operated in such a way that the current is forced to

operate with in a band. This has inherent short circuit capability but the switching

frequency continuously varies with the reference. Thus, designing a filter is very

difficult.

• Adaptive-hysteresis control where the ripple is varied to maintain constant operating

frequency. But, the need for more sensing is a major drawback for this technique.

• 1 − φ d-q control where in a pseudo quadrature signal is generated using the PLL

and then transformed into synchronous frame. The error is forced to zero (ideally)

with the help of PI regulators which shape the modulating signal. This method

provides with control over both active and reactive power. This requires a lot of

computation which burdens the processor. But the need for compensation added

complexity in practical implementation.

• Proportional and Resonant controller is another way of tracking the reference signal

without any transformations. This control is capable of tracking a fastly moving

signal. The implementation for various compensations is practically simple.

39

Page 52: Bhaskar

Proportional and Resonant controller

The proportional Integral controllers suffers from limited band-width characteristics. How-

ever, a very high bandwidth is required to reduce the error for high frequency signals. Con-

ventional PI regulators are used to track constant (DC) signals [44], [45]. A small phase

shift and a non-zero error at steady state is present while tracking the higher frequency

signals.

The power electronic converters whose ratings lie in the range of kV A limits the

selection of switching frequency or the sampling rate of the controller. Thus, producing

high bandwidth requires very small sampling time. Additionally, ADCs with very high

sampling rate are required which will increase the effort and the system costs. This P+R

controller provides a very high gain (ideally infinite) at its resonant frequency and rest

all components are forced to zero. This P+R controller is derived by transforming the PI

transfer function from rotating frame to stationary reference frame.

The transfer function for proportional resonant controller is given by,

Gcos(s) = Kp +2Kiωos

s2 + ω2o

Gsin(s) = Kp +2Kiωos2 + ω2

o

(4.18)

where, Ki is the coefficient of resonant term and Kp is the proportional gain, ωo is the

resonant frequency of the controller. Gcos(s) is always preferred as it offers better gain

margin which in turn improves the stability. If the error signal consists of several har-

monics, transforming each and every component to a DC quantity and forcing them to

zero involves a lot of computation. Instead transforming them to stationary frame forces

the error to zero [43]. And the non ideal integrator Ki

1+ sωc

when transformed to stationary

frame is given by:

Gc(s) =2Kiωcs

s2 + 2ωcs+ (ω2c + ω2

o)

=2Kiωcs

s2 + 2ωcs+ ω2o

(4.19)

Ideal PR provides infinite gain at the resonant frequency which makes it practically

impossible to implement it on the chip. Owing to the processor limitations, ωc is chosen

in the range of (5− 15) rad/s. Also, ωc effects the dynamic response. Kp is tuned similar

40

Page 53: Bhaskar

to that of a PI regulator which effects the phase margin, transient response and stability

of the closed loop control system. Ki provides a very high gain at resonant frequency and

does not effect on the system dynamic response. Along with the single frequency tuning,

other lower order harmonics are compensated by cascading the PR transfer functions at

selective harmonic frequencies.

Figure 4.5: Frequency response of an Ideal P+R controller with compensation

Gh(s) =∑

h=3,5,7..

2Kihs

s2 + (hωo)2(4.20)

Gh(s) =∑

h=3,5,7..

2Kihωcs

s2 + 2ωcs+ (hωo)2(4.21)

The parameters for harmonic compensator Kih do not influence the response of the

PR controller at fundamental frequency. Proper compensation requires tuning of HC

(Harmonic Compensator) coefficients [35]. The PR + Harmonic compensator responses

are shown in Fig. 4.5 where compensation is performed for 3rd, 5th and 7th harmonics.

4.3.3 Block Diagram of the Control Scheme

The main aim of the control scheme is to generate switching pulse pattern for the grid

connected transformer-less inverter. Fig. 4.6 shows the block diagram of the control

scheme used for the power processing [34].The phase information is extracted through

the enhanced PLL (EPLL) and the current reference is set depending on the input power

available.

