Page 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations Best Pracce Guide 4 (Issue 4)

Upload: ledien

Post on 12-Feb-2018

227 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 1

Electrical installationcondition reporting:Classification Codes fordomestic and similarelectrical installations

Best Prac�ce Guide 4 (Issue 4)

Page 2: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

In electronic format, this Guide is intended to be made available free of charge to all interested par es. Further copies may be downloaded from the websites of some of the contribu ng organisa ons.

The version of this Guide on the Electrical Safety First website(www.electricalsafetyfi rst.org.uk) will always be the latest. Feedback on any of the Best Prac ce Guides is always welcome – emailbpg@electricalsafetyfi rst.org.uk

Electrical Safety First is supported by all sectors of the electrical industry, approvals and research bodies, consumer interest organisa ons, the electrical distribu on industry, professional ins tutes and ins tu ons, regulatory bodies, trade and industry associa ons and federa ons, trade unions, and local and central government.

*Electrical Safety First (formerly the Na onal Inspec on Council for Electrical Installa on Contrac ng) is a charitable non-profi t making organisa on set up in 1956 to protect users of electricity against the hazards of unsafe and unsound electrical installa ons.

Published by:

Electrical Safety FirstUnit 331Metal Box Factory30 Great Guildford StreetLondon SE1 0HS

Tel: 0203 463 5100

Email: bpg@electricalsafetyfi rst.org.uk

Website: www.electricalsafetyfi rst.org.uk

Electrical Safety First and other contributors believe that the guidance and informa on contained in this Best Prac ce Guide is correct, but all par es must rely on their own skill and judgement when making use of it. Neither Electrical Safety First nor any contributor assumes any liability to anyone for any loss or damage caused by any error or omission in this Guide, whether such error or omission is the result of negligence or any other cause. Where reference is made to legisla on, it is not to be considered as legal advice. Any and all such liability is disclaimed.

© Electrical Safety Council. May 2015

Best Practice GuideElectrical Safety First is indebted to the following organisa ons for their contribu on and/or support to the development of this Guide:

BEAMA www.beama.org.uk

Bri sh Gas www.bri shgas.co.uk

BSI Product Services www.bsigroup.com

Certsure www.certsure.com

City & Guilds www.cityandguilds.com

EAL

www.eal.org.uk

Ins tu on of Engineering and Technology

www.theiet.org

NAPIT

www.napit.org.uk

SPACES

www.thespaces.org.uk

SELECT

www.select.org.uk

Several of the photographs in this Guide have been extracted from a superseded Electrical Safety First DVD, courtesy of Navigator Produc ons Ltd. Others were kindly supplied by Nick Blakeley Electrical and Bradford Metropolitan District Council.

This is one of a series of Best Prac ce Guides produced by Electrical Safety First* in associa on with leading industry bodies for the benefi t of electrical contractors and installers, and their customers.

Page 3: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 3

1. Introduction

Every electrical installa on deteriorates with use and me. Therefore, if the safety of the users is not to be put at risk, it is important that every installa on is periodically inspected and tested by a competent person. Indeed, it is recommended in BS 7671: 2008 as amended that every electrical installa on is subjected to periodic inspec on and tes ng (Regula on 135.1 refers).

The inspec on and tes ng should be carried out at appropriate intervals in order to determine what, if anything, needs to be done to maintain the installa on in a safe and serviceable condi on. The results of the inspec on and tes ng need to be clearly detailed in a report. Any observed damage, deteriora on, defects, dangerous condi ons and non-compliances with the requirements of the current edi on of BS 7671 that may give rise to danger should be recorded and appropriately classifi ed for remedial ac on.

It should be borne in mind that, as stated in the introduc on to BS 7671, exis ng installa ons that have been constructed in accordance with earlier edi ons of the Standard may not comply with the current edi on in every respect, but this does not necessarily mean that they are unsafe for con nued use or require upgrading.

Electrical installation condition reporting: Classification Codes for domestic and similar electrical installationsThe aim of this Guide is to provide prac cal guidance for skilled persons competent in electrical inspec on and tes ng on the use of the Classifi ca on Codes that need to be a ributed to each observa on recorded during the periodic inspec on and tes ng of an electrical installa on for the benefi t of the person ordering the report.

