C2 C1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S1 S2 S2 S2 S2 S2 S2 S3 S3 S3 S3 S3 S3 S3 S3 S3 S2 S2 S2 S1 S1 S1 C3 C4 FIRST FLOOR LIGHTING PLAN SECOND FLOOR LIGHTING PLAN SCALE 1:100 SCALE 1:100 C8 C7 C5 C11 C15 C12 C10 C14 C9 C6 C13 ACU ACU ACU ACU ACU WP WP FIRST FLOOR OUTLET PLAN SECOND FLOOR OUTLET PLAN SCALE 1:100 SCALE 1:100 C3 C4 C10 C11 C12 C14 C15 C1 C6 C7 C8 C9 C2 SPARE C13 C5 RISER DIAGRAM ] ] UPVC Pipe Ǥ Ǥ Κ Ⱦ PS No.6 AWG TW Copper Wire CONCRETE PEDESTAL POST M ELECTRIC KILO WATT HOUR METER (SOCKET TYPE) SERVICE ENTRANCE CAP SERVICE ENTRANCE WIRE C1 C2 C3 C5 C7 C9 C4 C6 C8 C10 C11 C13 C15 C12 C14 C16 GROUND CIRCUIT BREAKER DIAGRAM M 15 A 15 A 15 A 15 A 30 A 30 A 60 A 30 A 30 A 30 A SPARE 30 A 30 A 30 A 30 A 30 A SERVICE ENTRANCE CAP CONC. PEDESTAL POST ELECTRIC KILO WATT HOUR METER (SOCKET TYPE) Ǥ Ȁ Ǥ Κ ] (No. 6 TW COPPER WIRE) From the nearest Power Source (SURNECO) C16 C14 C13 C12 C11 C10 C8 C6 C4 C2 C1 C3 C5 C7 C15 C9 SPARE CIRCUIT LINES PPð $:* TW. COPPER WIRE FROM THE NEAREST POWER SOURCE SERVICE ENTRANCE CAP CONCRETE PEDESTAL POST SERVICE ENTRANCE LAYOUT PLAN SCALE 1:100 GENERAL NOTES AND SPECIFICATION 1. TYPE OF SERVICE SHALL BE SINGLE PHASE 220V, 50Hz. 2. NATURE OF WIRING SHALL BE RIGID PVC WIRING. 3. ALL ELECTRICAL WIRING/ MATERIALS SHALL BE STANDARDS CONFORMING WITH NATIONAL BUREAU OF STANDARDS. 4. ALL SWITCHES CONVENIENCE OUTLET SHALL FLUSH TYPE AND, TO BE INSTALLED OF STANDARD HEIGHT AND ABV. FLOOR LEVEL. 5. THE TWO CIRCUITS MUST BE PROVIDED AS SPECIFIED IN THE RISER DIAGRAM. 6. ALL ELECTRICAL INSTALLATION SHALL BE DONE STRICTLY UNDER THE SUPERVISION OF LICENSED MASTER ELECTRICIAN OR ELECTRICAL ENGR. 7. ALL ELECTRICAL INSTALLATION SHALL BE CONFORMED WITH THE LATEST ELECTRICAL PROVISION OF PHILIPPINE ELECTRICAL CODE AND OF LOCAL ORDINANCE RESULTING ELECTRICAL INSTALLATION. 8. ALL ELECTRICAL PLANS USED IN GOVERNMENT/ PRIVATE PROJECT ISSUED FOR BIDDING OR CONSTRUCTIONOR FOR ANY OTHER PURPOSES. 9. ELECTRICAL PLAN SUBMITTED TO ANY GORVERNMENT AGENCY CONCERNED SHALL BE ACKNOWLEDGED AND A CORRESPONDING ELECTRICAL PERMIT IMMEDIATELY ISSUED. 