The inverter output current is compared with the reference and the error signal is

processed by the PR controller. A feed forward term vg = Vm sin(ωot) is added to the

obtained value of the PR +harmonic controller. The resultant output is the duty ratio

41

Page 54: Bhaskar

Figure 4.6: Closed loop current control scheme for a single phase PV based grid-tiedinverter

(modulation signal) for the inverter switches. The feed forward term is used to improve the

starting condition/response of the system and used for disturbance rejection. Though feed

control has its own advantages, it makes the control loop unstable due to its anticipation.

4.4 Hardware Results

A 1kW laboratory prototype is developed to test all the three inverter topologies - H5,

HERIC, optimized H5 (see Fig. 4.2)and the improved NPCTLI for their common mode

characteristics, i.e., CMV and leakage current. Component specifications for the power

circuit are shown in Table 4.1. A programmable DC source and a lumped capacitor of

0.1µF are used to imitate a PV source and its parasitic capacitance. A 32-bit floating

point processor (TMS320F28335) is used to implement the control. Various results corre-

sponding to the common mode voltage (CMV) - vAN , vBN , iCM along with vAB and the

grid current ig and voltage vg are collected to validate the simulation results. Later on,

device losses are calculated to compare the efficiencies of all the four topologies.

Table 4.1: Hardware Specifications

PARAMETER RATINGPower 1 kW

Input Voltage (360− 700) VGrid voltage/ frequency 230 V /50 HzSwitching frequency (fs) 20 kHzFilter Inductor L1 & L2 3 mH

Filter Capacitor Cf 2 µFPower IGBT IKW15N120H3

DC link capacitor, CDC1 & CDC2 2200 µFPV Stray Capacitor, CPV 0.1 µFAdditional Capacitor, Ce 330pF

IGBT, Cj 29pF (IKW15N120H3)

42

Page 55: Bhaskar

4.4.1 H5 Topology

In this inverter configuration, the common mode voltage varies from +VPV

2in powering

mode to +2VPV

3in the free-wheeling mode. This is due to the fact that the circuit is

asymmetric. The chances of the failure of S5 due to the uneven thermal distribution.

Moreover the maximum leakage current is very high (< 50 mA) due to fast variation in

CMV. From Fig. 4.8, it is evident that in powering mode (vg > 0), vAN falls from 380V

(+VPV ) to 260 V (+2VPV

3). Before settling to 260 V, it performs oscillations due to the

resonant circuit formed by line inductors (L1, L2), CPV and switch capacitances (C3, C4,

C5) and eCPV .

Figure 4.7: Differential and Common-mode characteristics of H5 topology, vAN(200V/div),vBN(200V/div), vCM , vg (200V/div), ig (5A/div)

Later, the voltage settles to VPV

2due to the damping provided by the track resistance.

Hence, from the Fig. 4.9, it can be seen that the leakage current exceeding the peak

value of 50 mA and violates the V DE 126 − 1 − 1 standard limitations. Fig. 4.7 shows

the variation of inverter pole voltages (vAN , vBN), CMV , vg and ig respectively. Fourier

analysis for the leakage current is carried out and the value of iCM is found out to be 7.1

mA at 20 kHz(see Fig. 4.10).

4.4.2 Highly Efficient and Reliable Inverter concept (HERIC)

This topology has a very low switch count after H5 by SMA. Unlike H5 inverter, this

topology is symmetric(equal charging and discharging of C3 and C4). The thermal distri-

43

Page 56: Bhaskar

Figure 4.8: H5: Zoomed view of vAN(200V/div), vBN(200V/div) showing the oscillationsduring the free-wheeling period

Figure 4.9: H5: Inverter output voltage, vAB (200V/div), and the leakage current iCM(100 mA/div)

bution is even.

