Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801‐1 and EN 50173‐1 for Class E A channel. REPORT NUMBER 104204526CRT‐001b ISSUE DATE REVISED DATE 19‐February‐2020 12‐May‐2020 TESTS START DATE TESTS END DATE 19‐February‐2020 19‐February‐2020 PAGES 4 DOCUMENT CONTROL NUMBER GFT‐OP‐10a (6‐March‐2017) © 2017 INTERTEK

Upload: others

Post on 27-Jun-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Berk‐Tek Leviton Technologies LETTER REPORT  

SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801‐1 and EN 50173‐1 for Class EA channel.  REPORT NUMBER   104204526CRT‐001b  ISSUE DATE  REVISED DATE 19‐February‐2020  12‐May‐2020  TESTS START DATE  TESTS END DATE 19‐February‐2020  19‐February‐2020  PAGES 4  DOCUMENT CONTROL NUMBER GFT‐OP‐10a (6‐March‐2017) © 2017 INTERTEK  

Page 2:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

LETTER REPORT 

3933 US Route 11 Cortland, NY 13045  Telephone:  1‐607‐753‐6711 Facsimile:  1‐607‐758‐3659 www.intertek.com 

This report  is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than  to the Client  in accordance with the agreement,  for any  loss, expense or damage occasioned by the use of  this report. Only  the Client  is authorized  to permit  copying or distribution of  this  report and  then only  in  its entirety. Any use of  the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.      Version: 6‐March‐2017  Page 2 of 4  GFT‐OP‐10a

  12‐May‐2020  Intertek Report No. 104204526CRT‐001b   Intertek Project No. G104204526  Mr. Greg Hammond   Berk‐Tek Leviton Technologies   2222‐222nd Street SE Bothell, WA  98021    Subject:  Performance testing of Class EA unshielded channel per ISO/IEC 11801‐1 and EN 

50173‐1  Dear Mr. Hammond:  This letter report represents the results of our evaluation of the above referenced product(s) to the requirements contained in the following document(s):  ISO/IEC 11801‐1 Edition 1.0, Information technology – Generic cabling for customer premises ‐ Part 1: General requirements, dated November 2017  EN 50173‐1, Information technology ‐ Generic cabling systems ‐ Part 1: General Requirements, dated June 2018   SECTION 1    SUMMARY  Intertek wishes to inform you that the electrical transmission tests have been performed on your channel configuration. This testing was performed under project G104204526 and quotation Qu‐01035982 issued 06‐December‐2019. Compliant results were obtained for the relevant tests contained in section 6.3 of ISO/IEC 11801‐1 for channel transmission performance.   SECTION 2 NON‐CONFORMANCES  None    

Page 3:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

 

Berk‐Tek Leviton Technologies Intertek Report No: 104204526CRT‐001b 

 

Version: 6‐March‐2017  Page 3 of 4  GFT‐OP‐10a 

 SECTION 3 SAMPLE DESCRIPTION  The client supplied a 4‐connector unshielded channel as illustrated below identified as HIGH‐DENSITY CAT 6A PREMIUM+ UTP SYSTEM. The cabling configuration was bundled in a 6‐around‐1 configuration for alien crosstalk testing.   The samples were received on 03‐January‐2020 and were production samples in undamaged condition.  

  

Component Id 

Manufacturer  Description  Part number 

1  Leviton  Equipment Cords, 3 m  6AS10‐10* 

2  Leviton  Workstation Jack  6AUJK‐** 

2  Leviton  QuickPort Patch Panel  49255‐D48 

3  Leviton  Equipment Cords, 2 m  6AS10‐07* 

4  Leviton  110 Patch Panel  6A586‐U48 

5  Berk‐Tek  UTP CMP Horizontal Cable  LANmark‐SST 

6  Leviton  110‐Style Wiring Block  41D6A‐1F4 

7  Leviton  Equipment Cords, 5 m  6AS10‐15* 

 SECTION 4 TEST EQUIPMENT USED  The following test equipment was used to conduct the testing.  

Test equipment used  Model number Control number 

Calibration due date 

Keysight Network Analyzer  E8357A  E382  07‐January‐2021 

Keysight LCR Meter  4263B  R171  12‐February‐2020 

Temperature/humidity meter  OM‐EL‐USB‐2‐LCD  H243  28‐March‐2020 

 

Page 4:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

 

Berk‐Tek Leviton Technologies Intertek Report No: 104204526CRT‐001b 

 

Version: 6‐March‐2017  Page 4 of 4  GFT‐OP‐10a 

SECTION 5 TESTING  The table below represent a summary of the tests and results. The detailed test data is enclosed to this letter report.   

Test description ISO/IEC 11801‐1 

section EN 50173‐1 section 

Result 

DC loop resistance  6.3.3.6  5.2.2.7  Compliant 

DC resistance unbalance within a pair  6.3.3.7  5.2.2.8  Compliant 

DC resistance unbalance between pairs  6.3.3.7  5.2.2.8  Compliant 

Return Loss  6.3.3.1  5.2.2.2  Compliant 

Insertion Loss  6.3.3.2  5.2.2.3  Compliant 

NEXT and PSNEXT  6.3.3.3  5.2.2.4  Compliant 

ACR‐N, PSACR‐N  6.3.3.4  5.2.2.5  Compliant 

FEXT, ACR‐F and PSACR‐F  6.3.3.5  5.2.2.6  Compliant 

TCL  6.3.3.12.2  5.2.2.13  Compliant 

TCTL, ELTCTL  6.3.3.12.3  5.2.2.14  Compliant 

Propagation delay  6.3.3.10  5.2.2.11  Compliant 

Propagation delay skew  6.3.3.11  5.2.2.12  Compliant 

Coupling attenuation  6.3.3.12.4  5.2.2.15  Not applicable 

PSANEXT  6.3.3.13.2  5.2.2.16.1  Compliant 

Average PSANEXT  6.3.3.13.3  5.2.2.16.2  Compliant 

PSAACRF  6.3.3.13.4  5.2.2.17.1  Compliant 

Average PSAACRF  6.3.3.13.5  5.2.2.17.2  Compliant 

 SECTION 6 PROJECT STATUS & ACTION  Issuance of this letter report completes the performance testing of this channel cabling configuration electrical transmission performance per ISO/IEC 11801‐1 and EN 50173‐1 covered by Intertek Project No. G104204526 and quotation Qu‐01035982. The test results are compliant with the requirements of the standard and sections referred to on pages 2 and 4. The testing was performed at Intertek located in Cortland, NY.  If there are any questions regarding the results contained in this report, or any of the other services offered by Intertek, please do not hesitate to contact your dedicated Intertek Project Manager.  Completed by:  David Ayers    Reviewed by:  Antoine Pelletier Title:  Technician    Title:  Project Engineer 

Signature:    Signature 

Date  12‐May‐2020    Date:  12‐May‐2020 Please note: this Letter Report does not represent authorization for the use of any Intertek certification marks. 