10. ELECTRICAL INSTALLATION SHALL BE SUBMITTED PERMIT BEFORE WORK ON ANY ELECTRICAL INSTALLATION IS COMMENCED. NO. OF CIRCUITS DESCRIPTION C1 LIGHTING OUTLET LIGHTING OUTLET LIGHTING OUTLET POWER OUTLET ( A C U ) POWER OUTLET (CONVENIENCE) POWER OUTLET NO. OF SWITCHES S1 S2 S3 5 NO. OF C.O. 1 1 1 10 9 1 1 1 WATTAGE 352 W 352 W 238 W 410 W 1800 W 1200 W 1200 W 12000 W 1800 W 1620 W 1200 W 1200 W 1200 W AMPHERES 1.6 A 1.6 A 1.08A 1.86 A 1.82 A 5.45 A 5.45 A 54.54 A 8.18 A 7.36 A 5.45 A 5.45 A 5.45 A VOLTS 220 V 220 V 220 V 220 V 220 V 220 V 220 V 220 V 220 V 220 V 220 V 220 V 220 V SIZE OF WIRE 2.5 sq. mm SIZE OF CONDUITS CB / FUSE 15 A 15 A 15 A 15 A 30 A 30 A 30 A 60 A 30 A 30 A 30 A 30 A SCHEDULE OF LOADS C2 C3 C4 LIGHTING OUTLET FOR LIGHTING 1 5 4 4 2 1 FOR POWER LAYOUT POWER OUTLET ( A C U ) POWER OUTLET POWER OUTLET (CONVENIENCE) POWER OUTLET POWER OUTLET (CONVENIENCE) POWER OUTLET ( A C U ) POWER OUTLET ( A C U ) POWER OUTLET SPARE C6 C7 C8 C9 C10 C11 C13 C12 C14 C15 C16 7 7 2.5 sq. mm 2.5 sq. mm 2.5 sq. mm 1260 W 1260 W 5.73 A 5.73 A 220 V 220 V 5.5 sq. mm 5.5 sq. mm 5.5 sq. mm 8 sq. mm 5.5 sq. mm 5.5 sq. mm 5.5 sq. mm 5.5 sq. mm 5.5 sq. mm 5.5 sq. mm 5.5 sq. mm 30 A 30 A 30 A C5 1 3 1 4 1 1 ( R A N G E ) (CONVENIENCE) ( A C U ) (CONVENIENCE) 220 V 30 A TOTAL 100 A 115.75 A 25472 W 40 12 9 10 SAMPLE COMPUTATION: C1: I = V / R TOTAL AMPERES (I): =352 W / 220 V =1.6 AMPERES I = V / R = 25,472 W / 220 V TOTAL CURRENT (V): =115.78 AMPERES V = C1 + C2 + C3 + . . .+C15 DEMAND FACTOR : = 25,472 WATTS = 115.78 X 80 % = 92.63 AMPERES SINGLE FLOURESCENT LAMP PEN LIGHT DUPLEX CONVENIENCE OUTLET WASHING MACHINE OUTLET WATER HEATER OUTLET WH WM DRYER OUTLET DR RANGE OUTLET R REF REFRIGERATOR OUTLET LIGHTING AND POWER PANEL BOARD LPP C# CIRCUIT HOMERUNS FLUSH WALL SWITCH S AIRCONDITIONING OUTLET ACU SAFETY BREAKER LIGHTING CONNECTION CON. OUTLET CONNECTION SWITCH LINE GROUND LEGEND L L O C E T A T S O A G I R U S Y G O L O N H C E T F O E G E S I U R GA O C I T Y 1969 1975 1955 STUDENT: BSCE - 3A PROJECT TITLE: STARTED: SPEED NEATNESS LEGIBILITY ACCURACY EVALUATED BY: EXERCISE: FINISHED: INSTRUCTOR RATING OCAMPO, MARY KRISTELLE L. ARCH. MARLON C. SOLLOSO PROPOSED TWO STOREY RESIDENTIAL BUILDING