Though the inverter is symmetric, due to the lack of any clamping circuit, CMV per-

forms certain oscillations before attaining +VPV

2i.e. 190 V. Fig. 4.11 shows the differential

and common mode voltages vAB and vCM with grid voltage (vg) and current(ig). As

the grid voltage approaches to 0V, the powering period is very less. This results in very

high rise in the inverter pole voltages and hence CMV. This induces spikes in the leakage

44

Page 57: Bhaskar

Figure 4.10: H5: FFT analysis of the leakage current, FFT(iCM), 1mA/div

Figure 4.11: HERIC: Inverter pole voltages, vAN & vBN (200 V/div) CMV, vg(200V/div),ig(5A/div)

current.

In Fig. 4.12, the variation of pole voltages and the CMV are illustrated. Every tran-

sition gives rise to 60V spike in the CMV. Due to this high frequency spike, significant

leakage current flows through the PV stray capacitance. Fig. 4.13 shows the leakage cur-

rent and Fig. 4.14 shows the FFT analysis of iCM , whose value is ' 6.5 mA at fs = 20

kHZ.

4.4.3 Optimized H5 Inverter

To avoid the short circuit of DC link capacitance CDC1 during the switching of S5, S6,

a small dead time (0.8 µs) is provided between the successive switchings. Due to this,

45

Page 58: Bhaskar

Figure 4.12: HERIC Inverter: Oscillations performed by the pole voltages during thetransitions

Figure 4.13: HERIC Inverter: Differential voltagevAB(200V/div),leakage current,iCM(50mA/div), Grid voltage, vg(200V/div), grid current, ig(5A/div)

the control over the CMV through the clamping branch is lost. Fig. 4.15 illustrates the

inverter pole voltages, the CMV along with the grid voltage and current.

The neutral point ’O’ is maintained at +VDC

2by using a simple resistive divider circuit.

No active voltage balancing is used to maintain the mid-point voltage. Fig. 4.16 shows the

common mode characteristics in a zoomed manner. In the same way, the FFT analysis

for the leakage current is done shown in Fig. 4.18 where, the iCM is 5.4mA at 20 kHz.

46

Page 59: Bhaskar

Figure 4.14: HERIC: FFT Analysis for the leakage current of (iCM = 1mA/div)

Figure 4.15: oH5 Inverter: Pole voltages, vAN & vBN (200 V/div) CMV, vg(200V/div),ig(5A/div)

4.4.4 Improved NPC Transformer-less Inverter

An improved NPC based transformer-less inverter is designed by connecting two capac-

itors of 330 pF each across switches S3 and S4. The resulting waveforms are shown in

Fig. 4.19,19,20. The rise in the voltage is 100V before the modification, where as the

voltage variation' 20V . But, the peaky current which is absorbed by the additional

capacitors induce losses into the system.

Losses due to Additional Capacitors

Connecting additional capacitors effects the efficiency of the converter. The stored en-

ergy of the capacitors in the active(free-wheeling) period is dissipated(transferred) and

considered as switching losses. The losses are evaluated as follows,

47

Page 60: Bhaskar

Figure 4.16: oH5 Inverter: Zoomed waveforms of Variations in CMV along with vAN ,vBN

Figure 4.17: oH5 Inverter: Differential voltagevAB(200V/div),leakage current,iCM(50mA/div), Grid voltage, vg(200V/div), grid current, ig(5A/div)

Pe =1

2CeV

2e fs (4.22)

=1

2(330× 10−12 × 3802 × 20× 103)W

= 0.476W (4.23)

48

Page 61: Bhaskar

Figure 4.18: oH5 InverterFFT analysis of the leakage current iCM , 1 mA/div

Figure 4.19: Improved NPCTLI: Pole voltages, vAN & vBN (200 V/div) CMV,vg(200V/div), ig(5A/div)

The total loss in two capacitors is 0.953 W (2×Pe) which accounts for 0.09% of the rated

power.

