be0898 2014:15 tan

27
Faculty of Engineering and Environment Advanced Measurement and Technology Module Number: BE0898 Student ID: 13022981 Coursework Title: Building Design and Performance Critique Name of Chosen Study Building: Ellison Building Programme: BSc (Hons) Quantity Surveying Date of Submission: 10 th February 2015 Module Tutor: Alan Davies 2614 Words

Upload: soon-seng

Post on 07-Apr-2016

218 views

Category:

Documents


1 download

DESCRIPTION

BE0898 2014/15 Tan

TRANSCRIPT

Page 1: Be0898 2014:15 tan

 

Faculty of Engineering and Environment

Advanced Measurement and Technology

Module Number: BE0898

Student ID: 13022981

Coursework Title: Building Design and Performance Critique

Name of Chosen Study Building: Ellison Building

Programme: BSc (Hons) Quantity Surveying

Date of Submission: 10th February 2015

Module Tutor: Alan Davies

 

 

 

 

 

 

 

                    2614  Words    

Page 2: Be0898 2014:15 tan

                   

2  

 

Table  of  Contents  Section  1  :  Introduction  ............................................................................................................  3  

Driver  for  refurbishment  ...................................................................................................................  6  Refurbishment  or  New  Build  .............................................................................................................  6  Proposed  Refurbishment  Period  .......................................................................................................  7  

Section  2:  Body  .........................................................................................................................  8  Heating  ..............................................................................................................................................  8  Window  ...........................................................................................................................................  11  Ventilation  .......................................................................................................................................  13  Revolving  Door  ................................................................................................................................  16  Toilet  ................................................................................................................................................  18  Increasing  thermal  mass  ..................................................................................................................  20  

Section  3:  Conclusion  .............................................................................................................  23  

Section  4:  Reference  ...............................................................................................................  24    

   

Page 3: Be0898 2014:15 tan

                   

3  

Section  1:  Introduction    The  report  provides  a  critical  analysis  of  the  design  and  identifies  possible  improvement  in  usability  and  environmental  performance  of  Ellison  Building,  Northumbria  University.    

 

 

Figure  1:  Ellison  Building  Plan  View.  Source:  Google  Map,  (2015).  

Newcastle  Polytechnic  was  originally  established  in  1969.  It  was  known  as  Rutherford  College  of  Technology  before  changing  its  name  to  University  of  Northumbria  in  1992.  George  Kenyon,  City  Architect,  built  a  few  building  including  Library,  Lipman  Building  and  the  Ellison  Building  in  the  year  1949-­‐65  for  the  Rutherford  College  of  Technology  (Pevsner  et.  al,  1992).    

Ellison  building  consist  of  5  blocks  of  building  which  is  Block  A,  B,  C  D  and  E.  It  has  a  total  usable  floor  area  of  19,674.6m2  (Landmark,  2010).  It  is  home  to  the  faculty  of  Health  and  Life  Sciences,  and  the  faculty  of  Engineering  and  Environment.  There  are  a  total  of  over  20  laboratories  for  students  of  Applied  Sciences  courses  on  the  3rd,  4th,  5th,  and  6th  floors.    

Labs  including  wet  bench  style  labs  for  investigating  a  range  of  environmental  issues  are  located  in  Block  A  and  Grographical  Information  System  Computer  Laboratory  in  Block  D  are  built  for  students  of  Geography  and  Environment.    

There  are  Virtual  Reality  Suite  in  Block  B  and  Architecture  Studios  in  Block  C  for  students  of  Built  Environment.  Facilities  for  computing,  engineering  and  information  science  related  programmes  and  in  particular  industry  standard  engineering  equipment  are  located  in  Block  E  (Northumbria  University,  2010).      

 

Page 4: Be0898 2014:15 tan

                   

4  

Client University of Northumbria

Programme Offsite prior to commencement: 3 weeks Onsite: 21 weeks - 5 weeks ahead of programme (Aug 2007 to Dec 08).

Contract Value £922k

Scope of Work Existing and occupied teaching block that required panel stabilisation and concrete repair prior to aluminium cladding and window replacement. The whole project was carried out from cradle access due to very difficult site conditions.

Table  1:  Refurbishment  of  Ellison  Building  Block  E.  Source:  D+B  Facades  (2008).  

Ellison  Building  Block  E  has  been  refurbished  on  the  year  2008.  Refurbishment  works  include  fitting  aluminium  rainscreen,  insulation,  window  replacement,  concrete  repairs,  recoating  existing  stair  tower,  tiling  ground  floor  and  restraint  existing  panel.  This  project  took  21  weeks,  which  is  5  weeks  ahead  of  programme  to  complete  work  onsite  and  the  refurbishment  cost  £922,000.    