Upload: persistentengineer

Post on 16-Dec-2015

212 views

Category:

Documents


0 download

DESCRIPTION

building design

TRANSCRIPT

  • C2

    C1

    S1

    S1

    S1

    S1

    S1 S1

    S1

    S1

    S1

    S1S1

    S1S2

    S2

    S2

    S2

    S2

    S2

    S3

    S3

    S3

    S3

    S3

    S3

    S3

    S3S3

    S2

    S2

    S2

    S1

    S1

    S1

    C3 C4

    FIRST FLOOR LIGHTING PLAN SECOND FLOOR LIGHTING PLANSCALE 1:100 SCALE 1:100

    C8

    C7

    C5

    C11

    C15C12

    C10C14

    C9

    C6

    C13

    ACU

    ACU

    ACU

    ACU ACU

    WP

    WP

    FIRST FLOOR OUTLET PLAN SECOND FLOOR OUTLET PLANSCALE 1:100

    SCALE 1:100

    C3 C4

    C10 C11 C12 C14 C15

    C1

    C6 C7 C8 C9

    C2

    SPARE

    C13

    C5

    RISER DIAGRAM???????????????UPVC Pipe

    ??????????????????No.6 AWG TW Copper Wire

    CONCRETEPEDESTAL

    POST

    MELECTRIC KILO WATT

    HOUR METER(SOCKET TYPE)

    SERVICE ENTRANCE CAP

    SERVICE ENTRANCE WIRE

    C1 C2

    C3

    C5

    C7

    C9

    C4

    C6

    C8

    C10

    C11

    C13

    C15

    C12

    C14

    C16

    GROUND

    CIRCUIT BREAKER DIAGRAM

    M

    15 A 15 A

    15 A 15 A

    30 A 30 A

    60 A

    30 A

    30 A

    30 A

    SPARE

    30 A

    30 A

    30 A

    30 A

    30 A

    SERVICE ENTRANCE CAP

    CONC. PEDESTAL POST

    ELECTRIC KILO WATT HOUR METER(SOCKET TYPE)

    ????????????????????????????(No. 6 TW COPPER WIRE)

    From the nearestPower Source(SURNECO)

    C16

    C14C13

    C12

    C11C10

    C8C6

    C4

    C2

    C1

    C3

    C5

    C7

    C15

    C9

    SPARE

    CIRCUITLINES

    ?????????????

    TW. COPPER WIRE FROM THENEAREST POWERSOURCE

    SERVICEENTRANCE CAP

    CONCRETE PEDESTALPOST

    SERVICE ENTRANCE LAYOUT PLANSCALE 1:100

    GENERAL NOTES AND SPECIFICATION1. TYPE OF SERVICE SHALL BE SINGLE PHASE 220V, 50Hz.

    2. NATURE OF WIRING SHALL BE RIGID PVC WIRING.

    3. ALL ELECTRICAL WIRING/ MATERIALS SHALL BE STANDARDS CONFORMINGWITH NATIONAL BUREAU OF STANDARDS.

    4. ALL SWITCHES CONVENIENCE OUTLET SHALL FLUSH TYPE AND, TO BE INSTALLED OFSTANDARD HEIGHT AND ABV. FLOOR LEVEL.5. THE TWO CIRCUITS MUST BE PROVIDED AS SPECIFIED IN THE RISER DIAGRAM.

    6. ALL ELECTRICAL INSTALLATION SHALL BE DONE STRICTLY UNDER THE SUPERVISIONOF LICENSED MASTER ELECTRICIAN OR ELECTRICAL ENGR.7. ALL ELECTRICAL INSTALLATION SHALL BE CONFORMED WITH THE LATEST ELECTRICALPROVISION OF PHILIPPINE ELECTRICAL CODE AND OF LOCAL ORDINANCE RESULTINGELECTRICAL INSTALLATION.8. ALL ELECTRICAL PLANS USED IN GOVERNMENT/ PRIVATE PROJECT ISSUED FOR BIDDINGOR CONSTRUCTIONOR FOR ANY OTHER PURPOSES.9. ELECTRICAL PLAN SUBMITTED TO ANY GORVERNMENT AGENCY CONCERNED SHALL BEACKNOWLEDGED AND A CORRESPONDING ELECTRICAL PERMIT IMMEDIATELY ISSUED.10. ELECTRICAL INSTALLATION SHALL BE SUBMITTED PERMIT BEFORE WORK ON ANYELECTRICAL INSTALLATION IS COMMENCED.

    NO. OFCIRCUITS DESCRIPTION

    C1 LIGHTING OUTLETLIGHTING OUTLET

    LIGHTING OUTLET

    POWER OUTLET( A C U )

    POWER OUTLET(CONVENIENCE)

    POWER OUTLET

    NO. OF SWITCHES

    S1 S2 S3

    5

    NO. OFC.O.