4.5 Efficiency Analysis

To estimate the efficiency of a converter, various losses due to the components are esti-

mated. The average duty ratio of the switches/ diodes are calculated by the following

relations:

dIGBT = M sin(ωt) ; ddiode = M(1− sin(ωt)) (4.24)

49

Page 62: Bhaskar

Figure 4.20: Improved NPCTLI: Voltage distribution across the DC link capacitors,CDC1, CDC2, VON (200v/div)

Figure 4.21: Improved NPCTLI: FFT analysis of the leakage current iCM , 1 mA/div

where, M is the operating modulation index

50

Page 63: Bhaskar

Figure 4.22: Improved NPCTLI: FFT analysis of the leakage current iCM , 1 mA/div

Conduction Losses

The average conduction loss in an IGBT operating at switching frequency is given by [20]

[13],

PIGBT (fs) =1

2π∫0

i(t)vsw(t)dIGBT (t)d(ωt)

=M

4IMVt +

2M

3πI2MRce (4.25)

where, vsw(t) = Vt + i(t)Rce, Vt is the voltage drop when the current through the IGBT

is zero [24] and Rce is the on state resistance of the device. Also, IM is the peak induc-

tor current. Similarly, the diode conduction loss at switching frequency is given by the

relation,

Pdiode(fs) =1

2π∫0

i(t)vdiode(t)ddiode(t)d(ωt)

= IMVf

(1

π− M

4

)+ I2MRak

(1

4− 2M

)(4.26)

where, vdiode(t) = Vf + i(t)Rak, Vf is the voltage when current through it is zero, and Rak

is the ON drop resistance. Also, the conduction loss in IGBT operating at line frequency

51

Page 64: Bhaskar

is given by,

PIGBT (50Hz) =1

2π∫0

i(t)vsw(t)d(ωt)

=IMVtπ

+1

4I2MRce (4.27)

and diode conduction losses,

Pdiode(50Hz) =1

2π∫0

i(t)vdiode(t)d(ωt)

= I2MRak

(1

4− 2M

)(4.28)

Diode recovery losses

During the turn of switches (IGBTs), the energy is induced into the diode and this can

be calculated [13] as,

Prr =1

∫ π

0

(0.5VPV )(0.5Irr)fstbd(ωt)

= 0.125VPV Irrfstb (4.29)

where, fs is the operating frequency of the power switch, Irr is the reverse recovery current

in the diode and VPV is the input voltage.

Switching losses

The switching losses during the transition from ON to OFF for diode and the IGBT is

given in [25],

PIGBT−on =Vce (IM + Irr) (tr + ta)

2+VceIM tb

2+VceIrrtb

3(4.30)

Pdiode−off =Vf (IM + Irr) (tr + ta)

2+

(vdiode + Vf )Irrtb6

(4.31)

PIGBT−off =VceIM td

2+

11VceIM tf20

+VceIM ttail

20(4.32)

Pdiode−on =9VfIM tf

20+

19VfIM ttail20

(4.33)

Vce, tr, tf are the voltage across each IGBT, rise time, fall time. ta and tb are the recovery

times and ttail is the time taken for the tail current to go to zero. The total switching

52

Page 65: Bhaskar

losses is given by:

Psw = (PIGBT−on + Pdiode−off ) + (PIGBT−off + Pdiode−on) (4.34)

also,

Psw = (Eon + Eoff ) fs (4.35)

Eon and Eoff are the losses in energy in the switch at a particular operating point.

These vary w.r.t the operating voltage and maximum current. The second method from

Eq. 4.35 is used to calculate the switching losses and note that this equation is an ap-

proximate relation, which do not consider the diode ON losses.