Page 5:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 1

Low Frequency Report

DC Resistance (Ohms)

45

8.2951

8.3601

12

8.2116

8.2069

36

8.2247

8.2216

78

8.2935

8.3387

Limit (Ohms)

Resistance Unbalanced (%)

45

0.39

12

0.03

36

0.02

78

0.27

Limit (%)

3.00

Resistance Unbalanced Pair-Pair (%)

45 - 12

0.71

45 - 36

0.63

45 - 78

0.07

12 - 36

0.08

12 - 78

0.65

36 - 78

0.56

Limit (%)

DC Loop Resistance (Ohms)

45

16.6560

12

16.4180

36

16.4460

78

16.6310

Limit (Ohms)

25.0000

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 6:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 2

Insertion Loss

Insertion Loss (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-4.00

-4.16

-5.81

-6.49

-8.20

-9.17

-10.27

-11.50

-16.40

-20.93

-26.34

-30.14

-33.95

-37.44

-40.68

-43.74

-46.63

-49.39

45

-2.10

-3.79

-5.40

-6.04

-7.58

-8.46

-9.51

-10.67

-15.19

-19.41

-24.48

-27.86

-31.29

-34.54

-37.51

-40.52

-43.11

-45.49

-47.90

-50.76

-52.96

12

-2.21

-3.86

-5.33

-6.00

-7.47

-8.32

-9.36

-10.49

-14.82

-18.91

-23.78

-27.00

-30.44

-33.44

-36.26

-39.06

-41.50

-44.10

-46.26

-48.55

-50.51

36

-1.69

-3.48

-5.06

-5.71

-7.26

-8.16

-9.24

-10.38

-14.88

-19.13

-24.24

-27.69

-31.16

-34.24

-37.24

-40.09

-42.78

-45.28

-47.53

-50.29

-52.27

78

-2.01

-3.74

-5.26

-5.95

-7.44

-8.29

-9.35

-10.50

-14.94

-19.16

-24.20

-27.59

-31.11

-34.17

-37.16

-39.91

-42.45

-45.13

-47.45

-49.83

-52.20

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 7:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 3

NEXT - Near End

NEXT - Near End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-58.17

-56.58

-53.23

-51.63

-50.03

-48.42

-43.38

-39.93

-36.68

-34.78

-33.11

-31.75

-30.58

-29.58

-28.69

-27.89

45 - 12

-96.83

-78.93

-72.55

-76.80

-81.23

-75.16

-71.74

-70.99

-63.48

-54.04

-58.99

-57.18

-52.90

-60.61

-45.75

-44.72

-46.16

-42.69

-42.39

-46.80

-53.98

45 - 36

-96.12

-93.21

-81.00

-78.85

-85.28

-73.13

-82.47

-79.24

-69.48

-66.24

-56.74

-62.84

-47.89

-44.45

-43.95

-41.32

-44.22

-39.79

-34.72

-29.38

-30.78

45 - 78

-100.24

-91.08

-87.30

-81.38

-78.18

-92.20

-79.89

-68.75

-70.82

-69.33

-59.54

-52.31

-49.77

-49.29

-52.05

-60.32

-43.47

-46.12

-40.93

-43.07

-40.86

12 - 36

-92.80

-80.92

-77.48

-74.77

-80.95

-84.22

-73.63

-73.25

-62.97

-60.11

-51.07

-56.64

-59.74

-49.99

-58.07

-48.15

-54.74

-41.04

-38.07

-35.06

-31.85

12 - 78

-88.80

-88.29

-84.29

-72.38

-74.07

-78.54

-74.61

-72.50

-73.53

-70.39

-62.61

-55.25

-53.78

-50.77

-56.22

-50.21

-42.59

-50.29

-41.98

-45.48

-26.76

36 - 78

-92.07

-75.55

-78.52

-72.08

-77.19

-66.27

-64.27

-60.62

-58.04

-57.87

-59.49

-56.65

-54.76

-43.88

-42.84

-40.77

-42.79

-46.47

-47.49

-40.53

-34.12

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 8:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 4

NEXT - Far End

NEXT - Far End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-58.17

-56.58

-53.23

-51.63

-50.03

-48.42

-43.38

-39.93

-36.68

-34.78

-33.11

-31.75

-30.58

-29.58

-28.69

-27.89

45 - 12

-90.61

-86.04

-85.21

-86.36

-78.73

-77.33

-76.30

-72.93

-65.11

-64.56

-55.69

-51.89

-56.12

-66.38

-46.90

-45.98

-55.59

-53.33

-40.97

-50.65

-46.33

45 - 36

-93.34

-92.38

-77.28

-82.24

-72.24

-81.39

-87.47

-68.30

-75.92

-60.29

-54.76

-54.81

-58.17

-52.11

-61.65

-47.63

-41.65

-48.12

-40.70

-36.44

-33.67

45 - 78

-91.75

-87.71

-82.42

-84.95

-81.66

-81.71

-72.35

-75.99

-71.72

-63.00

-56.85

-52.99

-54.10

-51.96

-52.59

-48.14

-45.10

-50.72

-45.39

-46.46

-39.70

12 - 36

-93.62

-81.36

-76.48

-79.53

-75.51

-76.90

-78.42

-82.43

-61.60

-62.55

-66.76

-54.84

-50.27

-61.99

-44.56

-43.88

-49.18

-43.64

-39.52

-38.37

-39.38

12 - 78

-93.62

-86.77

-92.37

-74.48

-77.74

-75.45

-74.24

-74.35

-58.31

-68.17

-54.28

-52.36

-49.54

-50.83

-46.95

-43.94

-40.12

-43.25

-54.29

-37.30

-23.23

36 - 78

-89.05

-74.88

-74.23

-74.20

-72.29

-68.74

-65.85

-61.46

-63.39

-57.06

-59.47

-55.03

-57.20

-52.53

-48.75

-43.35

-46.23

-39.89

-43.04

-44.63

-42.64

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 9:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 5

PSNEXT - Near End

PSNEXT - Near End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-55.60

-54.00

-50.59

-48.97

-47.34

-45.71

-40.59

-37.08

-33.78

-31.85

-30.15

-28.76

-27.58

-26.56

-25.65

-24.84

45

-92.19

-78.46

-71.50

-73.72

-75.87

-70.97

-70.51

-66.24

-61.84

-53.66

-53.46

-50.74

-44.95

-43.13

-41.32

-39.65

-39.70

-37.35

-33.23

-29.12

-30.35

12

-86.40

-76.11

-71.04

-69.34

-72.36

-73.16

-67.77

-67.36

-59.95

-52.98

-50.16

-51.39

-49.81

-47.12

-45.09

-42.32

-40.82

-38.47

-35.56

-34.43

-25.58

36

-88.23

-74.35

-73.34

-69.05

-75.15

-65.39

-63.66

-60.26

-56.59

-55.43

-49.42

-53.12

-46.80

-40.61

-40.27

-37.62

-40.27

-36.84

-32.92

-28.08

-27.27

78

-86.86

-75.00

-76.94

-68.58

-71.20

-66.00

-63.70

-59.70

-57.70

-57.30

-55.20

-49.56

-47.37

-42.13

-42.16

-40.26

-38.16

-42.48

-37.88

-37.79

-25.89

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 10:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 6