The guidance is limited to the range of observa ons that are likely to be associated with domes c and similar electrical installa ons. It takes into account the publica on of Amendment 3 to BS 7671: 2008.

Inspec ng a socket-outlet

Page 4: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 4

An electrical installa on condi on report is, as its tle indicates, a report and not a cer fi cate. It provides an assessment of the in-service condi on of an electrical installa on against the requirements of the edi on of BS 7671 current at the me of the inspec on, irrespec ve of the age of the installa on.

The report is primarily for the benefi t of the person ordering the work and of persons subsequently involved in addi onal or remedial work, or further inspec ons. The report may be required for one or more of a variety of reasons, each of which may impose par cular requirements or limita ons on the inspec on and tes ng.

The report is required to include details of the extent of the installa on and of any limita ons of the inspec on and tes ng, including the reasons for any such limita ons and the name of the person with whom those limita ons were agreed. It should be noted that the greater the limita ons applying, the lesser is the scope of the inspec on and tes ng carried out, and hence the value of the report is correspondingly diminished. The report is also required to include a record of the inspec on and the results of tes ng.

The report provides a formal declara on that, within the agreed and stated limita ons, the details recorded, including the observa ons and recommenda ons, and the completed schedules of inspec on and test results, give an accurate assessment of the condi on of the electrical installa on at the me it was inspected.

A typical periodic inspec on no ce for an older installa on

Purpose of periodic inspection, testing and reporting

The main purpose of periodic inspec on and tes ng is to detect so far as is reasonably prac cable, and to report on, any factors impairing or likely to impair the safety of an electrical installa on.

The aspects to be covered include all of the following:

• Safety of persons against the eff ects of electric shock and burns

• Protec on against damage to property by fi re and heat arising from an installa on defect

• Confi rma on that the installa on is not damaged or deteriorated so as to impair safety

• Iden fi ca on of non-compliances with the current edi on of BS 7671, or installa on defects, which may give rise to danger.

Electrical installa ons in poor condi on present risks of fi re as well as electric shock

Page 5: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 5

The inspector

All persons carrying out the inspec on and tes ng of electrical installa ons must be competent todo so.

A con nuity test being carried out

To be competent to undertake the periodic inspec on and tes ng of an exis ng electrical installa on, persons must as a minimum:

• Have suffi cient knowledge and experience of electrical installa on ma ers to avoid injury to themselves and others

• Be familiar with, and understand, the requirements of the current edi on of BS 7671 including those rela ng to inspec on, tes ng and repor ng

• Be skilled in the safe applica on of the appropriate test instruments and procedures

• Have a sound knowledge of the par cular type of installa on to be inspected and tested

• Have suffi cient informa on about the func on and construc on of the installa on to allow them to proceed in safety.

If the inspector is competent and takes all the necessary safety precau ons including following the correct procedures, the process of inspec ng and tes ng should not create danger to persons, or cause damage to property.

Past events indicate that persons undertaking electrical installa on condi on repor ng need to have extensive knowledge and experience of electrical installa on ma ers to enable them to safely and accurately assess the condi on of an exis ng electrical installa on. This is especially so when they do not have access to the design or maintenance informa on rela ng to that installa on.

Guidance on safe isola on procedures is available in another Best Prac ce Guide (No 2 in the series) published by Electrical Safety First, which can be downloaded free of charge from www.electricalsafetyfi rst.org.uk and other contribu ng bodies.

Page 6: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 6

Periodic inspection and testing procedures

The procedures for periodic inspec on and tes ng diff er in some respects from those for the ini al verifi ca on of new installa on work. This is because the subject of an electrical installa on condi on report is usually an installa on which has been energised and in use for some me. Par cular a en on therefore needs to be given during the inspec on process to assessing the condi on of the installa on in respect of:

• Safety

• Wear and tear

• Corrosion

• Damage and deteriora on

• Excessive loading

• Age

• External infl uences

• Suitability (taking account of any changes in use or building extensions etc).

Inadequate provision of socket-outlets

Also, for reasons beyond the inspector’s control, the inspector may be unable to gain access to parts of the exis ng installa on. For example, it is usually imprac cable to inspect cables that have been concealed within the fabric of the building.