Power loss in line inductors

The power loss in the line frequency inductors is due to their equivalent series resistance

(ESRL). Loss due to (ESRL) is calculated by the following expression:

Pesr =1

π

π∫0

i2(t)ESRLd(ωt)

=1

2I2MESRL (4.36)

Table 4.2: Device specifications and losses at rated power

PARAMETERS (IKW15N120H3) VALUESVt(V) 0.8Rce(Ω) 14 m

PIGBT (50Hz),W 2.29Pdiode(50Hz),W 0.13PIGBT (fs),W 1.45Pdiode(fs),W 1.04

Prr,W 0.31Psw,W 8.35

Ptotal(fs),W 11.15PL1&L2(fs),W 2.18

European Efficiency

Table. 4.2 illustrates each device loss using the above discussed expressions at a rated

output power of 1 kW .The inverters do not operate at their peak efficiencies all the time.

53

Page 66: Bhaskar

Efficiencies which are a function of power output, are averaged together to evaluate the

European efficiency. This is evaluated by assigning a fixed time(weights) for which the

inverter is operated at that power level. Mathematically,

ηeuro = 0.04η10% + 0.05η20% + 0.12η30% + 0.21η50% + 0.53η75% + 0.05η100% (4.37)

The ηeuro for the improved transformerless inverter is found out to be 96.9% and a peak

efficiency of 97.2%.

In Fig. 4.23, efficiency of all the four topologies are plotted against the output power

(Prated = 1 kW ). It is also observed that, though the HERIC topology has the highest

efficiency, its leakage current characteristics are worse. And H5 topology is better in terms

of leakage current but has low efficiency. The improved NPCTLI has very good leakage

current characteristics and high efficiency.

Figure 4.23: Efficiency comparison for H5, HERIC, oH5 and Improved NPCTLI

4.6 Summary

A 1 kW hardware setup is designed and developed for a transformer-less grid connected

PV system. The hardware results implying the effects in all the presented topologies

are shown and the results for the improved NPC inverter are produced which are in

agreement with the simulation results. Finally efficiency calculations are done for all the

four topologies and compared with the improved inverter.

54

Page 67: Bhaskar

Chapter 5

Conclusion

Based on the literature survey, classification of various transformer-less inverters is car-

ried out. Merits and demerits of some of the existing topologies are demonstrated through

simulations. Various non ideal factors effecting the leakage current are mentioned in this

report. Parameters like junction capacitance of the switches during the circuit dead time

are analyzed to study their effect on leakage current. For this study, some of the very

popular inverters are chosen and the root cause (solution) is found out. An improved neu-

tral point clamped transformer-less topology is developed. The effects are demonstrated

using thorough simulation studies. A 1 kW generalized hardware prototype is designed to

validate four topologies - H5, oH5, HERIC and Improved NPCTLI. Finally, a comparison

is made on the basis on their common-mode characteristics and efficiency.

Future scope of work

After effects like the DC current injection, parallel operation of several transformer-less

inverters having same input source and having discrete input sources are not discussed in

this report. Further work can be initiated in this direction.

55

Page 68: Bhaskar

Chapter 6

Appendix

56

Page 69: Bhaskar

Bibliography

[1] R. Teodorescu, M. Liserre, “Grid connected converters for photovoltaic and wind

power systems”, John Wiley and Sons, UK, 2011.

[2] International Energy Agency (2008, Sep.), “Trends in photovoltaic applications:

Survey report of IEA countries between 1992 and 2008”, [Online]. Available:

http://www.iea-pvps.org/products/downloads/rep 1-18.pdf

[3] T. Kerekes, R. Teodorescu, P. Rodriguez, G. Vazquez, and E. Aldabas, “A new high-

efficiency single-phase transformerless PV inverter topology”, IEEE Trans. on Ind.

Electron., vol. 58, no. 1, pp. 184-191, Jan. 2011.

[4] M. Victor, F. Greizer, S. Bremicker, and U. Hubler, “Method of converting a direct

current voltage from a source of direct current voltage, more specifically from a

photovoltaic source of direct current voltage, into a alternating current voltage”, U.