 

 

 

Page 5: Be0898 2014:15 tan

                   

5  

 

Figure  2:  Display  Energy  Certificate  (DEC)  showing  energy  performance  operational  rating  of  Ellison  Building.  Source:  13022981  (2015).  

   

Page 6: Be0898 2014:15 tan

                   

6  

Display  Energy  Certificate  (DEC)  reveals  the  energy  consumption  of  a  building.  DEC  was  introduced  in  2008  and  it  is  compulsory  to  have  this  certificate  for  buildings  more  than  1000m2  used  by  public  authorities  or  institutions  that  provide  service  to  public  (Baker,  2009).  Rating  A  means  that  the  building  is  very  energy  efficient  which  should  have  the  lowest  fuel  bills  and  G  means  the  opposite.  Ellison  Buildings  are  currently  in  band  D.  Besides  that  we  can  see  that  the  annual  energy  use  of  electricity  98  kWh/m2/year  is  higher  than  the  typical  energy  use  of  85  kWh/m2/year  with  0%  use  of  renewable  energy.  

Driver  for  refurbishment  Building  Research  Establishment  Environmental  Assessment  Method  (BREEAM)  in  the  UK  was  recognised  by  the  construction  sector  as  accepted  benchmark  for  assessing  the  environmental  sustainability  of  non-­‐domestic  buildings  and  has  been  a  powerful  driver  for  improvement.  Most  of  the  company  including  government  body  have  environmental  policies  and  on  every  occasion  report  on  their  Corporate  Social  Responsibility  (CSR).  Carbon  emissions  play  an  important  role  in  this.  The  energy  efficiency  achievement  generally  emphasized  as  a  guideline  of  responsible  approach  in  the  community.  Refurbishment  of  existing  building  was  a  regular  approach  in  decreasing  carbon  emission  and  often  found  in  this  report  (Baker,  2009).  

Refurbishment  or  New  Build  

Figure  3:  Different  colour  illustrating  comparison  as  in  refurbishment  or  New  Build?  Source:  David  (2015)  

Refurbishment  will  have  less  environmental  impact  than  demolition  and  new  build.  This  is  because  energy  is  used  to  manufacture  building  components  and  by  replacing  them  means  introducing  new  carbon  emissions.  Also,  the  process  of  knocking  down  and  getting  rid  of  waste  produces  carbon  emission.  One  may  argue  that  a  new  building  will  use  less  energy  than  refurbish  building  but  new  building  generally  have  not  operate  as  good  as  estimated.  Refurbishment  by  means  of  replacing  and  upgrading  finishes  and  components  in  improving  environmental  quality  is  considered  a  better  choice  (Baker,  2009).  

Besides,  it  should  be  consider  that  Ellison  Buildings  are  university  building.  Students  all  year  long  besides  summer  will  use  Ellison  Building.  If  demolition  and  new  build  were  to  happen,  it  may  be  uneconomic  and  inconvenient  because  temporary  buildings  have  to  be  constructed.  Therefore,  low  energy  refurbishment  that  is  much  greener  is  proposed  (Baker,  2009).  

 

   

Page 7: Be0898 2014:15 tan

                   

7  

Proposed  Refurbishment  Period  The  project  is  proposed  to  be  on  site  in  the  summer  2015  and  completely  ready  for  the  start  of  the  2015/2016  academic  year,  in  order  to  reduce  any  possible  effect  on  the  regular  study  life  of  student  in  September.  Contractor  is  proposed  to  work  on  site  from  19th  May  2015  to  8th  September  2015  before  the  new  term  starts.  

 

 

Figure  4:  Northumbria  University  Term  Dates.  Source:  Northumbria  University  (2014)  

 

 

 

 

 

   

Page 8: Be0898 2014:15 tan

                   

8  

Section  2:  Body  

Heating    Ellison  buildings  are  heated  via  radiator  by  10  condensing  boiler  located  in  a  boiler  house.  They  are  heated  by  burning  gas  or  oil.  Biomass  boilers  burning  wood  chips/pallets  are  proposed  to  replace  the  current  condensing  boiler.  

 

Figure  5:  Biomass  boiler.  Source:  Jones  (2011)  

Biomass  boiler  burns  biomass  such  as  wood  chips,  pallets  or  logs  to  provide  heating  and  hot  water.  It  is  categorise  as  carbon-­‐neutral  renewable  energy  as  it  releases  the  same  quantity  of  carbon  dioxide  as  is  used  while  the  plants  were  growing  (Baxi,  2015).    

 

Table  2:  Savings  from  a  wood  pellet  boiler  used  for  central  heating.  Source:  Thorpe,  (2013)  

According  to  theecoexpert  (2015),  although  it  may  initially  cost  about  10  times  more  but  long  term  saving  accounts  more.  They  added  that  large  organisations  may  notice  a  drastic  decrease  of  £60,000  bill  saving  and  2,500  tonnes  reduction  of  carbon  emissions  per  year.  