Such restric ons are likely to result in the inspec on and tes ng of those parts of the installa on being limited, or being omi ed en rely from the process.

Where, during the course of inspec on or tes ng, an immediate danger is found to be present in an installa on (from an accessible exposed live part, for example), immediate ac on will be necessary to make it safe before con nuing. However, the discovery of the dangerous condi on should s ll be recorded in the report and classifi ed accordingly.

Inspectors should note that, even in domes c premises, Sec on 3 of the Health and Safety at Work etc Act 1974 and the Electricity at Work Regula ons 1989 eff ec vely require them to endeavour to make safe, before leaving site and with the agreement of the user or owner, any dangerous condi ons found in an installa on. For example, where there are accessible live parts due to blanks missing from a consumer unit, suitable temporary barriers should be provided to protect persons from direct contact with those live parts.

As persons using the installa on are at risk, it is not suffi cient simply to draw a en on to the danger when submi ng the electrical installa on condi on report. At the very least, the inspector must ensure that the client is made aware, at the me of discovery, of the danger that exists. An

agreement should be made with the client as to the appropriate ac on to be taken to remove the source of danger (for example, by switching off and isola ng the aff ected part of the installa on un l remedied), before con nuing with the inspec on or tes ng. In some cases, this may prevent inspec on and tes ng work from con nuing.

Page 7: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 7

An immediately dangerous situa on - Line conductor connected to the metallic enclosure of a light fi ng and thermal damage suffi cient to permit access to live parts

Some cer fi ca on, registra on and membership bodies make available ‘dangerous condi on no fi ca on’ forms. These assist inspectors to record, and then to communicate immediately to the person responsible for the safety of the installa on, any dangerous condi on discovered.

Page 8: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 8

Observations

The periodic inspec on and tes ng procedures should iden fy any damage, deteriora on, defects and condi ons within the installa on that give rise, or poten ally give rise, to danger. The procedures should also iden fy any defi ciencies for which remedial ac on would contribute to a signifi cant improvement in the safety of the electrical installa on.

A er due considera on, each such observed safety issue should be recorded at the appropriate point in the inspec on or test results schedule, and further detailed in the ‘observa ons’ sec on of the report.

The observa ons should be based on the requirements of the edi on of BS 7671 current at the me of the inspec on, not on the requirements of an earlier edi on current at the me the installa on was constructed.

Each observa on should be wri en in a clear, accurate and concise manner that is likely to be understood by the person ordering the work. Technical terms should be avoided or explained unless it is known that the recipient is an electrical engineer or electrician, for example.

An electrical installa on condi on report is intended to be a factual report on the condi on of an installa on, not a proposal for remedial work. Therefore, each recorded observa on should describe a specifi c defect, omission or item for which improvement is recommended.

The observa on should detail what the situa on is, and not what is considered necessary to put it right. For example, ‘excessive damage to the consumer unit enclosure’ would be appropriate, whereas ‘consumer unit to be replaced’ would not.

Only observa ons that can be supported by one or more regula ons in the edi on of BS 7671 current at the me of the periodic inspec on should be recorded. The par cular regula on number(s) need not be entered in the report (unless specifi cally required by the client), but should serve to remind the inspector that it is only compliance with BS 7671 that is to be considered. Observa ons based solely on personal preference or ‘custom and prac ce’ should not be included.

Recessed luminaire above a bath (outside the zones)

Page 9: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 9

Classification Codes

Each observa on rela ng to a concern about the safety of the installa on should be a ributed an appropriate Classifi ca on Code selected from the standard codes C1, C2, C3 and FI. Each code has a par cular meaning:

Code C1 ‘Danger present’. Risk of injury. Immediate remedial ac on required.

Code C2 ‘Poten ally dangerous’. Urgent remedial ac on required

Code C3 ‘Improvement recommended’.

Code FI ‘Further inves ga on required’

Only one of the standard Classifi ca on Codes should be a ributed to each observa on. If more than one Classifi ca on Code could be a ributed to an observa on, only the most serious one should be used (Code C1 being the most serious).

Where the inspec on and tes ng procedures iden fy an item which is dangerous or poten ally dangerous, it should be iden fi ed in the inspec on or test results schedule of the report by a ribu ng to it a Classifi ca on Code C1 or C2, as appropriate, in the ‘outcome’ column of the inspec on schedule or, where provided, the ‘remarks’ column of the test schedule.