    1

    1

    1

    10

    9

    1

    1

    1

    WATTAGE

    352 W

    352 W

    238 W

    410 W

    1800 W

    1200 W

    1200 W

    12000 W

    1800 W

    1620 W

    1200 W

    1200 W

    1200 W

    AMPHERES

    1.6 A

    1.6 A

    1.08A

    1.86 A

    1.82 A

    5.45 A

    5.45 A

    54.54 A

    8.18 A

    7.36 A

    5.45 A

    5.45 A

    5.45 A

    VOLTS

    220 V

    220 V

    220 V

    220 V

    220 V

    220 V

    220 V

    220 V

    220 V

    220 V

    220 V

    220 V

    220 V

    SIZE OF WIRE

    2.5 sq. mm ?

    SIZE OF CONDUITS CB / FUSE

    15 A

    15 A

    15 A

    15 A

    30 A

    30 A

    30 A

    60 A

    30 A

    30 A

    30 A

    30 A

    SCHEDULE OF LOADS

    C2C3C4 LIGHTING OUTLET

    FOR LIGHTING1

    5 4

    4

    21

    FOR POWER LAYOUT

    POWER OUTLET( A C U )

    POWER OUTLET

    POWER OUTLET(CONVENIENCE)

    POWER OUTLET

    POWER OUTLET(CONVENIENCE)

    POWER OUTLET( A C U )

    POWER OUTLET( A C U )

    POWER OUTLET

    SPARE

    C6C7C8C9C10C11

    C13C12

    C14C15C16

    7

    7

    2.5 sq. mm ?

    2.5 sq. mm ?

    2.5 sq. mm ?

    1260 W

    1260 W

    5.73 A

    5.73 A

    220 V

    220 V

    5.5 sq. mm ?

    5.5 sq. mm ?

    5.5 sq. mm ?

    8 sq. mm ?

    5.5 sq. mm ?

    5.5 sq. mm ?

    5.5 sq. mm ?

    5.5 sq. mm ?

    5.5 sq. mm ?

    5.5 sq. mm ?

    5.5 sq. mm ?

    30 A

    30 A

    30 A

    C5

    1

    3

    1

    4

    1

    1( R A N G E )

    (CONVENIENCE)

    ( A C U )

    (CONVENIENCE)

    220 V 30 A

    TOTAL 100 A115.75 A25472 W4012 9 10

    SAMPLE COMPUTATION:C1: I = V / R TOTAL AMPERES (I): =352 W / 220 V

    =1.6 AMPERES I = V / R = 25,472 W / 220 V

    TOTAL CURRENT (V): =115.78 AMPERES

    V = C1 + C2 + C3 + . . .+C15 DEMAND FACTOR : = 25,472 WATTS = 115.78 X 80 %

    = 92.63 AMPERES

    SINGLE FLOURESCENT LAMPPEN LIGHT

    DUPLEX CONVENIENCE OUTLET

    WASHING MACHINE OUTLETWATER HEATER OUTLETWH

    WMDRYER OUTLETDRRANGE OUTLETR

    REF REFRIGERATOR OUTLETLIGHTING AND POWER PANEL BOARDLPP

    C# CIRCUIT HOMERUNS

    FLUSH WALL SWITCHSAIRCONDITIONING OUTLETACUSAFETY BREAKERLIGHTING CONNECTIONCON. OUTLET CONNECTIONSWITCH LINEGROUND

    LEGEND

    LLOCETATS

    OA

    G IR

    U S

    YG

    OL

    ON

    HCE

    TFO

    EGE

    S IUR GAO CITY

    1969 1975

    1955

    STUDENT:

    BSCE - 3A

    PROJECT TITLE:

    STARTED:

    SPEED

    NEATNESS

    LEGIBILITY

    ACCURACY

    EVALUATED BY:EXERCISE:

    FINISHED: INSTRUCTOR

    RATING

    OCAMPO, MARY KRISTELLE L. ARCH. MARLON C. SOLLOSOPROPOSED TWO STOREYRESIDENTIAL BUILDING