PSNEXT - Far End

PSNEXT - Far End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-55.60

-54.00

-50.59

-48.97

-47.34

-45.71

-40.59

-37.08

-33.78

-31.85

-30.15

-28.76

-27.58

-26.56

-25.65

-24.84

45

-86.98

-83.13

-75.54

-78.86

-70.85

-74.85

-70.56

-66.33

-63.81

-57.36

-50.88

-48.27

-51.04

-48.95

-45.73

-42.37

-39.89

-45.35

-37.12

-35.85

-32.52

12

-87.59

-78.83

-75.83

-72.75

-72.25

-71.68

-70.63

-70.24

-55.92

-59.02

-51.74

-48.07

-46.38

-50.38

-41.18

-39.72

-39.49

-40.19

-37.09

-34.67

-23.10

36

-86.51

-73.88

-70.79

-72.33

-68.28

-67.92

-65.45

-60.42

-59.09

-54.52

-53.21

-50.03

-48.92

-49.05

-43.09

-39.81

-39.81

-37.92

-36.06

-33.90

-32.22

78

-86.09

-74.24

-73.51

-71.06

-70.78

-67.71

-64.27

-60.71

-56.67

-55.75

-51.55

-48.53

-47.69

-46.93

-44.02

-39.92

-38.17

-37.97

-40.83

-36.12

-23.08

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 11:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 7

ACR - Near End

ACR - Near End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

61.00

58.91

52.35

50.10

45.03

42.46

39.76

36.92

26.97

18.99

10.34

4.64

-0.84

-5.69

-10.10

-14.16

-17.95

-21.50

45 - 12

94.62

75.08

67.22

70.81

73.76

66.83

62.38

60.50

48.67

35.13

35.21

30.19

22.46

27.17

9.49

5.66

4.66

-1.41

-3.86

-1.75

3.47

45 - 36

94.43

89.72

75.94

73.14

78.01

64.97

73.23

68.85

54.60

47.11

32.50

35.16

16.73

10.21

6.71

1.24

1.44

-5.49

-12.80

-20.91

-21.49

45 - 78

98.23

87.34

82.04

75.43

70.74

83.91

70.54

58.25

55.87

50.17

35.34

24.73

18.66

15.12

14.88

20.41

1.02

0.98

-6.52

-6.76

-11.34

12 - 36

91.11

77.44

72.42

69.06

73.69

76.06

64.39

62.86

48.09

40.98

26.83

28.95

28.58

15.76

20.82

8.06

11.96

-4.24

-9.46

-15.22

-20.42

12 - 78

86.79

84.55

79.02

66.43

66.63

70.25

65.26

62.00

58.58

51.23

38.41

27.66

22.67

16.60

19.06

10.30

0.14

5.16

-5.47

-4.36

-25.44

36 - 78

90.06

71.80

73.26

66.13

69.75

57.98

54.92

50.12

43.10

38.71

35.29

29.06

23.65

9.70

5.68

0.86

0.34

1.34

0.04

-9.31

-18.08

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 12:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 8

ACR - Far End

ACR - Far End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

61.00

58.91

52.35

50.10

45.03

42.46

39.76

36.92

26.97

18.99

10.34

4.64

-0.84

-5.69

-10.10

-14.16

-17.95

-21.50

45 - 12

88.44

82.12

79.82

80.35

71.30

69.06

67.01

62.54

50.36

45.70

31.93

24.86

25.65

32.84

10.54

6.99

14.13

9.31

-5.35

1.97

-4.19

45 - 36

91.69

88.88

72.21

76.53

65.00

73.24

78.25

57.95

61.01

41.16

30.52

27.18

27.02

17.77

24.30

7.50

-1.16

2.63

-6.94

-13.92

-18.48

45 - 78

89.77

83.97

77.17

79.03

74.27

73.43

63.02

65.54

56.79

43.89

32.66

25.48

23.02

17.76

15.36

8.17

2.67

5.46

-2.03

-3.47

-12.52

12 - 36

91.97

77.86

71.41

73.83

68.27

68.74

69.20

72.08

46.69

43.42

42.52

27.21

19.12

27.66

7.21

3.74

6.36

-1.85

-8.12

-11.98

-12.77

12 - 78

91.64

83.03

87.12

68.56

70.36

67.17

64.91

63.89

43.37

49.06

30.09

24.84

18.45

16.63

9.73

3.97

-2.31

-2.00

6.87

-12.63

-29.00

36 - 78

87.07

71.14

68.97

68.28

64.91

60.47

56.52

51.01

48.45

37.95

35.28

27.51

26.12

18.33

11.52

3.38

3.80

-5.37

-4.38

-5.29

-9.58

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 13:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 9

PSACR - Near End

PSACR - Near End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

58.00

56.42

49.79

47.51

42.40

39.80

37.08

34.21

24.18

16.15

7.44

1.71

-3.80

-8.67

-13.10

-17.18

-20.98

-24.54

45

90.09

74.66

66.09

67.68

68.29

62.51

60.99

55.56

46.65

34.26

28.97

22.88

13.66

8.58

3.81

-0.87

-3.41

-8.14

-14.68

-21.64

-22.61

12

84.19

72.26

65.71

63.35

64.88

64.84

58.41

56.87

45.14

34.07

26.38

24.39

19.38

13.68

8.84

3.26

-0.69

-5.63

-10.70

-14.12

-24.92

36

86.54

70.87

68.28

63.35

67.89

57.23

54.42

49.88

41.71

36.30

25.18

25.43

15.64

6.37

3.03

-2.46

-2.51

-8.44

-14.61

-22.21

-25.00

78

84.85

71.26

71.68

62.63

63.76

57.70

54.35

49.20

42.76

38.14

31.00

21.98

16.26

7.96

5.00

0.35

-4.29

-2.65

-9.57

-12.04

-26.31

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 14:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 10

PSACR - Far End

PSACR - Far End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

58.00

56.42

49.79

47.51

42.40

39.80

37.08

34.21

24.18

16.15

7.44

1.71

-3.80

-8.67

-13.10

-17.18

-20.98

-24.54

45

84.91

79.31

70.13

72.83

63.31

66.40

61.09

55.73

48.65

37.99

26.45

20.34

19.67

14.37

8.20

1.84

-3.29

-0.34

-10.85

-15.05

-20.45

12

85.42

74.91

70.45

66.74

64.82

63.41

61.34

59.85

41.18

40.16

27.99

21.05

15.91

16.84

4.82

0.73

-1.97

-3.82

-9.24

-14.01

-27.42

36

84.85

70.38

65.72

66.63

61.04

59.76

56.24

50.07

44.18

35.38

28.97

22.40

17.77

14.71

5.74

-0.32

-3.00

-7.57

-11.58

-16.46

-19.92

78

84.12

70.50

68.26

65.13

63.39

59.43

54.94

50.26

41.73

36.64

27.36

21.02

16.61

12.73

6.79

-0.06

-4.26

-7.28

-6.59

-13.80

-29.14

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 15:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 11