Where the inspec on and tes ng procedures iden fy an item which is not dangerous or poten ally dangerous, but for which improvement is recommended, it should be iden fi ed in the inspec on or test results schedule of the report by a ribu ng to it a Classifi ca on Code C3 in the ‘outcome’ column of the inspec on schedule or, where provided, the ‘remarks’ column of the test schedule.

Where during inspec on and tes ng an immediate danger is observed that puts the safety of those using the installa on at risk, Classifi ca on Code C1 (danger present) must be given.

Where a Classifi ca on Code C1 is considered appropriate, the client is to be advised immediately, and also in wri ng, that immediate remedial ac on is required (or has been taken) to remove the danger. As previously indicated, this ac on is necessary to sa sfy the du es imposed on the inspector and other duty holders by the Health and Safety at Work etc Act 1974 and the Electricity at Work Regula ons 1989.

Wherever an item in the inspec on or test results schedule has been a ributed a Classifi ca on Code C1, C2, C3 or FI, there should be a corresponding observa on in the ‘observa ons’ sec on of the report.

Live parts exposed to touch

Page 10: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 10

In general terms, the Classification Codes should be used as follows:

Code C1 (Danger present)

This code should be used to indicate that danger exists, requiring immediate remedial ac on.

The persons using the installa on are at immediate risk. The person ordering the report should be advised to take ac on without delay to remedy the observed defi ciency in the installa on, or to take other appropriate ac on (such as switching off and isola ng the aff ected parts of the installa on) to remove the danger. The inspector should not wait for the full report to be issued before giving this advice.

As previously indicated, some cer fi ca on, registra on and membership bodies make available ‘dangerous condi on no fi ca on’ forms to enable inspectors to record, and then to communicate immediately to the person ordering the report, any dangerous condi on discovered.

Code C2 (Poten ally dangerous)

This code should be used to indicate that, whilst an observed defi ciency is not considered to be dangerous at the me of the periodic inspec on, it would become an immediate danger if a fault or other foreseeable event was to occur in the installa on or connected equipment.

The person ordering the report should be advised that, whilst the safety of those using the installa on may not be at immediate risk, remedial ac on should be taken as a ma er of urgency to remove the source of poten al danger.

Code C3 (Improvement recommended)

This code should be used to indicate that, whilst an observed defi ciency is not considered to be a source of immediate or poten al danger, improvement would contribute to a signifi cant enhancement of the safety of the electrical installa on.

FI (Further inves ga on required)

Usually, it should be possible to a ribute a Classifi ca on Code to each observa on without the need for further inves ga on.

The purpose of periodic inspec on, as previously stated, is not to carry out a fault-fi nding exercise, but to assess and report on the condi on of an installa on within the agreed extent and limita ons of the inspec on. Therefore, where an observa on can be a ributed a Classifi ca on Code, further inves ga on would not be required for the purposes of comple ng the condi on report.

Further inves ga on should be called for in respect of any observa on that could reasonably be expected to reveal danger or poten al danger. Further inves ga on should not be called for simply because it would be ‘nice to know’ – for example, why a socket-outlet is unearthed.

If an observa on cannot be a ributed a Classifi ca on Code due to reasonable doubt as to whether danger or poten al danger exists, the outcome of the assessment must be reported to be unsa sfactory.

The person ordering the report should be advised that the inspec on and/or tes ng has revealed a poten al safety issue which could not, due to the agreed extent or limita ons of the inspec on, be fully determined, and that the issue should be inves gated as soon as possible.

Examples of observa ons that might possibly jus fy further inves ga on are given on page 17.

Non-compliances with the requirements of the current edi on of BS 7671 that do not give rise to danger and do not require repor ng

Since Amendment 1, BS 7671: 2008 has not required non-compliances with the requirements of the current edi on of BS 7671 that do not give rise to danger or need improvement to be recorded in condi on reports. (Examples of such non-compliances are given on page 18.)