Page 9: Be0898 2014:15 tan

                   

9  

 

Table  3:  Tariff  classification  of  Renewable  Heat  Incentive.  Source:  Rameha,  (2015)    

A  government  fund,  Renewable  Heat  Incentive  (RHI)  was  established  in  2011  to  provide  support  and  encourage  the  use  sustainability  and  greener  product.  These  funds  will  help  with  the  huge  price  needed  (Great  Britain.  Department  of  Energy  &  Climate  Change,  2015).  

Page 10: Be0898 2014:15 tan

                   

10  

 

Figure  6:  Map  showing  proposed  storage  hut  and  car  park  extension.  Source:  Google  Map,  (2015).  

A  new  storage  hut  would  be  needed  to  store  the  wood  chips/pallets.  This  would  be  a  small  ordinary  form  of  building  propose  to  be  construct  using  car  park  space  beside  boiler  house.  Lorry  transportation  of  wood  chips/pallets  to  storage  hut  will  need  to  enter  through  College  St.  The  car  park  adjacent  to  sports  central  is  suggested  to  extend  using  the  green  field  to  accommodate  shortage  of  car  park.  

 

 

 

   

Page 11: Be0898 2014:15 tan

                   

11  

Window  Double  glazed  window  is  proposed  to  replace  the  current  single  glazed  window.  

 

Figure  7:  Typical  double  glazing  glasses.  Source:  South  Coast  Glazing  (no  date)  

Air  is  catch  in  the  middle  of  two  panels  of  glasses.  This  forms  as  an  insulation  fence  that  will  prevent  heat  from  being  lost.  Besides,  this  also  prevents  water  droplets  appearing  at  the  windows.  Furthermore,  this  prevents  transmission  of  noise  from  the  outside  (Fenn,  2014).  57w  

The  case  study  done  by  Saint-­‐Gobain  Group  (1999),  who  is  one  of  the  UK’s  top  glazing  company,  found  that  after  replacing  single  glazing  with  A-­‐rated  double  glazing  one  could  see  that  it  will  save  approximately  £8,211  and  22  tonnes  of  CO2  in  an  ordinary  detached  house.  The  similar  study  was  conducted  on  an  ordinary  semi-­‐detached  house  and  the  result  were  a  saving  of  £5,855  and  16  tonnes  of  CO2.  The  studies  were  measured  by  using  the  Glass  and  Glazing  Federation’s  (2015)  energy  saving  and  carbon  calculator.    

Energy  Saving  Trust  (2014)  states  that  a  regular  house  fixing  double  glazing  window  will  usually  reduce  carbon  dioxide  emissions  by  about  ¾  of  a  tonne  per  year.  This  is  an  important  saving  as  heat  lost  from  an  ordinary  home  through  the  windows  account  to  around  23%.    

Evidence  from  British  Fenestration  Rating  Council  (2008)  shows  that  a  saving  of  household  bills  up  to  $461  per  year  can  be  achieved  by  fixing  double  glazing  windows.    

   

Page 12: Be0898 2014:15 tan

                   

12  

U  values  express  the  thermal  transmittance  of  a  particular  product.  This  is  calculated  by  the  amount  of  heat  that  will  transmit  past  a  square  metre  of  a  product  when  one  of  the  side  vary  by  one  degree.  The  higher  the  values,  the  higher  the  heat  lost  of  that  product.  The  values  (W/m2  deg  K)  are  expressed  in  units  of  watts  per  square  metre  per  degree  of  temperature  difference  (English  Heritage,  2012).    

 

 

Figure  8:  A  diagram  showing  U-­‐value  of  single-­‐glazed  and  double-­‐glazed  window.  Source:  English  Heritage  (2012).    

The  diagram  above  shows  a  decrease  of  U  value  will  be  achieved  after  replacing  double  glazed  window.  

   

Page 13: Be0898 2014:15 tan

                   

13  

Ventilation    Concurrent  Mix  Mode  ventilation  is  proposed  in  relation  to  the  current  ventilation  system.  

Many  argue  that  it  feels  very  stuffy  in  most  of  the  lecture  theatre  particularly  in  EBA002.  Even  though  3  extract  fans  were  installed  in  EBA002  but  it  still  feels  warm.  One  of  the  reasons  may  be  that  the  fans  emit  much  noise  while  operating  and  so  most  decided  to  switch  it  off  while  having  a  lecture.  Heat  will  pretty  much  be  felt  by  students  sitting  furthest  from  the  windows,  if  not  all.  This  may  be  cause  by  lack  of  air  circulation  to  the  middle  of  the  building.  One  may  experience  nausea,  bloody  noses  and  even  headache  if  ventilation  problem  were  not  handled  properly  (Torres,  2014).  118  

 

Figure  9:  A  right  study  environment  is  crucial  in  developing  good  students.  Source:  Dudley  (2014)  

Concurrent  mixed  mode  ventilation  is  proposed.  For  a  big  building  like  Ellison  Building,  natural  ventilation  is  not  enough  to  provide  comfortable  condition  for  the  occupant  in  the  middle  of  the  building;  therefore  mechanical  ventilation  needs  to  be  fixed  there  (Brager  and  Lehrer,  2013).    