FEXT - Near End

FEXT - Near End (dB)

f (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

1-2

-79.93

-71.97

-71.27

-73.25

-73.79

-65.68

-61.93

-62.58

-65.41

-62.02

-62.39

-72.52

-70.65

-68.04

-67.42

-69.12

-70.32

-73.33

-92.25

-88.42

-81.29

1-3

-86.35

-75.94

-71.81

-70.87

-68.86

-68.44

-68.13

-68.54

-79.51

-67.98

-69.29

-73.55

-68.24

-78.29

-72.62

-72.15

-82.05

-72.34

-76.68

-82.41

-74.06

1-4

-81.89

-72.20

-70.37

-71.08

-81.51

-68.94

-62.94

-60.80

-58.00

-63.65

-61.25

-73.87

-65.89

-65.31

-77.91

-69.71

-70.91

-90.52

-72.92

-74.31

-85.45

2-1

-81.28

-71.70

-70.95

-72.32

-72.51

-65.23

-61.71

-62.09

-65.30

-62.28

-62.62

-76.55

-73.62

-66.84

-67.18

-68.06

-69.05

-74.43

-81.88

-84.89

-78.71

2-3

-90.33

-78.93

-76.98

-74.63

-70.71

-68.47

-67.48

-66.63

-66.01

-65.30

-77.11

-71.27

-72.87

-70.47

-91.79

-78.59

-78.61

-81.33

-84.73

-83.56

-77.92

2-4

-95.23

-90.12

-85.42

-89.47

-80.96

-77.78

-78.64

-79.54

-76.31

-78.98

-83.72

-81.88

-76.45

-78.63

-83.13

-86.11

-92.94

-94.46

-96.99

-97.30

-90.52

3-1

-84.95

-75.63

-71.49

-70.78

-68.79

-68.21

-68.32

-69.23

-79.19

-66.63

-69.96

-75.33

-67.39

-77.47

-71.84

-72.59

-84.76

-71.73

-77.55

-77.09

-74.52

3-2

-91.16

-81.49

-76.54

-73.80

-69.25

-68.42

-67.58

-66.25

-66.45

-65.01

-72.35

-69.97

-70.90

-72.14

-77.30

-79.64

-75.52

-91.94

-80.72

-92.29

-78.75

3-4

-102.43

-90.69

-83.99

-81.55

-76.49

-75.47

-80.35

-77.47

-74.33

-68.35

-67.18

-71.81

-72.29

-82.76

-69.06

-70.31

-78.37

-79.52

-74.00

-78.95

-79.39

4-1

-82.76

-72.34

-70.46

-71.47

-77.52

-68.36

-62.80

-61.34

-57.63

-63.66

-61.32

-74.46

-66.36

-65.93

-79.49

-71.62

-70.94

-90.45

-74.18

-74.65

-86.03

4-2

-86.20

-80.27

-82.88

-87.40

-91.44

-82.08

-76.67

-81.36

-74.73

-83.60

-85.09

-85.71

-79.53

-77.86

-81.07

-90.18

-83.08

-85.04

-95.48

-89.88

-93.24

4-3

-100.32

-87.43

-82.33

-79.34

-75.33

-76.07

-75.73

-88.58

-79.03

-69.33

-66.70

-69.75

-73.78

-102.68

-71.52

-70.11

-81.94

-78.37

-75.11

-85.29

-89.09

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 16:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 12

FEXT - Far End

FEXT - Far End (dB)

f (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

1-2

-80.96

-71.91

-71.03

-72.34

-72.79

-65.21

-61.78

-62.16

-65.29

-62.34

-62.59

-77.58

-74.01

-66.98

-67.40

-67.88

-68.74

-74.55

-80.43

-83.49

-79.11

1-3

-84.80

-76.00

-71.93

-70.83

-68.96

-68.54

-68.41

-69.55

-79.36

-66.82

-70.07

-75.32

-67.29

-76.98

-72.02

-72.81

-84.72

-71.83

-77.15

-77.36

-74.40

1-4

-82.78

-72.18

-70.37

-71.61

-77.37

-68.05

-62.82

-61.25

-57.51

-63.56

-61.31

-74.24

-65.93

-65.75

-80.05

-71.24

-70.68

-92.19

-74.43

-74.40

-84.31

2-1

-81.41

-71.72

-71.05

-72.79

-73.73

-65.52

-61.82

-62.25

-65.20

-61.80

-62.19

-72.66

-70.68

-67.80

-67.10

-69.47

-70.11

-72.76

-88.58

-88.68

-82.82

2-3

-94.84

-81.64

-76.38

-73.89

-69.27

-68.54

-67.49

-66.39

-66.32

-65.19

-72.34

-69.78

-70.79

-71.97

-77.03

-79.81

-75.34

-94.35

-81.35

-96.20

-78.11

2-4

-91.08

-79.50

-82.49

-86.59

-92.84

-82.37

-76.13

-81.20

-74.56

-83.25

-83.87

-90.77

-79.33

-77.98

-81.12

-92.09

-83.81

-83.88

-92.19

-92.75

-91.05

3-1

-84.87

-75.53

-71.44

-70.56

-68.64

-67.86

-67.77

-68.37

-79.37

-67.70

-68.89

-73.47

-68.33

-78.96

-72.34

-71.85

-81.95

-72.58

-76.36

-81.75

-73.34

3-2

-87.96

-78.90

-76.89

-74.27

-70.48

-68.54

-67.32

-66.66

-65.78

-65.18

-76.73

-71.21

-72.66

-70.79

-89.78

-78.56

-78.23

-81.81

-84.00

-82.69

-77.70

3-4

-100.48

-87.11

-82.08

-78.31

-74.83

-75.30

-75.57

-87.45

-78.79

-68.97

-66.41

-69.44

-73.34

-95.95

-71.20

-69.82

-81.84

-77.98

-74.82

-85.16

-87.41

4-1

-82.91

-72.20

-70.40

-71.11

-81.21

-68.84

-62.95

-60.71

-57.93

-63.54

-61.10

-74.02

-65.98

-65.28

-77.91

-69.76

-70.85

-89.53

-72.59

-74.15

-85.42

4-2

-95.85

-93.45

-85.74

-90.49

-81.16

-77.91

-78.49

-79.78

-76.82

-78.85

-84.39

-82.06

-76.66

-78.75

-83.70

-88.04

-91.86

-90.89

-92.47

-102.47

-96.41

4-3

-103.28

-91.21

-84.17

-82.73

-77.20

-76.10

-80.87

-77.82

-74.58

-68.65

-67.28

-71.94

-72.73

-83.70

-69.23

-70.55

-78.87

-80.30

-74.36

-78.57

-78.97

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 17:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 13