Page 11: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 11

Summary of the condi on of the installa on

The summary should adequately describe the general condi on of the installa on in terms of electrical safety, taking into account the specifi c observa ons made. It is essen al to provide a clear summary of the condi on of the installa on having considered, for example:

• The adequacy of the earthing and bonding arrangements

• The suitability of the consumer unit and other control equipment

• The type(s) of wiring system, and its condi on

• The serviceability of equipment, including accessories

• The presence of adequate iden fi ca on and no ces

• The extent of any wear and tear, damage or other deteriora on

• Changes in use of the premises that have led to, or might lead to, defi ciencies in the installa on.

Minimal descrip ons such as ‘poor’, and superfi cial statements such as ‘recommend a rewire’, are considered unacceptable as they do not indicate the true condi on of an installa on. It will o en be necessary or appropriate to explain the implica ons of an electrical installa on condi on report in a covering le er, for the benefi t of recipients who require addi onal advice and guidance about their installa on.

For example, where an installa on has deteriorated or been damaged to such an extent that its safe serviceable life can reasonably be considered to be at an end, a recommenda on for renewal should be made in a covering le er, giving adequate suppor ng reasons. Reference to the covering le er should be made in the report.

A er due considera on, the overall condi on of the installa on should be given as either ‘sa sfactory’ or ‘unsa sfactory’ in the appropriate place on the condi on report.

If any observa on in the report has been given a Code C1 or Code C2 classifi ca on as categorised in this Guide, or if any observa ons require further inves ga on to determine whether danger or poten al danger exists, the overall assessment of the condi on of the installa on must be reported to be ‘unsa sfactory’.

If there are no observa ons in the report classifi ed as C1 , C2 or FI, it would not be reasonable to report the overall condi on of the installa on as unsa sfactory.

The recommended interval un l the next inspec on should be made condi onal upon all observa ons that have been given a Classifi ca on Code C1 (danger present) being remedied immediately and all observa ons that have been given a Code C2 (poten ally dangerous) or that require further inves ga on being remedied or inves gated respec vely as a ma er of urgency.

Where the space provided for the descrip on of the general condi on of the installa on is insuffi cient for the purpose and it is necessary to con nue the descrip on on an addi onal page(s), the page number(s) of the addi onal page(s) should be recorded.

Unsa sfactory connec on to a downlighter

Page 12: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 12

Examples of the useof Classifi ca on Codes

Examples of the use of Classification Codes

It is en rely a ma er for the competent person conduc ng the inspec on to decide on the Classifi ca on Code to be a ributed to an observa on. The inspector’s own judgement as a competent person should not be unduly infl uenced by the person ordering the work. The person(s) signing the report are fully responsible for its content and accuracy.

The following examples are not exhaus ve. All references to RCD protec on mean addi onal protec on by an RCD having a rated opera ng (tripping) current (IΔn) not greater than 30 mA and an opera ng me not exceeding 40 ms at a residual current of 5 IΔn.

C1 – Danger present• Exposed live parts that are accessible to touch,

such as where:

• a fuse carrier or circuit-breaker is missing from a consumer unit and a blanking piece is not fi ed in its place

• termina ons or connec ons have no (or damaged) barriers or enclosures

• live conductors have no (or damaged) insula on

• an accessory is badly damaged.

• Conduc ve parts have become live as the result of a fault

• Incorrect polarity

Socket-outlet with broken face plate

Page 13: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 13

Examples of the useof Classifi ca on Codes

Page 13

C2 – Poten ally dangerous• Absence of a reliable and eff ec ve means

of earthing for the installa on

• A public u lity water pipe being used as the means of earthing for the installa on

• A gas or oil pipe being used as the means of earthing for the installa on

• Cross-sec onal area of the earthing conductor does not sa sfy adiaba c requirements (that is, does not comply with Regula on 543.1.1)

• Absence of a circuit protec ve conductor for a ligh ng circuit supplying items of Class I equipment, or connected to switches having metallic face plates1

• Absence of a no ce warning that ligh ng circuits have no circuit protec ve conductor

• Absence of a circuit protec ve conductor for a circuit, other than a ligh ng circuit, supplying Class I equipment

• Absence of earthing at a socket-outlet

• Absence of main protec ve bonding of extraneous-conduc ve-parts entering the premises

• Inadequate cross-sec onal area of a main protec ve bonding conductor where the conductor is less than 6 mm2 or where there is evidence of thermal damage

• Absence of supplementary bonding where required2, such as in a loca on containing a bath or shower, where any of the following three condi ons are not sa sfi ed:

• All fi nal circuits of the loca on comply with the requirements of Regula on 411.3.2 for automa c disconnec on, and

• All fi nal circuits of the loca on have addi onal protec on by means of a 30 mA RCD, and

• All extraneous-conduc ve-parts of the loca on are eff ec vely connected to the protec ve equipoten al bonding (main earthing terminal).