S. Patent 7-411-802, Aug. 12, 2008.

[5] W. M. Blewitt, D. J. Atkinson, J. Kelly, R. A. Lakin, “Approach to low-cost preven-

tion of DC injection in transformerless grid connected inverters”, Power Electronics,

IET, vol. 3, no. 1, pp. 111-119, Jan. 2010.

[6] “Capacitive Leakage currents”, SMA Solar technology, Appl.note 7418, ver. 2.5, Al-

beitstrom.

[7] S.V. Araujo, P. Zacharias, R. Mallwitz, “Highly efficient single-phase transformerless

inverters for grid-connected photovoltaic systems”, IEEE Trans. Ind. Electron., vol.

57, no. 9, pp. 3118 - 3128, Sept. 2010.

[8] S. B. Kjaer, J. K. Pedersen, F. Blaabjerg, “A review of single-phase grid-connected

inverters for photovoltaic modules”, IEEE Trans. on Ind. Electron., vol. 41, no. 5,

pp. 1292 - 1306, Sep/Oct. 2005.

57

Page 70: Bhaskar

[9] E. Koutroulis, and, F. Blaabjerg, “Methodology for the optimal design of trans-

formerless grid-connected PV inverters”, IET, Power Electronics, vol. 5, no. 8, pp.

1491-1499, Sept. 2012.

[10] VDE-AR-N 4105: Power generation systems connected to the low-voltage distribu-

tion network - technical minimum requirements for the connection to and parallel

operation with low - voltage distribution networks, DIN-VDE Normo, 2011.

[11] J.M. Sosa, G. Escobar, M.P.R. Rodriguez, G. Vazquez, M.A. Juarez, and M. Dios-

dado, “Comparative evaluation of L and LCL filters in transformerless grid tied con-

verters for active power injection”, IEEE Int. Autumn Meeting on Power Electron.

and Computing (ROPEC), pp. 1-6, 2014.

[12] Y. Gu, W. Li, Z. Yi, B. Yang, C. Li, and X. He, “Tansformerless inverter with virtual

DC bus concept for cost-effective grid-connected PV power systems”, IEEE Trans.

on Power Electron., vol. 28, no. 2, pp. 793-805, Feb. 2013.

[13] W. Yu, J. Lai, H. Qian, and C. Hutchens, “High-Efficiency MOSFET inverter with

H6-type configuration for photovoltaic non-isolated AC-module applications”, IEEE

Trans. on Power Electron., vol. 26, no. 4, pp. 1253-1260, Apr. 2011.

[14] B. Yang, W. Li, Y. Gu, W. Cui, and X. He, “Improved transformerless inverter With

Common-Mode Leakage Current Elimination for a Photovoltaic grid-connected power

system”, IEEE Trans. on Power Electron., vol. 27, no. 2, pp. 752-762, Feb. 2012.

[15] T.K.S. Freddy, N.A. Rahim, W. Hew, and H. S. Che, “Comparison and analysis of

single-phase transformerless grid-connected PV inverters”, IEEE Trans. on Power

Electron., vol.29, no.10, pp.5358-5369, Oct. 2014.

[16] L. Zhang, K. Sun, Y. Xin, and M. Xing, “H6 transformerless full-bridge PV grid-tied

inverters”, IEEE Trans. on Power Electron., vol. 29, no. 3, pp. 1229-1238, Mar. 2014.

[17] F. Blaabjerg, K. Ma, and Y. Yang, “Power electronics - The key technology for

Renewable Energy Systems”, Ninth Int. Conf. Eco.l Vehicles and Ren. Energy, pp.

1-11, 2014.

[18] Y. Xue, L. Chang, S. B. Kjaer, J. Bordonau, and T. Shimizu, “Topologies of sin-

gle phase inverter for small power generators: An overview”, IEEE Trans. on Ind.