 

Figure  10:  A  concurrent  mix  mode  ventilation  system  in  a  typical  office.  Source:  Brager  and  Lehrer  (2013)  

   

Page 14: Be0898 2014:15 tan

                   

14  

Another  reason  that  makes  it  feels  stuffy  may  be  the  closure  of  window  most  of  the  time.  The  installation  of  carbon  dioxide  sensor  with  light  indicator  is  proposed.      

Table  4:  Representation  of  physiological  effects  to  the  room  CO2  concentration.  Source:  Enocean  (2011)  

The  indoor  air  quality  is  indicated  by  the  concentration  of  carbon  dioxide  in  a  room.  A  room  is  considered  as  well  ventilated  when  the  carbon  dioxide  concentration  is  between  800  to  1200  ppm.  If  the  ppm  falls  below  that  800ppm,  more  energy  will  be  required  for  heating  and  cooling.  At  the  same  time  if  the  ppm  rises  above  1200ppm,  it  may  cause  the  occupant  to  be  drowse  Enocean  (2011).    

   

Page 15: Be0898 2014:15 tan

                   

15  

How  it  works  

Two  carbon  dioxide  sensors  will  need  to  be  placed,  one  in  the  return  radiator  ductwork  and  one  in  the  lecture  theatre.  Once  the  lecture  theatre  is  in  use,  the  sensor  will  detect  the  rise  of  CO2  from  occupants  and  guide  the  heater  to  reduce  and  ventilation  to  include  more  usage  of  outside  air.  In  contrast,  when  occupants  leave  the  theatre  and  a  fall  of  CO2  detected,  the  usage  of  outside  air  will  be  reduced.  There  will  be  less  amount  of  energy  required  to  keep  the  building  warm  or  chill  (OSEH,  1998).    

 

 

Figure  11:  LCD  Display  Guide  of  a  Carbon  Dioxide  Sensor  Source:  Omni  (2009)  

Displaying  green  under  normal  condition,  the  colour  will  raise  to  yellow  and  then  to  red  upon  higher  concentration  of  CO2.  Under  normal  situation  the  sensor  will  be  in  green  and  the  colour  will  step  up  to  yellow  and  then  to  red  when  it  detects  more  concentration  of  CO2.  This  sensor  is  popular  for  offices  and  schools  in  which  will  direct  the  occupant  to  open  windows  and  fans  once  the  indicator  hits  red  so  that  more  air  will  flow  and  thus  reduces  carbon  dioxide  concentration  (Euro-­‐gas,  no  date).    

 

 

   

Page 16: Be0898 2014:15 tan

                   

16  

Revolving  Door    Revolving  doors  are  proposed  to  replace  all  automatic  sliding  doors.  

A  difference  in  air  pressure  basically  causes  air  to  move  in  and  out  of  a  building.  Warm  air  rises  to  the  ceiling  of  a  building  during  the  winter  and  as  long  as  there  is  any  opening  on  the  ground  floor,  chill  air  tends  to  move  in  and  substitute  them.  In  contrast,  warm  air  move  in  during  the  summer  to  substitute  chill  air  (Heerwagen,  1996).  

 

 

Figure  12:  Typical  revolving  doors.  Source:  Whibley  (2015)  

This  is  a  problem  to  engineers  to  think  of  a  way  to  allow  individual  to  enter  and  exit  the  building  on  the  same  time  decreasing  unwanted  air  movement.  Over  100  years  ago  before  anyone  was  talking  about  carbon  emission  or  environmental  impact,  the  revolving  door  was  introduced  as  a  solution  to  this  problem.  A  revolving  door  is  not  airtight  as  some  air  will  exit  and  some  will  enter  the  building  whenever  the  door  spins  however  not  so  much  air  flows  compared  to  a  sliding  door  (Stromberg,  2014).    

   

Page 17: Be0898 2014:15 tan

                   

17  

Besides,  additional  revolving  door  is  proposed  to  construct  on  the  entrance  of  Block  A.  Many  students  were  seen  to  be  queuing  to  enter  and  exit  Block  A  during  peak  hours  and  most  of  the  time  swinging  door,  adjacent  to  the  revolving  door  have  to  be  used.  