• The main RCD or voltage-operated earth leakage circuit-breaker on a TT system fails to operate when tested with an instrument or integral test bu on

• Absence of RCD protec on for portable or mobile equipment that may reasonably be expected to be used outdoors

• Absence of RCD protec on for socket-outlets in a loca on containing a bath or shower, other than for SELV or shaver socket-outlets

• Socket-outlets other than SELV or shaver socket-outlets located less than 3 m horizontally from the boundary of zone 1 in a loca on containing a bath or shower

• Absence of fault protec on (protec on against indirect contact) by RCD where required, such as for a socket-outlet circuit in an installa on forming part of a TT system

Unsa sfactory electrical connec ons

Absence of reliable means of earthing due to inadequate connec on

1 See the Electrical Safety First Best Prac ce Guide No 1 – Replacing a consumer unit in domes c premises 2 Where the presence of supplementary bonding cannot be confi rmed by inspec on it may be verifi ed by a con nuity test (<0.05 Ω)

Page 14: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 14

Examples of the useof Classifi ca on Codes

• Circuits with ineff ec ve overcurrent protec on (due, for example, to oversized fuse wire in rewireable fuses)

• A protec ve device installed in a neutral conductor only

• Separate protec ve devices in line and neutral conductors (for example, double-pole fusing)

• Earth fault loop impedance value greater than that required for opera on of the protec ve device within the me prescribed in the version of BS 7671/IEE/IET Wiring Regula ons or manufacturers’ published data current at the me of installa on

• A ring fi nal circuit having a discon nuous conductor

• A ring fi nal circuit cross-connected with another circuit

• Unsa sfactory electrical connec on, such as:

• a loose connec on showing signs of overhea ng,

• type, number and/or size of conductors unsuitable for the means of connec on,

• conductors incorrectly inserted or located in terminals, or

• termina on secured on insula on

• A ‘borrowed neutral’, for example where a single fi nal circuit neutral is shared by two fi nal circuits (such as an upstairs ligh ng circuit and a separately-protected downstairs ligh ng circuit)

• Insula on resistance of less than 1 MΩ between live conductors connected together and Earth, when measured at the consumer unit with all fi nal circuits connected

• Insula on of live conductors deteriorated to such an extent that the insula ng material readily breaks away from the conductors

• Sheath of an insulated and sheathed non-armoured cable not taken inside the enclosure of an accessory, such as at a socket-outlet or ligh ng switch, where the unsheathed cores are accessible to touch and/or likely to come into contact with metalwork. (Note: Code C3 would apply if the unsheathed cores are not accessible to touch nor likely to come into contact with metalwork)

• Unenclosed electrical connec ons, such as at luminaires. (Such a defect can contribute to a fi re, par cularly where extra-low voltage fi lament lamps are used)

• Fire risk from incorrectly installed electrical equipment, including incorrectly selected or installed downlighters

• Fire risk from lamps exceeding the maximum rated wa age for the luminaires, or placed too close to combus ble materials

• Evidence of excessive heat (such as charring) from electrical equipment causing damage to the installa on or its surroundings

• Unsa sfactory func onal opera on of equipment where this might result in danger

Crumbling vulcanised rubber insula on

Checking a fuse carrier (base missing)

Page 15: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 15

Examples of the useof Classifi ca on Codes

• Immersion heater does not comply with BS EN 60335-2-73 (that is, it does not have a built-in cut-out that will operate if the stored water temperature reaches 98 OC if the thermostat fails), and the cold water storage tank is plas c

• Electrical equipment having an inadequate degree of ingress protec on (IP ra ng) for the external infl uences likely to occur in the loca on, if this results in poten al danger

• Absence of warning no ces indica ng the presence of an alterna ve or secondary source of electricity, such as a standby generator or microgenerator

• Fixed equipment does not have a means of switching off for mechanical maintenance, where such maintenance involves a risk of burns, or injury from mechanical movement.