ACRF (ELFEXT) - Near End

ACRF (ELFEXT) - Near End (dB)

f (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-62.51

-51.25

-45.20

-43.26

-39.18

-37.24

-35.30

-33.36

-27.34

-23.26

-19.45

-17.24

-15.30

-13.71

-12.38

-11.22

-10.19

-9.28

1-2

-77.72

-68.12

-65.94

-67.25

-66.32

-57.35

-52.58

-52.09

-50.59

-43.11

-38.62

-45.52

-40.21

-34.60

-31.17

-30.07

-28.82

-29.22

-46.00

-39.87

-30.78

1-3

-84.66

-72.46

-66.75

-65.16

-61.60

-60.28

-58.89

-58.16

-64.63

-48.84

-45.04

-45.86

-37.08

-44.06

-35.37

-32.07

-39.27

-27.06

-29.15

-32.12

-21.79

1-4

-79.89

-68.46

-65.11

-65.13

-74.06

-60.65

-53.60

-50.30

-43.05

-44.49

-37.05

-46.29

-34.78

-31.13

-40.75

-29.80

-28.46

-45.38

-25.46

-24.48

-33.25

2-1

-79.18

-67.91

-65.55

-66.28

-64.93

-56.77

-52.20

-51.42

-50.11

-42.87

-38.14

-48.69

-42.33

-32.29

-29.67

-27.55

-25.94

-28.94

-33.98

-34.13

-25.76

2-3

-88.64

-75.45

-71.92

-68.92

-63.45

-60.31

-58.24

-56.25

-51.14

-46.17

-52.86

-43.59

-41.71

-36.24

-54.54

-38.50

-35.82

-36.05

-37.20

-33.28

-25.65

2-4

-93.22

-86.38

-80.16

-83.52

-73.51

-69.49

-69.29

-69.04

-61.37

-59.82

-59.52

-54.29

-45.33

-44.46

-45.96

-46.20

-50.49

-49.33

-49.54

-47.47

-38.32

3-1

-82.85

-71.84

-66.09

-64.75

-61.20

-59.75

-58.81

-58.56

-64.00

-47.22

-45.48

-47.46

-36.10

-42.93

-34.33

-32.07

-41.65

-26.24

-29.65

-26.33

-21.57

3-2

-88.94

-77.63

-71.21

-67.81

-61.78

-60.10

-58.23

-55.76

-51.63

-46.10

-48.58

-42.97

-40.46

-38.70

-41.04

-40.59

-34.02

-47.84

-34.46

-43.74

-28.24

3-4

-100.42

-86.95

-78.73

-75.60

-69.05

-67.18

-71.00

-66.97

-59.39

-49.19

-42.98

-44.22

-41.18

-48.59

-31.90

-30.40

-35.93

-34.39

-26.55

-29.12

-27.20

4-1

-80.66

-68.55

-65.05

-65.43

-69.94

-59.90

-53.28

-50.67

-42.45

-44.25

-36.84

-46.60

-35.07

-31.38

-41.98

-31.11

-27.82

-44.96

-26.27

-23.88

-33.08

4-2

-83.99

-76.42

-77.55

-81.40

-83.97

-73.76

-67.32

-70.88

-59.92

-64.69

-61.32

-58.71

-49.09

-44.42

-44.81

-51.12

-41.58

-40.94

-49.22

-41.33

-42.74

4-3

-98.63

-83.95

-77.27

-73.64

-68.07

-67.91

-66.49

-78.20

-64.15

-50.19

-42.46

-42.06

-42.62

-68.44

-34.28

-30.02

-39.16

-33.09

-27.58

-35.00

-36.82

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 18:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 14

ACRF (ELFEXT) - Far End

ACRF (ELFEXT) - Far End (dB)

f (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-62.51

-51.25

-45.20

-43.26

-39.18

-37.24

-35.30

-33.36

-27.34

-23.26

-19.45

-17.24

-15.30

-13.71

-12.38

-11.22

-10.19

-9.28

1-2

-78.79

-68.00

-65.64

-66.33

-65.36

-56.94

-52.49

-51.77

-50.55

-43.48

-38.84

-50.56

-43.54

-33.44

-31.03

-28.89

-27.28

-30.54

-34.10

-34.81

-28.58

1-3

-83.15

-72.50

-66.86

-65.13

-61.72

-60.38

-59.20

-59.20

-64.45

-47.68

-45.83

-47.69

-36.14

-42.64

-34.67

-32.68

-41.91

-26.34

-29.50

-27.01

-22.26

1-4

-80.81

-68.44

-65.12

-65.69

-69.99

-59.78

-53.50

-50.79

-42.58

-44.45

-37.12

-46.73

-34.85

-31.55

-42.82

-31.26

-28.25

-46.94

-27.01

-24.48

-32.09

2-1

-79.33

-67.90

-65.65

-66.76

-66.20

-57.07

-52.34

-51.65

-50.05

-42.43

-37.75

-44.72

-39.32

-33.22

-29.57

-28.95

-26.93

-27.07

-40.60

-37.78

-29.85

2-3

-93.19

-78.15

-71.30

-68.18

-62.02

-60.38

-58.28

-56.04

-51.41

-46.05

-48.09

-42.15

-39.64

-37.63

-39.67

-39.68

-32.53

-48.86

-33.71

-45.85

-25.96

2-4

-89.11

-75.76

-77.24

-80.67

-85.46

-74.10

-66.80

-70.75

-59.63

-64.14

-59.68

-63.26

-48.25

-43.78

-43.89

-52.11

-41.38

-38.63

-44.77

-42.82

-38.83

3-1

-82.80

-71.71

-66.03

-64.53

-61.10

-59.41

-58.30

-57.77

-64.22

-48.33

-44.46

-45.53

-36.97

-44.38

-34.80

-31.32

-38.77

-26.89

-28.38

-30.85

-20.38

3-2

-85.79

-74.99

-71.50

-68.26

-63.05

-60.27

-58.03

-56.27

-51.03

-46.32

-52.98

-44.19

-42.19

-37.25

-53.42

-39.57

-36.78

-37.80

-37.68

-34.01

-27.18

3-4

-98.50

-83.37

-76.83

-72.39

-67.44

-67.03

-66.24

-77.00

-63.85

-49.85

-42.22

-41.92

-42.25

-61.75

-33.98

-29.85

-39.41

-32.72

-27.40

-35.24

-35.18

4-1

-80.84

-68.38

-65.00

-65.08

-73.67

-60.39

-53.48

-50.11

-42.78

-44.17

-36.67

-46.09

-34.61

-30.70

-40.38

-29.23

-27.66

-43.83

-24.61

-23.26

-32.45

4-2

-93.68

-89.54

-80.36

-84.48

-73.73

-69.64

-69.20

-69.39

-62.07

-59.99

-60.64

-55.04

-46.19

-45.20

-47.34

-49.05

-50.40

-46.88

-46.15

-53.78

-45.88

4-3''''''''''''''''''''''''''''''''''

-101.63

-87.71

-79.10

-77.03

-69.96

-67.95

-71.66

-67.47

-59.67

-49.52

-43.04

-44.31

-41.58

-49.36

-31.88

-30.42

-36.05

-34.80

-26.71

-28.22

-26.82

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 19:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 15

PSFEXT - Near End

PSFEXT - Near End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

45

-77.07

-68.26

-66.34

-66.83

-67.47

-62.66

-58.85

-58.17

-57.24

-59.13

-58.40

-68.43

-63.06

-63.31

-65.97

-65.37

-67.44

-69.75

-71.34

-73.48

-73.05

12

-80.56

-70.88

-69.85

-70.23

-68.27

-63.39

-60.62

-60.72

-62.44

-60.45

-62.43

-69.86

-69.21

-65.08

-67.05

-67.63

-68.58

-73.58

-79.92

-81.02

-75.16

36

-83.84

-74.50

-70.11

-68.79

-65.63

-64.90

-64.80

-64.26

-65.60

-61.68

-64.55

-67.08

-64.91

-70.73

-66.81

-67.98

-73.37

-71.01

-71.81

-74.82

-72.21

78

-80.76

-71.55

-69.90

-70.71

-73.21

-67.52

-62.41

-61.29

-57.52

-62.57

-60.19

-68.34

-65.46

-65.66

-70.42

-67.77

-70.36

-77.29

-71.59

-74.17

-83.77

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 20:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 16