Electron., vol. 19, No. 6, pp. 1305 - 1314, Sept. 2004.

58

Page 71: Bhaskar

[19] R. Gonzalez, J. Lopez, P. Sanchis, and L. Marroyo, “Transformerless inverter for

single-phase photovoltaic systems”, IEEE Trans. on Power Electron., vol. 22, no. 2,

pp. 693-697, Mar. 2007.

[20] W. Yu, J. S. Lai, H. Qian, and C. Hutchens, “High-efficiency MOSFET inverter with

H6-type configuration for photovoltaic nonisolated AC-module applications”, IEEE

Trans. on Ind. Electron., vol. 26, no. 4, pp. 1253 - 1260, Apr. 2011.

[21] O. Lopez, F. D. Freijedo, A. G. Yepes, P. Fernandez - Comesana, J. Malvar, R.

Teodorescu, and J. Doval - Gandoy, “Eliminating ground current in a transformerless

photovoltaic applications”, IEEE Trans. Energy Convers., vol. 25, no. 1, pp. 140 -

147, Mar. 2010.

[22] H. Xiao and S. Xie, “Transformerless split-inductor neutal point clamped three-level

PV grid-connected inverter”, IEEE Trans. Power Electron., vol. 27, no. 4, pp. 1799 -

1808, Apr. 2012.

[23] R. Gonzalez, E. Gubia, J. Lopez, and L. Marroyo, “Transformerless single-phase

multilevel-based photovoltaic inverter”, IEEE Trans. Ind. Electron., vol. 55, no. 7,

pp. 2694 - 2702, Jul. 2008.

[24] B. Ji, J. Wang, and J. Zhao, “High-efficiency single-phase transformerless PV H6

inverter with hybrid modulation method”, IEEE Trans. on Ind. Electron., vol. 60,

no. 5, pp. 2104-2115, May 2013.

[25] H. Xiao, S. Xie, Y. Chen, and R. Huang, “An Optimized transformerless photovoltaic

grid-connected inverter”, IEEE Trans. on Ind. Electron., vol. 58, no. 5, pp. 1887-1895,

May 2011.

[26] J.R. Dreher, F. Marangoni, L. Schuch, M.L. da S Martins, and L.D. Flora, “Compar-

ison of H-bridge single-phase transformerless PV string inverters”, 10th IEEE/IAS

Int. Conf. on Ind. App. (INDUSCON), pp. 1-8, Nov. 2012.

[27] L. Zhang, K. Sun, L. Feng, H. Wu, and Y. Xing, “A family of neutral point

clamped full-bridge topologies for transformerless photovoltaic grid-tied inverters”,

IEEE Trans. on Power Electron., vol. 28, no. 2, pp. 730-739, Feb. 2013.

[28] B. N. Alajmi, K. H. Ahmed, G. P. Adam, and B. W. Williams, “Single phase single-

stage transformer less grid-connected system”, IEEE Trans. Power Electron., vol. 28,

no. 6, pp. 2664 - 2676, Jun. 2013.

59

Page 72: Bhaskar

[29] H. Schmidt, S. Christoph, and J. Ketterer, “Current inverter for direct/ alternating

currents, has direct and alternating connections with an intermediate power store, a

bridge circuit, rectifier diodes and a inductive choke”, DE Patent DE10221592 (A1),

Dec. 04, 2003.

[30] C. Anandababu, B. G. Fernandes, “A novel neutral point clamped transformerless in-

verter for grid-connected photovoltaic system”, Proc. IEEE 39th Ann. Ind. Electron.

Conf (IECON)., 2013, pp. 6962 - 6967.

[31] C. Anandababu, B. G. Fernandes, “Improved full-bridge neutral point clamped trans-

formerless inverter for photovoltaic grid-connected system”, in Proc. IEEE 39th

Annu. Ind. Electron. Conf (IECON)., 2013, pp. 7996 - 8001.