C3 – Improvement recommended

• Absence of RCD protec on for a socket-outlet that is unlikely to supply portable or mobile equipment for use outdoors, does not serve a loca on containing a bath or shower, and the use of which is otherwise not considered by the inspector to result in poten al danger.(Note: Code C2 would apply if the circuit supplied a socket-outlet in a loca on containing a bath or shower in accordance with Regula on 701.512.3)

• Absence of RCD protec on for cables installed at a depth of less than 50 mm from a surface of a wall or par on where the cables do not incorporate an earthed metallic covering, are not enclosed in earthed metalwork, or are not mechanically protected against penetra on by nails and the like.

• Absence of RCD protec on for circuits of a loca on containing a bath or shower where sa sfactory supplementary bonding is present

• Reliance on a voltage-operated earth-leakage circuit-breaker for fault protec on (protec on against indirect contact), subject to the device being proved to operate correctly. (Note: If the circuit-breaker relies on a water pipe not permi ed by Regula on 542.2.6 as the means of earthing, this would a ract a Code C2 classifi ca on.)

• Absence of a quarterly test no ce for any RCD or voltage-operated earth-leakage circuit-breaker

Older immersion heater without thermal cut-out

Page 16: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 16

Examples of the useof Classifi ca on Codes

• Absence of circuit protec ve conductors in circuits having only Class II (or all-insulated) luminaires and switches3

• Absence of ‘Safety Electrical Connec on — Do Not Remove’ no ce

• Sheath of an insulated and sheathed non-armoured cable not taken inside the enclosure of an accessory, such as at a socket-outlet or ligh ng switch. (Note: Code C2 would apply if unsheathed cores are accessible to touch and/or likely to come into contact with metalwork)

• Bare protec ve conductor of an insulated and sheathed cable not sleeved with insula on, colour coded to indicate its func on

• Electrical equipment having an inadequate degree of ingress protec on (IP ra ng) for the external infl uences likely to occur in the loca on, if this does not result in poten al danger

• Socket-outlet mounted in such a posi on as to result in poten al damage to socket, plug and/or fl ex

• Absence of a no ce indica ng that the installa on has wiring colours to two versions of BS 7671 (if appropriate)

• Absence of circuit iden fi ca on details

• For inspec ons carried out a er 1 January 2016 - Presence of a consumer unit or similar switchgear made from combus ble material (e.g. plas c) that is not inside a non-combus ble enclosure and which is:

• Located under wooden staircase, or

• within a sole route of escape from the premises (Note: If unsa sfactory connec ons are found during inspec on, this would warrant a code C2 classifi ca on to be recorded)

• For inspec ons carried out a er 1 July 2015 – Cables in escape routes not adequately supported to prevent premature collapse in the event of a fi re (Note: In loca ons other than in individual dwellings, such as communal areas forming part of an escape route, this would warrant a code C2 classifi ca on to be recorded)

Cable sheath not taken inside metallic enclosure

3 See the Electrical Safety First Best Prac ce Guide No 1 – Replacing a consumer unit in domes c premises

Page 17: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 17

Examples of the useof Classifi ca on Codes

FI – Further inves ga on required

• Characteris cs of electricity supply (such as voltage or external earth fault loop impedance) do not conform to supply industry norms

• Presence of circuits that cannot be readily iden fi ed or traced.

Items worthy of note that do not warrant a classifi ca on code (These comments would not appear on the EICR)

• The absence of a fi re detec on and alarm system (smoke/heat/carbon monoxide detectors etc)

• The absence of an emergency ligh ng system in a loca on normally requiring such a system (for example in a communal area of a block of fl ats)

• Combus ble materials stored in close proximity to the electrical intake equipment (consumer unit / meter / service head)

• For inspec ons carried out a er 1 January 2016 - Presence of a consumer unit or similar switchgear made from combus ble material (e.g. plas c) that is not inside a non-combus ble enclosure and which is NOT:

• Located under wooden staircase, or

• within a sole route of escape from the premises (Note: If unsa sfactory connec ons are found during inspec on, this would warrant a code C2 classifi ca on to be recorded)

Main bonding connec on not made before branch pipework

Consumer units having rewireable fuses can con nue to provide sa sfactory service (Cover removed for illustra ve purposes)