 

Figure  13:  Students  queuing  to  exit  Block  A.  Source:  13022981  (2015)  

A  case  study  on  the  usage  of  revolving  door  was  done  by  a  group  of  Massachusetts  Institute  of  Technology  students  in  one  building  on  campus,  E25.  They  found  that  only  23%  of  students  make  use  of  the  revolving  doors.  Based  on  their  calculation,  a  swinging  door  allowed  as  much  as  8  times  more  air  to  flow  into  the  building  compared  to  a  revolving  door.  The  group  of  students  state  that  if  the  average  local  weather  were  applied  to  the  equation  and  everyone  were  to  use  the  revolving  doors  it  would  have  saved  more  than  75,000  kilowatt-­‐hours  of  energy  which  is  about  1.5%  of  the  total  required  to  energy  heat  and  cool  the  building  and  prevent  14.6  tonnes  of  carbon  dioxide  from  being  emitted  (Cullum  et  al.,  2006).  

 

 

 

 

 

 

 

 

   

Page 18: Be0898 2014:15 tan

                   

18  

Toilet    

 

Figure  14:  Block  A,  1st  Floor  Man’s  Toilet.  Source:  13022981  (2015)  

Toilets  particularly  Man  toilet  in  Block  A,  1st  floor  if  not  all  is  currently  using  compression  washer  taps.  Spray  taps  with  Passive  Infrared  (PIR)  sensor  are  proposed  to  replace  them.    

 

Figure  15:  Traditional  tap  in  man  toilet.  Source  13022981  (2015)  

According  to  Higher  Education  Statistic  Agency  (2013),  Northumbria  University  generally  have  147,295  m3  of  total  water  consumption  on  the  year  2012-­‐2013.  This  is  relatively  high  compared  to  other  universities.    

The  amount  of  water  used  as  cleaning  hands  by  washbasin  and  sinks  accounts  for  about  8%.  Traditional  taps  need  about  4  litres  of  water  per  hand  wash,  which  can  be  reduced  to  2  litre  of  less  by  installing  water  efficiency  taps  (Gray,  2012).    

Case  study  done  by  South  West  Tourism  (2009)  shows  that  more  than  100  litres  of  water  saved  per  guest  night  by  fixing  spray  tap.  It  was  added  that  the  saving  significantly  reduces  the  cost  of  heating  hot  water.  Spray  tap  can  save  about  75%  of  water  compared  to  normal  taps.  Besides,  it  can  be  installed  into  existing  tap  head  (Buckle,  2015).      

Page 19: Be0898 2014:15 tan

                   

19  

 

 

Figure  16:  PIR  sensor  tap.  Source:  Sadoo  (2010)  

However,  a  lot  of  water  will  be  wasted  when  a  tap  is  left  dripping  after  using.  Therefore  it  is  not  recommended  to  keep  the  compression  washer  taps.  By  installing  PIR  sensor  tap,  the  flow  of  water  will  start  and  stop  automatically  as  it  detects.  Also,  bacteria  does  not  transmit  as  it  is  touch  free  whereby  placing  hands  will  automatically  turn  on  tap.  This  does  control  the  infection  among  toilet  users  (Pearson,  2013).    

 

 

 

   

Page 20: Be0898 2014:15 tan

                   

20  

Increasing  thermal  mass    Thermal  mass  of  Ellision  Building  is  proposed  to  increase  by  adding  insulation  on  the  outside  of  the  building.    

Thermal  mass  means  the  ability  of  particular  material  to  absorb  and  store  heat  energy.  It  acts  as  a  thermal  battery  (Reardon,2013).    

 

Figure  17:  Thermal  mass  during  the  summer.  Source:  Reardon  (2013)  

During  the  summer,  a  particular  material  absorbs  heat  during  the  day  and  releases  it  by  night  to  cooling  breezes,  keeping  the  house  comfortable  (Reardon,2013).    

 

Figure  18:  Thermal  mass  during  the  winter.  Source:  Reardon  (2013)  

While  in  winter,  the  material  can  store  heat  from  the  sun  or  heaters  helping  the  building  to  stay  warm  and  releases  the  heat  by  night  (Reardon,2013).  

   

Page 21: Be0898 2014:15 tan

                   

21  

Internal  or  External  Insulation  

 

Figure  19:  Internal  wall  insulation.  Source:  Bere  Architects  (2011)  

According  to  Bere  Architects  (2011),  internal  insulation  is  not  a  good  choice  as  it  will  have  higher  thermal  bridges,  loss  of  internal  thermal  mass  and  naturally  results  in  higher  u-­‐  values  therefore  lower  energy  savings.  The  internal  insulation  in  the  above  figure  shows  a  weighty  thermal  bridge  of  0.16  W/mK.  The  dew  point  in  case  is  in  side  of  the  external  wall  around  12degree  line.  This  face  a  significant  risk  of  condensation  within  internal  insulation  and  this  can  result  in  damage  to  internal  floor  finishes  and  on  serious  occasion,  a  risk  of  structural  failure.    