PSFEXT - Far End

PSFEXT - Far End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

45

-77.74

-68.24

-66.28

-66.77

-67.02

-62.23

-58.76

-58.33

-56.81

-59.07

-58.57

-70.61

-63.17

-63.13

-65.92

-65.37

-66.52

-69.93

-71.90

-72.28

-72.82

12

-80.71

-70.65

-69.68

-70.18

-67.92

-63.70

-60.65

-60.79

-62.42

-60.13

-61.76

-67.94

-67.42

-66.10

-66.52

-69.07

-68.83

-72.40

-80.26

-86.38

-76.68

36

-82.86

-73.63

-70.03

-68.53

-65.86

-64.77

-64.20

-64.40

-65.38

-62.22

-64.20

-66.29

-66.04

-70.16

-68.69

-67.37

-75.52

-71.09

-72.20

-78.08

-71.86

78

-82.59

-72.07

-70.08

-70.75

-74.63

-67.66

-62.76

-60.58

-57.78

-62.27

-60.15

-69.57

-64.85

-65.03

-68.53

-67.09

-70.18

-79.46

-70.34

-72.79

-78.02

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 21:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 17

PSACRF (PSELFEXT) - Near End

PSACRF (PSELFEXT) - Near End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-59.51

-48.25

-42.20

-40.26

-36.18

-34.24

-32.30

-30.36

-24.34

-20.26

-16.45

-14.24

-12.30

-10.71

-9.38

-8.22

-7.19

-6.28

45

-74.97

-64.47

-60.94

-60.79

-59.88

-54.20

-49.34

-47.50

-42.05

-39.72

-33.92

-40.56

-31.77

-28.76

-28.46

-24.86

-24.33

-24.26

-23.43

-22.72

-20.09

12

-78.35

-67.02

-64.52

-64.24

-60.79

-55.06

-51.26

-50.24

-47.62

-41.54

-38.66

-42.86

-38.78

-31.64

-30.79

-28.58

-27.07

-29.47

-33.67

-32.47

-24.66

36

-82.16

-71.02

-65.05

-63.08

-58.36

-56.74

-55.56

-53.88

-50.72

-42.55

-40.31

-39.39

-33.75

-36.49

-29.57

-27.89

-30.59

-25.73

-24.28

-24.53

-19.94

78

-78.76

-67.81

-64.64

-64.76

-65.76

-59.23

-53.07

-50.79

-42.57

-43.41

-36.00

-40.76

-34.35

-31.48

-33.26

-27.86

-27.92

-32.15

-24.14

-24.34

-31.57

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 22:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 18

PSACRF (PSELFEXT) - Far End

PSACRF (PSELFEXT) - Far End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-59.51

-48.25

-42.20

-40.26

-36.18

-34.24

-32.30

-30.36

-24.34

-20.26

-16.45

-14.24

-12.30

-10.71

-9.38

-8.22

-7.19

-6.28

45

-75.66

-64.42

-60.88

-60.74

-59.48

-53.79

-49.29

-47.73

-41.66

-39.70

-34.14

-42.68

-31.80

-28.55

-28.39

-24.84

-23.33

-24.24

-23.92

-21.38

-19.86

12

-78.54

-66.73

-64.30

-64.17

-60.49

-55.43

-51.36

-50.40

-47.68

-41.28

-38.01

-40.91

-36.95

-32.55

-30.15

-30.08

-27.37

-28.39

-33.93

-37.69

-26.16

36

-81.21

-70.13

-64.96

-62.83

-58.62

-56.62

-54.99

-54.05

-50.47

-43.08

-39.96

-38.66

-34.90

-35.82

-31.33

-27.23

-32.71

-25.60

-24.56

-27.73

-19.72

78

-80.62

-68.33

-64.83

-64.83

-67.24

-59.39

-53.43

-50.12

-42.85

-43.16

-35.96

-42.05

-33.76

-30.83

-31.30

-27.11

-27.75

-34.21

-22.92

-22.87

-25.80

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 23:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 19

Return Loss - Near End

Return Loss - Near End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-19.00

-18.96

-17.98

-17.49

-17.01

-16.53

-14.04

-12.00

-10.10

-8.99

-8.02

-7.23

-6.56

-6.00

-6.00

-6.00

45

-33.50

-30.44

-49.28

-52.23

-59.43

-54.82

-47.33

-35.30

-43.11

-47.99

-29.07

-43.95

-39.67

-30.97

-32.03

-25.71

-21.40

-14.89

-26.24

-17.09

-19.54

12

-27.64

-44.77

-46.81

-51.67

-30.94

-29.54

-59.36

-31.61

-39.21

-40.99

-27.29

-45.57

-34.80

-31.23

-35.29

-47.18

-46.88

-33.51

-37.29

-38.60

-29.08

36

-28.46

-33.48

-45.01

-42.09

-42.11

-40.21

-47.04

-37.03

-31.93

-36.69

-31.62

-29.73

-23.25

-32.45

-32.17

-35.95

-30.39

-21.30

-39.25

-19.06

-28.84

78

-27.91

-36.19

-31.94

-52.03

-39.00

-42.49

-39.91

-40.47

-45.39

-31.55

-38.09

-43.57

-54.33

-32.32

-31.74

-29.99

-27.32

-32.14

-43.68

-51.77

-37.33

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 24:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 20

Return Loss - Far End

Return Loss - Far End (dB)

Freq (MHz)

1.

4.

8.

10.

16.

20.

25.

31.25

62.5

100.

155.

200.

250.

300.

350.

400.

450.

500.

550.

600.

650.

Limit

-19.00

-18.96

-17.98

-17.49

-17.01

-16.53

-14.04

-12.00

-10.10

-8.99

-8.02

-7.23

-6.56

-6.00

-6.00

-6.00

45

-43.42

-28.30

-35.05

-30.68

-62.23

-46.34

-37.73

-28.64

-34.20

-37.78

-32.14

-33.44

-34.10

-29.15

-25.27

-29.02

-24.08

-17.39

-35.71

-41.90

-16.80

12

-23.76

-30.68

-26.48

-28.75

-30.47

-34.02

-27.21

-23.31

-32.42

-26.75

-26.77

-26.59

-41.45

-30.32

-30.10

-22.29

-50.74

-21.95

-22.90

-24.55

-34.56

36

-31.00

-37.23

-36.01

-59.12

-38.81

-44.78

-46.02

-57.94

-47.58

-38.18

-29.70

-70.87

-47.29

-36.85

-34.59

-38.24

-25.04

-25.33

-22.17

-25.48

-27.64

78

-29.46

-45.76

-31.67

-43.90

-48.28

-45.89

-50.66

-35.83

-30.57

-46.06

-30.26

-35.03

-26.61

-31.74

-45.23

-31.34

-25.12

-27.43

-24.52

-43.32

-32.48

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 25:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 21