Page 18: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 18

Examples of the useof Classifi ca on Codes

Non-compliances with the current edi on of BS 7671 that do not give rise to danger and do not require repor ng

• Absence of a reliable earth connec on to a recessed metallic back box of an insulated accessory, such as where there is no ‘earthing tail’ connec ng the earthing terminal of the accessory to the box, and the box does not have a fi xed lug that comes into contact with an earthed eyelet on the accessory

• Inadequate cross-sec onal area of a main protec ve bonding conductor provided that the conductor is at least 6 mm2 and that there is no evidence of thermal damage

• Absence of supplementary bonding for installed Class II equipment where required (such as in a loca on containing a bath or shower), in case the equipment is replaced with Class I equipment in the future

• Main protec ve bonding to gas, water or other installa on pipe is inaccessible for inspec on, tes ng and maintenance, or connec on not made before any branch pipework. (Note: The connec on should preferably be within 600 mm of the meter outlet union or at the point of entry to the building if the meter is external.)

• Protec ve conductor of a ligh ng circuit not (or incorrectly) terminated at the fi nal circuit connec on point to a Class II (or insulated) item of equipment, such as at a switch moun ng box or luminaire

• Switch lines not iden fi ed as line conductors at termina ons (for example, a conductor having blue insula on is not sleeved brown in switches or ligh ng points)

• Circuit protec ve conductors or fi nal circuit conductors in a consumer unit not arranged or marked so that they can be iden fi ed for inspec on, tes ng or altera on of the installa on

• Installa on not divided into an adequate number of circuits to minimise inconvenience for safe opera on, fault clearance, inspec on and tes ng

• Inadequate number of socket-outlets. (Note: A Code C3 or, where appropriate C2, if extension leads run through doorways, walls or windows, or under carpets, or are otherwise being used in an unsafe manner)

• Use of unsheathed fl ex for ligh ng pendants

• Cable core colours complying with a previous edi on of BS 7671.

Absence of supplementary bonding

Page 19: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 19

Examples of the useof Classifi ca on Codes

Items that should not be listed as non-compliances with BS 7671 and do not require repor ng (Mythbus ng)

• Absence of earthing and/or bonding tometallic sinks and baths (unless they areextraneous-conduc ve-parts in their own right)

• The use of rewireable fuses (where they provide adequate circuit protec on)

• The use of circuit-breakers to BS 3871

• Absence of barriers inside a consumer unit (provided the cover is removable only with the use of a key or tool)

• Absence of bonding connec ons to boiler pipework (where the pipework is not an extraneous-conduc ve-part in its own right)

• Shaver supply units installed in zone 2 of a loca on containing a bath or shower and located where direct spray from a shower is unlikely

• Absence of switches on socket-outlets and fused connec on units

• Any other observa on not directly related to electrical safety and hence to the suitability of the installa on for con nued service.

Label warning against storing combus ble materials near to electrical equipment

Page 20: Best Practice Guide 4 - Electrical Safety First · PDF filePage 1 Electrical installation condition reporting: Classification Codes for domestic and similar electrical installations

Page 20Page 16

The latest versions of all the BestPracticeGuides are available todownload from www.electricalsafetyfirst.org.uk

Replacing aconsumer unit indomestic premiseswhere lightingcircuits have noprotectiveconductor

Best Prac (Issue 2)

Guidance on the management of electrical safety and safe isolation procedures for low voltage installations

Best Prac (Issue 2)

Connecting amicrogenerationsystem to adomestic orsimilar electricalinstallation(in parallel with themains supply)

Best Prac (Issue 2)

Electrical installationcondition reporting:Classification Codes fordomestic and similarelectrical installations

Best Prac (Issue 3)

Electricalinstallationsand theirimpact on thefire performanceof buildings:Part 1 - Domestic premises:Single family units(houses, flats, maisonettes,bungalows)

Best Prac

Consumer unitreplacementin domestic andsimilar premises

Best Prac (Issue 2)

Test instrumentsfor electricalinstallations:Accuracy andconsistency

Best Prac

Selection anduse of plug-insocket-outlettest devices

Best Prac

Safe installation of retrofit self-ballastedLED lamps

Best Prac