 

Page 22: Be0898 2014:15 tan

                   

22  

Figure  20:  External  wall  insulation.  Source:  Bere  Architects  (2011)  

In  contrast,  the  external  insulation  is  a  better  choice  for  an  occupier  as  it  keeps  the  brickwork  warm.  The  thermal  bridge  value  for  the  above  figure  is  0  W/mK  which  means  there  will  be  no  thermal  bridge  and  risk  of  condensation  and  so  no  damage  of  the  internal  finishes.  The  most  important  of  all,  thermal  mass  can  be  fully  utilised  on  the  inside  of  the  house.  

A  case  study  was  conducted  by  Kingspan  (2010)  where  631  flats  in  Scholes  Village  were  extensively  refurbished  with  external  wall  insulation  u-­‐value  of  0.28  W/m2  K.  The  result  shows  estimate  savings  of  1136  tonnes  of  carbon  dioxide  emission  per  year  with  fuel  saving  of  £300  per  household  per  year.  

 

 

 

 

   

Page 23: Be0898 2014:15 tan

                   

23  

Section  3:  Conclusion In  conclusion,  Ellison  building  is  proposed  to  refurbish  in  order  to  be  more  energy  efficient.  Biomass  boilers,  which  are  more  eco-­‐friendly,  suggested.  Besides  that,  double  glazing  windows  are  proposed.  To  improve  ventilation,  concurrent  ventilation  system  is  suggested.  In  addition,  carbon  dioxide  sensor  with  light  indicator  will  lead  the  occupier  to  either  open  or  close  the  window.  Revolving  door  are  also  suggested.  Taps  in  the  toilet  are  to  be  replaced  and  finally  increasing  thermal  mass  of  Ellison  Building  are  proposed.  The  suggested  refurbishment  could  provide  improvement  in  the  building  environmental  performance  and  usability  of  the  building.  

 

 

 

 

 

 

   

Page 24: Be0898 2014:15 tan

                   

24  

Section  4:  Reference  Baker,  N.V.  (2009)  The  Handbook  of  Sustainable  Refurbishment:  Non-­‐Domestic  Buildings.  Available  at:  http://www.thenbs.com/topics/environment/articles/strategylowemissionrefurbishment.asp  (Accessed:  3  February  2015  ).  

Baxi  (2015),  Biomass  boilers.  Available  at:  http://www.baxi.co.uk/renewables/biomass.htm  (Accessed:  3  February  2015).  

Bere  Architects  (2011)  Landmark  planning  appeal  success  for  external  insulation  in  a  conservation  area.  Available  at:  http://www.bere.co.uk/blog/landmark-­‐planning-­‐appeal-­‐success-­‐external-­‐insulation-­‐conservation-­‐area  (Accessed:  1  February  2015).  

British  Fenestration  Rating  Council  (2008)  Save  Money.  Available  at:  http://www.bfrc.org/  (Accessed:  27  January  2015).  

Buckle,  I.  (2015)  Water  Management.  Available  at:  http://www.sustainablehotel.co.uk/Improve_water.html  (Accessed:  28  January  2015).  

Cullum,  B.A.,  Lee,  O.,  Sukkasi,  S.,  and  Wesolowski,  D.  (2006)  Modifying  habits  towards  sustainability:  a  study  of  revolving  door  usage  on  the  MIT  campus,  Massachusetts  Institute  of  Technology.  [Online]  Available  at:  http://web.mit.edu/~slanou/www/shared_documents/366_06_REVOLVING_DOOR.pdf  (Accessed:  30  January  2015).  

David  (2015)  20+  Garbage  Disposal  models  comparison  table  [Online].  Available  at:  http://garbagedisposal360.com/compare/  (Accessed:  29  February  2015).  

Dudley  (2014)  Dudley  Ladies  Press  Release  2.  Available  at:    https://www.google.co.uk/search?q=stuffy&espv=2&biw=832&bih=637&source=lnms&tbm=isch&sa=X&ei=vfvMVKHmG838aIesgIAO&ved=0CAYQ_AUoAQ#tbm=isch&q=hot+weather+animation&imgdii=_&imgrc=ftQk3OfZOe-­‐FPM%253A%3BwL4pLEXRak7HDM%3Bhttp%253A%252F%252Fwww.dudleyladies.co.uk%252Fimages%252Fcurrent%252520news%252520images%252FMCj04244840000%255B1%255D.gif%3Bhttp%253A%252F%252Fwww.dudleyladies.co.uk%252Foldnews.htm%3B206%3B188  (Accessed:  3  February  2015).      

D+B  facades  (2008)  Educational  and  Residential  Video  Case  Studies:  Exemplifying  the  Benefits  of  Adopting  a  High-­‐Quality,  Whole-­‐Life  Approach  to  External  Refurbishment.  Available  at:  http://www.dbfacades.com/projects.html  (Accessed:  2  February  2015).  