Insertion Loss

45

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

0

0 200 400 600 800

Limit Margin : 0.348 dB @ 3.748 MHz

12

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

0

0 200 400 600 800

Limit Margin : 0.294 dB @ 3.748 MHz

36

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

0

0 200 400 600 800

Limit Margin : 0.663 dB @ 3.748 MHz

78

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

0

0 200 400 600 800

Limit Margin : 0.411 dB @ 3.748 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 26:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 22

NEXT - Near End

45 - 12

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 11.543 dB @ 93.054 MHz

45 - 36

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 6.421 dB @ 438.101 MHz

45 - 78

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 10.083 dB @ 204.281 MHz

12 - 36

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 11.027 dB @ 423.487 MHz

12 - 78

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 8.109 dB @ 482.754 MHz

36 - 78

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 7.902 dB @ 395.883 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 27:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 23

NEXT - Far End

45 - 12

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 13.030 dB @ 482.754 MHz

45 - 36

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 11.083 dB @ 468.952 MHz

45 - 78

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 11.122 dB @ 437.289 MHz

12 - 36

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 11.732 dB @ 457.586 MHz

12 - 78

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 9.611 dB @ 356.913 MHz

36 - 78

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-90

-100

-110

-20

0 200 400 600 800

Limit Margin : 9.791 dB @ 19.173 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 28:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 24

PSNEXT - Near End

45

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Limit Margin : 8.429 dB @ 472.199 MHz

12

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Limit Margin : 9.808 dB @ 482.754 MHz

36

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Limit Margin : 6.934 dB @ 473.011 MHz

78

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Limit Margin : 9.047 dB @ 485.189 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 29:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 25

PSNEXT - Far End

45

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Limit Margin : 11.521 dB @ 431.606 MHz

12

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Limit Margin : 11.176 dB @ 356.913 MHz

36

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Limit Margin : 10.948 dB @ 4.559 MHz

78

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Limit Margin : 10.715 dB @ 362.596 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 30:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 26

ACR - Near End

45 - 12

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 12.926 dB @ 2.936 MHz

45 - 36

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 10.217 dB @ 438.101 MHz

45 - 78

dB

Frequency (MHz)

-50

0

50

100

150

0 200 400 600 800

Limit Margin : 12.675 dB @ 204.281 MHz

12 - 36

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 13.576 dB @ 14.302 MHz

12 - 78

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 12.277 dB @ 482.754 MHz

36 - 78

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 9.891 dB @ 19.173 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 31:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 27

ACR - Far End

45 - 12

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 16.189 dB @ 2.936 MHz

45 - 36

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 14.850 dB @ 473.823 MHz

45 - 78

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 15.026 dB @ 330.933 MHz

12 - 36

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 14.561 dB @ 4.559 MHz

12 - 78

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 13.228 dB @ 356.913 MHz

36 - 78

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 10.384 dB @ 4.559 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 32:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 28

PSACR - Near End

45

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 12.071 dB @ 472.199 MHz

12

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 13.227 dB @ 2.936 MHz

36

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 10.601 dB @ 473.011 MHz

78

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 12.165 dB @ 19.173 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 33:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 29

PSACR - Far End

45

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 14.895 dB @ 431.606 MHz

12

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 14.091 dB @ 4.559 MHz

36

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 11.635 dB @ 4.559 MHz

78

dB

Frequency (MHz)

-20

-40

0

20

40

60

80

100

0 200 400 600 800

Limit Margin : 11.635 dB @ 4.559 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 34:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 30

FEXT - Near End

45 - 12

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

45 - 36

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

45 - 78

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

12 - 45

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

12 - 36

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

12 - 78

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

36 - 45

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

36 - 12

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

36 - 78

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

78 - 45

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

78 - 12

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

78 - 36

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 35:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 31

FEXT - Far End

45 - 12

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

45 - 36

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

45 - 78

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

12 - 45

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

12 - 36

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

12 - 78

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

36 - 45

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

36 - 12

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

36 - 78

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

78 - 45

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

78 - 12

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

78 - 36

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-110

-40

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 36:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 32

PSFEXT - Near End

45

dB

Frequency (MHz)

-60

-70

-80

-90

-50

0 200 400 600 800

12

dB

Frequency (MHz)

-60

-70

-80

-90

-50

0 200 400 600 800

36

dB

Frequency (MHz)

-65

-70

-75

-80

-85

-90

-60

0 200 400 600 800

78

dB

Frequency (MHz)

-60

-70

-80

-90

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 37:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 33

PSFEXT - Far End

45

dB

Frequency (MHz)

-60

-70

-80

-90

-50

0 200 400 600 800

12

dB

Frequency (MHz)

-60

-70

-80

-90

-50

0 200 400 600 800

36

dB

Frequency (MHz)

-65

-70

-75

-80

-85

-60

0 200 400 600 800

78

dB

Frequency (MHz)

-60

-70

-80

-90

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 38:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 34

ACRF (ELFEXT) - Near End

45 - 12

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 16.553 dB @ 453.526 MHz

45 - 36

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 19.823 dB @ 364.220 MHz

45 - 78

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 15.034 dB @ 424.299 MHz

12 - 45

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 15.217 dB @ 453.526 MHz

12 - 36

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 20.008 dB @ 127.964 MHz

12 - 78

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

36 - 45

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 17.859 dB @ 386.953 MHz

36 - 12

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 20.539 dB @ 127.153 MHz

36 - 78

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 17.596 dB @ 278.161 MHz

78 - 45

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 14.950 dB @ 426.734 MHz

78 - 12

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

78 - 36

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 16.276 dB @ 394.259 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 39:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 35

ACRF (ELFEXT) - Far End

45 - 12

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 16.355 dB @ 185.608 MHz

45 - 36

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 18.073 dB @ 386.953 MHz

45 - 78

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 15.090 dB @ 61.391 MHz

12 - 45

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 15.103 dB @ 454.338 MHz

12 - 36

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 20.225 dB @ 127.964 MHz

12 - 78

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

36 - 45

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 18.901 dB @ 364.220 MHz

36 - 12

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 20.399 dB @ 127.964 MHz

36 - 78

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 16.173 dB @ 394.259 MHz

78 - 45

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 14.714 dB @ 424.299 MHz

78 - 12

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

78 - 36

dB

Frequency (MHz)

-20

-30

-40

-50

-60

-70

-80

-90

-100

-110

-10

0 200 400 600 800

Limit Margin : 17.717 dB @ 278.973 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 40:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 36

PSACRF (PSELFEXT) - Near End

45

dB

Frequency (MHz)

-20

-40

-60

-80

0

0 200 400 600 800

Limit Margin : 15.242 dB @ 425.111 MHz

12

dB

Frequency (MHz)

-20

-40

-60

-80

-100

0

0 200 400 600 800

Limit Margin : 18.356 dB @ 132.836 MHz

36

dB

Frequency (MHz)

-20

-40

-60

-80

-100

0

0 200 400 600 800

Limit Margin : 18.550 dB @ 391.824 MHz

78

dB

Frequency (MHz)

-20

-40

-60

-80

-100

0

0 200 400 600 800

Limit Margin : 16.285 dB @ 394.259 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 41:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 37

PSACRF (PSELFEXT) - Far End

45

dB

Frequency (MHz)