[32] H. Xiao, and S. Xie, “Leakage current analytical model and application in single-

phase transformerless photovoltaic grid-connected inverter”, IEEE Trans. on Elect.

Comp., vol. 52, no. 4, pp. 902-913, Nov. 2010.

[33] C. Winterhalter, R. Kerkman, D. Schlegel, and D. Leggate, “The effect of circuit

parasitic impedance on the performance of IGBTs in voltage source inverters”, Six-

teenth Annual IEEE Appl. Power Electron. Conf. and Exp., APEC, vol. 2, no. 2,

pp.995-1001, 2001

[34] F. Blaabjerg, R. Teodorescu, M.Liserre, and A.V. Timbus, “Overview of control and

grid synchronization for distributed power generation systems”, IEEE Trans. on Ind.

Electron., vol. 53, no. 5, pp. 1398-1409, Oct. 2006.

[35] Y. Yang, and F. Blaabjerg, “Synchronization in single-phase grid-connected photo-

voltaic systems under grid faults”, 3rd IEEE Int. Symp. on Power Electron. for Dist.

Gen. Systems (PEDG), vol. 1, no. 3, pp. 476-482, Jun. 2012.

[36] Y. Yang, F. Blaabjerg, and Z. Zou, “Benchmarking of gid fault modes in single-phase

grid-connected photovoltaic systems”, IEEE Trans. on Ind. Appl., vol. 49, no. 5, pp.

2167-2176, Oct. 2013.

[37] M.K. Ghartemani, S.A. Khajehoddin, P.K. Jain, and A. Bakhshai, “Problems of

startup and phase jumps in PLL systems”, IEEE Trans. on Power Electron., vol. 27,

no. 4, pp. 1830-1838, Apr. 2012.

60

Page 73: Bhaskar

[38] M.K. Ghartemani, and M.R. Iravani, “A method for synchronization of power elec-

tronic converters in polluted and variable-frequency environments”, IEEE Trans. on

Power Sys., vol. 19, no. 3, pp. 1263-1270, Aug. 2004.

[39] R.M.S. Filho, P.F. Seixas, P.C. Cortizo, L.A.B. Torres, and A.F. Souza, “Comparison

of three single-phase PLL algorithms for UPS applications”, IEEE Trans. on Ind.

Electron., vol. 55, no. 8, pp. 2923-2932, Aug. 2008.

[40] Paulo S. R. Diniz, “Adaptive filtering: algorithms and practical implementation”,

Springer, 2010.

[41] F.D. Freijedo, J. Doval-Gandoy, O. Lopez, and E. Acha, “Tuning of phase-locked

loops for power converters under distorted utility conditions”, IEEE Trans. on Ind.

Appl., vol. 45, no. 6, pp. 2039-2047, Dec. 2009.

[42] Y. Yang, F. Blaabjerg, H. Wang, “Low-Voltage Ride-Through of Single-Phase Trans-

formerless Photovoltaic Inverters”, IEEE Trans. Ind. Appl., vol. 50, no. 3, pp. 1942-

1952, May. 2014.

[43] F. Blaabjerg, R. Teodorescu, M.Liserre, and P.C. Loh, “Proportional-resonant con-

trollers and filters for grid-connected voltage-source converters”, IEE Proc. Elect.

Power Appl., vol. 153, no. 5, pp. 750-762, Sep. 2006.

[44] D.N. Zmood, D.G. Holmes, and G.H. Bode, “Frequency-domain analysis of three-

phase linear current regulators”, IEEE Trans on Ind. Appl., vol. 37, no. 2, pp. 601-

610, Mar. 2001.

[45] D.N. Zmood, and D.G. Holmes, “Stationary frame current regulation of PWM in-

verters with zero steady-state error”, IEEE Trans. on Power Electron., vol. 18, no.

3, pp. 814-822, May 2003.

61