Energy  Saving  Trust  (2014)  Energy  Saving  Trust  endorsed  products.  Available  at:  http://www.energysavingtrust.org.uk/businesses/content/product-­‐standards  (Accessed:  6  February  2015).  

English  Heritage  (2012)  Energy  Efficiency  and  Historic  Buildings:  Application  of  Part  L  of  the  Building  Regulations  to  historic  and  traditionally  constructed  buildings,  pp.51  ,fig.  [Online].  Available  at:  http://www.english-­‐heritage.org.uk/publications/energy-­‐efficiency-­‐historic-­‐buildings-­‐ptl/eehb-­‐partl.pdf  (Accessed:  8  February  2015).    

Page 25: Be0898 2014:15 tan

                   

25  

Enocean  (2011)  CO2  sensor:  Design  concept  for  solar-­‐powered  CO2  sensor.  Available  at:  https://www.enocean.com/fileadmin/redaktion/pdf/app_notes/AN313_CO2_Sensor.pdf  (Accessed:  2  February  2015).  

Euro-­‐gas  (no  date)  Carbon  dioxide  co2  relay  indoor  air  quality  monitor,  traffic  light  option,  0-­‐3000ppm.  Available  at:  http://euro-­‐gasman.com/carbon-­‐dioxide-­‐co2-­‐relay-­‐indoor-­‐air-­‐quality-­‐monitor-­‐with-­‐traffic-­‐light-­‐option.html  (Accessed:  31  January  2015).  

Fenn,  K.  (2014)  Saving  Energy  Through  Double  Glazing.  Available  at:  http://www.energysavingsecrets.co.uk/savingenergythroughdoubleglazing.html  (Accessed:  30  January  2015).  

Google  Map  (2015)  ‘Ellison  Building’,  1:50,000.  Google  Map  [Online].  Available  at:  https://www.google.co.uk/maps/place/Northumbria+University/@54.9780226,-­‐1.6066334,811m/data=!3m1!1e3!4m2!3m1!1s0x487e70e112c5e9f7:0x79a7c60c923dce07  (Accessed:  5  February  2015).  

Glass  and  Glazing  Federation  (2015)  Energy  Saving  Calculator.  Available  at:  http://www.ggf.org.uk/energy-­‐savings-­‐calculator  (Accessed:  29  January  2015).  

Gray,  J.  (2012)  Water  and  Sustainable  Design.  Available  at:  http://www.sustainablebuild.co.uk/sustainabledesignwater.html  (Accessed:  28  January  2015).    

Great  Britain.  Department  of  Energy  &  Climate  Change  (2015)  Increasing  the  use  of  low-­‐carbon  technologies  [Online].  Available  at:  https://www.gov.uk/government/policies/increasing-­‐the-­‐use-­‐of-­‐low-­‐carbon-­‐technologies/supporting-­‐pages/renewable-­‐heat-­‐incentive-­‐rhi  (Accessed:  5  February  2015).  

Heerwagen,  D.  (1996)  Observing  air  flow  in  buildings.  Prepared  for  the  Vital  Signs  Project,  University  of  California,  Berkeley,  [Online].  Available  at:  http://arch.ced.berkeley.edu/vitalsigns/res/downloads/rp/airflow/HEER1-­‐BG.PDF  (Accessed:  7  February  2015).  

Higher  Education  Statistic  Agency  (2013)  Estate  Management  Record:  Environmental  Information  2012/2013.  Available  at:  https://www.hesa.ac.uk/index.php?option=com_pubs&Itemid=&task=show_year&pubId=1736&versionId=55&yearId=303  (Accessed:  5  February  2015).  

Jones,  L.  (2011)  What  to  expect  from  your  biomass  boiler  [Online].  Available  at:  https://www.google.co.uk/search?q=biomass+boiler&espv=2&biw=791&bih=637&source=lnms&tbm=isch&sa=X&ei=R4HOVLyADqTD7gaI-­‐YGwAQ&ved=0CAcQ_AUoAg#imgdii=_&imgrc=9In50sUvR2WOEM%253A%3B0RvsJ1r5s6HVZM%3Bhttp%253A%252F%252Fwww.yougen.co.uk%252Fi%252Fblog%252F131228079653681.jpg%3Bhttp%253A%252F%252Fwww.yougen.co.uk%252Fblog-­‐entry%252F1721%252FWhat%252Bto%252Bexpect%252Bfrom%252Byour%252Bbiomass%252Bboiler%252F%3B568%3B560  (Accessed:  7  February  2015).  

Page 26: Be0898 2014:15 tan

                   

26  

Kingspan  (2010)  Domestic  Refurbishment.  Available  at:  http://www.kingspaninsulation.co.uk/getattachment/d41f7463-­‐cd86-­‐4d1a-­‐98fc-­‐010dc191135c/Domestic-­‐Refurbishment.aspx?disposition=attachment  (Accessed:  2  February  2015).  