-20

-40

-60

-80

0

0 200 400 600 800

Limit Margin : 15.205 dB @ 481.942 MHz

12

dB

Frequency (MHz)

-20

-40

-60

-80

-100

0

0 200 400 600 800

Limit Margin : 18.414 dB @ 132.024 MHz

36

dB

Frequency (MHz)

-20

-40

-60

-80

-100

0

0 200 400 600 800

Limit Margin : 17.725 dB @ 394.259 MHz

78

dB

Frequency (MHz)

-20

-40

-60

-80

-100

0

0 200 400 600 800

Limit Margin : 17.079 dB @ 424.299 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 42:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 38

Return Loss - Near End

45

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Limit Margin : 8.625 dB @ 476.259 MHz

12

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Limit Margin : 9.860 dB @ 16.738 MHz

36

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Limit Margin : 10.456 dB @ 13.490 MHz

78

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Limit Margin : 10.914 dB @ 47.589 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 43:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 39

Return Loss - Far End

45

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Limit Margin : 8.250 dB @ 28.104 MHz

12

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Limit Margin : 6.454 dB @ 6.183 MHz

36

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Limit Margin : 13.635 dB @ 490.873 MHz

78

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Limit Margin : 10.889 dB @ 477.883 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 44:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 40

Propagation Delay - Near End

45

ns

Frequency (MHz)

500

520

540

560

580

0 200 400 600 800

Limit Margin : 26.420 ns @ 3.748 MHz

12

ns

Frequency (MHz)

400

450

500

550

600

0 200 400 600 800

Limit Margin : 68.180 ns @ 3.748 MHz

36

ns

Frequency (MHz)

500

520

540

560

580

0 200 400 600 800

Limit Margin : 33.440 ns @ 3.748 MHz

78

ns

Frequency (MHz)

400

450

500

550

600

0 200 400 600 800

Limit Margin : 63.330 ns @ 3.748 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 45:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 41

Propagation Delay Skew - Near End

Skew

ns

Frequency (MHz)

40

42

44

46

48

50

0 200 400 600 800

Limit Margin : 8.060 ns @ 1.312 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 46:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 42

TCL - Near End

45

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-20

0 200 400 600 800

12

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-20

0 200 400 600 800

36

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-20

0 200 400 600 800

78

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-20

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 47:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 43

TCL - Far End

45

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-20

0 200 400 600 800

12

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-20

0 200 400 600 800

36

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-20

0 200 400 600 800

78

dB

Frequency (MHz)

-30

-40

-50

-60

-70

-80

-20

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 48:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 44

TCTL - Near End

45

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

12

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

36

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

78

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 49:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 45

TCTL - Far End

45

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

12

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

36

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

78

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 50:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 46

ELTCTL - Near End

45

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

12

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

36

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

78

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 51:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 47

ELTCTL - Far End

45

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

12

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

36

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

78

dB

Frequency (MHz)

-10

-20

-30

-40

-50

-60

-70

-80

0

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 10:03:54 AM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21 °C

Complies

Page 52:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 1

ANEXT - Near End

CH #1, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 53:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 2

ANEXT - Near End

CH #2, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 54:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 3

ANEXT - Near End

CH #3, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 55:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 4

ANEXT - Near End

CH #4, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 56:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 5

ANEXT - Near End

CH #5, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 57:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 6

ANEXT - Near End

CH #6, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 58:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 7

ANEXT - Far End

CH #1, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 59:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 8

ANEXT - Far End

CH #2, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 60:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 9

ANEXT - Far End

CH #3, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 61:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 10

ANEXT - Far End

CH #4, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 62:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 11

ANEXT - Far End

CH #5, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 63:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 12

ANEXT - Far End

CH #6, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 64:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 13

AFEXT - Near End

CH #1, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 65:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 14

AFEXT - Near End

CH #2, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 66:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 15

AFEXT - Near End

CH #3, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 67:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 16

AFEXT - Near End

CH #4, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 68:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 17

AFEXT - Near End

CH #5, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 69:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 18

AFEXT - Near End

CH #6, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 70:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 19

AFEXT - Far End

CH #1, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #1, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 71:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 20

AFEXT - Far End

CH #2, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #2, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 72:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 21

AFEXT - Far End

CH #3, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #3, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 73:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 22

AFEXT - Far End

CH #4, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #4, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 74:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 23

AFEXT - Far End

CH #5, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #5, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 75:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 24

AFEXT - Far End

CH #6, 45 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 45

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 12

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 36

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 45 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 12 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 36 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

CH #6, 78 - Victim, 78

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-110

-50

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 76:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 25

PSANEXT - Near End

Victim, 45

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-40

0 200 400 600 800

Limit Margin : 14.248 dB @ 498.991 MHz

Victim, 12

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-40

0 200 400 600 800

Limit Margin : 11.654 dB @ 495.744 MHz

Victim, 36

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-40

0 200 400 600 800

Limit Margin : 10.339 dB @ 430.794 MHz

Victim, 78

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-40

0 200 400 600 800

Limit Margin : 10.179 dB @ 458.398 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 77:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 26

PSANEXT - Far End

Victim, 45

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-40

0 200 400 600 800

Limit Margin : 17.997 dB @ 328.498 MHz

Victim, 12

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-40

0 200 400 600 800

Limit Margin : 15.998 dB @ 3.748 MHz

Victim, 36

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-40

0 200 400 600 800

Limit Margin : 15.063 dB @ 6.995 MHz

Victim, 78

dB

Frequency (MHz)

-50

-60

-70

-80

-90

-100

-40

0 200 400 600 800

Limit Margin : 8.022 dB @ 6.995 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 78:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 27

PSAACRF (PSAELFEXT) - Near End

Victim, 45

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Victim, 12

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Victim, 36

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Victim, 78

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 79:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 28

PSAACRF (PSAELFEXT) - Far End

Victim, 45

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Victim, 12

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Victim, 36

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Victim, 78

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 80:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 29

Average PSANEXT - Near End

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-50

0 200 400 600 800

Limit Margin : 10.558 dB @ 498.179 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 81:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 30

Average PSANEXT - Far End

dB

Frequency (MHz)

-60

-70

-80

-90

-100

-50

0 200 400 600 800

Limit Margin : 16.247 dB @ 6.995 MHz

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 82:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 31

Average PSAACRF (PSAELFEXT) - Near End

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies

Page 83:  · Berk‐Tek Leviton Technologies LETTER REPORT SCOPE OF WORK Performance testing of a cabling configuration electrical transmission performance to the requirements of ISO/IEC 11801

Page 32

Average PSAACRF (PSAELFEXT) - Far End

dB

Frequency (MHz)

-40

-60

-80

-100

-20

0 200 400 600 800

Client

Specification

Part No

Test Started

Description

Operator Name

Report No

Length (m)

Temperature

Test Status

Berk-Tek Leviton Technologies

ISO-IEC 11801-1 and EN 50173-1 Class Ea Channel

4-Connector channel

2/19/2020 1:56:04 PM

HIGH-DENSITY CAT 6A PREMIUM+ UTP SYSTEM

Craig Williams

104204526CRT-001b

100.

21.5 °C

Complies