beam paradox brand.pdf
DESCRIPTION
BeamTRANSCRIPT
1. Description
Avoid direct exposure to strong lights, such as sunlight and headlights.Avoid light in a direct path of 0~4° of optical axis.
2. Cautions on Installation
Do not install the unit on unsteady surfaces.
Do not install in a site where beam may be interrupted by trees or plants; consider seasonal changes.
Do not install in placeswhere units may be splashed frequently by dirty water or direct sea spray. (Causes dirt or salt build up on enclosures.)
Beam DetectorPB-30 / PB-60
Installation Instructions
3. Response Time700 50
Response time (m/sec.)
Features- Twin beams- Aspheric lens type- External light protection- Wide adjustment
Function- Protection against frost/dew- Maximum range : 5 times that of the protection range
Mounting plate Receiver Transmitter Cover
Terminals
Monitor jack
Good LED
Verticaladjustmentscrew
View finder
Lens
Alarm LED
Tamper
Responsetimeadjustment
Power LED
Tamper
MODEL l APB-30 30m (100ft) 0.9m (3ft) PB-60 60m (200ft) 1.8m (6ft)
4. Protection Distance and Expansion of beam
Protection distance and expansion of beam
5. Installation
6. Optical Alignment
Read voltage from monitor jack with a digital voltmeter to confirm optical alignment and to obtain the highest reliability.1. Supply power with cover detached.2. Set Transmitter lens to Receiver lens by using the view finder.
Look through view finder on either side and line up optics horizontally andvertically until the opposite unit is visible. Using the adjustment, the lenscan move horizontally (0~180°) and vertically (0~14°) allowing the unit to workin all directions. The opposite Transmitter or Receiver should appear onthe view finder of inside middle mirror.
3. Adjust the Transmitter horizontally and vertically to get highest voltage reading.Adjust the Receiver horizontally and vertically to get highest voltage reading.
4. Confirm the beam level by inserting a testerin monitor jack of receiver.
- Reference table.
Protection distance l
A
Horizontal adjustment
Verticaladjustment
Monitor Jack Output Voltage Beam level3.0V or higher Good3.0V or lower Readjustment
7’
90’
- Remove cover from unit and slide the mounting plate to detach it.
- Break grommet on mounting plateand pull wire through it. Securethe plate with 4mm screws.
- With your wire exposed, break knock-outs on the rear of unit, pull wire through as shown in the figurebelow and attach it to the mounting plate.
- After wiring is complete,adjust alignment, check operation and attach cover.
5-1 Wall mounting
5-2 Pole mounting
Wire hole
Receiver
View finder
SymptomPower LED does notlight
Alarm LED does not light when the beam is broken.
Alarm LED continues tolight
Intermittent alarms.
Possible Cause1. No power supply.2. Bad wiring connection, broken wire or
short.1. No power supply.2. Bad wiring connection, broken wire or
short.3. Beam is reflected on another object
and sent into the receiver.4. Two beams aren’t broken
simultaneously1. Beam alignment is out.2. Shading object between Tx. and Rx.3. Optics of units are soiled.4. Improper channel.1. Bad wiring connection.2. Change of supply voltage.3. Shading object between Tx. and Rx.4. A large electric noise source, such as
power machine, is located nearby Tx.and Rx.
5. Unstable installation of Transmitterand Receiver.
6. Soiled optics of Tx. and Rx.7. Improper alignment.8. Small animals may pass through the 2
beams
Remedy1. Turn on the power.2. Check wiring.
1. Turn on the power.2. Check wiring.
3. Remove the reflecting object orchange beam direction.
4. Break 2 beams simultaneously.
1. Check and adjust again.2. Remove the shading object.3. Clean the optics with a soft cloth.4. Check channel.1. Check again.2. Stabilize supply voltage.3. Remove the shading object.4. Change the place for installation.
5. Stabilize.
6. Clean the optics with a soft cloth 7. Check and adjust again.8.Set the response time longer.
7. Terminal assignment
After installation, test operation by walk testing.
Status LED Display Action Transmitter Power ON Green LED ONReceiver Good Red LED OFF / Green LED ON
Alarm Red LED ON / Green LED OFF
8. Troubleshooting
GOOD(Green)/ALARM(Red) POWER(Green) : When Beam is alive, When Beam alignment is out, Red LED ON Green LED ONWhen Beam alignment is on, Green LED ON
Responsespeed POWER
NC NO
9. Technical Characteristics
10. Dimensions
1601 NW 84 AVE, Miami, FL 33126Phone: (305) 994-8186 / Fax: (305) 994-8167Email: [email protected]
MODEL
Protection range
Detection method
Infrared beam
Response time
Supply voltage
Current
LED
Alarm output
Tamper output
Temperature
Beam adjustment
Mounting site
Material
Weight
Twin synchronized pulsed beams
IR LED
50 ~ 700mS
DC 10.8 ~ 18V (Non-polarity)
Receiver : 27mA, Transmitter : 30mA
Tx : Power (Green)Rx : Good (Green), Alarm (Red)
Dry contact relay output 1C
Dry contact 1b (Rx)
-20°C ~ +60°C (-4°F ~ +140°F
Horizontal : 180° , Vertical : 14°
Indoor / Outdoor
Cover (PC resin), Base (ABS resin)
Receiver : 369g, Transmitter : 357g
PB-30
30m (100ft)
PB-60
60m (200ft)