Landmark  (2010)  Advisory  Report:  Report  Reference  Number:  0555-­‐2036-­‐0313-­‐0600-­‐7921.  Available  at:  https://www.ndepcregister.com/reportSearchAddressListReports.html?id=da2b8326545feefcf0591fb2f90d96fd  (Accessed:  27  January  2015).  

Northumbria  University  (2010)  City  Campus  Tour  Guide  [Online].  Available  at:  https://www.northumbria.ac.uk/static/5007/srpdfs/CT.pdf  (Accessed:  29  January  2015).  

Northumbria  University  (2014)  Timetable  Week  Numbers  [Online].  Available  at:  http://nuweb.northumbria.ac.uk/timetabling/tt/WeekNumbers.htm  (Accessed:  29  January  2015).  

Omni  (2009)  GS-­‐CO2  Carbon  Dioxide,  RH  &  Temperature  Sensors.  Available  at:  http://www.omniinstruments.co.uk/products/product/moredetails/gs-­‐co2.id1275.html  (Accessed:  30  January  2015).  

OSEH  (1998)  Carbon  dioxide  sensor  usage  in  the  power  center  for  the  performing  arts.  Available  at:  http://www.p2000.umich.edu/energy_conservation/ec3.htm  (Accessed:  31  January  2015).    Pearson,  R.  (2013)  Sensor  Taps.  Available  at:  http://www.robertpearson.co.uk/products/sensor-­‐taps/  (Accessed:  2  February  2015).    

Pevsner,  N.,  Richmond,  I.,  Grundy,  J.  and  McCombie,  G.  (1992)  Northumberland  2nd  edn.  London:  Penguin  1992,  pp.453.  

Rameha  (2015)  Renewable  Heat  Incentive  Scheme.  Available  at:  http://www.remeha.co.uk/renewable-­‐heat-­‐incentive-­‐scheme  (Accessed:  3  February  2015).  

Reardon,  C.  (2013)  Thermal  Mass.  Available  at:  http://www.yourhome.gov.au/passive-­‐design/thermal-­‐mass  (Accessed:  5  February  2015).  

Saint-­‐Gobain  Group  (1999)  How  much  money  can  I  save  from  energy  efficient  windows?  Available  at:  http://www.saint-­‐gobain.co.uk/  (Accessed:  2  February  2015).  

Sadoo  (2010)  Sensor  Faucet.  Available  at:  http://www.sadoocn.com/Faucet/Sensor_Faucet_1.html  (Accessed:  8  February  2015).  

South  Coast  Glazing  (no  date)  Double  glazing  units.  Available  at:  http://www.southcoastglazing.co.uk/double_glazing.php  (Accessed:  31  January  2015).  

South  West  Tourism  (2009)  Saving  water  in  bathrooms  and  washrooms.  Available  at:  http://www.swtourismalliance.org.uk/files/download.php?m=documents&f=100721150705-­‐SavingWaterinBathroomsandwashrooms.pdf  (Accessed:  27  January  2015).  

Page 27: Be0898 2014:15 tan

                   

27  

Stromberg,  J.  (2014)  Do  Revolving  doors  actually  save  energy?  Available  at:  http://www.vox.com/2014/8/13/5995537/do-­‐revolving-­‐doors-­‐save-­‐energy  (Accessed:  30  January  2015).  

Theecoexpert  (2015)  Cost  of  Biomass  Boilers.  Available  at:  http://www.theecoexperts.co.uk/cost-­‐of-­‐biomass-­‐boilers  (Accessed:  6  February  2015).  

Thorpe,  D.  (2013)  What  type  of  green  boiler  would  best  fit  my  needs?  [Online]  Available  at:  http://www.superhomes.org.uk/resources/green-­‐boiler/  (Accessed:  5  February  2015).  

Torres,  V.(2014)  ‘Parents  Voice  Concern  Over  Lack  Of  Air  Conditioning  In  Schools’,  CBS  Los  Angeles,  17  September  [Online].  Available  at:  http://losangeles.cbslocal.com/2014/09/17/parents-­‐voice-­‐concern-­‐over-­‐lack-­‐of-­‐air-­‐conditioning-­‐in-­‐schools/  (Accessed:  7  February  2015)  

Whibley,  S.  (2015)  Tracey:  Please  stop  using  the  disabled  door  in  Alan  Turing,  it’s  making  me  cold.  Available  at:  http://manchester.tab.co.uk/2015/01/15/can-­‐everyone-­‐stop-­‐using-­‐disabled-­‐door-­‐traceys-­‐getting-­‐cold/  (Accessed:  31  January  2015).  

13022981  (2015)  Ellison  Building.  [Photograph].  Newcastle  upon  Tyne